S-06

S-04
North Elevation House A General notes.
10,040 15,474
3,540 5,000 1,500 13,774 1,700 (To be read in conjunction with standard specifications)
500
200 3,340 200 4,600 200 1,300 200 200 3,640 200 150 3,580 150 1,500 200 3,454 200 1,500 200 (All dimensions are in millimetres)
RESIDENTIAL & COMMERCIAL BUILDINGS
1,420 900 1,220 1,200 2,600 1,200 1,500 3,040 800 2,200 1,500 1,180 700 1,600 900 1,854 1,700 1.1. All dimensions to be checked on site, written dimensions to be followed in
900 2,400 700 1,900 1,900 900 900 preference to scaled dimensions.
2. Depth of foundations to be determined on site but not to be less than 1200 deep.
3. Wall foundations to consist of 1:3:6 concrete mix, reinforced with 3 Nos. 16mm

East Elevation House A


House A
diameter M.S. bars with 8 mm diameter M.S. bar links at 300 c/c. Cover to
North Elevation House B North Elevation House B reinforcement to be 75mm min. (R.C. foundations of columns to Structural Eng.'s detail).
4. D.P.C. to be three-ply approved quality bituminous felt.

300

S-01
5. Foundations should not encroach into adjoining plots.

1,200

S-01
6. 500 g polythene sheeting and anti-termite treatment to be provided under ground floor
Balcony

S-02
concrete slab.

S-02
400
200

7. The ground floor level to be minimum 600 above the existing natural ground level or
2,000 litre as agreed on site.
West Elevation

350 8. Garage and carport floor slab to be reinforced with B.R.C. mesh 64.
1,000

1,000

Crest tank

200
6,884 9. All walls less than 200 thick to be reinforced with hoop iron at every alternate course.
800

5,810

1,900
10. P.V. denotes permanent vent and F.L. denotes fan-light.

800
11. All reinforced concrete work is to be in accordance with Structural Engineer's details.
12. All sanitary work to be in accordance with M.O.H. rules and regulations.
200

13. Urinals to consist of glazed clay.


Master 14. Where drain passes under building or drive-way area, pipe to be of cast iron or encased
1,923

in 150 concrete.

200

200

2,230

2,230
Bedroom 15. All wate pipes and soil pipes are to be in ducts and the bends to have all cleaning eyes

1,560
accessible from outside.

4,
2,060
2,750

8
16. All windows to have P.C. cill, built-in P.V., pelmet box and timberwindow board to detail.

5,500

22
Master Sitting & Dining rooms to have bigger pelmet boxes to detail.

5,300
17. All windows and external glazed doors to have burglar proofing to detail.
Bath 9
38 18. Provide standard type timber cornice and skirting where required.
900
900

7,
4,300

19. All door frames to be rebated & moulded & be full width of wall with moulded

4,110

4,110
1,500
1,900
architraves to detail. Provide rubber door stops to all doors.
Master

5,920

East Elevation House B


20. Stair case doors to be self closing and 1/2 hour fire resistance.
S-03

900
900
790

East Elevation House B


S-03 Bath S-03 21. All internal plaster to be lime, two coats steel float finished.

1,900

6,820
5,920
800
22. No roof timber to be placed within 300 of chimney flue.

6,120
Bedroom 2 23. All sanitary fittings to be ''shanks'' or ''armitage'' or other approved type.
Bedroom 3 24. Provide 1500 high white glazed wall tiles on all exposed walls in kitchen, baths,
2,277

(girls' room) toilets, showers and cloak rooms.

2,
750

56
25. Provide medicine cabinet with mirror and glass shelf over all W.H.B.

1,861

2,250

7
2,240 200 (except in domestic staff house) size600 x 400 x 150 deep.

200

200
26. Provide approved type C.P. shower fittings with tap, C.P. towel rails, hooks, bolts etc. in

800 1,000
bath and showers. All tubs to have telephone shower fittings. (W.H.B. to have mixer fittings)
200

200
27. All manholes within building area, drive-way and parking area to have heavy duty air

710 550
1,441

Prayer room tight covers and double sealed.


11,200

3,234

1,410
13,600

13,600

150
1,700 28. Provide G.I. 125 X 100 rainwater down pipes and 125 x 100 G.I. box gutter with brackets

2,
Landing
1,500
1,900

700
900
1,900

34
or etc. where shown.
2,300

2,400

5
710
29. Provide 150 wide open rainwater concrete channels 1800 long to all downpipes.
S-05 S-05 1,000 150 1,230 200 2,104 150 1,200

11,820

11,820
DOWN UP 30. Painting to be 4 coats (last coat at retention time).
Family room

499

200
200
31. Lay 1 layer of paving slabs 600 x 600 on sand along the perimeter of buildings & S.Q.
1,059

1
22 2 32. Provide D.P.C. to all boundary walls.

22 x 159 = 3,500
33. Each house, flat or floor to have separate water & electrical meter. Owner to pay

1,000
21
9
3
1,000 200

1,200
07

1,767

1,767
20
790 7 meter charges.

2,100
4

1,567
1,059 Bedroom 2 66 4,
1,875

19 34. All ironmongery to be imported type. Samples to be produced.


9 4,
200

200
38

West Elevation House B


18
Landing 35. Samples of fittings, materials etc. to be produced & approved before commencing work.
6

7,

6,700

2,070

4,079
West Elevation House B
17 7

200

1,900
16 8
1,250 1,150 WAREHOUSES, FACTORIES, WORKSHOPS ETC.

800
Bedroom 3 Master 4

3,630
15 9

04

3,630
2.1. The following clauses mentioned above to apply 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
Prayer room 14 10

Bedroom 5,
86 13, 14, 18, 19, 20, 21, 23, 27, 28, 30, 32, 34.

1,347
700
900
22 13
(girls' room)
11
700
900

877

1,0

1,851
3,1 2. All office windows to have P.C. cills, built in P.V., Pelmet boxes & timber window
21
or 12
3,800

37
2,230
3,700
DOWN UP
20 22 Cills & Skirtings.

8
1,630
19 3. Steel trusses/portal frames & purlins to be painted with 2 coats of oil paint.

3,233
Family room
1
18 2 1,112 4. Windows to be burglar proofed with 16 mm twisted M.S. bars at 125 mm c/c, lugs,
22 x 159 = 3,500

2,100
2,025

17 3
stiffners etc. to be provided.
16 4
5. All steel doors to have wickets to detail.

4,133

4,133
15 5
6. All steel doors to be made of 75 x 75 x 6 M.S. angle frames with 14 g thick

200
14 6
M.S. plate panels & provided with heavy duty hinges/sliding gears & 3 Nos. cleats on

3,5
13 both sides for locks, handles etc. If sliding gear is outside provide G.C.I. cover.
200

200
7
6,550 4

7
400

400
12 8
Each panel should not be bigger than 600 x 600.
balcony 04

2
550 150
2,070

2,070
5,
11 9
350 7. Toilets - provide white glazed tiles to 1200 height everywhere. Provide mirrors 600 x 450

1,870

S-022,070
10
5 over all W.H.B.s, paper holders, 2 Nos. coat hooks behind each door.
56 8. Fire Fighting Equipment to be provided as shown on plan.
3,
1,200

1,200
R 6,178
House B
1,400

1,400
House B 2 9. Each Godown to have separate water & electrical meter. Owner to pay for meter charges.
1,900

1,900

19
800

800

, TARMAC DRIVES

S-02
3
S-06

First Floor Plan R 4,800 Roof Plan 3.1 50 mm Premix laid in two layers on 150 quarry chips on 300 hardcore filling well

200
244

200
450
consolidated & rolled with 14 tons roller. Provide P.C. Curbs to all sides. Drives to be
6,313
200
200

200

200

well sloped for draining the rainwater.


