You are on page 1of 45

INGENIERA DESARROLLO Y GESTIN

ENERGTICA
IDGE

POWER SOLUTIONS

ESTUDIOS DE OPERATIVIDAD
DE LA CTE IQUITOS

ANLISIS DE LA OPERACIN EN ESTADO


ESTACIONARIO (ANLISIS DE FLUJO DE
CARGA Y CORTOCIRCUITO)
ESTIMACIONES DE ESTABILIDAD

LIMA, OCTUBRE DE 2015


INGENIERA
DESARROLLO
GESTIN ENERGTICA

NDICE

1. INTRODUCCIN ........................................................................................................ 5
2. OBJETIVO .................................................................................................................. 6
3. INFORMACIN UTILIZADA ....................................................................................... 7
3.1. Descripcin del Proyecto .............................................................................................. 7
3.2. Periodo de Estudio ....................................................................................................... 10
3.3. Oferta del Sistema Elctrico Iquitos ........................................................................... 10
3.4. Demanda del Sistema Elctrico Iquitos ..................................................................... 11
4. METODOLOGA ....................................................................................................... 13
4.1. Tolerancia a la Circulacin de la Corriente de Secuencia Negativa ....................... 13
4.2. Anlisis de Flujo de Potencia ...................................................................................... 13
4.3. Anlisis de Cortocircuito ............................................................................................. 14
4.4. Determinacin del Tiempo Crtico de Despeje de Falla ........................................... 14
4.5. Anlisis de Estabilidad Transitoria ............................................................................. 14
5. CRITERIOS TCNICOS ............................................................................................ 15
6. EXIGENCIAS DE DISEO ........................................................................................ 16
6.1. Tolerancia a Corrientes de Secuencia Inversa .......................................................... 16
7. ANLISIS EN ESTADO ESTACIONARIO ................................................................. 18
7.1. Flujo de Potencia en Operacin Normal .................................................................... 18
7.1.1. Caso Base Sin Proyecto ......................................................................................... 18
7.1.2. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 19
7.1.3. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 20
7.2. Cortocircuito en Estado Estacionario ........................................................................ 22
7.2.1. Caso Base Sin Proyecto ......................................................................................... 22
7.2.2. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 22
7.2.3. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 23
7.2.4. Mxima Generacin 2024 .......................................................................................... 24
8. TIEMPOS CRTICOS DE DESPEJE DE FALLA ........................................................ 25
8.1.1. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 25
8.1.2. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 27
8.1.3. Resultados Tiempos Crticos de Despeje de Falla .................................................... 29
9. ESTABILIDAD TRANSITORIA ANTE FALLAS ......................................................... 30
10. ESTABILIDAD DE FRECUENCIA ............................................................................. 33
10.1. Eventos Importantes en el Ao 2015 .......................................................................... 33
10.2. Criterio para los Rels de Umbral de Frecuencia ..................................................... 35
10.2.1. Primer umbral de rechazo .......................................................................................... 35
10.2.2. Numero de etapas ..................................................................................................... 35
10.2.3. Temporizacin............................................................................................................ 35

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 2
INGENIERA
DESARROLLO
GESTIN ENERGTICA

10.2.4. Cantidad de carga rechazada .................................................................................... 35


10.3. Criterio para los Rels de Derivada de Frecuencia .................................................. 35
10.4. Resultados del ERCMF ................................................................................................ 36
11. CONCLUSIONES Y RECOMENDACIONES ............................................................. 42
12. ANEXOS ................................................................................................................... 43

NDICE DE CUADROS

Cuadro 3.1 Parmetros de Generadores ................................................................................... 7


Cuadro 3.2 Constantes de Tiempo y Constantes de Inercia de Generadores .......................... 7
Cuadro 3.3 Parmetros de Transformadores ............................................................................ 8
Cuadro 3.4 Parmetros de Lneas y Cables .............................................................................. 8
Cuadro 3.5 Despacho de Generadores en el Periodo 1 9 MW ............................................ 10
Cuadro 3.6 Despacho de Generadores en el Periodo 2 12 MW .......................................... 11
Cuadro 3.7 Demanda de Alimentadores .................................................................................. 12
Cuadro 6.1 Tolerancia de Corrientes de Secuencia Negativa ................................................. 17
Cuadro 7.1 Tensin en Barras Caso Base 2015 .................................................................. 18
Cuadro 7.2 Niveles de Carga (%) Caso Base 2015.............................................................. 19
Cuadro 7.3 Tensin en Barras Periodo 1 con C.T.E. Iquitos 9 MW ..................................... 19
Cuadro 7.4 Niveles de Carga (%) Periodo 1 con C.T.E. Iquitos 9 MW................................. 20
Cuadro 7.5 Tensin en Barras Periodo 2 con C.T.E. Iquitos 12 MW ................................... 21
Cuadro 7.6 Niveles de Carga (%) Periodo 2 con C.T.E. Iquitos 12 MW .............................. 21
Cuadro 7.7 Niveles de Cortocircuito Caso Base 2015 .......................................................... 22
Cuadro 7.8 Niveles de Cortocircuito Periodo 1 con C.T.E. Iquitos 9 MW ............................. 23
Cuadro 7.8 Niveles de Cortocircuito Periodo 2 con C.T.E. Iquitos 12 MW ........................... 23
Cuadro 7.10 Niveles de Cortocircuito Mxima Generacin .................................................. 24
Cuadro 8.1 Tiempos Crticos de Despeje de Falla .................................................................. 29
Cuadro 10.1 Indicadores ERCMF ............................................................................................ 36
Cuadro 10.2 Indicadores ERCMF ............................................................................................ 36
Cuadro 10.3 Resultados ERCMF ............................................................................................. 41

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 3
INGENIERA
DESARROLLO
GESTIN ENERGTICA

NDICE DE FIGURAS

Figura 3.1 Diagrama Unifilar del Proyecto ................................................................................. 9


Figura 6.1 Corriente de Secuencia Inversa Falla en 0.48 kV ............................................... 16
Figura 6.2 Corriente de Secuencia Inversa Falla en 33 kV .................................................. 17
Figura 8.1 Tiempo Crtico de Despeje de Falla Mxima Demanda (9 MW) tc=180 ms .... 25
Figura 8.2 Tiempo Crtico de Despeje de Falla Media Demanda (9 MW) tc=190 ms ....... 26
Figura 8.3 Tiempo Crtico de Despeje de Falla Mnima Demanda (9 MW) tc=200 ms ..... 26
Figura 8.4 Tiempo Crtico de Despeje de Falla Mxima Demanda (12 MW) tc=180 ms .. 27
Figura 8.5 Tiempo Crtico de Despeje de Falla Media Demanda (12 MW) tc=185 ms ..... 28
Figura 8.6 Tiempo Crtico de Despeje de Falla Mnima Demanda (12 MW) tc=190 ms ... 28
Figura 9.1 Falla 1 con Recierre Exitoso LT Iquitos Sta. Rosa en Mxima Demanda ......... 30
Figura 9.2 Falla 1 con Recierre Exitoso LT Iquitos Sta. Rosa en Mnima Demanda .......... 31
Figura 9.2 Salida Automtica GT Wartsila N 6 ....................................................................... 33
Figura 9.2 Salida Automtica de GT Cat Mak N 2 .................................................................. 34
Figura 9.2 Otros Eventos Importantes ..................................................................................... 34
Figura 10.1 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) Mxima Demanda .... 37
Figura 10.2 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Media Demanda ....... 37
Figura 10.2 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Mnima Demanda ..... 38
Figura 10.3 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mxima Demanda ... 39
Figura 10.4 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Media Demanda ..... 39
Figura 10.4 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mnima Demanda ... 40

