ITPU 2008A
numbers of Rectifier Modules are powered for providing DC power up to 3 BTS and for
threshold. The SMPS Rectifiers operate over a wide voltage range (90-300V Single
Phase) eliminating the need of any additional Line Conditioning Unit (LCU), SVR or
Provision is made for metering the energy consumed by each BTS. Required
measurements, controls and alarm processing are done through Micro-processor based
Control Modules. All required equipments including rectifiers for ultimate capacity of
300A are accommodated in a 19 Rack of height 1660 mm.
Salient Features
No need of using any SVR (LCU) or Servo Stabiliser improving system efficiency
resulting in low operating cost and heat dissipation.
Power Plant capable of giving full power over wide voltage range (90-300V) and
temperature range (0-50 degree C) without any degradation.
Low Capital and Operating cost compared to conventional PIU and SMPS solutions
Optional IP 55 Cabinet
Technical Specifications
AMF Function
Protections
Input MCB (TPN) Suitable for Capacity
Voltage protection at incoming power input a) High Voltage Disconnect (HVD)
b) Low Voltage Disconnect (LVD)
Lightening protection The input shall be protected from multi -strike lightening
10/350 micro seconds, 50KA, as per IEC 61312-3 ( Optional)
DG Protection system
LLOP Essential
Low Fuel Critical
Over load Adjustable
Voltage Protection HVD & LVD- +-5V above/below the range
HCT / HWT Individual
Delays
DG on load After DG starts and supply is healthy
Blackout delay 10 seconds between mains and DG contactor changeover.
DG cooling time 5 minutes
DG start attempts Three attempts with delay between attempts (40 -40 -40 sec )
DG Lock time After three very short mains restoration 10-10-20 minutes.
Stop Command duration Settable from 0 to 30 Seconds
Battery charger & DG controller unit Automatic DG battery, SMPS charger with boost/trickle
charging & with constant current charging facility (12V)
Charger suitable for charging the SMF/Conventional battery
of 150AH.
Generator controller with start, stop relays & other monitoring
& control features
Complete shutoff during fire/smoke
Provision of Auto manual mode selection
Mains measurements Input Voltage (Individually for all three phases and DG )
LED / LCD Indications Mains ON, Load on Mains, Load on DG, Smoke/ Fire Alarm,
Over Load, LCU fail, Fuel Low, DG fail to start, DG fail to
stop, Alternator fail, LLOP, System battery low, DG battery
low, HCT/HWT, DG Manual, High shelter temperature
Potential Free Contacts Mains fail, Shelter Door open/ Intruder, Low fuel level,
Common DG fault -- LLOP/Alt fault/HCT/HWT/V belt/Dg fail
to start/DG fail to stop
Smoke/Fire, Load on DG, DG on, DG Fail to stop, DG Fail to
start, DG over load, High Room Temperature, Site on battery
Power factor 0.99 at full load and Nominal input (>0.95 in other working
conditions)
Current harmonic distortion Less than 10% for load 50 to 100%
Efficiency 90% (typical) at full load and Nominal input
Ripple & noise 100mV peak-to-peak & less than 2mv Sophomoric
Acoustic noise Less than 45dBA.
Transient response Limited to 5% & recovery within 10mSec
Protections Galvanic Isolation (Input out of range), Over voltage, over
load, short circuit.
Indications AC on, AC abnormal, under voltage, over voltage, Over load,
Fan Fail, Fuse Fail, Rectifier Fail, Communication Fail
Environmental Conforming to QM333 category B2 of QA Wing of BSNL.
Cooling Forced Cooling.
DC Distribution Custom configurable as per requirement.
LVD Single, Two Stage (Optional)
Disconnect Voltage 44.4V, reconnect 51.5V (settable)
Temp. Compensation 3mV / degree Centigrade / cell.
Metering AC Input Voltage
System, Load & Battery Current
System, Load & Battery Voltage
Individual Module Current
Status AC Available
System OK
LVD
System on Float Mode
System on Charge Mode
Environment Specification
Operating Temperature 0 50 C.
Storage Temperature -100C to + 600 C.
Humidity 95% Max.