1,851
1,540 600 400 800 400 600 750 800 1,650 800
500
700 500 Total Floor Area = 149.8 m2 ROOFING FELT ON R.C. SLAB
1,900 1,900 1,900 1,900 900 4.1. Four layers of Bituminous roofing felt on 50 pumice screed on 50 hollow pots on

S-01
S-01
R.C. flat roof to structural
200 1,340 200 2,400 200 550 150 3,300 200 1,300 200 Engineer's detail, screed laid to fall min. 75 in 3000 (provide aluminium trim on all edges).
First layer asbestos based felting 16 kg/10 sq.m.
1,540 2,800 5,700 Second layer asbestos fellting 23 kg/10 sq.m.
790 1,100 1,500 1,750 400 1,000 400 400 4,001 4,133 Third layer asbestos based felting 50 kg/10 sq.m.
10,040 1,900 1,900 1,900 Top layer 12 stone chippings bedded in bituflex.
House A 200 590 200 3,550 200 2,600 200 3,801 2,233 1,700 200
(If 3rd layer is mineral finish, chippings may not be laid).
2. Guarantee of 2 years to be provided.
South Elevation House A First Floor Plan 2. Roof Plan 1:100 3. Lay Funtkote to ''colas A4 specification''.
790 6,550 4,001 4,133
5.1. All Existing work shown uncoloured.
Total Floor Area = 120.6 m2 15,474 All new work shown shaded or in Red.
Work to be demolished dotted or in yellow.
South Elevation House B This drawing is to be read in conjunction with drawing Nos.
S-04

P.C. SUMS OR PROVISIONAL SUMS


6.1. Contractor is to include the following P.C. Sums or Provisional Sums in his Contract
and must allow for attendance to all Sub-Contractors and his profit in his Tender.
1. First Floor plan 1:100 1. First Floor plan 1:100 a) Contingencies: Shs. ...............................................
b) Electrical work: Shs. ..............................................
c) Gates, pillars and Electrical lamp wiring etc.: Shs. ...............................................
d) Drive-way and parking areas: Shs. ............................................

S-06
nk

e) Fittings: Shs. .............................................


S-06

S-04
ta

f) Plumbing: Shs. .............................................


S-04
ic

g) Lithography charges payable


(M/S PLANNING & DESIGN ASSOCIATES) Shs. ............................................
pt

North Elevation House A


Se

h) Complete roof work, fabrication &


10,040
North Elevation House A 15,474
installation etc. by Contractor Shs. ...............................................
to

i) Shs. .............................................
3,540 5,000 1,500 13,774 1,700
j) Shs. ............................................
MH 200 3,340 200 4,600 200 1,300 200 200
200 3,640 200 2,000 200 6,584 150 600 1,500 200
620 2,500 420 1,000 3,000 1,000 1,500
2,400 2,400 200 200 3,540 5,700
3,040 800 2,000 1,130 1,500 2,150 800 1,354 600 800 900
700 3,400 700 1,900 2,400 1,900 1,900 2,400

West Elevation House A


East Elevation House A
House A

North Elevation House B


2,000

1 Proposed residential building on plot 7529


03

2,600
S-01
4,
1,600

Front Block 244 Kyadondo county Ssabagabo Subcounty

S-02
porch to At Kisugu Mengo District, Kampala
400 400

600 200
800 200

open deck S ep
West Elevation

MH MH
1,375

tic
1,000

1,900
200
1,900

GT GT GT
t an

200
200
200

MH k

7,100
150 400
200

4,
Back
200
1,500

03
1,000
1,560

2,600
1
Pantry
1,800

2,060
porch No. Revision/Issue Date

1,110
MH

6,
53
4,100

4
200

GT
5,300
1,900
1,500

4,110

1,900
1,500

700

200
4,300

kitchen

East Elevation House B


3
S-03 S-03 50 Consultant:
8,100

5,920
2,
6,120

2,910
2,500
2,400

lounge

2,600
2,400
Bedroom 4
1,861

dining
1,900
2,450

F
200
600

3,860
250
Consultants
200
900
200

200

200

200 200

11,900
1,410

2,660
F
dining

1,260
900
700

3
11,200

stairs 23 plot 137/A


13,600

13,600

5,
1,900

2,400
2,300

800

900

11,820

11,820
Pantry
DOWN UP
S-05 Kira road
MH
499
2,400

S-05 Side S-05


3,100

200

200
kitchen
1
22 2 P.O.Box, 33096, Kampala

200
porch
22 x 159 = 3,500
1,000

21 3
tel. 0414 234025, 0790837463
800
600 950

1,200
200

1,392
2,400
20 4

1,
GT 19 jr.utlonline.co.ug

30
5

2,582
18

1
6
2,400

West Elevation House B

7,400
150 600

17
200

2,382
200

7
1,300

200

1,400

16
stairs
8
800

1,500
3,630

15
lounge
9

990
14 10
350 150 13 11 Project:
1,200

Laundry 12 4
Bedroom 4
2,230

53 PROPOSED RESIDENTIAL BLDGS.


700
900

22

6,
1,630

21
3,700
4,100

961
DOWN UP
3,400

5,
20

1,399

23
3,050

19 1
ON PLOT 7529 BLOCK 244 KISUGU

3
1,650 150

18 2
22 x 159 = 3,500

2,100

17
GT
3
16 Client:

3,118
4
200

3,318

3,318
15
MR. KENNETH SEMAFUMU
5
14 6
13
MH GT MH
200

200

front R 5,300
2,070

2,070

P.O. BOX 16568, KAMPALA


1,870
400

400

12 8

1,380
11 9
10
porch

1,200
House B Consultant:

1,400
1,200

1,200

350
1,400

1,400

S-02
1,900

1,900

Arch. ABDU-WAHAB NYANZI


800

800

R 4,000

S-06
GT Ground Floor Plan
200

MH MH 200
S-06

1,399 Reg. No. 191, PC. No. 2287

200
Total Floor Area = 152.5 m2 2,000 litre
200

200

200

200

320 500
520 700 600 400 800 400 600 750 800 1,650 800 700 500 961 Crest tank
900 1,900 1,900 1,900 1,900 900
S-01

350 1,890 2,800 6,050 Description: Drwg. No.


200 1,340 200 2,400 200 550 150 3,300 200 1,300 200 790 1,750 800 700 750 400 1,000 400 400 1,675 1,500 1,641 3,318
MH 1,400 900 1,900 1,900 1,900 200 2,400 200
1,540 2,800 5,700 200 590 200 2,350 200 1,000 200 2,600 200 4,616 3,118 200 House A AS SHOWN AL/MYG/16-02-1
10,040
House A 790 6,550 4,816 3,318 Roof Plan Revision: Issue status:
15,474 South Elevation House A
South Elevation House A Ground Floor Plan BOQ
Date: August 2016 final design
Total Floor Area = 134.7 m2 South Elevation House B 2. Roof Plan 1:100 Scale: as shown A1 paper
construction
schematic design
S-04

0. Ground Floor Plan 1:100 0. Ground Floor Plan 1:100


PLOT 7283 PLOT 7282
General notes.
Boundary wall 23.1 North Elevation House B
12,498
Boundary wall 37.9 (To be read in conjunction with standard specifications)

2.7
(All dimensions are in millimetres)

2.7 5.4

S-01
606,812,876 mm 2
RESIDENTIAL & COMMERCIAL BUILDINGS

S-02
2,475

2,475
1.1. All dimensions to be checked on site, written dimensions to be followed in
MH MH Soak-away pit preference to scaled dimensions.

ry wall
GT GT GT
7,353 Septic tank 2. Depth of foundations to be determined on site but not to be less than 1200 deep.
MH 3. Wall foundations to consist of 1:3:6 concrete mix, reinforced with 3 Nos. 16mm
152,505,512 mm 2
13,774 12,095 diameter M.S. bars with 8 mm diameter M.S. bar links at 300 c/c. Cover to
reinforcement to be 75mm min. (R.C. foundations of columns to Structural Eng.'s detail).

PLOT 2069
4. D.P.C. to be three-ply approved quality bituminous felt.

Bounda
5. Foundations should not encroach into adjoining plots.
6. 500 g polythene sheeting and anti-termite treatment to be provided under ground floor

East Elevation House B


6,120
S-03 S-03 concrete slab.
7. The ground floor level to be minimum 600 above the existing natural ground level or
as agreed on site.
8. Garage and carport floor slab to be reinforced with B.R.C. mesh 64.

9,750
9. All walls less than 200 thick to be reinforced with hoop iron at every alternate course.
790 6,550 6,434 1,700

11.3
10. P.V. denotes permanent vent and F.L. denotes fan-light.
11. All reinforced concrete work is to be in accordance with Structural Engineer's details.

Area for future


MH 12. All sanitary work to be in accordance with M.O.H. rules and regulations.

GT House B 13. Urinals to consist of glazed clay.


14. Where drain passes under building or drive-way area, pipe to be of cast iron or encased
in 150 concrete.

West Elevation House B

3,630
Boundary wall
15. All wate pipes and soil pipes are to be in ducts and the bends to have all cleaning eyes

Development
accessible from outside.

22,824
8,781 16. All windows to have P.C. cill, built-in P.V., pelmet box and timberwindow board to detail.
7,847 Sitting & Dining rooms to have bigger pelmet boxes to detail.
17. All windows and external glazed doors to have burglar proofing to detail.
18. Provide standard type timber cornice and skirting where required.