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 4
INGENIERA
DESARROLLO
GESTIN ENERGTICA

1. INTRODUCCIN

El proyecto comprende la instalacin de una central elctrica con una capacidad total de salida
de 12 MW a 10.5 kV - 60 Hz, 0.8 factor de potencia, Potencia Continua. Una mquina adicional
ser cmo reserva, para mantenimientos y/o reparaciones de cualquier de las otras mquinas.

La Central Elctrica contiene lo siguiente:

15 generadores de 1000 kWe 1250 kVA (Continuous Power)

1 generador de reserva (standby)

7 Tanques de Combustible, de 25.000 Litros cada uno + mangueras

1 Estacin de Bomba de Transferencia de Diesel (incl. 1 bomba de reserva)

2 Transformadores de 6.6 MVA 480 V 10.500 V

1 Transformador de 3.3 MVA 480 V 10.500 V

1 Sala de Control con paneles de operacin remoto

Cables de BT de 15 metros x 240 mm

Cables de MT

La planta operar sincronizada y aportando al sistema aislado Iquitos.

Todos los equipos tienen la capacidad para operar 24/7 (24 horas/7 das por semana), menos
durante mantenimiento, por lo que se usa la mquina de reserva. Los generadores operarn a
480 Volt 60Hz

En el presente estudio se realizaron los siguientes anlisis elctricos:

Modelamiento del Sistema Elctrico Iquitos con la Central Trmica de Emergencia.

Exigencias de diseo, se determina la tolerancia a la circulacin de la corriente de


secuencia inversa correspondiente a una falla asimtrica cercana.

Anlisis elctricos en estado estacionario para condiciones normales de operacin antes


y despus del ingreso del proyecto.

Clculo de las corrientes de cortocircuito.

Verificaciones de estabilidad transitoria

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 5
INGENIERA
DESARROLLO
GESTIN ENERGTICA

2. OBJETIVO

El presente estudio de Operatividad tiene los siguientes objetivos principales:

Determinar la tolerancia a la circulacin de corriente de secuencia negativa que puede


circular por los devanados de armadura de los generadores de la C.T.E. Iquitos, con el
objetivo de verificar que esta magnitud pueda ser tolerada durante un tiempo superior al
de la actuacin de la ltima proteccin de respaldo de la red en el caso de fallas
asimtricas.

El objetivo de los anlisis de flujo de potencia, es evaluar el impacto de la incorporacin


de las nuevas instalaciones sobre el comportamiento en estado estacionario del Sistema
Elctrico de ELOR, en particular de la zona de influencia del proyecto, analizando los
niveles de tensin en las barras de las subestaciones y sobrecarga de lneas y
transformadores.

Los anlisis de cortocircuito, estarn orientados a determinar la influencia que tiene el


proyecto en los niveles de corriente de cortocircuito de las nuevas instalaciones, de
manera que esta informacin sea utilizada para la verificacin de la capacidad de ruptura
de los equipos de maniobra y proteccin.

Determinar el tiempo crtico de despeje de falla asociado a la constante de inercia


prevista para la C.T.E. Iquitos, demostrndose la factibilidad de conectar estas
instalaciones al Sistema Elctrico de ELOR desde el punto de vista de estabilidad del
sistema.

Evaluar la estabilidad transitoria, con los tiempos normales de operacin de las


protecciones, para encontrar desde el punto de vista dinmico, el impacto que puede
producir sobre el sistema la ocurrencia de disturbios de magnitud importante, tales como
cortocircuitos en lneas cercanas al rea del proyecto.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 6
INGENIERA
DESARROLLO
GESTIN ENERGTICA

3. INFORMACIN UTILIZADA

3.1. Descripcin del Proyecto

En la Figura 3.1, se muestra el diagrama unifilar del rea de influencia considerada en el estudio,
la C.T.E. Iquitos se encuentra encerrado con lneas de color azul.

El proyecto comprende la instalacin de 15 generadores con potencia nominal 1.25 MVA cada
uno, factor de potencia de 0.8 y tensin nominal 0.48 kV. Adems contar con dos
transformadores de 6.6 MVA (2x3.3 MVA) y un transformador de 3.3 MVA, la relacin de
transformacin es 10.5/0.48 kV en la C.T.E. Iquitos y la conexin al Sistema Elctrico Iquitos se
realizar en la celda de reserva BAO907 (Barra Wartsila G20MW) en 10.5 kV mediante cables
N2XSY de capacidad 354 A y 531 A.

En el Cuadro 3.1 se presentan los parmetros de los generadores.

Cuadro 3.1 Parmetros de Generadores

Name rstr xl xd xq xd' xq' xd'' xq'' x0 x2


p.u. p.u. p.u. p.u. p.u. p.u. p.u. p.u. p.u. p.u.
CATMAK_9.087MVA 0.0061 0.1000 2.1200 1.0600 0.3630 1.0600 0.2140 0.2350 0.0640 0.2250
CATMAK_9.293MVA 0.0000 0.1000 1.6930 1.0600 0.3630 1.0600 0.2140 0.2350 0.0640 0.2250
CAT_1.7MVA-0.48KV 0.0150 0.1000 1.9149 1.0486 0.2500 0.3000 0.1563 0.1571 0.1000 0.2000
CAT_2.0MVA-0.48KV 0.0150 0.1000 1.9149 1.0486 0.2500 0.3000 0.1563 0.1571 0.1000 0.2000
CAT_2.28MVA-0.48KV 0.0150 0.1000 1.9149 1.0486 0.2500 0.3000 0.1563 0.1571 0.1000 0.2000
GM-N1_3.125MVA-10.5KV 0.0150 0.1000 1.9149 1.0486 0.2500 0.3000 0.1563 0.1571 0.1000 0.1600
PWS_1.25MVA-0.48KV 0.0087 0.0300 3.5300 2.2800 0.2200 0.3000 0.1600 0.3200 0.0300 0.2300
WARTSILA_8MVA 0.0053 0.1000 2.1200 0.9800 0.3710 0.3000 0.2510 0.3830 0.1380 0.2000
WARTSILA_9.878MVA 0.0140 0.0990 1.5700 0.7850 0.3150 0.7690 0.1650 0.1810 0.0540 0.2000

