REL NO LTR NO REVISION DWN CKD APVD DATE
ECO - 129979 C 1 SEE SHT 5 TLD JTB T.AJAYI 25OCT12
D D
Notes:
1. Fusing requirements for Arc flash protection for TB7 (Bus/Utility Voltage Sense)*: If your potential circuits have available incident energy > 1.2 Cal/cm2 or 5J/cm2 then you need to protect for arc flash in the lines feeding TB7**.
Available Incident energy > 1.2 Cal/cm2 or 5J/cm2 is typically found when any of the the following is true:
B) Paralleled OR
2. Fusing requirements for Arc flash protection for TB7 (Bus/Utility Voltage Sense)*: If Available Incident energy is > 1.2 Cal/cm2 or 5J/cm2 then the use of current limiting fuses or other suitable means in the lines feeding J22 and TB7** are needed.
B) Use 600Vac rejection type fuse holder with AIC=200kA rating, e.g. Ferraz Shawmut 30323R or equiv.
**Fusing protecting the circuit feeding TB7 must also meet all local code requirements.
0630-2941
0630-3613
0630-3080
0630-2867
0630-2868
0630-2873
A A
DIM
M_POZO
DIAGRAM, SCHEMATIC
HOLE
.X ` 10.00-17.49 +0.25/-0.13
DATE SITE CODE
17.50-24.99 +0.30/-0.13 01-04-2011
.XX` - CONFIDENTIAL - DWG DWG
PGK
FOR INTERPRETATION FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 1 OF 6 C
6 5 4 3 2 1
Sw B+ K7 SW B+ T26
REMOTE E-STOP 3300 TB1-16 1B P2-12
1A 1B
5 4 S7-B 3B
JUMPER 1 2A 2B J20-11
1 2 3300 TB1-15
3A 3B P2-5 6 1 P-SWB+ 2B
REMOTE J20-11 Starter Disconnect Input T26
P2-13
P3-B
JUMPER 2 4A 4B
E-STOP 4 3
REMOVE K10-86
1B
E-STOP B+
PCC3300 J20-13 Relay Coil B+ Supply
J20-16 Oil Priming Pump Relay Driver
Starter K9
5 4
X10 (10A) B1-BAT P3-A
P3-C
HEATER CONTROL (P3)
D D
JUMPERS 2B X20 (20A)
P20-3 B1-BAT
P2-14 ENG SP4
1 AND 2 TO
INSTALL
3B BASEBOARD P20-15 P2-6 6 1 P2-10
K4-S1
SP4 1B
FUSED B+ K9-1 S1
K4
S2
4B P2-15
REMOTE E- P20-14 FSO K8 TB-BAT
2B
STOP K16-A X21 (20A)
P20-9 5 4 3B B1-BAT K4-BAT K4 K4+
USER INTERFACE GND P20-10
P20-20 P2-7 6 1
P21-9 (AUX 105)
HMI-SP1
4B
5B
P20-21 SwB+ - 3B BATTERY Starter 1 Starter 2
LOCAL E-STOP B+ F-FSO 3A
PART NUMBERS P20-5 A B P2-11
FSO (K1) CHARGING
3 4 ALTERNATOR G1-B+
FUSED B+ PCC3300: 0327-1601 P20-17 S7-C B+ 24VDC
E-STOP 2 1 INPUT (WAKE-UP ON OPEN) P25-2 P20-22 S7-B GND
COOLANT
G1-D+
B1-BAT BT1
LEVEL (S7)
P20-2
P20-4
S7-D SIG G KS KS
RETURN P25-6 HARNESS, INTERFACE SHIELD GROUNDED IN FOUR PLACES
(WORT BOX): HARNESS ENGINE:
A035H837
P20-7
G1-GND
M BT2 M
TB15-1 GND A035H282 P20-12
K10-SP B+ RETURN GND-ENG
TB15-3 RS485 A P29 must be P20-1 1B
HMI 320 PC
TOOL
TB15-4 RS485 B
disconnected to
use PC Tools on
P20-6
P20-18 3B
P2-8
B1-GND KS B1-SW1 KS
BARGRAPH
1B BUS L1
2B BUS L2 USE PTs
IF LL
TB7-1
TB7-2 9 6 J4-5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
SEE SHEET 5
LEGEND
3B BUS L3 TB7-3 TB15-5 WAKE-UP3
VOLTAGE FUSED B+ - 2B SEE SHEET 5
P1-3 PCC NET A (+) 4B BUS L4 >600VAC TB7-4 A B
PART NUMBERS P1-5 (AUX 101) AUX 101 IS REQUIRED FOR EXHAUST SEE SHEET 5 OPTIONAL
P1-4 PCC NET B(-) P26-2 TEMPERTURE SENSING.
