You are on page 1of 7

VISIO 6 5 4 2 1

3
REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 129979 C 1 SEE SHT 5 TLD JTB T.AJAYI 25OCT12

D D

PowerCommand 3.3 FOR KTA38 HYDRO MECHANICAL GENSET


PAGE TITLE DESCRIPTION
1 INDEX COVER PAGE
2 WIRING DIAGRAM SCHEMATIC, ELECTRICAL CONNECTIONS
3 GENSET LOCATION, GENSET DEVICE LOCATIONS ON GENSET AND HMI
4 LOCATION DIAGRAM, CONTROLS DEVICE LOCATIONS IN CONTROL BOX
5 OPTIONS ACCESSORY CONNECTIONS
6 ADDITIONAL PINOUTS ADDITIONAL PINOUT CONNECTIONS
C C

Notes:

1. Fusing requirements for Arc flash protection for TB7 (Bus/Utility Voltage Sense)*: If your potential circuits have available incident energy > 1.2 Cal/cm2 or 5J/cm2 then you need to protect for arc flash in the lines feeding TB7**.

Available Incident energy > 1.2 Cal/cm2 or 5J/cm2 is typically found when any of the the following is true:

A) LL Voltage > 240Vac OR

B) Paralleled OR

C) Alternator size > 125kVA

2. Fusing requirements for Arc flash protection for TB7 (Bus/Utility Voltage Sense)*: If Available Incident energy is > 1.2 Cal/cm2 or 5J/cm2 then the use of current limiting fuses or other suitable means in the lines feeding J22 and TB7** are needed.

The following suggested current limiting fuses will accomplish this:


B B
A) Fuse rating: 600Vac, 0.5A, AIC=200kA, fast acting, current limiting, Class CC (e.g. Ferraz Shawmut ATMR or equiv.)

B) Use 600Vac rejection type fuse holder with AIC=200kA rating, e.g. Ferraz Shawmut 30323R or equiv.

C) Fuses must be placed near the voltage source.

* Per NFPA 70E and Cummins Electrical Safety Policy.

**Fusing protecting the circuit feeding TB7 must also meet all local code requirements.

3. For enclosure-container wiring diagrams refer to the following drawings.

0630-2941

0630-3613

0630-3080

0630-2867

0630-2868

0630-2873

A A

UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN


DIMENSIONS ARE IN MILLIMETERS
DO NOT SCALE PRINT CKD
N_SCHOTTLER
CUMMINS POWER GENERATION
X ` 0.00- 4.99 +0.15/-0.08
N_SCHOTTLER

5.00- 9.99 +0.20/-0.10 APVD

DIM
M_POZO
DIAGRAM, SCHEMATIC

HOLE
.X ` 10.00-17.49 +0.25/-0.13
DATE SITE CODE
17.50-24.99 +0.30/-0.13 01-04-2011
.XX` - CONFIDENTIAL - DWG DWG

PGK
FOR INTERPRETATION FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 1 OF 6 C

6 5 4 3 2 1

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 1 of 7
VISIO 6 5 4 2 1
3
REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 129979 C - - TLD JTB T.AJAYI 25OCT12

Sw B+ K7 SW B+ T26
REMOTE E-STOP 3300 TB1-16 1B P2-12
1A 1B
5 4 S7-B 3B
JUMPER 1 2A 2B J20-11
1 2 3300 TB1-15
3A 3B P2-5 6 1 P-SWB+ 2B
REMOTE J20-11 Starter Disconnect Input T26
P2-13
P3-B
JUMPER 2 4A 4B
E-STOP 4 3
REMOVE K10-86
1B
E-STOP B+
PCC3300 J20-13 Relay Coil B+ Supply
J20-16 Oil Priming Pump Relay Driver
Starter K9

5 4
X10 (10A) B1-BAT P3-A
P3-C
HEATER CONTROL (P3)