2,070
GT MH 19. All door frames to be rebated & moulded & be full width of wall with moulded
MH
architraves to detail. Provide rubber door stops to all doors.
20. Stair case doors to be self closing and 1/2 hour fire resistance.

S-02
21. All internal plaster to be lime, two coats steel float finished.
6,216 1,918 22. No roof timber to be placed within 300 of chimney flue.

wall
23. All sanitary fittings to be ''shanks'' or ''armitage'' or other approved type.
24. Provide 1500 high white glazed wall tiles on all exposed walls in kitchen, baths,

S-01
toilets, showers and cloak rooms.

ry
25. Provide medicine cabinet with mirror and glass shelf over all W.H.B.
3 2 1 (except in domestic staff house) size600 x 400 x 150 deep.

Bounda
26. Provide approved type C.P. shower fittings with tap, C.P. towel rails, hooks, bolts etc. in
2 West Elevation House A 1:100 bath and showers. All tubs to have telephone shower fittings. (W.H.B. to have mixer fittings)
27. All manholes within building area, drive-way and parking area to have heavy duty air
tight covers and double sealed.
Bou South Elevation House B 400
nda 31, 28. Provide G.I. 125 X 100 rainwater down pipes and 125 x 100 G.I. box gutter with brackets
etc. where shown.
ry w
Soak-away pit
all 25,3
00
8. 1 29. Provide 150 wide open rainwater concrete channels 1800 long to all downpipes.
30. Painting to be 4 coats (last coat at retention time).
31. Lay 1 layer of paving slabs 600 x 600 on sand along the perimeter of buildings & S.Q.

3 32. Provide D.P.C. to all boundary walls.


33. Each house, flat or floor to have separate water & electrical meter. Owner to pay
meter charges.
34. All ironmongery to be imported type. Samples to be produced.
Bou 35. Samples of fittings, materials etc. to be produced & approved before commencing work.
nda

13,399
ry w

5,
WAREHOUSES, FACTORIES, WORKSHOPS ETC.

60
all

Septic tank
6m swing

0
2.1. The following clauses mentioned above to apply 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,

Boundary wall
13, 14, 18, 19, 20, 21, 23, 27, 28, 30, 32, 34.
gate 2. All office windows to have P.C. cills, built in P.V., Pelmet boxes & timber window

10,750
6m sliding Cills & Skirtings.

PLOT 5613

2
3. Steel trusses/portal frames & purlins to be painted with 2 coats of oil paint.
gate 6,7
0 0 4. Windows to be burglar proofed with 16 mm twisted M.S. bars at 125 mm c/c, lugs,

S-06
stiffners etc. to be provided.

S-04
5. All steel doors to have wickets to detail.
6. All steel doors to be made of 75 x 75 x 6 M.S. angle frames with 14 g thick

3
North Elevation House A M.S. plate panels & provided with heavy duty hinges/sliding gears & 3 Nos. cleats on
both sides for locks, handles etc. If sliding gear is outside provide G.C.I. cover.
Each panel should not be bigger than 600 x 600.

ay
MH 7. Toilets - provide white glazed tiles to 1200 height everywhere. Provide mirrors 600 x 450
1,995

-W
over all W.H.B.s, paper holders, 2 Nos. coat hooks behind each door.
8. Fire Fighting Equipment to be provided as shown on plan.

54.6

4
9. Each Godown to have separate water & electrical meter. Owner to pay for meter charges.

East Elevation House A


West Elevation House A

ve
TARMAC DRIVES
PLOT 7531

all
3,275

Dri
3.1 50 mm Premix laid in two layers on 150 quarry chips on 300 hardcore filling well

w
consolidated & rolled with 14 tons roller. Provide P.C. Curbs to all sides. Drives to be
well sloped for draining the rainwater.

ary
3,540

N ROOFING FELT ON R.C. SLAB

und
7,100
4.1. Four layers of Bituminous roofing felt on 50 pumice screed on 50 hollow pots on
MH R.C. flat roof to structural

Bo
GT Engineer's detail, screed laid to fall min. 75 in 3000 (provide aluminium trim on all edges).
First layer asbestos based felting 16 kg/10 sq.m.
Second layer asbestos fellting 23 kg/10 sq.m.
Third layer asbestos based felting 50 kg/10 sq.m.

14,575
Top layer 12 stone chippings bedded in bituflex.

301
(If 3rd layer is mineral finish, chippings may not be laid).

House A 2. Guarantee of 2 years to be provided.

29,
3. Lay Funtkote to ''colas A4 specification''.

ay
5.1. All Existing work shown uncoloured.
S-05 S-05
All new work shown shaded or in Red.

-W
Work to be demolished dotted or in yellow.
This drawing is to be read in conjunction with drawing Nos.

6,700

ve
1 East Elevation House A 1:100 P.C. SUMS OR PROVISIONAL SUMS

8
Dri
Boundary wall
6.1. Contractor is to include the following P.C. Sums or Provisional Sums in his Contract
and must allow for attendance to all Sub-Contractors and his profit in his Tender.

34.
GT
1,552 1,540 2,800 5,700 1,871 a) Contingencies: Shs. ...............................................
134,695,500 mm2

b) Electrical work: Shs. ..............................................

MH MH GT c) Gates, pillars and Electrical lamp wiring etc.: Shs. ...............................................

S-06

ll
d) Drive-way and parking areas: Shs. ............................................

wa
MH e) Fittings: Shs. .............................................

ary
f) Plumbing: Shs. .............................................

und
South Elevation House A g) Lithography charges payable

9,904
(M/S PLANNING & DESIGN ASSOCIATES) Shs. ............................................

Bo
h) Complete roof work, fabrication &

S-04

ay
installation etc. by Contractor Shs. ...............................................

13,907

-W
i) Shs. .............................................
05
11,0
w all j) Shs. ............................................

ve
d ary

Dri
n
Bou 86

8,092
99
,8
12

8,8
y
- Wa

4,002
v e
Dri Proposed residential building on plot 7529
Block 244 Kyadondo county Ssabagabo Subcounty
At Kisugu Mengo District, Kampala

10.0

ACCESS ROAD
No. Revision/Issue Date

3 North Elevation House A 1:100 4 South Elevation House A 1:100 Consultant:

-1. Site Layout 1:200


Consultants plot 137/A
Kira road
P.O.Box, 33096, Kampala
tel. 0414 234025, 0790837463
jr.utlonline.co.ug

Project:
PROPOSED RESIDENTIAL BLDGS.
ON PLOT 7529 BLOCK 244 KISUGU
Client:
MR. KENNETH SEMAFUMU
P.O. BOX 16568, KAMPALA
Consultant:
Arch. ABDU-WAHAB NYANZI
Reg. No. 191, PC. No. 2287

Description: Drwg. No.


AS SHOWN AL/MYG/16-02-2

Revision: Issue status:


BOQ
Date: August 2016 final design
construction
Scale: as shown A1 paper schematic design

East Elevation House B 1:100 West Elevation House B 1:100 South Elevation House B 1:100
Window List
Window sill Window head
Floor (Story) Window Name Quantity W x H Size 2D Symbol 3D Back View
height height
General notes.
Ground Floor Plan Double Sash Window 16 1 1,350x400 1,000 1,400 (To be read in conjunction with standard specifications)

(All dimensions are in millimetres)


RESIDENTIAL & COMMERCIAL BUILDINGS
1.1. All dimensions to be checked on site, written dimensions to be followed in
Ground Floor Plan Double Sash Window 16 4 1,500x1,900 500 2,400 preference to scaled dimensions.
2. Depth of foundations to be determined on site but not to be less than 1200 deep.
3. Wall foundations to consist of 1:3:6 concrete mix, reinforced with 3 Nos. 16mm
diameter M.S. bars with 8 mm diameter M.S. bar links at 300 c/c. Cover to
reinforcement to be 75mm min. (R.C. foundations of columns to Structural Eng.'s detail).
4. D.P.C. to be three-ply approved quality bituminous felt.
20x20x2mm RHS bar Ground Floor Plan Glass Block Wall 16 5 400x1,900 500 2,400 5. Foundations should not encroach into adjoining plots.
6. 500 g polythene sheeting and anti-termite treatment to be provided under ground floor
with pointed top welded concrete slab.
7. The ground floor level to be minimum 600 above the existing natural ground level or
to frame rails as agreed on site.
8. Garage and carport floor slab to be reinforced with B.R.C. mesh 64.
9. All walls less than 200 thick to be reinforced with hoop iron at every alternate course.
Ground Floor Plan Window 16 1 800x1,400 1,000 2,400 10. P.V. denotes permanent vent and F.L. denotes fan-light.
11. All reinforced concrete work is to be in accordance with Structural Engineer's details.
40x25x3mm RHS Frames 12. All sanitary work to be in accordance with M.O.H. rules and regulations.
13. Urinals to consist of glazed clay.
bolted to columns 14. Where drain passes under building or drive-way area, pipe to be of cast iron or encased
in 150 concrete.
15. All wate pipes and soil pipes are to be in ducts and the bends to have all cleaning eyes
Ground Floor Plan Window 16 2 600x1,900 500 2,400 accessible from outside.
16. All windows to have P.C. cill, built-in P.V., pelmet box and timberwindow board to detail.
Sitting & Dining rooms to have bigger pelmet boxes to detail.
17. All windows and external glazed doors to have burglar proofing to detail.
18. Provide standard type timber cornice and skirting where required.
40x25x3mm RHS 19. All door frames to be rebated & moulded & be full width of wall with moulded
architraves to detail. Provide rubber door stops to all doors.
Ground Floor Plan Window 16 2 800x1,400 500 1,900 20. Stair case doors to be self closing and 1/2 hour fire resistance.
columns 21. All internal plaster to be lime, two coats steel float finished.
22. No roof timber to be placed within 300 of chimney flue.
40x25x3mm RHS 23. All sanitary fittings to be ''shanks'' or ''armitage'' or other approved type.
24. Provide 1500 high white glazed wall tiles on all exposed walls in kitchen, baths,
1200