HMI 114: MODBUS
P1-5 SYSTEM WAKE-UP J26-3 AVR PWM- 1B
0300-6366-02 SEE FUSING REQUIREMENTS ON SHEET 1.
J26-5 AVR B+ RETURN FACTORY CONNECTIONS
P6-2 B+ RETURN J26-6 N/A 1
P12-1 3B
P6-1 HMI FUSED B+ D1
J26-7 FIELD CURRENT- 2 4B FAST ON CONNECTOR
P12-4
J26-8 B+ RETURN 3 5B
P12-2
J26-9 AVR B+
P12-5 HARNESS, HARNESS, SET SCREW TERMINAL
J26-14 FIELD CURRENT+
P12-3 ALTERNATING INTERFACE
CURRENT: PCC3300 TO AUX 105: J26-16 AVR PWM+ LOW COOLANT TEMPERATURE (S4)
P12-6 PLUG CONNECTOR
A034Y614 A035G905 J26-17 N/A
J26-18 KEYSWITCH B+ OUT
- GENSET VOLTAGE
P22-1
P26-15
RING TERMINAL
DRIVER ALTERNATOR P22-2
P26-1 P1939 SHLD
RATING P26-10 P1939 (-)
B
P22-3
B
G
P26-11 P1939 (+) 120 ohm Opens @ 85F, Closes @ 65F
S: P22-4
P26-12 PCC NET A (+)
4 AMPS P26-13 PCC NET B (-)
PEAK : P26-4 SHLD
6 AMPS
+
AUX 104 FUEL ACTUATOR (6AMP MAX)
ACT (-)
P21-12 GOV POWER STAGE ACT (+)
TERMINAL BLOCK
AUX 105 P21-8
P21-2
Part numbers
J1-1
J1-2
P1 - 1
P1 - 2
N W V U HM ECM & AVR P21-3 120 ohm Aux 104: 0327-1507 J1-5
P1-5 GOV PS POWER
CT-23
POWERSTAGE B+ RETURN - 1B Sockets: 0323-1200 J1-3
P1-3 GOV PS POWER
CT22-1 87 85
P21-9 FUSED B+ - 3B OIL PRESSURE (E1)
K10 KEYSWITCH
CT-22 E1-B
CT22-2/3 30 86
P21-11 E1-A
E-STOP B+ - 2B
CT23-1 PART NUMBERS E1-C
CT-21 AUX 105: A028T766
CT23-2/3
G FIELD (+)
FIELD (-)
AVR CONTROL
P17-1
P17-2
P11-13 SENSE
P11-14 RETURN
P11-15 SENSE
E4-B
P11-16 RETURN
UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN
PC TOOL
TB15-1 GND DIMENSIONS ARE IN MILLIMETERS
DO NOT SCALE PRINT
N_SCHOTTLER
CUMMINS POWER GENERATION
J5-1 CKD
RS485 SHIELD
COOLANT TEMP RIGHT BANK (E3) X ` 0.00- 4.99 +0.15/-0.08
N_SCHOTTLER
TB15-3 RS485 A HARNESS, INTERFACE E3-A 5.00- 9.99 +0.20/-0.10 APVD
HOLE
M_POZO
DIM
J5-3
J5-4
TB15-4 RS485 B PC TOOL: A040G672 E3-B .X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
TB15-5 WAKE-UP 17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
J5-5 .XX` - CONFIDENTIAL - DWG DWG
PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 2 OF 6 C
6 5 4 3 2 1
D D
MAG PICKUP
(P1)
A
C
C C
C
A
B B
OIL OIL
TB-BAT K4
TEMPERATURE GND ENG PRESSURE
T 26 (E4) (E1)
B B
COOLANT
LEVEL (S7) SEE NOTE 1
HMI 114
A A
RADIATOR VIEW
CT-21
CT-23
CT-22
UNLESS OTHERWISE SPECIFIED, ALL SIM TO DWN
CUMMINS POWER GENERATION
N_SCHOTTLER
DIMENSIONS ARE IN MILLIMETERS
LOCAL E-STOP X `
DO NOT SCALE PRINT CKD N_SCHOTTLER
0.00- 4.99 +0.15/-0.08
5.00- 9.99 +0.20/-0.10 APVD M_POZO