D D
JUMPERS 2B X20 (20A)
P20-3 B1-BAT
P2-14 ENG SP4
1 AND 2 TO
INSTALL
3B BASEBOARD P20-15 P2-6 6 1 P2-10
K4-S1
SP4 1B
FUSED B+ K9-1 S1
K4
S2
4B P2-15
REMOTE E- P20-14 FSO K8 TB-BAT
2B
STOP K16-A X21 (20A)
P20-9 5 4 3B B1-BAT K4-BAT K4 K4+
USER INTERFACE GND P20-10
P20-20 P2-7 6 1
P21-9 (AUX 105)
HMI-SP1
4B
5B
P20-21 SwB+ - 3B BATTERY Starter 1 Starter 2
LOCAL E-STOP B+ F-FSO 3A
PART NUMBERS P20-5 A B P2-11
FSO (K1) CHARGING
3 4 ALTERNATOR G1-B+
FUSED B+ PCC3300: 0327-1601 P20-17 S7-C B+ 24VDC
E-STOP 2 1 INPUT (WAKE-UP ON OPEN) P25-2 P20-22 S7-B GND
COOLANT
G1-D+
B1-BAT BT1
LEVEL (S7)
P20-2
P20-4
S7-D SIG G KS KS
RETURN P25-6 HARNESS, INTERFACE SHIELD GROUNDED IN FOUR PLACES
(WORT BOX): HARNESS ENGINE:
A035H837
P20-7
G1-GND
M BT2 M
TB15-1 GND A035H282 P20-12
K10-SP B+ RETURN GND-ENG
TB15-3 RS485 A P29 must be P20-1 1B
HMI 320 PC
TOOL
TB15-4 RS485 B
disconnected to
use PC Tools on
P20-6
P20-18 3B
P2-8
B1-GND KS B1-SW1 KS

TB15 USE SHIELDED TWISTED PAIR P2-9 ENG SP3 B1-SW2


DISPLAY TB15-5 WAKE-UP1
FOR PCC NET
P20-19
P20-8
P25-2
ONLY TERMINATE SHIELD ON
P29-4 AUTO (CONFIGURABLE WAKE-UP) P25-6
HARNESS, INTERFACE P25-11
ONE END TB1-1 PCC NET A (+)
PC TOOL: A035A671 P29-6 RUN (WAKE-UP)
TB1-2 PCC NET B (-) CUSTOMER INPUTS
P25-10
TB1-3 B+ RETURN P2-1 1B FUEL LEVEL RETURN
J25-1 CI#4 FUEL LEVEL SWITCH (WAKE-UP)
HARNESS, INTERFACE TB1-5 CUSTOMER FUSED B+ P2-3 2B P20-18
J25-7
(PCC3300 TO HMI): TB1-4 SEE SHEET 5 P2-2 3B P20-19
J25-12 A035G075 CI#12 RUPTURE BASIN SWITCH (WAKE-UP)
TB1-6 SEE SHEET 5 P2-4 4B RUPTURE BASIN RETURN
PART NUMBERS: PCC NET SHLD P25-9
P25-3 TB1-7 SEE SHEET 5
HMI 320: P29-2 PCC NET (-)
TB1-8 SEE SHEET 5 P1-3
P25-4
0300-6315-02 HARNESS, INTERFACE P1-4
P29-1 PCC NET (+)
SP3 P25-5
P25-8
PCC3300-AUX101:
TB1-9 SEE SHEET 5
TB1-10 SEE SHEET 5 P1-5 AUX 101
C
A035E359
C P29-3 SYSTEM WAKE-UP
TB1-11 SEE SHEET 5
TB15-5 WAKE-UP3
P1-2
P11
TB1-12 SEE SHEET 5 P1-1 REMOTE I/O SEE SHEET 5
BUS CT SHORTING BLOCK BUS CURRENT TB1-13 SEE SHEET 5 SEE SHEET 5
CT1-1B
CT1 P10
TB1-14 SEE SHEET 5 P14-2 SEE SHEET 5 SEE SHEET 5
CT1-2B TB1-15 P14-1 SEE SHEET 5 SEE SHEET 5
P28-1 HMI FUSED B+ SP1 FUSED B+,4B CT2-3B
REMOTE E-STOP 2B PART EXHAUST TEMP RIGHT BANK RTD (E7)
CT2 TB1-16 P10-3, P11-6 P11-6 SENSE E7-A
CT2-4B
REMOTE E-STOP 1B NUMBERS
P10-9, P11-5 P11-5 RETURN E7-B
P28-3 B+ RETURN SP2 CT3-5B CT3
AUX 101: P10-4, P11-8 P11-8 SENSE
CT3-6B 0327-1536 P10-10, P11-7 P11-7 RETURN
PC TOOL SEE SHEET 5 SEE SHEET 5 EXHAUST TEMP LEFT BANK RTD (E6)
TB15-1 GND J4-1
HARNESS, BUS: SEE SHEET 5 SEE SHEET 5 E6-A
HARNESS, INTERFACE W1 SHIELD K16
A035E847 E6-B
HMI 114 BUS VOLTAGE
PC TOOL TO PCC3300:
A040D379
TB15-3 RS485 A
TB15-4 RS485 B 8
7 4
5
J4-3
J4-4
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5