toilets, showers and cloak rooms.


braces
Ground Floor Plan Window 16 5 700x900 1,500 2,400 25. Provide medicine cabinet with mirror and glass shelf over all W.H.B.
(except in domestic staff house) size600 x 400 x 150 deep.
26. Provide approved type C.P. shower fittings with tap, C.P. towel rails, hooks, bolts etc. in
bath and showers. All tubs to have telephone shower fittings. (W.H.B. to have mixer fittings)
50x1mm plates formed 27. All manholes within building area, drive-way and parking area to have heavy duty air
tight covers and double sealed.
to shape 28. Provide G.I. 125 X 100 rainwater down pipes and 125 x 100 G.I. box gutter with brackets
Ground Floor Plan Window 16 10 800x1,900 500 2,400 etc. where shown.
2200

29. Provide 150 wide open rainwater concrete channels 1800 long to all downpipes.
30. Painting to be 4 coats (last coat at retention time).
31. Lay 1 layer of paving slabs 600 x 600 on sand along the perimeter of buildings & S.Q.
Slanted clay tile 200mm thick concrete 32. Provide D.P.C. to all boundary walls.
33. Each house, flat or floor to have separate water & electrical meter. Owner to pay
coping blockwork in cem. mortar First Floor plan Double Sash Window 16 4 1,500x1,900 500 2,400 meter charges.
34. All ironmongery to be imported type. Samples to be produced.
35. Samples of fittings, materials etc. to be produced & approved before commencing work.
Textured render
WAREHOUSES, FACTORIES, WORKSHOPS ETC.
wall finish
1000

2.1. The following clauses mentioned above to apply 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
13, 14, 18, 19, 20, 21, 23, 27, 28, 30, 32, 34.
First Floor plan Glass Block Wall 16 4 400x1,900 500 2,400
200 2. All office windows to have P.C. cills, built in P.V., Pelmet boxes & timber window

150
Fair faced brickwork Cills & Skirtings.
d.p.c 3. Steel trusses/portal frames & purlins to be painted with 2 coats of oil paint.
below steel column 4. Windows to be burglar proofed with 16 mm twisted M.S. bars at 125 mm c/c, lugs,
stiffners etc. to be provided.
frame 5. All steel doors to have wickets to detail.
First Floor plan Window 16 1 710x1,900 500 2,400 6. All steel doors to be made of 75 x 75 x 6 M.S. angle frames with 14 g thick
M.S. plate panels & provided with heavy duty hinges/sliding gears & 3 Nos. cleats on
both sides for locks, handles etc. If sliding gear is outside provide G.C.I. cover.
Each panel should not be bigger than 600 x 600.

2400 2400 FOUNDATION DETAILS


7. Toilets - provide white glazed tiles to 1200 height everywhere. Provide mirrors 600 x 450
over all W.H.B.s, paper holders, 2 Nos. coat hooks behind each door.
8. Fire Fighting Equipment to be provided as shown on plan.
TO BE DETERMINED BY First Floor plan Window 16 4 900x900 1,500 2,400 9. Each Godown to have separate water & electrical meter. Owner to pay for meter charges.
TARMAC DRIVES
Ground level ENGINEER ON SITE 3.1 50 mm Premix laid in two layers on 150 quarry chips on 300 hardcore filling well
BOUNDARY WALL ELEVATION consolidated & rolled with 14 tons roller. Provide P.C. Curbs to all sides. Drives to be
well sloped for draining the rainwater.

First Floor plan Window 16 5 700x900 1,500 2,400 ROOFING FELT ON R.C. SLAB
4.1. Four layers of Bituminous roofing felt on 50 pumice screed on 50 hollow pots on
R.C. flat roof to structural
SECTION Engineer's detail, screed laid to fall min. 75 in 3000 (provide aluminium trim on all edges).
First layer asbestos based felting 16 kg/10 sq.m.
Second layer asbestos fellting 23 kg/10 sq.m.
First Floor plan Window 16 11 800x1,900 500 2,400 Third layer asbestos based felting 50 kg/10 sq.m.
boundary wall 1:25 Top layer 12 stone chippings bedded in bituflex.
(If 3rd layer is mineral finish, chippings may not be laid).
2. Guarantee of 2 years to be provided.
3. Lay Funtkote to ''colas A4 specification''.

5.1. All Existing work shown uncoloured.


All new work shown shaded or in Red.
Roof pitch 25 Roof pitch 25 Work to be demolished dotted or in yellow.
This drawing is to be read in conjunction with drawing Nos.
Mangalore clay tiles Mangalore clay tiles
On 25x25 battens On 25x25 battens P.C. SUMS OR PROVISIONAL SUMS
On galvanised Iron sheets On galvanised Iron sheets 6.1. Contractor is to include the following P.C. Sums or Provisional Sums in his Contract
and must allow for attendance to all Sub-Contractors and his profit in his Tender.
On 100x75 Principal rafters On 100x75 Principal rafters
a) Contingencies: Shs. ...............................................
On 100x50 common rafters On 100x50 common rafters
On 75x50 Under purlins On 75x50 Under purlins b) Electrical work: Shs. ..............................................

On 75x50 struts On 75x50 struts c) Gates, pillars and Electrical lamp wiring etc.: Shs. ...............................................

On 75x50 ties On 75x50 ties d) Drive-way and parking areas: Shs. ............................................
On 100x75 tie-beam On 100x75 tie-beam e) Fittings: Shs. .............................................
On 75x100 wall plate On 75x100 wall plate f) Plumbing: Shs. .............................................
g) Lithography charges payable
(M/S PLANNING & DESIGN ASSOCIATES) Shs. ............................................
2000 ltrs
1,380
2,273

h) Complete roof work, fabrication &


Crest Tank 2000 ltrs installation etc. by Contractor Shs. ...............................................
Crest Tank
1,580

i) Shs. .............................................
j) Shs. ............................................
350
1,017

300 350
200
163
800

800

800
200

Proposed residential building on plot 7529


1,100

600

Bedroom 2 200x300 R.C. Balcony Master Bedroom Master Bath Block 244 Kyadondo county Ssabagabo Subcounty
394

394
543
(girl's room) ring beam with At Kisugu Mengo District, Kampala
4Y12 & R6@
300

300

300
300

300
175c/c
200x300 R.C.
3,500

3,500

3,500
ring beam with
3,600 4Y12 & R6@
1,900

1,900

175c/c No. Revision/Issue Date


2,400

1,200 2,400 1,761

2,400

2,400
2,600

Stairs Consultant:

850
500

500

200

7,000
200

100
Consultants
200

850
1,100

6,000
650

550
1,050

Master Bath Pantry Lintol


Front Porch Lintol Dining plot 137/A
Kira road
Lintol Lounge
P.O.Box, 33096, Kampala

250
250

250
tel. 0414 234025, 0790837463
218 218 jr.utlonline.co.ug
750
3,500

3,500

400
3,300

3,300
1,350

3,300
1,900

1,520 230

Project:
2,400

600

2,400

2,400
PROPOSED RESIDENTIAL BLDGS.
159

45 kg LPG
1,750

2,000
1,500

Gas cylinder ON PLOT 7529 BLOCK 244 KISUGU


D.P.C D.P.C
810

Client:
900
159

MR. KENNETH SEMAFUMU


500

Ground level
P.O. BOX 16568, KAMPALA
Ground level Ground level Ground level
90

100

Ceramic floor tiles Ceramic floor tiles Consultant:


150

150

150
150

On 25mm cement-sand screed On 25mm cement-sand screed Arch. ABDU-WAHAB NYANZI


On 150mm site concrete On 150mm site concrete Reg. No. 191, PC. No. 2287
On guage 2000 polythene On guage 2000 polythene
sheeting sheeting
On 50mm sand blinding On 50mm sand blinding
On 200mm Hardcore On 200mm Hardcore
Description: Drwg. No.
On murrum backfill compacted in On murrum backfill compacted in
AS SHOWN AL/MYG/16-02-3
layers not exceeding 200mm layers not exceeding 200mm
thick thick
Revision: Issue status:
BOQ
*** NOTE; Other foundation *** NOTE; Other foundation Date: August 2016 final design
details details construction
will be determined by Engineer will be determined by Engineer Scale: as shown A1 paper schematic design
on site. on site.