DIM
DIAGRAM, SCHEMATIC
HOLE
.X ` 10.00-17.49 +0.25/-0.13
VIEW A-A 17.50-24.99 +0.30/-0.13
DATE SITE CODE
VIEW B-B .XX` - CONFIDENTIAL - FOR INTERPRETATION
01-04-2011
DWG DWG
PGF D
FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 A035H705 3 OF 6 C
6 5 4 3 2 1
D D
1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4
B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B
C
B L L L/N L/N G L1 L2 L3 N
C
1B 2B 3B 4B 5B 6B
AUX 104
TB1 TB8
K7 K8 K9 J18
J TB3 TB5 TB10
1
J26 J14
J25
TB
15
J4 DC WIRE
J J17 ENTRANCE
B 10 B
TB
J J3 J20 9
11
J21
J2 J11
TB
15
A A
AUX 101 AUX 105 3300
DIM
M_POZO
VIEW C-C DIAGRAM, SCHEMATIC
HOLE
.X ` 10.00-17.49 +0.25/-0.13
DATE SITE CODE
17.50-24.99 +0.30/-0.13 01-04-2011
.XX` - CONFIDENTIAL - FOR INTERPRETATION DWG DWG
PGK D
FIRST USED ON SHEET
SIZE REV
PROPERTY OF CUMMINS OF DIMENSIONING AND
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 A035H705 4 OF 6 C
6 5 4 3 2 1
PARALLELING CIRCUIT
OPTIONAL RELAYS BREAKER RELAY CONTROL
PCC
3300 TB1
A1 13 21 43 43 ALARM
A2 14 22 44 44
RELAY K21 RTD CONNECTIONS
ALARM MODULE THERMISTOR RELAY
FUSED B+ -1A
D PCC J22-4 (N) D
TB1-5 3300 TB1 WHITE
B+
K19 N.D.E
TB1-6 RED
A1 13 21 43 43 CONFIGURABLE K17 BEARING
A1 13 21 43 43 AUDIBLE (TIMER 0-10SEC) RED RTD
RESET
RELAY K13 PCC 3300 TB8-7
TB1-8 A2 14 22 44 44
A2 14 22 44 44 ALARM WHITE
TB1-9 MODULE J22-3 (W) FAT (2A) D.E
B+ RETURN -2B RED
TB1-5 J1+ BEARING
TB1-10 B+ A1 A2 R RED RTD
GND
A1 13 21 43 43
CONFIGURABLE CIRCUIT BREAKER TRIPPED 16 18 26 28
J2- K18 WHITE
A2 14 22 44 44 RELAY K14 (TEMPERATURE RED
PCC PTC W2
3300 TB8 TB1-8 MONITORING) 15 25
PC3300 TB10 Ta Tb RED RTD
K20 TB1-9 WHITE
TB10-2 Generator Circuit Breaker
A1 13 21 43 43 A1 13 21 43 43 TB1-10 RED
CONFIGURABLE GND V2
A2 14 22 44 44 RELAY K15 A2 14 22 44 44 SDE Contact RED RTD
K17
WHITE
(DELAYED MAKE)
RED U2
TB5
CLOSE STATUS OUTPUT RED RTD
PCC 3300 TB8-12 WHITE
TB8-9 RED W1
TB8-10
OPEN STATUS OUTPUT RED RTD
TB10-10
WHITE
RED
C
V1
C
RED RTD
WHITE
ALT. TEMP
THERMISTORS RED U1
RED RTD
Fuel Level
GROUND FAULT RELAY
PCC
3300 TB8 B+ RETURN - 2B CT1
RHI1 Fused B+ - 1A
CT3
RHI1 PCC
FUSE1 3300 TB1
A1 A2 T1 T2
4A
252
253
254
255
90
N
E
E
B
TB8-8
5 3 8 K22 B
K23
6 4 1
RH99M
HT1 HT2
PCC 3300 TB1-13 - WIRING DIAGRAMS SHOWN ON THIS SHEET
BATT -VE
(B+ RETURN) ARE GENERALIZED, SEE SPECIFIC INSTALLATION
TB8-13
DRAWINGS FOR EACH OPTION FOR MORE
BATT +VE INFORMATION.