BARGRAPH
1B BUS L1
2B BUS L2 USE PTs
IF LL
TB7-1
TB7-2 9 6 J4-5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
LEGEND
3B BUS L3 TB7-3 TB15-5 WAKE-UP3
VOLTAGE FUSED B+ - 2B SEE SHEET 5
P1-3 PCC NET A (+) 4B BUS L4 >600VAC TB7-4 A B
PART NUMBERS P1-5 (AUX 101) AUX 101 IS REQUIRED FOR EXHAUST SEE SHEET 5 OPTIONAL
P1-4 PCC NET B(-) P26-2 TEMPERTURE SENSING.
HMI 114: MODBUS
P1-5 SYSTEM WAKE-UP J26-3 AVR PWM- 1B
0300-6366-02 SEE FUSING REQUIREMENTS ON SHEET 1.
J26-5 AVR B+ RETURN FACTORY CONNECTIONS
P6-2 B+ RETURN J26-6 N/A 1
P12-1 3B
P6-1 HMI FUSED B+ D1
J26-7 FIELD CURRENT- 2 4B FAST ON CONNECTOR
P12-4
J26-8 B+ RETURN 3 5B
P12-2
J26-9 AVR B+
P12-5 HARNESS, HARNESS, SET SCREW TERMINAL
J26-14 FIELD CURRENT+
P12-3 ALTERNATING INTERFACE
CURRENT: PCC3300 TO AUX 105: J26-16 AVR PWM+ LOW COOLANT TEMPERATURE (S4)
P12-6 PLUG CONNECTOR
A034Y614 A035G905 J26-17 N/A
J26-18 KEYSWITCH B+ OUT
- GENSET VOLTAGE
P22-1
P26-15
RING TERMINAL
DRIVER ALTERNATOR P22-2
P26-1 P1939 SHLD
RATING P26-10 P1939 (-)
B
P22-3
B

G
P26-11 P1939 (+) 120 ohm Opens @ 85F, Closes @ 65F
S: P22-4
P26-12 PCC NET A (+)
4 AMPS P26-13 PCC NET B (-)
PEAK : P26-4 SHLD
6 AMPS
+
AUX 104 FUEL ACTUATOR (6AMP MAX)
ACT (-)
P21-12 GOV POWER STAGE ACT (+)

TERMINAL BLOCK
AUX 105 P21-8
P21-2
Part numbers
J1-1
J1-2
P1 - 1
P1 - 2
N W V U HM ECM & AVR P21-3 120 ohm Aux 104: 0327-1507 J1-5
P1-5 GOV PS POWER

CT21-1 P1 Mate: 0323-2216 : P1-4 ACT LS DRIVER


J1-4

CT-23
POWERSTAGE B+ RETURN - 1B Sockets: 0323-1200 J1-3
P1-3 GOV PS POWER

CT21-2/3 P21-6 K10-SP

CT22-1 87 85
P21-9 FUSED B+ - 3B OIL PRESSURE (E1)
K10 KEYSWITCH
CT-22 E1-B
CT22-2/3 30 86
P21-11 E1-A
E-STOP B+ - 2B
CT23-1 PART NUMBERS E1-C
CT-21 AUX 105: A028T766
CT23-2/3

XU (.5A) P11-5 GOVERNOR PWM + MAG PICK-UP (P1)


P11-4 GOVERNOR PWM - P1-A
USE PTs XV (.5A)
P11-1 +5V P1-B
IF LL XW (.5A) P11-2 RETURN
VOLTAGE P11-3 SENSE
>600VAC COOLANT TEMP LEFT BANK (E2)
E2-A
AVR POWER P11-8 SHIELD E2-B
A PMG-P2 P18-1 P11-9 + A
PMG-P3 P18-2 P11-10 -
PMG-P4 P18-3 P11-11 SENSE OIL TEMPERATURE (E4)
PMG P11-12 RETURN E4-A