Cuadro 3.2 Constantes de Tiempo y Constantes de Inercia de Generadores


Name Td' Td0' Td'' Tq'' Td0'' Tq0'' H[Sgn]
s s s s s s s
CATMAK_9.087MVA 0.6250 3.6500 0.0300 0.0500 0.0509 0.2255 1.0350
CATMAK_9.293MVA 0.6250 2.9148 0.0300 0.0500 0.0509 0.2255 1.0120
CAT_1.7MVA-0.48KV 0.4741 3.6314 0.0122 0.0091 0.0195 0.0607 2.0000
CAT_2.0MVA-0.48KV 0.4741 3.6314 0.0122 0.0091 0.0195 0.0607 2.0000
CAT_2.28MVA-0.48KV 0.4741 3.6314 0.0122 0.0091 0.0195 0.0607 2.0000
GM-N1_3.125MVA-10.5KV 0.4741 3.6314 0.0122 0.0091 0.0195 0.0607 2.0000
PWS_1.25MVA-0.48KV 0.1300 2.0859 0.0100 0.0500 0.0138 0.3563 0.4510
WARTSILA_8MVA 0.6300 3.6000 0.0291 0.0399 0.0430 0.1020 0.5300
WARTSILA_9.878MVA 0.6090 3.0353 0.0210 0.1800 0.0401 0.7648 0.7760

Los transformadores elevadores de la C.T.E. Iquitos son de 3.3 MVA KNAF, 10.5 2x 4.76%/0.48
kV, con rangos de taps 9.52%. En el siguiente Cuadro se muestran los parmetros de los
transformadores del Sistema Elctrico Iquitos y de la C.T.E. Iquitos.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 7
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Cuadro 3.3 Parmetros de Transformadores


Name rtd.Pow. HV-rtd.Volt. LV-Rtd.Volt. Shc Volt. Cop.Los. Name No Load Cur. No Load Los.
MVA kV kV % kW % kW
1.0MVA 10.1/0.4KV Dyn11_7.11% 1 10.1 0.4 7.11 8.8 Dyn11 0.1651 1.65
1.0MVA 10.5/0.4KV Dyn11_7.14% 1 10.5 0.4 7.14 8.8 Dyn11 0.1651 1.65
1.0MVA 10.5/0.4KV Dyn11_7.20% 1 10.5 0.4 7.2 8.8 Dyn11 0.1651 1.65
1.5MVA 10.5/0.4KV Dyn11_5.4% 1.5 10.5 0.4 5.4 12 Dyn11 0.144475 2.11
1.5MVA 10.5/0.4KV Dyn11_5.92% 1.5 10.5 0.4 5.92 12 Dyn11 0.144475 2.11
1.6MVA 10.5/0.4KV Dyn11_6% 1.6 10.5 0.4 6 12.7 Dyn11 0.144475 2.11
13MVA 60/10KV Ynd5_6.92% 13 60 10 6.92 70 YNd5 0.6 12
14MVA 60/10KV Ynd5_8.7% 14 60 10 8.7 77.5 YNd5 0.55 14.5
14MVA 60/10KV Ynd5_8.88% 14 60 10 8.88 78 YNd5 0.55 14.52
2.0MVA 10.5/0.4KV Dyn11_6% 2 10.5 0.4 6 15.5 Dyn11 0.144475 2.8875
2.5MVA 10.5/0.48KV YNyn6_6.49% 2.5 10.5 0.48 6.49 19 YNyn6 0.142 3.5475
2.5MVA 10.5/0.4KV Dyn11_5.81% 2.5 10.5 0.4 5.81 19 Dyn11 0.142 3.5475
3.0MVA 10.5/0.4KV Yd5_5.81% 3 10.5 0.4 5.81 22.5 Yd5 0.33 4.235
3.3MVA 10.5/0.48KV Dyn11_9.73% 3.3 10.5 0.48 9.73 33.554 Dyn11 0.51 3.422
7.0MVA 22.9/10KV Ynd5_5.85% 7 22.9 10 5.85 45 YNd5 0.87 8
7.5MVA 60/10KV Ynd5_7.20% 7.5 60 10 7.2 48.2 YNd5 0.85 9

Cuadro 3.4 Parmetros de Lneas y Cables


Name Length Rtd. Voltage R'(AC,20C) X' B' R0'(AC) X0' B0'
km kV Ohm/km Ohm/km uS/km Ohm/km Ohm/km uS/km
A GENERAL MOTOR 0.0600 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
BARRA ALSTOM-SET IQUITOS 0.2400 10.5 0.0623 0.1926 231.10 0.5190 0.2124 230.72
CATMAT 01-02 0.0260 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
Cab_AuxWartsila 0.0400 10.5 0.1029 0.1282 154.57 0.4116 0.5127 159.35
Cab_AuxWartsilaG20MW 0.0400 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
Cab_CATMAK-05 0.0400 10.5 0.1548 0.1131 147.03 0.6190 0.4524 152.42
Cab_CATMAK-N01 0.0500 10.5 0.0793 0.1244 173.42 0.3174 0.4976 180.13
Cab_CATMAK-N02 0.0500 10.5 0.0793 0.1244 173.42 0.3174 0.4976 180.13
Cab_PSE NORTE 0.0400 10.5 0.2710 0.1508 109.33 1.0841 0.6032 110.84
Cab_RESERVA 0.0400 10.5 0.2710 0.1508 109.33 1.0841 0.6032 110.84
Cab_S-01 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-02 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-03 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-04 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-06 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-07 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-08 0.0400 10.5 0.2710 0.1508 109.33 1.0841 0.6032 110.84
Cab_S-10 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_S-11 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_SR-1 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_SR-2 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_SR-4 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_SR-6 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_SR-9 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_ServAuxi 0.0300 10.5 0.1029 0.1282 154.57 0.4116 0.5127 159.35
Cab_T-01 0.0380 10.5 0.0623 0.1926 231.10 0.5190 0.2124 230.72
Cab_T-02 0.0540 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Cab_WARTSILA-N01 0.0300 10.5 0.4600 0.2582 106.69 1.2620 0.6660 106.01
Cab_WARTSILA-N02 0.0400 10.5 0.1200 0.2096 186.61 0.7250 0.3492 187.06
Cab_WARTSILA-N03 0.0400 10.5 0.1200 0.2096 186.61 0.7250 0.3492 187.06
Cab_WARTSILA-N04 0.0400 10.5 0.0855 0.1926 231.10 0.5430 0.2124 230.72
Cab_WARTSILA-N05 0.1200 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
Cab_WARTSILA-N06 0.1150 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
Cab_WARTSILA-N07 0.1100 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
IQUITOS-SANTA ROSA 60KV 5.5000 60 0.1900 0.4480 3.75 0.4370 1.3460 1.86
Line(2) 0.0400 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
Max353.8Amp 0.0400 10.5 0.1021 0.1169 124.41 0.4085 0.4675 124.71
Max353.8Amp(1) 0.0700 10.5 0.1021 0.1169 124.41 0.4085 0.4675 124.71
Max530.7Amp 0.0350 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
SKODA-CAT-N3 0.5000 10.5 0.1555 0.1244 105.56 0.6222 0.4976 106.24
SKODA-GRUPOS RAPIDOS 0.5000 10.5 0.1021 0.1169 124.41 0.4085 0.4675 124.71
WARTSILA G20MW-SET IQUITOS 0.2540 10.5 0.0623 0.1926 231.10 0.5190 0.2124 230.72
WARTSILA-CATMAK 0.0520 10.5 0.0623 0.1926 231.10 0.5190 0.2124 230.72
WARTSILA-SKODA 0.0150 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58
WARTSILA-WARTSILA G20MW 0.0780 10.5 0.0786 0.1131 139.49 0.3142 0.4524 138.58