S-02 Building Section 1:50 S-01 Building Section 1:50


Roof pitch 25
Mangalore clay tiles
On 25x25 battens
On galvanised Iron sheets
On 100x75 Principal rafters
On 100x50 common rafters General notes.
On 75x50 Under purlins
On 75x50 struts (To be read in conjunction with standard specifications)
On 75x50 ties (All dimensions are in millimetres)
On 100x75 tie-beam RESIDENTIAL & COMMERCIAL BUILDINGS
On 75x100 wall plate 1.1. All dimensions to be checked on site, written dimensions to be followed in
preference to scaled dimensions.
2. Depth of foundations to be determined on site but not to be less than 1200 deep.
3. Wall foundations to consist of 1:3:6 concrete mix, reinforced with 3 Nos. 16mm
diameter M.S. bars with 8 mm diameter M.S. bar links at 300 c/c. Cover to
350 reinforcement to be 75mm min. (R.C. foundations of columns to Structural Eng.'s detail).
4. D.P.C. to be three-ply approved quality bituminous felt.
5. Foundations should not encroach into adjoining plots.
6. 500 g polythene sheeting and anti-termite treatment to be provided under ground floor
concrete slab.
7. The ground floor level to be minimum 600 above the existing natural ground level or
as agreed on site.
8. Garage and carport floor slab to be reinforced with B.R.C. mesh 64.
9. All walls less than 200 thick to be reinforced with hoop iron at every alternate course.

800
10. P.V. denotes permanent vent and F.L. denotes fan-light.

1,100

1,100
11. All reinforced concrete work is to be in accordance with Structural Engineer's details.
12. All sanitary work to be in accordance with M.O.H. rules and regulations.
Master Bedroom Bedroom 2 Bedroom 3 13. Urinals to consist of glazed clay.
14. Where drain passes under building or drive-way area, pipe to be of cast iron or encased
in 150 concrete.
15. All wate pipes and soil pipes are to be in ducts and the bends to have all cleaning eyes
200x300 R.C. accessible from outside.

300
ring beam with 16. All windows to have P.C. cill, built-in P.V., pelmet box and timberwindow board to detail.
Sitting & Dining rooms to have bigger pelmet boxes to detail.
4Y12 & R6@ 17. All windows and external glazed doors to have burglar proofing to detail.
18. Provide standard type timber cornice and skirting where required.

3,500
175c/c 19. All door frames to be rebated & moulded & be full width of wall with moulded
architraves to detail. Provide rubber door stops to all doors.

1,900
20. Stair case doors to be self closing and 1/2 hour fire resistance.

2,400
Balcony 21. All internal plaster to be lime, two coats steel float finished.

1,900
22. No roof timber to be placed within 300 of chimney flue.
23. All sanitary fittings to be ''shanks'' or ''armitage'' or other approved type.
24. Provide 1500 high white glazed wall tiles on all exposed walls in kitchen, baths,
toilets, showers and cloak rooms.
25. Provide medicine cabinet with mirror and glass shelf over all W.H.B.
(except in domestic staff house) size600 x 400 x 150 deep.
26. Provide approved type C.P. shower fittings with tap, C.P. towel rails, hooks, bolts etc. in
bath and showers. All tubs to have telephone shower fittings. (W.H.B. to have mixer fittings)
27. All manholes within building area, drive-way and parking area to have heavy duty air
tight covers and double sealed.

500
500
100
28. Provide G.I. 125 X 100 rainwater down pipes and 125 x 100 G.I. box gutter with brackets
etc. where shown.
29. Provide 150 wide open rainwater concrete channels 1800 long to all downpipes.

200
30. Painting to be 4 coats (last coat at retention time).

200
31. Lay 1 layer of paving slabs 600 x 600 on sand along the perimeter of buildings & S.Q.
32. Provide D.P.C. to all boundary walls.

1,100
33. Each house, flat or floor to have separate water & electrical meter. Owner to pay

6,000

650
1,200

550
meter charges.
Kitchen Bedroom 4 34. All ironmongery to be imported type. Samples to be produced.
Lounge 35. Samples of fittings, materials etc. to be produced & approved before commencing work.

WAREHOUSES, FACTORIES, WORKSHOPS ETC.


2.1. The following clauses mentioned above to apply 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,

250

250
13, 14, 18, 19, 20, 21, 23, 27, 28, 30, 32, 34.
2. All office windows to have P.C. cills, built in P.V., Pelmet boxes & timber window
Cills & Skirtings.

750

3,500
3. Steel trusses/portal frames & purlins to be painted with 2 coats of oil paint.
4. Windows to be burglar proofed with 16 mm twisted M.S. bars at 125 mm c/c, lugs,
stiffners etc. to be provided.
Front 5. All steel doors to have wickets to detail.

1,900
6. All steel doors to be made of 75 x 75 x 6 M.S. angle frames with 14 g thick

2,400
Porch M.S. plate panels & provided with heavy duty hinges/sliding gears & 3 Nos. cleats on

600
both sides for locks, handles etc. If sliding gear is outside provide G.C.I. cover.
2,400

Each panel should not be bigger than 600 x 600.


7. Toilets - provide white glazed tiles to 1200 height everywhere. Provide mirrors 600 x 450
over all W.H.B.s, paper holders, 2 Nos. coat hooks behind each door.
8. Fire Fighting Equipment to be provided as shown on plan.
D.P.C. 9. Each Godown to have separate water & electrical meter. Owner to pay for meter charges.

900
TARMAC DRIVES
3.1 50 mm Premix laid in two layers on 150 quarry chips on 300 hardcore filling well

500
consolidated & rolled with 14 tons roller. Provide P.C. Curbs to all sides. Drives to be
well sloped for draining the rainwater.

Ground level ROOFING FELT ON R.C. SLAB


100

Ceramic floor tiles

150
4.1. Four layers of Bituminous roofing felt on 50 pumice screed on 50 hollow pots on
R.C. flat roof to structural
On 25mm cement-sand screed Engineer's detail, screed laid to fall min. 75 in 3000 (provide aluminium trim on all edges).
First layer asbestos based felting 16 kg/10 sq.m.
On 150mm site concrete Second layer asbestos fellting 23 kg/10 sq.m.
On guage 2000 polythene Third layer asbestos based felting 50 kg/10 sq.m.
Top layer 12 stone chippings bedded in bituflex.
sheeting (If 3rd layer is mineral finish, chippings may not be laid).
2. Guarantee of 2 years to be provided.
On 50mm sand blinding 3. Lay Funtkote to ''colas A4 specification''.
On 200mm Hardcore 5.1. All Existing work shown uncoloured.
On murrum backfill compacted in All new work shown shaded or in Red.
Work to be demolished dotted or in yellow.
layers not exceeding 200mm This drawing is to be read in conjunction with drawing Nos.
thick
P.C. SUMS OR PROVISIONAL SUMS
Roof pitch 25 6.1. Contractor is to include the following P.C. Sums or Provisional Sums in his Contract
Mangalore clay tiles *** NOTE; Other foundation and must allow for attendance to all Sub-Contractors and his profit in his Tender.

On 25x25 battens details a) Contingencies: Shs. ...............................................

On galvanised Iron sheets will be determined by Engineer Roof pitch 25 b) Electrical work: Shs. ..............................................
On 100x75 Principal rafters on site. Mangalore clay tiles c) Gates, pillars and Electrical lamp wiring etc.: Shs. ...............................................
On 100x50 common rafters On 25x25 battens d) Drive-way and parking areas: Shs. ............................................
On 75x50 Under purlins S-06 Building Section 1:50 On galvanised Iron sheets e) Fittings: Shs. .............................................
On 75x50 struts On 100x75 Principal rafters
f) Plumbing: Shs. .............................................
On 75x50 ties On 100x50 common rafters
g) Lithography charges payable
On 100x75 tie-beam On 75x50 Under purlins (M/S PLANNING & DESIGN ASSOCIATES) Shs. ............................................