G FIELD (+)
FIELD (-)
AVR CONTROL
P17-1
P17-2
P11-13 SENSE
P11-14 RETURN
P11-15 SENSE
E4-B

P11-16 RETURN
UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN
PC TOOL
TB15-1 GND DIMENSIONS ARE IN MILLIMETERS
DO NOT SCALE PRINT
N_SCHOTTLER
CUMMINS POWER GENERATION
J5-1 CKD
RS485 SHIELD
COOLANT TEMP RIGHT BANK (E3) X ` 0.00- 4.99 +0.15/-0.08
N_SCHOTTLER
TB15-3 RS485 A HARNESS, INTERFACE E3-A 5.00- 9.99 +0.20/-0.10 APVD

HOLE
M_POZO

DIM
J5-3
J5-4
TB15-4 RS485 B PC TOOL: A040G672 E3-B .X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
TB15-5 WAKE-UP 17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
J5-5 .XX` - CONFIDENTIAL - DWG DWG

PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 2 OF 6 C

6 5 4 3 2 1

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 2 of 7
VISIO 6 5 4 2 1
3
REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 129979 C - - TLD JTB T.AJAYI 25OCT12

D D

COOLANT LOW COOLANT COOLANT


TEMP RIGHT TEMPERATURE COOLANT TEMP LEFT
BANK (E3) (S4) LEVEL (S7) BANK (E2)

MAG PICKUP
(P1)
A
C

C C

C
A
B B

OIL OIL
TB-BAT K4
TEMPERATURE GND ENG PRESSURE
T 26 (E4) (E1)

B B

COOLANT
LEVEL (S7) SEE NOTE 1

HMI 114

HMI 320 - LOW COOLANT LEVEL SENSOR (S7) IS LOCATED


AT THE TOP OF THE RADIATOR.

- NOT ALL CONNECTION POINTS ARE SHOWN,


SEE SPECIFIC HARNESS INSTALLATION
DRAWINGS FOR EACH OPTION FOR MORE
INFORMATION.

A A

RADIATOR VIEW
CT-21
CT-23
CT-22
UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN
CUMMINS POWER GENERATION
N_SCHOTTLER
DIMENSIONS ARE IN MILLIMETERS
LOCAL E-STOP X `
DO NOT SCALE PRINT CKD N_SCHOTTLER
0.00- 4.99 +0.15/-0.08
5.00- 9.99 +0.20/-0.10 APVD M_POZO

DIM
DIAGRAM, SCHEMATIC

HOLE
.X ` 10.00-17.49 +0.25/-0.13
VIEW A-A 17.50-24.99 +0.30/-0.13
DATE SITE CODE
VIEW B-B .XX` - CONFIDENTIAL - FOR INTERPRETATION
01-04-2011
DWG DWG

PGF D
FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 A035H705 3 OF 6 C

6 5 4 3 2 1

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 3 of 7
VISIO 6 5 4 2 1
3
REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 129979 C - - TLD JTB T.AJAYI 25OCT12

D D

CI#12 RUPTURE BASIN


SWITCH (WAKE-UP)
SWITCH (WAKE-UP)
CI#4 FUEL LEVEL
K22 FAT BUS CT
K18 (2A)
F-FSO K23 SHORTING
(3A) K17 BLOCK
K16 MODBUS REMOTE E-STOP FUSED SW B+ B+ OPTIONAL RELAYS 6X (K13,K14,K15,K19,K20,K21) 1A 2A 3A 4A 5A 6A
HEATER BUS
E-STOP B+ B+ RETURN POWER VOLTAGE
1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4
A A A A A A A A A A
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A

1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4
B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B

C
B L L L/N L/N G L1 L2 L3 N
C
1B 2B 3B 4B 5B 6B

AUX 104

TB1 TB8
K7 K8 K9 J18
J TB3 TB5 TB10
1
J26 J14
J25
TB
15

J4 DC WIRE
J J17 ENTRANCE
B 10 B
TB
J J3 J20 9
11
J21

J2 J11
TB
15

CT3 CT2 CT1


J14 J1 J12
AC WIRE J22 TB7
ENTRANCE

A A
AUX 101 AUX 105 3300

UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN


CUMMINS POWER GENERATION
N_SCHOTTLER
DIMENSIONS ARE IN MILLIMETERS
X ` DO NOT SCALE PRINT CKD N_SCHOTTLER
0.00- 4.99 +0.15/-0.08
5.00- 9.99 +0.20/-0.10 APVD