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 8
WARTSILA-CATMAK
N2XSY 6/10KV 3x500 mm2
Cab_S-03 0.0520 km
N2XSY 8.7/15KV 3x120 mm2
0.0400 km

S-03
Cab_S-04
B_CATMAK-05

N2XSY 8.7/15KV 3x120 mm2


Z_CATMAK-05

0.0400 km tr2_AuxWartsilaG20MW
1.5MVA 10.5/0.4KV Dyn11_5.92% Cab_AuxWartsilaG20MW
N2XSY 8.7/15KV 3x240 mm2

S-04
0.0400 km tr2_AuxCATMAK-05
1.6MVA 10.5/0.4KV Dyn11_6%
tr2_AuxCATMAK
1.6MVA 10.5/0.4KV Dyn11_6% Cab_ServAuxi

0
N2XSY 3-1x185 mm2
0.0300 km Cab_WARTSILA-N05
0

N2XSY 8.7/15KV 3x240 mm2

AuxWARTSILAG20MW
AuxCAT MAK-05

0.1200 km Cab_CATMAK-05

0
~
N2XSY 6/10KV 3x120 mm2

AuxCAT MAK
SG
0.0400 km

B_WART SILA G20MW


Cab_CATMAK-N01
~

N2XSY 3-1x240 mm2


SG

B_CATMAK 01-02
0.0500 km

WARTSILA-N05

~
CAT MAK-05

SG
Cab_WARTSILA-N06
N2XSY 8.7/15KV 3x240 mm2
Cab_CATMAK-N02 0.1150 km

~
N2XSY 3-1x240 mm2

SG
Breaker/Switch

0.0500 km

~
SG
WARTSILA-N06
WARTSILA-WARTSILA G20MW
N2XSY 8.7/15KV 3x240 mm2

CAT MAK-N01 CAT MAK-N02


Cab_S-07 Cab_WARTSILA-N07 0.0780 km
INGENIERA

N2XSY 8.7/15KV 3x120 mm2 N2XSY 8.7/15KV 3x240 mm2


0.0400 km 0.1100 km

S-07
SG

0.0260 km
DESARROLLO

CAT MAT 01-02


tr2_AuxSKODA Cab_WARTSILA-N04

WARTSILA-N07
1.0MVA 10.5/0.4KV Dyn11_7.20% 6/10KV-1992 3x500 mm2 ALU

N2XSY 8.7/15KV 3x240 mm2


0.0400 km
~
SG

AuxSKODA
B_W ARTSILA

WARTSILA-N04

Cab_S-08
N2XSY 3-1x70 mm2
1250 A 0.0400 km
S-08
GESTIN ENERGTICA

Max353.8Amp(1)
N2XSY 8.7/15KV 3x185 mm2
0.0700 km
Cab_PSE NORTE
N2XSY 3-1x70 mm2
PSE NORTE 0.0400 km

~
B_G1-G3

G01
SG
tr2_CTE-IQUITOS01 Cab_WARTSILA-N03
3.3MVA 10.5/0.48KV Dyn11_9.73% 6/10KV-1992 3x300 mm2 ALU

GR_01
EPLI SAC_01 0.0400 km
3.0MVA 10.5/0.4KV Yd5_5.81%

B_G1-G6

~
~
~

G02
SG
SG
SG

1
CAT 3516-N01
WARTSILA-N03

0 Cab_RESERVA

~
~
N2XSY 3-1x70 mm2

G03
SG
SG
RESERVA 0.0400 km
B_SKODA

CAT 3516-N05
0.0150 km

GR_02
0.5000 km

EPLI SAC_02 Cab_WARTSILA-N02


WARTSILA-SKODA

2.5MVA 10.5/0.48KV YNyn6_6.49% 6/10KV-1992 3x300 mm2 ALU

~
~

B_G4-G6

G04
SG
SG
tr2_CTE-IQUITOS02 0.0400 km
N2XSY 8.7/15KV 3x240 mm2

3.3MVA 10.5/0.48KV Dyn11_9.73%


SKODA-GRUPOS RAPIDOS
~

N2XSY 8.7/15KV 3x185 mm2


SG

CAT 3516-N06
1

~
~

G05
SG
SG
Cab_S-02
WARTSILA-N02

1
N2XSY 8.7/15KV 3x120 mm2
0.0400 km

CAT 3512B-PM16

~
GR_03

G06
S-02

SG
EPLI SAC_03
2.5MVA 10.5/0.4KV Dyn11_5.81%
~
SG

Cab_WARTSILA-N01
6/10KV-1992 3x70 mm2 ALU
GRUPOS RAPIDOS

0.0300 km
CAT 3512B-PM17
1

~
~

SG
SG

~
B_G7-G9

G07
SG
tr2_CTE-IQUITOS03
0.0350 km
Cab_S-10
WARTSILA-N01

CAT 3512B-PM19

Max530.7Amp
3.3MVA 10.5/0.48KV Dyn11_9.73% N2XSY 8.7/15KV 3x120 mm2
0.0400 km

B_G7-G12
0.5000 km

~
G08
N2XSY 8.7/15KV 3x240 mm2
S-10

SG
T-3
SKODA-CAT-N3

1.0MVA 10.1/0.4KV Dyn11_7.11%

1
N2XSY 8.7/15KV 3x120 mm2

CAT -N3 10.5KV

~
G09

Pgina 9
SG
0

~
SG

T-4 T-6
1.0MVA 10.1/0.4KV Dyn11_7.11% 1.5MVA 10.5/0.4KV Dyn11_5.4%
CAT 3516-N03

~
~

B_G10-G12

G10
SG
SG

tr2_CTE-IQUITOS04 A GENERAL MOTOR


3.3MVA 10.5/0.48KV Dyn11_9.73% N2XSY 8.7/15KV 3x120 mm2
0
1

0.0600 km

POWER SOLUTIONS
CAT 3516-N02
GENERAL MOTOR

(1)

~
~

G11
SG
SG

T-6(1)
GM-N1

1.0MVA 10.5/0.4KV Dyn11_7.14%


1
CAT -N3 0.48KV

Line(2)
N2XSY 8.7/15KV 3x120 mm2

~
G12
SG
0.0400 km
0.0400 km
Max353.8Amp
1

~
SG

T-6(2)
1.0MVA 10.5/0.4KV Dyn11_7.14%
CAT 3516-N04

Cab_S-11
N2XSY 8.7/15KV 3x185 mm2

N2XSY 8.7/15KV 3x120 mm2

~
B_G13-G15
B_G13-G15(1)