Low Fuel warning SHUNT TRIP
(SW B+) 32 31 34 25 26 27 11 14
TB1-12 ST-1
HE1 HE2
TB1-13 ST-2
TEST
Customer Inputs
ON (RELAY OPERATIONAL)
Terminal block
1A 2A 3A 4A
RESET
Low Fuel Shutdown
1A 2A 3A 4A 5A
1B 2B 3B 4B 5B
ALTERNATOR HEATER
HP
HA
HOLE
M_POZO
DIM
.X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
.XX` - CONFIDENTIAL - DWG DWG
PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 5 OF 6 C
6 5 4 3 2 1
TB5-1 GENSET CB CLOSE STATUS TB9-10 + KVAR LOAD SHARE LEVEL J4-5 RELAY 8 COM
TB5-2 GENSET CB CLOSE STATUS TB9-11 - KVAR LOAD SHARE LEVEL J4-6 RELAY 8 NC
TB5-3 GENSET CB OPEN STATUS
TB5-4 GENSET CB OPEN STATUS
J10-1 CAN H
TB5-5 GENSET CB OPEN STATUS
J10-2 CAN L
TB5-6 UTILITY CB CLOSE STATUS
J10-3 INPUT #3 CURRENT SOURCE (SEE SHEET 2)
TB5-7 UTILITY CB CLOSE STATUS
J10-4 INPUT #4 CURRENT SOURCE (SEE SHEET 2)
TB5-8 UTILITY CB OPEN STATUS TB10-1 RETURN
J10-5 INPUT #5 CURRENT SOURCE
TB5-9 UTILITY CB OPEN STATUS TB10-2 RETURN
J10-6 INPUT #6 CURRENT SOURCE
TB10-3 UTILITY CB POS A SWITCH
J10-7 5VDC SUPPLY #1 (20 mA MAX)
TB10-4 UTILITY CB POS B/CONFIGURABLE INPUT #23 SWITCH
J10-8 5VDC SUPPLY #2 (20 mA MAX)
TB10-5 UTILITY CB TRIPPED SWITCH
J10-9 INPUT #3 CURRENT RETURN (SEE SHEET 2)
TB10-6 UTILITY CB INHIBIT/CONFIGURABLE INPUT #25 SWITCH
J10-10 INPUT #4 CURRENT RETURN (SEE SHEET 2)
TB10-7 GENSET CB POS A SWITCH
J10-11 INPUT #5 CURRENT RETURN
TB10-8 GENSET CB POS B/CONFIGURABLE INPUT #26 SWITCH B
J10-12 INPUT #6 CURRENT RETURN
TB10-9 RETURN
TB10-10 GENSET CB TRIPPED SWITCH
TB10-11 GENSET CB INHIBIT/CONFIGURABLE INPUT #28 SWITCH
J11-1 INPUT #1 RETURN
TB10-12 UTILITY SINGLE MODE VERIFY/CONFIGURABLE INPUT #29 SWITCH
J11-2 INPUT #1 SENSE
TB10-13 SYNC ENABLE/CONFIGURABLE INPUT #28 SWITCH
J11-3 INPUT #2 RETURN
TB10-14 LOAD DEMAND STOP CONFIGURABLE I/P#31
J11-4 INPUT #2 SENSE
TB10-15 RAMP LOAD/UNLOAD CONFIGURABLE I/P#32
J11-5 INPUT #3 SENSE RETURN (SEE SHEET 2)
TB10-16 RETURN
J11-6 INPUT #3 SENSE (SEE SHEET 2)
TB10-17 RETURN
J11-7 INPUT #4 SENSE RETURN (SEE SHEET 2)
J11-8 INPUT #4 SENSE (SEE SHEET 2)
J11-9 INPUT #5 SENSE RETURN
J11-10 INPUT #5 SENSE
J11-11 INPUT #6 SENSE RETURN
J11-12 INPUT #6 SENSE
J11-13 INPUT #7 RETURN
J11-14 INPUT #8 SENSE (ANALOG 0-38VDC)
J11-15 INPUT #8 RETURN
J11-16 INPUT #8 SENSE (ANALOG 0-38VDC)
A A
HOLE
M_POZO
DIM
.X ` 10.00-17.49 +0.25/-0.13
DATE
DIAGRAM, SCHEMATIC
17.50-24.99 +0.30/-0.13 01-04-2011 SITE CODE
.XX` - CONFIDENTIAL - DWG DWG
PGK
FOR INTERPRETATION FIRST USED ON SHEET
OF DIMENSIONING AND SIZE REV
PROPERTY OF CUMMINS
ANG TOL: ` SCALE
:
POWER GENERATION
TOLERANCING, SEE
ASME Y14.5M-1994 KTA38 D A035H705 6 OF 6 C