DIM
M_POZO
VIEW C-C DIAGRAM, SCHEMATIC

HOLE
.X ` 10.00-17.49 +0.25/-0.13
DATE SITE CODE
17.50-24.99 +0.30/-0.13 01-04-2011
.XX` - CONFIDENTIAL - FOR INTERPRETATION DWG DWG

PGK D
FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 A035H705 4 OF 6 C

6 5 4 3 2 1

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 4 of 7
VISIO 6 5 4 2 1
3
REL NO LTR NO REVISION DWN CKD APVD DATE
REMOVE TB10-5 B+ AND TB10-10 GND CONNECTIONS,
ECO - 129979 C 1 ADD B+ RETURN -2B AND FUSED B+ -1A (ZONE D-5) TLD JTB T.AJAYI 25OCT12

PARALLELING CIRCUIT
OPTIONAL RELAYS BREAKER RELAY CONTROL

PCC
3300 TB1
A1 13 21 43 43 ALARM
A2 14 22 44 44
RELAY K21 RTD CONNECTIONS
ALARM MODULE THERMISTOR RELAY
FUSED B+ -1A
D PCC J22-4 (N) D
TB1-5 3300 TB1 WHITE
B+
K19 N.D.E
TB1-6 RED
A1 13 21 43 43 CONFIGURABLE K17 BEARING
A1 13 21 43 43 AUDIBLE (TIMER 0-10SEC) RED RTD

RESET
RELAY K13 PCC 3300 TB8-7
TB1-8 A2 14 22 44 44
A2 14 22 44 44 ALARM WHITE
TB1-9 MODULE J22-3 (W) FAT (2A) D.E
B+ RETURN -2B RED
TB1-5 J1+ BEARING
TB1-10 B+ A1 A2 R RED RTD
GND
A1 13 21 43 43
CONFIGURABLE CIRCUIT BREAKER TRIPPED 16 18 26 28
J2- K18 WHITE
A2 14 22 44 44 RELAY K14 (TEMPERATURE RED
PCC PTC W2
3300 TB8 TB1-8 MONITORING) 15 25
PC3300 TB10 Ta Tb RED RTD
K20 TB1-9 WHITE
TB10-2 Generator Circuit Breaker
A1 13 21 43 43 A1 13 21 43 43 TB1-10 RED
CONFIGURABLE GND V2
A2 14 22 44 44 RELAY K15 A2 14 22 44 44 SDE Contact RED RTD
K17
WHITE
(DELAYED MAKE)
RED U2
TB5
CLOSE STATUS OUTPUT RED RTD
PCC 3300 TB8-12 WHITE

TB8-9 RED W1
TB8-10
OPEN STATUS OUTPUT RED RTD
TB10-10
WHITE
RED
C
V1
C
RED RTD
WHITE
ALT. TEMP
THERMISTORS RED U1
RED RTD

HEATERS (COOLANT, CONTROL BOX, ALTERNATOR)

HEATER CONTROL BOX

Fuel Level
GROUND FAULT RELAY

PCC
3300 TB8 B+ RETURN - 2B CT1
RHI1 Fused B+ - 1A
CT3
RHI1 PCC
FUSE1 3300 TB1
A1 A2 T1 T2
4A

PCC 3300 TB1-14


126
250

252

253

254

255

90
N

E
E

High level warning


L

B
TB8-8
5 3 8 K22 B
K23
6 4 1
RH99M
HT1 HT2
PCC 3300 TB1-13 - WIRING DIAGRAMS SHOWN ON THIS SHEET
BATT -VE
(B+ RETURN) ARE GENERALIZED, SEE SPECIFIC INSTALLATION
TB8-13
DRAWINGS FOR EACH OPTION FOR MORE
BATT +VE INFORMATION.
Low Fuel warning SHUNT TRIP
(SW B+) 32 31 34 25 26 27 11 14
TB1-12 ST-1
HE1 HE2
TB1-13 ST-2

TEST
Customer Inputs

ON (RELAY OPERATIONAL)
Terminal block
1A 2A 3A 4A

CONTROL BOX HEATER


1B 2B 3B 4B

RESET
Low Fuel Shutdown
1A 2A 3A 4A 5A

1B 2B 3B 4B 5B
ALTERNATOR HEATER

Ground Fault Relay is available on single set


applications only.
A A

HP
HA

UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN


DIMENSIONS ARE IN MILLIMETERS
DO NOT SCALE PRINT
N_SCHOTTLER
CUMMINS POWER GENERATION
CKD
X ` 0.00- 4.99 +0.15/-0.08
N_SCHOTTLER