G13
SG tr2_CTE-IQUITOS05 0.0400 km
3.3MVA 10.5/0.48KV Dyn11_9.73%
1
S-11

TR2_CUMMINSN1
2.0MVA 10.5/0.4KV Dyn11_6%
~
G14
SG

Cab_S-06
N2XSY 8.7/15KV 3x120 mm2
1
~

0.0400 km
SG
1

~
C.T.E. IQUITOS

G15
CUMMINS-N1
S-06

SG
Figura 3.1 Diagrama Unifilar del Proyecto

tr2_AuxWartsila Cab_AuxWartsila
0.2540 km

1.5MVA 10.5/0.4KV Dyn11_5.92% N2XSY 3-1x185 mm2


0.0400 km
N2XSY 8.7/15KV 3x500 mm2
WARTSILA G20MW-SET IQUITOS
0

AuxWARTSILA

SR522.9KV
Breaker/Switch(1)

Tr2-SR5 Cab_S-01
7.0MVA 22.9/10KV Ynd5_5.85% N2XSY 8.7/15KV 3x120 mm2
0.0400 km
S-01

SR-5

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


0
B_ALSTOM

Cab_SR-4
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
PowerFactory 15.1.7
SR-4
SANTA_ROSA60KV

T-03
BARRA_A_10.5KV

13MVA 60/10KV Ynd5_6.92%


Cp_SRosa
-4

Z_SR

T-04
7.5MVA 60/10KV Ynd5_7.20%
Serv.Aux
-4

SR-2

Cab_SR-2
IQUITOS60KV

N2XSY 8.7/15KV 3x120 mm2


0.2400 km

0.0400 km T-01
C.T .E. IQUIT OS

Cab_T-01
IQUITOS10.5KV

14MVA 60/10KV Ynd5_8.7% N2XSY 8.7/15KV 3x500 mm2


DIAGRAMA UNIFILAR
5.5000 km

0.0380 km
N2XSY 8.7/15KV 3x500 mm2
BARRA ALSTOM-SET IQUITOS

EST UDIO DE OPERAT IVIDAD

Cab_SR-6
060_CT Iquitos - Iquitos
0

N2XSY 8.7/15KV 3x120 mm2


IQUITOS-SANTA ROSA 60KV

0.0400 km T-02 Cab_T-02


14MVA 60/10KV Ynd5_8.88% N2XSY 8.7/15KV 3x120 mm2
SR-6

0.0540 km

Cab_SR-1
0

N2XSY 8.7/15KV 3x120 mm2


0.0400 km
Date:
SR-1

Annex:

Cab_SR-9
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
SR-9
BARRA_B_10.5KV

Project: EOCTEIQ

9/16/2015
Graphic: RED_IQUIT OS

DIgSILENT
INGENIERA
DESARROLLO
GESTIN ENERGTICA

3.2. Periodo de Estudio

Segn los alcances indicados trminos de referencia CONTRATACIN DEL SUMINISTRO DE


ENERGA POR GENERACIN ADICIONAL PARA EL SISTEMA ELCTRICO IQUITOS, la
instalacin de la C.T.E. Iquitos consta de dos periodos:

Periodo 1: Inicio de Operacin Comercial 30 de setiembre 2015: 9 MW

Periodo 2: 01 de Octubre 2015 31 de Julio 2016: 12 MW

3.3. Oferta del Sistema Elctrico Iquitos

En el siguiente cuadro se presenta la oferta existente y la oferta de la C.T.E. Iquitos en los


periodos de avenida y estiaje, mxima, media y mnima demanda.

Cuadro 3.5 Despacho de Generadores en el Periodo 1 9 MW


CTE 9MW Mxima Demanda Media Demanda Mnima Demanda
Name Act.Pow. Act.Pow. Act.Pow.
MW MW MW
CAT 3512B-PM16 0.78 0.69 0.22
CAT 3512B-PM17 0.78 0.69 0.22
CAT 3512B-PM19 0.78 0.69 0.22
CAT 3516-N01 0.78 0.69 0.22
CAT 3516-N02 0.78 0.69 0.22
CAT 3516-N03 0.78 0.69 0.22
CAT 3516-N04 0.78 0.69 0.22
CAT 3516-N05 0.78 0.69 0.22
CAT 3516-N06 0.78 0.69 0.22
CATMAK-05 - - -
CATMAK-N01 - - -
CATMAK-N02 4.65 4.13 1.34
CUMMINS-N1 1.16 1.03 0.34
G01 0.75 0.75 0.75
G02 0.75 0.75 0.75
G03 0.75 0.75 0.75
G04 0.75 0.75 0.75
G05 0.75 0.75 0.75
G06 0.75 0.75 0.75
G07 0.75 0.75 0.75
G08 0.75 0.75 0.75
G09 0.75 0.75 0.75
G10 0.75 0.75 0.75
G11 0.75 0.75 0.75
G12 0.75 0.75 0.75
G13 - - -
G14 - - -
G15 - - -
GM-N1 - - -
WARTSILA-N01 3.10 2.76 0.90
WARTSILA-N02 3.10 2.76 0.90
WARTSILA-N03 3.10 2.76 0.90
WARTSILA-N04 4.65 4.13 1.34
WARTSILA-N05 6.09 5.41 1.76
WARTSILA-N06 6.09 5.41 1.76
WARTSILA-N07 6.09 5.41 1.76
TOTAL 54.05 49.01 21.98

Nota: Grupos G01 al G15 conforman la C.T.E. Iquitos

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 10
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Cuadro 3.6 Despacho de Generadores en el Periodo 2 12 MW


CTE 12 MW Mxima Demanda Media Demanda Mnima Demanda
Name Act.Pow. Act.Pow. Act.Pow.
MW MW MW
CAT 3512B-PM16 0.72 0.62 0.17
CAT 3512B-PM17 0.72 0.62 0.17
CAT 3512B-PM19 0.72 0.62 0.17
CAT 3516-N01 0.72 0.62 0.17
CAT 3516-N02 0.72 0.62 0.17
CAT 3516-N03 0.72 0.62 0.17
CAT 3516-N04 0.72 0.62 0.17
CAT 3516-N05 0.72 0.62 0.17
CAT 3516-N06 0.72 0.62 0.17
CATMAK-05 - - -
CATMAK-N01 - - -
CATMAK-N02 4.34 3.72 1.03
CUMMINS-N1 1.09 0.93 0.26
G01 0.80 0.80 0.80
G02 0.80 0.80 0.80
G03 0.80 0.80 0.80
G04 0.80 0.80 0.80
G05 0.80 0.80 0.80
G06 0.80 0.80 0.80
G07 0.80 0.80 0.80
G08 0.80 0.80 0.80
G09 0.80 0.80 0.80
G10 0.80 0.80 0.80
G11 0.80 0.80 0.80
G12 0.80 0.80 0.80
G13 0.80 0.80 0.80
G14 0.80 0.80 0.80
G15 0.80 0.80 0.80
GM-N1 - - -
WARTSILA-N01 2.89 2.48 0.69
WARTSILA-N02 2.89 2.48 0.69
WARTSILA-N03 2.89 2.48 0.69
WARTSILA-N04 4.34 3.72 1.03
WARTSILA-N05 5.68 4.87 1.35
WARTSILA-N06 5.68 4.87 1.35
WARTSILA-N07 5.68 4.87 1.35
TOTAL 53.96 48.00 21.97

Nota: Grupos G01 al G15 conforman la C.T.E. Iquitos

La oferta de la C.T.E. Iquitos es 9 MW en el periodo 1 y 12 MW en el segundo periodo.

