SIZE OF TRANSFORMER AND VOLTAGE DROP AT STARTING OF LARGE MOTO

Transformer Detail:
Transformer Size
Transformer Secondary Voltage:(v2)
% Impedance: (z)
Allowable Voltage Drop in System:
:Motors Detail ( More Than One No of Motor):
Total KW of Three Phase Motors:
Total KW of Single Phase Motors:
Volt: (L-L)
Volt: (L-N)
Power Factor:
Locaked Rotor Current: (Max)
Total Three Phase Motors Full Load Current
Total Single Phase Motors Full Load Current
Total Motors Full Load Current
Motor InRush KVA At Starting

:Calculations:
Full Load Current of Transformer : (IL)
Short Circuit Current at Transformer Secondary: (Isc)
Max KVA of Transformer at Isc
Motor InRush KVA At Starting
Voltage Drop at Transformer Secondary Due to Motor inRush
Transformer Secondary Voltage

:Result:
(1) Motor Full Load Current <= 65% Transformer Full Load Current
(2) Voltage Drop at Transformer Secondary Due to Motor inRush
(3) Transformer Size:
Size of Transformer is Adequate
STARTING OF LARGE MOTORS

6000 KVA
415 Volt
8.00%
10%

700 Kw
0 Kw
415 Volt
240 Volt
0.8
600%
1217.34 Amp
0.00 Amp
1217.34 Amp
5250 KVA

8347 Amp
104343 Amp
75000 KVA
5250 KVA
7.0% 93%
386 Volt

Yes
Low
6000 KVA