Professional Documents
Culture Documents
2-ACI 211.1-91 Standard Practice For Selecting Proportions For Normal, Heavyweight, and Mass Concrete - Procedure For Mix Design
2-ACI 211.1-91 Standard Practice For Selecting Proportions For Normal, Heavyweight, and Mass Concrete - Procedure For Mix Design
The ACI 211.1-91 (Reapproved 2009) describes methods to create mix designs for
hydraulic cement concrete. In this summary, I will borrow heavily from the language,
graphs, and tables of the manual to create a guideline for mix design of normal weight
concrete that will be used for educational purposes at Stevens.
where S.G. is the specific gravity of a material and 62.4 lb/ft 3 is the density of water.
For example, a bag of cement (94 lbs.) in a bulk state occupies approximately 1 cubic
foot of volume. If the cement was consolidated and without voids it would
approximately occupy only 0.48 cubic feet. Therefore, the volume the cement will
actually occupy in a batch of concrete will be its absolute volume of 0.48 cubic feet.
EXAMPLE: What is the weight of cement that occupies an absolute volume of 1 cubic
foot?
Weight = Absolute Volume x S.G. x 62.4 lb/ft3
EXAMPLE: Design a batch of 1.25 f3 of concrete for a footing. Design for a strength of
4000 psi. The available materials, along with the data that we will need to design the
mix, are given in the table below.
Before you can use Tabel 6.3.3 you must decide if you need air-entrained concrete.
Usually, if the concrete is exposed to freeze-thaw, as is the case of concrete placed in
foundations, you will need air-entrainment.
For our example, for a slump of 3 inches and a maximum aggregate size of 1 inch, use
the air-entrained part of the table to find that you will need 295 lbs of water per cubic
yard of concrete. The fine print under the table specifies that the water should be
reduced by 25 lbs if you are using well rounded aggregates. Therefore, in this example
we will use 270 lbs of water.
The same table also shows that the recommended percent of air content is 6% for
severe exposure (concrete that is exposed to deicing chemicals, or may become highly
saturated by continued contact with moisture or free water prior to freezing-- such as
pavements, bridge decks, foundations, etc.)
Since different aggregates, cements and cementitious materials (fly ash, slag,silica
fume, etc) generally produce different strengths at the same w/c ratios, it is highly
desirable to have or develop the relationship of strength to w/c ratio for the materials
actually used. In absence of such data, Table 6.3.4(a) and (b) can be used. The
strength shown in the tables is for test specimens cured for 28 days in laboratory
conditions.
In this example, for a 4000psi, air-entrained concrete you should pick w/c = 0.48 (the
maximum permissible is 0.5 taken from Table 6.3.4(b))
STEP 5. Calculation of cement content.
Water/cement=0.48
Cement=270/0.48=560 lbs
The dry weight of coarse aggregate then is its volume times its dry-rodded weight per
cubic foot, ie,
The weights that we calculate above are dry weights. For the batch we will add
Absorbed water does not become part of the mixing water. However, the free water will
add to the water content so we must account for it.
Water, to be added 193 lbs Note, total wt/yd3=3830. See Table 6.3.7.1
Cement 560 lbs
Coarse Aggregate, Wet 1875 lbs
Fine Aggregate, Wet 1206 lbs
2.4 Class Problem
Create the mix for one cubic yard of concrete for the following specifications.
Type I cement
Coarse aggregate bulk specific gravity=2.68 and an absorption of 0.5%. Dry unit wt of
coarse aggr.=100 lbs/cubic foot. Maximum aggr. Size =1.5 in
Concrete is required for a portion of a structure that will be below ground level in a
location where it will NOT be exposed to severe weathering or sulfate attack.
Structural considerations require it to have an average 28-day compressive strength of
3500 psi. A slump of 3 to 4 inches is required.
ANSWER