3.4. Demanda del Sistema Elctrico Iquitos

La demanda de los alimentadores del sistema Elctrico Iquitos para el ao 2015, fue
proporcionada por la Empresa Electro Oriente, esta informacin se detalla en el siguiente cuadro.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 11
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Cuadro 3.7 Demanda de Alimentadores

CENTRAL/SUBESTACIN Carga MXIMA MEDIA MNIMA


S-08 4.83 4.13 1.84
PSE IQUITOS NORTE - - -
S-02 3.76 3.63 1.45
CENTRAL DE GENERACIN WARTSILA S-10 4.59 4.51 1.36
S-11 2.86 2.89 1.20
S-06 5.37 4.91 1.41
S-01 2.64 3.05 1.67
CENTRAL DE GENERACIN CATMAK 5 Aux. Cat Mak 5 - - -
CENTRAL DE GENERACIN NUEVO
Transformador Auxiliar 0.55 0.51 0.45
WARTSILA
S-03 3.46 2.86 1.62
S-04 2.97 2.80 1.18
CENTRAL DE GENERACIN CATMAK S-07 3.72 2.93 1.33
Aux. Cat Mak 0.45 0.41 0.35
Auxiliar skoda
CENTRAL DE GENERACIN GRUPOS
Auxiliares
RPIDOS
SR-1 3.31 2.74 1.34
SR-2 4.53 3.56 1.71
SR-3 - - -
SR-4 2.56 2.45 0.91
SUBESTACIN SANTA ROSA
SR-5 4.26 3.41 2.02
SR-6 2.60 2.34 1.07
SR-9 1.55 1.69 1.57
Auxiliares
TOTAL 54.01 48.81 22.47

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 12
INGENIERA
DESARROLLO
GESTIN ENERGTICA

4. METODOLOGA

4.1. Tolerancia a la Circulacin de la Corriente de Secuencia Negativa

El anlisis es realizado para determinar el mximo valor instantneo de la corriente de secuencia


negativa que circulara por los devanados de armadura del generador de la C.T.E. Iquitos. Para
ello se simula fallas del tipo bifsicas y sin contacto a tierra en la barra de baja y alta tensin del
transformador principal, la unidad de generacin debe soportar este nivel de corriente durante el
tiempo suficiente que permita actuar hasta la ltima proteccin de respaldo.

Segn la norma ANSI, la capacidad trmica de corto tiempo del rotor se calcula de acuerdo a la
siguiente expresin:

(I2)2 x t = n

Siendo:

I2: Componente de secuencia negativa de la corriente de armadura del generador en p.u.

t: Tiempo que el generador puede soportar la circulacin de la corriente de secuencia


negativa (en segundos)

n: Constante de diseo del generador

De acuerdo a la Norma ANSI C37.102.1987, las maquinas con potencias nominales menores a
800 MVA pueden soportar en forma permanente corrientes de secuencia negativa del orden del
10% de la corriente nominal.

Igualmente, la misma norma especfica que la constante de tiempo (I2/I0)2.t de los generadores
con potencias menores a 800 MVA es de 40 s.

La secuencia de simulacin de la falla es la siguiente:

0 ms : Falla bifsica sin contacto a tierra en la barra de baja o alta tensin.

100 ms : Despeje de la falla.

De los resultados de la secuencia de simulacin, se debe verificar el tiempo que el generador


puede soportar la circulacin de la corriente de secuencia negativa es menor de 40 segundos de
acuerdo a lo descrito anteriormente.

4.2. Anlisis de Flujo de Potencia

La metodologa aplicada, consiste en resolver el problema de flujo de potencia utilizando el


software Digsilent Power Factory, con la finalidad de obtener las magnitudes de las tensiones y
el flujo de potencia en las lneas de transmisin y transformadores en estado estacionario para
un punto especfico de operacin del SEIN, definido por una topologa que permanece invariable

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 13
INGENIERA
DESARROLLO
GESTIN ENERGTICA

durante el proceso de clculo. La solucin del problema de flujo de potencia permite obtener
principalmente los siguientes resultados:

Sobrecargas en lneas de transmisin y transformadores.

Niveles de tensiones en las barras de las subestaciones.

Corriente en operacin por los equipos de proteccin y maniobra.

Los anlisis de flujo de potencia, se realizan en condiciones normales de operacin con la C.T.E.
Iquitos en los Periodo 1 con 9 MW y Periodo 2 con 12 MW.

Los resultados de flujo de potencia en condiciones normales de operacin son presentados en


cuadros y salidas graficas del DIGSILENT.

4.3. Anlisis de Cortocircuito

El clculo de las corrientes de cortocircuito se realiza segn la norma IEC60909 2001, para fallas
bifsicas a tierra, monofsicas y trifsicas en las barras del Sistema Elctrico Iquitos. Este
anlisis se realizar para las situaciones de mxima, media y mnima demanda para el ao 2015.

Los resultados del anlisis de cortocircuito, se presentan en cuadros y salidas graficas del
DIGSILENT. Asimismo se simula el escenario de mxima generacin, con todos los generadores
operando, con el fin de calcular las mayores corrientes de cortocircuito.

4.4. Determinacin del Tiempo Crtico de Despeje de Falla

Para determinar el tiempo crtico de despeje de falla, se debe efectuar la evaluacin de la


estabilidad transitoria de primera oscilacin de las nuevas unidades de generacin, con los
tiempos normales de operacin de las protecciones.

Para ello, se aplic una falla trifsica en la barra de alta tensin del transformador elevador de la
C.T.E. Iquitos durante 100 ms, luego se procedi a incrementarlo hasta que el generador
perdiese el sincronismo.

El anlisis se realiza para las situaciones de mxima, media y mnima demanda en los periodos
1 y 2.

4.5. Anlisis de Estabilidad Transitoria

Para encontrar desde el punto de vista dinmico, el impacto que puede producir sobre el sistema
la ocurrencia de disturbios de magnitud importante, tales como cortocircuitos, se analizan los
siguientes casos:

Falla monofsica con recierre exitoso en la lnea Iquitos Santa Rosa 60 kV, al 1% de
la lnea desde la S.E. Iquitos.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 14
INGENIERA
DESARROLLO
GESTIN ENERGTICA

5. CRITERIOS TCNICOS

Los criterios tcnicos para el anlisis en estado estacionario se describen a continuacin y han
sido obtenidas del documento Procedimiento tcnico del COES, PR-20 - Ingreso, modificacin
y retiro de instalaciones del SEIN, aprobado mediante Resolucin OSINERGMIN N 035-2013-
OS/CD del 14 de marzo de 2013.