On 75x100 wall plate On 75x50 struts h) Complete roof work, fabrication &
On 75x50 ties installation etc. by Contractor Shs. ...............................................

On 100x75 tie-beam i) Shs. .............................................

1,991
On 75x100 wall plate j) Shs. ............................................

350 8,540

800
Proposed residential building on plot 7529
800

800

800
800
Block 244 Kyadondo county Ssabagabo Subcounty
1,100

1,100
300
350 Bedroom 3 Bedroom 2 Master Bath
At Kisugu Mengo District, Kampala
Bedroom 2 Prayer room 200x300 R.C.
200x300 R.C.
ring beam with ring beam with
300

300

300
300
4Y12 & R6@ 4Y12 & R6@
900

175c/c 175c/c
3,500

3,500

3,500
1,900
No. Revision/Issue Date
1,900

1,900
2,400

2,400
2,400

1,500

Consultant:
850

600
500

500
500
200

200
Consultants
200

200
1,100

1,100

1,100
650

650

650

650
plot 137/A
Kitchen Kira road
Bedroom 4 Kitchen Dining Side porch Pantry P.O.Box, 33096, Kampala
tel. 0414 234025, 0790837463
250

250

250

250
jr.utlonline.co.ug

750
3,500

3,500

3,500
Project:
1,900

1,900
PROPOSED RESIDENTIAL BLDGS.
2,400

2,400

2,500

600
2,400

2,400

ON PLOT 7529 BLOCK 244 KISUGU


Client:
MR. KENNETH SEMAFUMU

900
D.P.C D.P.C.
500

500
P.O. BOX 16568, KAMPALA
Ground level Ground level Ground level Ground level Consultant:
100

Ceramic floor tiles Ceramic floor tiles Arch. ABDU-WAHAB NYANZI


150

150
150

On 25mm cement-sand screed On 25mm cement-sand screed Reg. No. 191, PC. No. 2287
On 150mm site concrete On 150mm site concrete
On guage 2000 polythene On guage 2000 polythene
sheeting sheeting Description: Drwg. No.
On 50mm sand blinding On 50mm sand blinding
On 200mm Hardcore On 200mm Hardcore AS SHOWN AL/MYG/16-02-4
On murrum backfill compacted in On murrum backfill compacted in
layers not exceeding 200mm layers not exceeding 200mm Revision: Issue status:
thick thick BOQ
Date: August 2016 final design
*** NOTE; Other foundation *** NOTE; Other foundation construction
details details Scale: as shown A1 paper schematic design
will be determined by Engineer will be determined by Engineer
on site. on site.

S-03 Building Section 1:50 S-05 Building Section 1:50


Door List
Door head
Floor (Story) Door Name Quantity W x H Size 2D Symbol 3D Back View General notes.
height
(To be read in conjunction with standard specifications)

Ground Floor Plan Arch Top Door Opening 16 1 1,000x2,400 2,400 (All dimensions are in millimetres)
RESIDENTIAL & COMMERCIAL BUILDINGS
1.1. All dimensions to be checked on site, written dimensions to be followed in
preference to scaled dimensions.
2. Depth of foundations to be determined on site but not to be less than 1200 deep.
3. Wall foundations to consist of 1:3:6 concrete mix, reinforced with 3 Nos. 16mm
Ground Floor Plan Arch Top Door Opening 16 1 1,200x2,400 2,400 diameter M.S. bars with 8 mm diameter M.S. bar links at 300 c/c. Cover to
reinforcement to be 75mm min. (R.C. foundations of columns to Structural Eng.'s detail).
4. D.P.C. to be three-ply approved quality bituminous felt.
5. Foundations should not encroach into adjoining plots.
6. 500 g polythene sheeting and anti-termite treatment to be provided under ground floor
concrete slab.
Ground Floor Plan Arch Top Door Opening 16 1 1,200x2,400 2,400 7. The ground floor level to be minimum 600 above the existing natural ground level or
as agreed on site.
8. Garage and carport floor slab to be reinforced with B.R.C. mesh 64.
9. All walls less than 200 thick to be reinforced with hoop iron at every alternate course.
10. P.V. denotes permanent vent and F.L. denotes fan-light.
11. All reinforced concrete work is to be in accordance with Structural Engineer's details.
12. All sanitary work to be in accordance with M.O.H. rules and regulations.
Ground Floor Plan Arch Top Door Opening 16 1 1,400x2,400 2,400 13. Urinals to consist of glazed clay.
14. Where drain passes under building or drive-way area, pipe to be of cast iron or encased
in 150 concrete.
15. All wate pipes and soil pipes are to be in ducts and the bends to have all cleaning eyes
accessible from outside.
16. All windows to have P.C. cill, built-in P.V., pelmet box and timberwindow board to detail.
Sitting & Dining rooms to have bigger pelmet boxes to detail.
Ground Floor Plan Arch Top Door Opening 16 1 1,410x2,400 2,400 17. All windows and external glazed doors to have burglar proofing to detail.
18. Provide standard type timber cornice and skirting where required.
19. All door frames to be rebated & moulded & be full width of wall with moulded
architraves to detail. Provide rubber door stops to all doors.
20. Stair case doors to be self closing and 1/2 hour fire resistance.
21. All internal plaster to be lime, two coats steel float finished.
22. No roof timber to be placed within 300 of chimney flue.
Ground Floor Plan Arch Top Door Opening 16 1 2,500x2,400 2,400 23. All sanitary fittings to be ''shanks'' or ''armitage'' or other approved type.
24. Provide 1500 high white glazed wall tiles on all exposed walls in kitchen, baths,
toilets, showers and cloak rooms.
25. Provide medicine cabinet with mirror and glass shelf over all W.H.B.
(except in domestic staff house) size600 x 400 x 150 deep.
26. Provide approved type C.P. shower fittings with tap, C.P. towel rails, hooks, bolts etc. in
Ground Floor Plan Arch Top Door Opening 16 2 2,000x2,400 2,400 bath and showers. All tubs to have telephone shower fittings. (W.H.B. to have mixer fittings)
27. All manholes within building area, drive-way and parking area to have heavy duty air
tight covers and double sealed.
28. Provide G.I. 125 X 100 rainwater down pipes and 125 x 100 G.I. box gutter with brackets
etc. where shown.
29. Provide 150 wide open rainwater concrete channels 1800 long to all downpipes.
30. Painting to be 4 coats (last coat at retention time).
Ground Floor Plan Built-in Wardrobe 16 1 450x2,400 2,400 31. Lay 1 layer of paving slabs 600 x 600 on sand along the perimeter of buildings & S.Q.
32. Provide D.P.C. to all boundary walls.
33. Each house, flat or floor to have separate water & electrical meter. Owner to pay
meter charges.
34. All ironmongery to be imported type. Samples to be produced.
35. Samples of fittings, materials etc. to be produced & approved before commencing work.
Ground Floor Plan Built-in Wardrobe 16 1 600x2,400 2,400 WAREHOUSES, FACTORIES, WORKSHOPS ETC.
2.1. The following clauses mentioned above to apply 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
13, 14, 18, 19, 20, 21, 23, 27, 28, 30, 32, 34.
2. All office windows to have P.C. cills, built in P.V., Pelmet boxes & timber window
Cills & Skirtings.
Ground Floor Plan Built-in Wardrobe 16 1 1,110x2,400 2,400 3. Steel trusses/portal frames & purlins to be painted with 2 coats of oil paint.
4. Windows to be burglar proofed with 16 mm twisted M.S. bars at 125 mm c/c, lugs,
stiffners etc. to be provided.
5. All steel doors to have wickets to detail.
6. All steel doors to be made of 75 x 75 x 6 M.S. angle frames with 14 g thick
M.S. plate panels & provided with heavy duty hinges/sliding gears & 3 Nos. cleats on
both sides for locks, handles etc. If sliding gear is outside provide G.C.I. cover.
Ground Floor Plan Built-in Wardrobe 16 2 1,200x2,400 2,400 Each panel should not be bigger than 600 x 600.
7. Toilets - provide white glazed tiles to 1200 height everywhere. Provide mirrors 600 x 450
over all W.H.B.s, paper holders, 2 Nos. coat hooks behind each door.
8. Fire Fighting Equipment to be provided as shown on plan.
9. Each Godown to have separate water & electrical meter. Owner to pay for meter charges.
TARMAC DRIVES
North Elevation House B 1:100 Ground Floor Plan Door with Transom 16 1 1,000x2,400 2,400 3.1 50 mm Premix laid in two layers on 150 quarry chips on 300 hardcore filling well
consolidated & rolled with 14 tons roller. Provide P.C. Curbs to all sides. Drives to be
well sloped for draining the rainwater.