5.00- 9.99 +0.20/-0.10 APVD

HOLE
M_POZO

DIM
.X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
.XX` - CONFIDENTIAL - DWG DWG

PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 5 OF 6 C

6 5 4 3 2 1

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 5 of 7
VISIO 6 5 4 2 1
3
REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 129979 C - - TLD JTB T.AJAYI 25OCT12

PCC3300 TB1-1 PCC NET A (+) SEE SHEET 2


TB1-2 PCC NET B (-) SEE SHEET 2
BASEBOARD TB1-3 B+ RETURN SEE SHEET 2
PCC3300
PART NUMBERS
TB1-5 CUSTOMER FUSED B+ SEE SHEET 2 BASEBOARD
PCC3300: 0327-1601 TB1-4 CONFIGURABLE O/P #5
PART NUMBERS AUX 101
TB1-6 CONFIGURABLE O/P #1-A PCC3300: 0327-1601 J2-1 RELAY 1 NO D
TB1-7 CONFIGURABLE O/P #1-B TB8-1 DISCRETE INPUT RETURN REMOTE I/O J2-2 RELAY 1 COM
TB1-8 CONFIGURABLE O/P #2-A TB8-2 DISCRETE INPUT RETURN J2-3 RELAY 1 NC
TB1-9 CONFIGURABLE O/P #2-B TB8-3 DELAYED OFF RELAY DRIVER J2-4 RELAY 2 NO
TB1-10 REMOTE START RETURN TB8-4 SWITCHED B+ RELAY DRIVER J2-5 RELAY 2 COM
TB1-11 REMOTE START TB8-5 REMOTE FAULT RESET J2-6 RELAY 2 NC
TB1-12 CONFIGURABLE I/P #1 TB8-6 START TYPE J2-7 RELAY 3 NO
TB1-13 RETURN TB8-7 CONFIGURABLE INPUT #13 J2-8 RELAY 3 COM
TB1-14 CONFIGURABLE I/P #2 TB8-8 CONFIGURABLE INPUT #14 J2-9 RELAY 3 NC
TB1-15 REMOTE E-STOP SEE SHEET 2 TB8-9 CONFIGURABLE OUTPUT #4 J2-10 RELAY 4 NO
TB1-16 REMOTE E-STOP SEE SHEET 2 TB8-10 CONFIGURABLE OUTPUT #3 J2-11 RELAY 4 COM
TB8-11 LOAD DUMP RELAY DRIVER J2-12 RELAY 4 NC
TB8-12 DISCRETE INPUT RETURN
TB3-1 RETURN TB8-13 DISCRETE INPUT RETURN
TB3-2 MASTER CAN SHIELD
J3-1 RELAY 5 NO
TB3-3 MASTER CAN L
J3-2 RELAY 5 COM
TB3-4 MASTER CAN H
J3-3 RELAY 5 NC
TB3-5 CONFIGURABLE OUPUT #20 STATUS
TB9-1 KW LOAD SETPOINT J3-4 RELAY 6 NO
TB3-6 CONFIGURABLE OUPUT #21 STATUS
TB9-2 ANALOG RETURN J3-5 RELAY 6 COM
TB3-7 SPARE OUTPUT FOR FURTURE USE
TB9-3 KVAR LOAD SETPOINT J3-6 RELAY 6 NC
TB3-8 CONFIGURABLE OUPUT #22 STATUS C
TB9-4 VOLTAGE BIAS OUTPUT / CONFIGURABLE ANALOGY OUTPUT #2 OUTPUT PREDICTOR
TB3-9 TRANSFER INHIBIT/CONFIGURABLE INPUT #20 SWITCH
TB9-5 SPEED BIAS OUTPUT / CONFIGURABLE ANALOG OUTPUT #1 OUTPUT PREDICTOR
TB3-10 RETRANSFER INHIBIT/CONFIGURABLE INPUT #21 SWITCH
TB9-6 ANALOGY RETURN J4-1 RELAY 7 NO
TB3-11 MASTER FIRST START STATUS
TB9-7 KW LOAD SHARE LEVEL J4-2 RELAY 7 COM
TB3-12 RETURN
TB9-8 NOT USED J4-3 RELAY 7 NC
TB9-9 LOAD SHARE SHIELD J4-4 RELAY 8 NO

