You are on page 1of 3

PT PLN (PERSERO) Doc. No.

TRANSMISI JAWA BAGIAN TIMUR DAN BALI


APP MADIUN Valid.
DAFTAR SETELAN RELE PROTEKSI GI NGANJUK T/L Bay 70 kV KERTOSONO #1,2

1. Proteksi : GI NGANJUK T/L Bay 70 kV KERTOSONO #1,2

JENIS RELAI TIPE EVALUASI ENJINIRING APP MADIUN


ALSTOM
CT = 400/5 A
OCR MICOM
In = 5 A
P142
Address Description Setting Value
DEVICE CONFIGURATION
Active Settings Group 1
Setting Group 1 Enabled
Overcurrent Enabled
Earth Fault 1 Enabled
CT & VT Ratios Visible
Setting Values Secondary
CT AND VT Ratios
Phase CT Prim. 400 A
Phase CT Secy 5A
E/F CT Prim 400 A
E/F CT Secy 5A

GROUP 1 OVERCURRENT
I>1 Function IEC SI
I>1 Direction Non-Dir
I>1 Current Set 6 A (1,2 A x In)
I>1 TMS TMS 0,213 (SI)
I>1 Reset Char DT
I>1 rRESET 0s
I>2 Function Disabled
I>3 Status Disabled
I>4 Status Disabled
V CONTROLLED O/C
VCO Status Disabled

1/3 Daftar Evaluasi Setelan Rele Dibuat : Disetujui :


Proteksi Pangarso Utomo Basis Sukarja
Rev. 00 GI 70 kV TULUNGAGUNG Tgl : Mei 2017 Tgl: Mei 2017
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO )TJBTB
PT PLN (PERSERO) Doc. No.
TRANSMISI JAWA BAGIAN TIMUR DAN BALI
APP MADIUN Valid.
DAFTAR SETELAN RELE PROTEKSI GI NGANJUK T/L Bay 70 kV KERTOSONO #1,2

JENIS RELAI TIPE EVALUASI ENJINIRING APP MADIUN


ALSTOM PT = 66/0,11 kV
DGR MICOM CT = 400/5 A
P142 In = 5 A
Address Description Setting Value
DEVICE CONFIGURATION
Active Settings Group 1
Setting Group 1 Enabled
Overcurrent Enabled
Earth Fault 1 Enabled
CT & VT Ratios Visible
Setting Values Secondary
CT AND VT Ratios
Phase CT Prim. 400 A
Phase CT Secy 5A
E/F CT Prim 400 A
E/F CT Secy 5A

GROUP 1 EARTH FAULT


I>1 Function DT
I>1 Direction Directional Fwd
I>1 Current Set 0,35 A (0,07x In)
I>1 TMS 0,5 s (DT)
IN1> Char Angle 00
IN1> Pol Zero Sequence
IN1> VNpol Set 5
IN1> V2pol Set 5
IN1> I2pol Set 0,08
I>1 rRESET 0s
I>2 Function Disabled
I>3 Status Disabled
I>4 Status Disabled
V CONTROLLED O/C
VCO Status Disabled

2/3 Daftar Evaluasi Setelan Rele Dibuat : Disetujui :


Proteksi Pangarso Utomo Basis Sukarja
Rev. 00 GI 70 kV TULUNGAGUNG Tgl : Mei 2017 Tgl: Mei 2017
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO )TJBTB
PT PLN (PERSERO) Doc. No.
TRANSMISI JAWA BAGIAN TIMUR DAN BALI
APP MADIUN Valid.
DAFTAR SETELAN RELE PROTEKSI GI NGANJUK T/L Bay 70 kV KERTOSONO #1,2

JENIS RELAI TIPE EVALUASI ENJINIRING APP MADIUN


ALSTOM
CT = 400/5 A
DGR MICOM
In = 5 A
P142
Address Description Setting Value
GROUP 1 FAULT LOCATOR
Line Lenght (miles) 10.411 miles (16,765
km)
Line Impedance 7.444
Line Angle 60,67 deg
kZn Residual 0.581
kZn Res. Angle 18,365 deg

3/3 Daftar Evaluasi Setelan Rele Dibuat : Disetujui :


Proteksi Pangarso Utomo Basis Sukarja
Rev. 00 GI 70 kV TULUNGAGUNG Tgl : Mei 2017 Tgl: Mei 2017
RUANG LINGKUP SERTIFIKASI ISO 9001:2000
PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO )TJBTB