Tensin
Estado Normal: debe estar dentro del rango 5 % de las tensiones nominales de los
equipos instalados en las subestaciones, principalmente transformadores de potencia.
Asimismo, en el caso de las barras del sistema de transmisin, las tensiones en Estado
Normal deben estar en el rango de 2.5 % de las tensiones de operacin.

Estado de Emergencia: se debe mantener un nivel de tensin comprendido entre 0.90 y


1.10 p.u. de la tensin de operacin, en todas las barras con tensin nominal de 220 kV.
Debe estar en el rango de 0.90 y 1.05 p.u. de la tensin de operacin en todas las barras
con tensin igual o menor a 138 kV.

Sobrecargas
Estado Normal: no se admite sobrecargas ni en lneas ni en transformadores de
potencia.

Estado de Alerta (Contingencia N-1): lneas y transformadores: En esta etapa las


simulaciones deben arrojar sobrecargas menores o iguales al 20%. Posteriormente, en
la etapa de conexin de las instalaciones, estas magnitudes sern declaradas por el
titular en las fichas tcnicas mostradas en el Anexo 4 del Procedimiento tcnico PR-20.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 15
INGENIERA
DESARROLLO
GESTIN ENERGTICA

6. EXIGENCIAS DE DISEO

En el presente captulo, se determinara la tolerancia a la circulacin de la corriente inversa.

6.1. Tolerancia a Corrientes de Secuencia Inversa

Se simula una falla bifsica sin contacto a tierra en los bornes de generacin 0.48 kV y en el lado
de alta tensin del generador elevador 10.5 kV, determinndose el cual de los casos se obtiene
una mayor corriente de secuencia inversa.

Figura 6.1 Corriente de Secuencia Inversa Falla en 0.48 kV

DIgSILENT
2.323
0.002 s
Y = 2.212 p.u.

1.836

1.350

0.863

0.376

-0.111
-0.100 0.119 0.339 0.558 0.777 [s] 0.997
G01: Negative-Sequence Current, Magnitude in p.u.
G04: Negative-Sequence Current, Magnitude in p.u.
G07: Negative-Sequence Current, Magnitude in p.u.
G10: Negative-Sequence Current, Magnitude in p.u.
G13: Negative-Sequence Current, Magnitude in p.u.

SEC_INVERSA Date:
Annex: /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 16
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 6.2 Corriente de Secuencia Inversa Falla en 33 kV

DIgSILENT
1.466
0.002 s
Y = 1.396 p.u.

1.159

0.852

0.545

0.237

-0.070
-0.100 0.119 0.339 0.558 0.777 [s] 0.997
G01: Negative-Sequence Current, Magnitude in p.u.
G07: Negative-Sequence Current, Magnitude in p.u.
G10: Negative-Sequence Current, Magnitude in p.u.

SEC_INVERSA Date:
Annex: /1

Para determinar el tiempo de tolerancia a corrientes de secuencia negativa, consideramos que


las corrientes de secuencia negativa obtenidas en los diferentes eventos permanecen constantes
durante la eliminacin de la falla. Se determina el tiempo de tolerancia a dichas corrientes
aplicando la formula descrita en la seccin 4.1.

Los resultados para los casos planteados se presentan en el cuadro siguiente.

Cuadro 6.1 Tolerancia de Corrientes de Secuencia Negativa

I2 tiempo
Falla en: Tensin (kV)
(p.u.) (segundos)
Lado de Baja Tensin 0.48 2.212 8.18
Lado de Alta Tensin 10.5 1.396 20.53

En el cuadro anterior se observa, que la falla que produce mayor incremento de corriente de
secuencia negativa, es la falla bifsica en 0.48 kV y ste tolerar dicha corriente de 2.212 p.u.
por 8.18 segundos.

De acuerdo a los resultados este tiempo de tolerancia de 8.18 segundos, an bajo la hiptesis
que la corriente inversa no decrece con el tiempo, supera ampliamente cualquier tiempo
razonable que pudiera ser asignado para un esquema de respaldo.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 17
INGENIERA
DESARROLLO
GESTIN ENERGTICA

7. ANLISIS EN ESTADO ESTACIONARIO

En el presente captulo, se realizar el anlisis de estado estacionario, se evalan los niveles de


tensin y niveles de carga en lneas y transformadores.

7.1. Flujo de Potencia en Operacin Normal

Las simulaciones se realizaron utilizando el programa Digsilent Versin 15.1.7, los anlisis
incluyen las situaciones con proyecto y sin proyecto (Periodo 1 y 2), en las condiciones de
mxima, media y mnima demanda para el ao 2015.

En el Anexo A, se pueden observar los resultados de las simulaciones de flujo de potencia en


condiciones normales de operacin.

7.1.1. Caso Base Sin Proyecto

Se ha simulado los flujos de potencia para la configuracin sin la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:

a) Respecto a las tensiones en las barras de las subestaciones, en el siguiente cuadro se


presenta el resumen de los niveles de tensin en kV y en p.u.:

Cuadro 7.1 Tensin en Barras Caso Base 2015


Nombre Tensin BASE - 2015
Subestacin Barra Nominal Mxima Media Mnima
Digsilent [kV] [kV] [p.u.] [kV] [p.u.] [kV] [p.u.]
SKODA B_SKODA 10.5 10.5 1.000 10.5 1.000 10.5 1.000
CATMAK 01-02 B_CATMAK 01-02 10.5 10.5 1.000 10.5 1.000 10.5 1.000
WARTSILA B_WARTSILA 10.5 10.5 0.999 10.5 0.999 10.5 1.000
B_ALSTOM 10.5 10.5 0.999 10.5 0.999 10.5 1.000
B_CATMAK-05 10.5 10.5 0.999 10.5 0.999 10.5 1.000
WARTSILA G20MW B_WARTSILA G20MW 10.5 10.5 1.000 10.5 1.000 10.5 1.000
CAT-N3 10.5KV 10.5 10.5 1.000 10.5 1.000 10.5 1.000
GENERAL MOTOR GENERAL MOTOR 10.5 10.5 1.000 10.5 1.000 10.5 1.000
GRUPOS RAPIDOS 10.5 10.5 1.003 10.5 1.003 10.5 1.000
IQUITOS IQUITOS10.5KV 10.5 10.5 0.997 10.5 0.998 10.5 0.999
IQUITOS60KV 60 60.8 1.013 61.2 1.021 62.3 1.038
SANTA ROSA BARRA_A_10.5KV 10.5 10.2 0.969 10.3 0.986 10.5 1.000
BARRA_B_10.5KV 10.5 10.1 0.963 10.3 0.978 10.4 0.989
SANTA_ROSA60KV 60 60.1 1.001 60.7 1.011 62.0 1.034

Del cuadro anterior se observa que las tensiones en el sistema, estn dentro de los rangos
aceptables de operacin normal 5%.

b) Respecto a las sobrecargas del Sistema Elctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, lneas de transmisin y transformadores:

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 18
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Cuadro 7.2 Niveles de Carga (%) Caso Base 2015

Tensin BASE - 2015


Lnea / Transformador Nominal Mxima Media Mnima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.26 9.32 22.83
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.71 17.29
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.92 4.61 35.26
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.88 39.74 9.14 19.99
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 16.24 57.26 13.83 48.75 1.91 6.73
T-01 14MVA 60/10KV Ynd5_8.7% 11.09 75.66 9.32 63.55 4.71 32.05
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.28 4.61 31.41

Del cuadro anterior se observa que las sobrecargas en cables, lneas y transformadores son
menores al 100%.