TB5-1 GENSET CB CLOSE STATUS TB9-10 + KVAR LOAD SHARE LEVEL J4-5 RELAY 8 COM
TB5-2 GENSET CB CLOSE STATUS TB9-11 - KVAR LOAD SHARE LEVEL J4-6 RELAY 8 NC
TB5-3 GENSET CB OPEN STATUS
TB5-4 GENSET CB OPEN STATUS
J10-1 CAN H
TB5-5 GENSET CB OPEN STATUS
J10-2 CAN L
TB5-6 UTILITY CB CLOSE STATUS
J10-3 INPUT #3 CURRENT SOURCE (SEE SHEET 2)
TB5-7 UTILITY CB CLOSE STATUS
J10-4 INPUT #4 CURRENT SOURCE (SEE SHEET 2)
TB5-8 UTILITY CB OPEN STATUS TB10-1 RETURN
J10-5 INPUT #5 CURRENT SOURCE
TB5-9 UTILITY CB OPEN STATUS TB10-2 RETURN
J10-6 INPUT #6 CURRENT SOURCE
TB10-3 UTILITY CB POS A SWITCH
J10-7 5VDC SUPPLY #1 (20 mA MAX)
TB10-4 UTILITY CB POS B/CONFIGURABLE INPUT #23 SWITCH
J10-8 5VDC SUPPLY #2 (20 mA MAX)
TB10-5 UTILITY CB TRIPPED SWITCH
J10-9 INPUT #3 CURRENT RETURN (SEE SHEET 2)
TB10-6 UTILITY CB INHIBIT/CONFIGURABLE INPUT #25 SWITCH
J10-10 INPUT #4 CURRENT RETURN (SEE SHEET 2)
TB10-7 GENSET CB POS A SWITCH
J10-11 INPUT #5 CURRENT RETURN
TB10-8 GENSET CB POS B/CONFIGURABLE INPUT #26 SWITCH B
J10-12 INPUT #6 CURRENT RETURN
TB10-9 RETURN
TB10-10 GENSET CB TRIPPED SWITCH
TB10-11 GENSET CB INHIBIT/CONFIGURABLE INPUT #28 SWITCH
J11-1 INPUT #1 RETURN
TB10-12 UTILITY SINGLE MODE VERIFY/CONFIGURABLE INPUT #29 SWITCH
J11-2 INPUT #1 SENSE
TB10-13 SYNC ENABLE/CONFIGURABLE INPUT #28 SWITCH
J11-3 INPUT #2 RETURN
TB10-14 LOAD DEMAND STOP CONFIGURABLE I/P#31
J11-4 INPUT #2 SENSE
TB10-15 RAMP LOAD/UNLOAD CONFIGURABLE I/P#32
J11-5 INPUT #3 SENSE RETURN (SEE SHEET 2)
TB10-16 RETURN
J11-6 INPUT #3 SENSE (SEE SHEET 2)
TB10-17 RETURN
J11-7 INPUT #4 SENSE RETURN (SEE SHEET 2)
J11-8 INPUT #4 SENSE (SEE SHEET 2)
J11-9 INPUT #5 SENSE RETURN
J11-10 INPUT #5 SENSE
J11-11 INPUT #6 SENSE RETURN
J11-12 INPUT #6 SENSE
J11-13 INPUT #7 RETURN
J11-14 INPUT #8 SENSE (ANALOG 0-38VDC)
J11-15 INPUT #8 RETURN
J11-16 INPUT #8 SENSE (ANALOG 0-38VDC)

A A

UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN


DIMENSIONS ARE IN MILLIMETERS
DO NOT SCALE PRINT
N_SCHOTTLER
CUMMINS POWER GENERATION
CKD
X ` 0.00- 4.99 +0.15/-0.08
N_SCHOTTLER

5.00- 9.99 +0.20/-0.10 APVD

HOLE
M_POZO

DIM
.X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
.XX` - CONFIDENTIAL - DWG DWG

PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 6 OF 6 C

6 5 4 3 2 1

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 6 of 7
Part A035H705 C
Description Legacy Name External Regulations Application Status Release Phase Code Security Classification Alternates
DIAGRAM,SCHEMATIC A035H705 None Production & Service Production Proprietary

Part Specifications :A035H705 C


Name Description Legacy Name
A030B356 SPECIFICATION,MATERIAL CES10903
A035H706 DRAWING,ENGINEERING A035H706

Drawing Name: A035H706 Revision: C


Part Name: A035H705 Revision: C
Sheet 7 of 7