ROOFING FELT ON R.C. SLAB


4.1. Four layers of Bituminous roofing felt on 50 pumice screed on 50 hollow pots on
Ground Floor Plan Door with Transom 16 2 600x2,400 2,400 R.C. flat roof to structural
Engineer's detail, screed laid to fall min. 75 in 3000 (provide aluminium trim on all edges).
First layer asbestos based felting 16 kg/10 sq.m.
Second layer asbestos fellting 23 kg/10 sq.m.
Third layer asbestos based felting 50 kg/10 sq.m.
Top layer 12 stone chippings bedded in bituflex.
(If 3rd layer is mineral finish, chippings may not be laid).
Ground Floor Plan Door with Transom 16 11 900x2,400 2,400 2. Guarantee of 2 years to be provided.
3. Lay Funtkote to ''colas A4 specification''.

5.1. All Existing work shown uncoloured.


All new work shown shaded or in Red.
Work to be demolished dotted or in yellow.
Ground Floor Plan Sliding Door with Transom 16 1 1,392x2,400 2,400 This drawing is to be read in conjunction with drawing Nos.

P.C. SUMS OR PROVISIONAL SUMS


Roof pitch 25 6.1. Contractor is to include the following P.C. Sums or Provisional Sums in his Contract
and must allow for attendance to all Sub-Contractors and his profit in his Tender.
Mangalore clay tiles
Ground Floor Plan Sliding Door with Transom 16 1 2,500x2,400 2,400 a) Contingencies: Shs. ...............................................
On 25x25 battens
b) Electrical work: Shs. ..............................................
On galvanised Iron sheets
c) Gates, pillars and Electrical lamp wiring etc.: Shs. ...............................................
On 100x75 Principal rafters
d) Drive-way and parking areas: Shs. ............................................
On 100x50 common rafters Ground Floor Plan Sliding Door with Transom 16 1 2,600x2,400 2,400
On 75x50 Under purlins e) Fittings: Shs. .............................................

On 75x50 struts 2000 ltrs f) Plumbing: Shs. .............................................

On 75x50 ties Crest Tank g) Lithography charges payable


(M/S PLANNING & DESIGN ASSOCIATES) Shs. ............................................
On 100x75 tie-beam Ground Floor Plan Sliding Door with Transom 16 1 3,000x2,400 2,400 h) Complete roof work, fabrication &
On 75x100 wall plate installation etc. by Contractor Shs. ...............................................

1,380 i) Shs. .............................................

1,600
j) Shs. ............................................
First Floor plan Arch Top Door Opening 16 2 1,000x2,400 2,400

1,600
1,580
280
219

200
First Floor plan Built-in Wardrobe 16 1 450x2,400 2,400
Proposed residential building on plot 7529
Block 244 Kyadondo county Ssabagabo Subcounty
800

200

1,100
600
Prayer Room First Floor plan Built-in Wardrobe 16 1 552x2,400 2,400 At Kisugu Mengo District, Kampala
394

350 Master Bath

300
300

200x300 R.C. First Floor plan Built-in Wardrobe 16 1 800x2,400 2,400


ring beam with
3,500

4Y12 & R6@


175c/c No. Revision/Issue Date
First Floor plan Built-in Wardrobe 16 1 1,030x2,400 2,400

1,900
2,400

2,400
Consultant:
Stairs First Floor plan Built-in Wardrobe 16 1 1,110x2,400 2,400
500
200

Consultants
200

First Floor plan Built-in Wardrobe 16 1 1,150x2,400 2,400


1,100
6,000

650

650

1,200 plot 137/A


Dining Kira road
Lintol Lintol First Floor plan Built-in Wardrobe 16 1 1,230x2,400 2,400 P.O.Box, 33096, Kampala
tel. 0414 234025, 0790837463
159

jr.utlonline.co.ug
250

250

First Floor plan Built-in Wardrobe 16 2 1,300x2,400 2,400


3,500
400

Project:
159

1,900
1,900

PROPOSED RESIDENTIAL BLDGS.


First Floor plan Built-in Wardrobe 16 4 600x2,400 2,400
2,400

Open deck
ON PLOT 7529 BLOCK 244 KISUGU
230
2,000

200 450
1,432

Client:
100

D.P.C.
MR. KENNETH SEMAFUMU
First Floor plan Built-in Wardrobe 16 10 1,200x2,400 2,400
750

P.O. BOX 16568, KAMPALA


500

500

219 219
450

Ground level Consultant:


Ground level
1,202

Arch. ABDU-WAHAB NYANZI


350

Ceramic floor tiles First Floor plan Door with 2 Sidelights and Transom 16 1 2,100x2,400 2,400
150

250 On 25mm cement-sand screed Reg. No. 191, PC. No. 2287
200 150 On 150mm site concrete
On guage 2000 polythene
sheeting First Floor plan Door with Transom 16 1 1,000x2,400 2,400 Description: Drwg. No.
On 50mm sand blinding
On 200mm Hardcore AS SHOWN AL/MYG/16-02-5
On murrum backfill compacted in
layers not exceeding 200mm First Floor plan Door with Transom 16 13 900x2,400 2,400 Revision: Issue status:
thick BOQ
Date: August 2016 final design
*** NOTE; Other foundation construction
details First Floor plan Sliding Door with Transom 16 1 2,600x2,400 2,400 Scale: as shown A1 paper schematic design
will be determined by Engineer
on site.

S-04 Building Section 1:50


2.7
23
.1

5.4
Fro
m Mu 37 General notes.
.9
yen

.6
54
ga (To be read in conjunction with standard specifications)
Tan

2.7
k Hil (All dimensions are in millimetres)

l Muyenga Resort Hotel

.3
38.1 RESIDENTIAL & COMMERCIAL BUILDINGS

11
.8 1.1. All dimensions to be checked on site, written dimensions to be followed in
(formerly Muyenga Club) 10 34 preference to scaled dimensions.
.0 2. Depth of foundations to be determined on site but not to be less than 1200 deep.
3. Wall foundations to consist of 1:3:6 concrete mix, reinforced with 3 Nos. 16mm
SITE diameter M.S. bars with 8 mm diameter M.S. bar links at 300 c/c. Cover to
Plot 7529 reinforcement to be 75mm min. (R.C. foundations of columns to Structural Eng.'s detail).
4. D.P.C. to be three-ply approved quality bituminous felt.
Block 244 5. Foundations should not encroach into adjoining plots.
6. 500 g polythene sheeting and anti-termite treatment to be provided under ground floor
concrete slab.
7. The ground floor level to be minimum 600 above the existing natural ground level or
as agreed on site.
8. Garage and carport floor slab to be reinforced with B.R.C. mesh 64.
9. All walls less than 200 thick to be reinforced with hoop iron at every alternate course.
10. P.V. denotes permanent vent and F.L. denotes fan-light.
11. All reinforced concrete work is to be in accordance with Structural Engineer's details.
12. All sanitary work to be in accordance with M.O.H. rules and regulations.
13. Urinals to consist of glazed clay.
14. Where drain passes under building or drive-way area, pipe to be of cast iron or encased
in 150 concrete.
15. All wate pipes and soil pipes are to be in ducts and the bends to have all cleaning eyes
accessible from outside.
16. All windows to have P.C. cill, built-in P.V., pelmet box and timberwindow board to detail.
Sitting & Dining rooms to have bigger pelmet boxes to detail.
17. All windows and external glazed doors to have burglar proofing to detail.
18. Provide standard type timber cornice and skirting where required.
19. All door frames to be rebated & moulded & be full width of wall with moulded
Muyenga architraves to detail. Provide rubber door stops to all doors.
20. Stair case doors to be self closing and 1/2 hour fire resistance.
Community 21. All internal plaster to be lime, two coats steel float finished.
22. No roof timber to be placed within 300 of chimney flue.
23. All sanitary fittings to be ''shanks'' or ''armitage'' or other approved type.
Police post 24. Provide 1500 high white glazed wall tiles on all exposed walls in kitchen, baths,
toilets, showers and cloak rooms.
25. Provide medicine cabinet with mirror and glass shelf over all W.H.B.
(except in domestic staff house) size600 x 400 x 150 deep.
26. Provide approved type C.P. shower fittings with tap, C.P. towel rails, hooks, bolts etc. in
bath and showers. All tubs to have telephone shower fittings. (W.H.B. to have mixer fittings)
27. All manholes within building area, drive-way and parking area to have heavy duty air
tight covers and double sealed.
28. Provide G.I. 125 X 100 rainwater down pipes and 125 x 100 G.I. box gutter with brackets
etc. where shown.

e
29. Provide 150 wide open rainwater concrete channels 1800 long to all downpipes.

los
30. Painting to be 4 coats (last coat at retention time).
31. Lay 1 layer of paving slabs 600 x 600 on sand along the perimeter of buildings & S.Q.

ec
32. Provide D.P.C. to all boundary walls.
33. Each house, flat or floor to have separate water & electrical meter. Owner to pay

ch
meter charges.
34. All ironmongery to be imported type. Samples to be produced.

