Two identical three-phase Y-connected alternators A and B share equally a
load of 10 MW at 33-kV and 80 % lagging pf. The synchronous reactance of each machine is 4 ohms per phase and the armature resistance is negligible. Alternator A has its field excitation adjusted to carry 125 A lagging current, what is the current supplied by alternator B? A. 96 A B. 97 A C. 98 A D. 95 A