Ro
35. Samples of fittings, materials etc. to be produced & approved before commencing work.

WAREHOUSES, FACTORIES, WORKSHOPS ETC.

e
2.1. The following clauses mentioned above to apply 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,

os
13, 14, 18, 19, 20, 21, 23, 27, 28, 30, 32, 34.
2. All office windows to have P.C. cills, built in P.V., Pelmet boxes & timber window

cl
Cills & Skirtings.

ga
3. Steel trusses/portal frames & purlins to be painted with 2 coats of oil paint.
4. Windows to be burglar proofed with 16 mm twisted M.S. bars at 125 mm c/c, lugs,

an
stiffners etc. to be provided.

Lw
5. All steel doors to have wickets to detail.
6. All steel doors to be made of 75 x 75 x 6 M.S. angle frames with 14 g thick
M.S. plate panels & provided with heavy duty hinges/sliding gears & 3 Nos. cleats on
both sides for locks, handles etc. If sliding gear is outside provide G.C.I. cover.
Each panel should not be bigger than 600 x 600.
7. Toilets - provide white glazed tiles to 1200 height everywhere. Provide mirrors 600 x 450
over all W.H.B.s, paper holders, 2 Nos. coat hooks behind each door.

ad
Hotel International 8. Fire Fighting Equipment to be provided as shown on plan.
9. Each Godown to have separate water & electrical meter. Owner to pay for meter charges.

Ro
Muyenga TARMAC DRIVES
3.1 50 mm Premix laid in two layers on 150 quarry chips on 300 hardcore filling well

gi
consolidated & rolled with 14 tons roller. Provide P.C. Curbs to all sides. Drives to be

lun
well sloped for draining the rainwater.

se

Ka
ROOFING FELT ON R.C. SLAB

clo
4.1. Four layers of Bituminous roofing felt on 50 pumice screed on 50 hollow pots on
Bu R.C. flat roof to structural

i
lik

las
Engineer's detail, screed laid to fall min. 75 in 3000 (provide aluminium trim on all edges).
iro First layer asbestos based felting 16 kg/10 sq.m.
Ro Second layer asbestos fellting 23 kg/10 sq.m.

ga
ad Third layer asbestos based felting 50 kg/10 sq.m.
Top layer 12 stone chippings bedded in bituflex.

Mu
(If 3rd layer is mineral finish, chippings may not be laid).
2. Guarantee of 2 years to be provided.
3. Lay Funtkote to ''colas A4 specification''.

5.1. All Existing work shown uncoloured.


All new work shown shaded or in Red.
Work to be demolished dotted or in yellow.
This drawing is to be read in conjunction with drawing Nos.

NOTES AND REVISIONS. ACCESS / LOCATION PLAN TO P.C. SUMS OR PROVISIONAL SUMS
6.1. Contractor is to include the following P.C. Sums or Provisional Sums in his Contract

From
and must allow for attendance to all Sub-Contractors and his profit in his Tender.
Earth cover
PERCOLATION TRENCHES.
1- At least one foot of percolation trench should be provided for every
Plot 7529 block 244 Kyadondo County, a) Contingencies: Shs. ...............................................

Impervious layer and corrugated iron eight litres of effluent to be disposed at 24 hours.
Ssabagabo Subcounty at Kisugu b) Electrical work: Shs. ..............................................

B
sheets or similar Muyenga

ukasa
c) Gates, pillars and Electrical lamp wiring etc.: Shs. ...............................................
2-When sediment is seen in effluent the tank should be desludged
600x450mm cast iron Quarry
cover and frame.
without delay.

3-One trench should be at rest whilst the other is in use no trench


Makindye Division KCCA d) Drive-way and parking areas:
e) Fittings:
Shs. ............................................
Shs. .............................................

(NOT TO SCALE)
should be used continously for more than a month.
1950

f) Plumbing: Shs. .............................................

- Kye
4-For deep tanks the cover slab should be 375mm above working level g) Lithography charges payable
and manholes only carried up to ground level walls of manhole to be (M/S PLANNING & DESIGN ASSOCIATES) Shs. ............................................
carried on 230x230mm concrete beams with 68mm diameter rods.
h) Complete roof work, fabrication &

itabya
installation etc. by Contractor Shs. ...............................................
SIZES OF INSPECTION CHAMBERS i) Shs. .............................................

PLAN OF TOP 1,500


DEPTH TO
INVERT
up to 450mm
INTERNAL
DIMENSIONS
450 x 450mm
WALL
THICKNESS
115mm
FOUNDATION
THICKNESS
125mm
j) Shs. ............................................

475 x 900mm 450 x 600mm 115mm 125mm PLOT 7283 PLOT 7282
iron channel stop. SOAKPIT TYPE 2. 925 x 1500mm 600 x 1050mm 225mm 125mm

23.1 37.9
over 1500mm 750 x 1050mm 225mm 240mm Boundary wall Boundary wall

2.7
layer of brushwood

2.7 5.4

2,475

2,475
Proposed residential building on plot 7529
Brickwork to be built in 1:6 cement mortar and rendered 7,453 13,749 39,298
internally in 1:3 cement paste 12mm thick foundation to be 1:3:6 Block 244 Kyadondo county Ssabagabo Subcounty
B

agricultural pipes min. cement concrete.


At Kisugu Mengo District, Kampala

PLOT 2069
fall 1:100
6
L 40,21

6,070

6,070
effluent distribution DIMENSIONS OF SEPTIC TANK
750

chamber.

11.3
No OF Percolation
vent USERS
L B D CAPACITY
IN LITRES
trench length in
metre run.
chamber.

3,630

3,630
Boundary wall
600 1000 8
6 1800 750 900 No. Revision/Issue Date
PLAN PERCOLATION TRENCH 10 2300 750 900
1260 12
815
97,613,430 mm2

3,900 9,034
SECTIONS SOAKPIT TYPE 1. 15 2500 750 900
1520 18
Precast reinforced concrete
20 2900 750 900
1600 24 Existing single Consultant:
slab 100mm thick.(mix 1:2:4).
25 3300 750 900
1860 30

36
storey incomplete
2100
30 2400 900 1050
structure to be demolished
1
38.
2220 42
35 2600 900 1050
75 300

working level. 40 3000 900 1050


2620 48

Consultants

PLOT 5613
working level. 2880 54
45 3300 900 1050
3280 60
plot 137/A
50 3600 900 1050
Kira road
450

3920 66
230mm thick
60 3200 1100 1200 P.O.Box, 33096, Kampala
70 3800 1200
4680 72 tel. 0414 234025, 0790837463
brickwall. 1100
jr.utlonline.co.ug
5240 78
80 4300 1100 1200
5800 84
D

90 4700 1100 1200


D

230
230mm thick concrete 230
100 5300 1100 1200
6560 80
54.6 PLOT 7531 Project:
L 230
450

7860 94
base. 3000 B 230 125 4300 1400 1700
N PROPOSED RESIDENTIAL BLDGS.

47,398
9260 100
150 5000 1400 1500
10660 106
ON PLOT 7529 BLOCK 244 KISUGU
175 5800 1400 1500
12080 112 Client:
200 6550 1400 1500
MR. KENNETH SEMAFUMU
Boundary wall

13280 118
225 6550 1400 1650

LONGITUDINAL SECTION CROSS SECTION 250 7150 1400 1650


15520 224 P.O. BOX 16568, KAMPALA
275 7150 1400 1800
15860 230 Consultant:

8
16840 236 Arch. ABDU-WAHAB NYANZI

34.
300 7600 1400 1800
Reg. No. 191, PC. No. 2287

Description: Drwg. No.

STANDARD TYPE SEPTIC TANK. AS SHOWN

Revision:
AL/MYG/16-02-6

Issue status:
BOQ
Date: August 2016 final design
construction
10.0 Scale: as shown A1 paper schematic design
septic tank-1 1:50

-1. Site Layout (1) 1:300