En el Anexo A1, se puede observar los resultados de las simulaciones de flujo de potencia sin
proyecto.

7.1.2. Periodo 1 con C.T.E. Iquitos 9 MW

Se ha simulado los flujos de potencia para la configuracin con la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:

a) Respecto a las tensiones en las barras de las subestaciones, en el siguiente cuadro se


presenta el resumen de los niveles de tensin en kV y en p.u.:

Cuadro 7.3 Tensin en Barras Periodo 1 con C.T.E. Iquitos 9 MW

Nombre Tensin PERIODO1


Subestacin Barra Nominal Mxima Media Mnima
Digsilent [kV] [kV] [p.u.] [kV] [p.u.] [kV] [p.u.]
C.T.E. IQUITOS B_G1-G6 10.5 10.5 1.000 10.5 1.000 10.5 1.000
B_G7-G12 10.5 10.5 1.000 10.5 1.000 10.5 1.000
B_G13-G15(1) 10.5 10.5 1.000 10.5 1.000 10.5 1.000
SKODA B_SKODA 10.5 10.5 1.000 10.5 1.000 10.5 1.000
CATMAK 01-02 B_CATMAK 01-02 10.5 10.5 1.000 10.5 1.000 10.5 1.000
WARTSILA B_WARTSILA 10.5 10.5 0.999 10.5 0.999 10.5 1.000
B_ALSTOM 10.5 10.5 0.999 10.5 0.999 10.5 1.000
B_CATMAK-05 10.5 10.5 0.999 10.5 0.999 10.5 1.000
WARTSILA G20MW B_WARTSILA G20MW 10.5 10.5 1.000 10.5 1.000 10.5 1.000
CAT-N3 10.5KV 10.5 10.5 1.000 10.5 1.000 10.5 1.000
GENERAL MOTOR GENERAL MOTOR 10.5 10.5 0.999 10.5 0.999 10.5 1.000
GRUPOS RAPIDOS 10.5 10.5 1.000 10.5 1.000 10.5 1.000
IQUITOS IQUITOS10.5KV 10.5 10.5 0.997 10.5 0.998 10.5 0.999
IQUITOS60KV 60 60.8 1.013 61.2 1.021 60.7 1.012
SANTA ROSA BARRA_A_10.5KV 10.5 10.2 0.969 10.3 0.986 10.4 0.995
BARRA_B_10.5KV 10.5 10.1 0.963 10.3 0.978 10.4 0.990
SANTA_ROSA60KV 60 60.1 1.001 60.7 1.011 60.5 1.008

Del cuadro anterior se observa que las tensiones en el sistema, estn dentro de los rangos
aceptables de operacin normal 5%.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 19
INGENIERA
DESARROLLO
GESTIN ENERGTICA

b) Respecto a las sobrecargas del Sistema Elctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, lneas de transmisin y transformadores:

Cuadro 7.4 Niveles de Carga (%) Periodo 1 con C.T.E. Iquitos 9 MW

Tensin PERIODO 1
Lnea / Transformador Nominal Mxima Media Mnima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.26 9.33 22.85
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.71 17.31
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.92 4.62 35.30
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.88 39.74 9.15 20.52
Max353.8Amp(1) N2XSY 8.7/15KV 3x185 mm2 5.02 61.39 5.02 61.36 5.02 61.30
Max530.7Amp N2XSY 8.7/15KV 3x240 mm2 5.01 53.02 5.01 53.00 5.01 52.95
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 17.45 61.54 15.67 55.25 6.76 23.81
T-01 14MVA 60/10KV Ynd5_8.7% 11.08 75.66 9.32 63.55 4.71 32.61
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.28 4.62 31.96
tr2_CTE-IQUITOS01 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS02 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS03 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS04 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS05 3.3MVA 10.5/0.48KV Dyn11_9.73% 0.02 0.46 0.02 0.46 0.02 0.46

Del cuadro anterior se observa que las sobrecargas en lneas y transformadores son menores al
100%.

En el Anexo A2, se puede observar los resultados de las simulaciones de flujo de potencia con
proyecto para el ao de ingreso.

7.1.3. Periodo 2 con C.T.E. Iquitos 12 MW

Se ha simulado los flujos de potencia para la configuracin con la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:

c) Respecto a las tensiones en las barras de las subestaciones, en el siguiente cuadro se


presenta el resumen de los niveles de tensin en kV y en p.u.:

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 20
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Cuadro 7.5 Tensin en Barras Periodo 2 con C.T.E. Iquitos 12 MW

Nombre Tensin PERIODO2


Subestacin Barra Nominal Mxima Media Mnima
Digsilent [kV] [kV] [p.u.] [kV] [p.u.] [kV] [p.u.]
C.T.E. IQUITOS B_G1-G6 10.5 10.5 1.000 10.5 1.000 10.5 1.000
B_G7-G12 10.5 10.5 1.000 10.5 1.000 10.5 1.000
B_G13-G15(1) 10.5 10.5 1.000 10.5 1.000 10.5 1.000
SKODA B_SKODA 10.5 10.5 1.000 10.5 1.000 10.5 1.000
CATMAK 01-02 B_CATMAK 01-02 10.5 10.5 1.000 10.5 1.000 10.5 1.000
WARTSILA B_WARTSILA 10.5 10.5 0.999 10.5 0.999 10.5 1.000
B_ALSTOM 10.5 10.5 0.999 10.5 0.999 10.5 1.000
B_CATMAK-05 10.5 10.5 0.999 10.5 0.999 10.5 1.000
WARTSILA G20MW B_WARTSILA G20MW 10.5 10.5 1.000 10.5 1.000 10.5 1.000
CAT-N3 10.5KV 10.5 10.5 1.000 10.5 1.000 10.5 1.000
GENERAL MOTOR GENERAL MOTOR 10.5 10.5 0.999 10.5 0.999 10.5 1.000
GRUPOS RAPIDOS 10.5 10.5 1.000 10.5 1.000 10.5 1.000
IQUITOS IQUITOS10.5KV 10.5 10.5 0.997 10.5 0.997 10.5 0.999
IQUITOS60KV 60 60.8 1.013 61.2 1.021 60.7 1.012
SANTA ROSA BARRA_A_10.5KV 10.5 10.2 0.969 10.3 0.986 10.3 0.984
BARRA_B_10.5KV 10.5 10.1 0.963 10.3 0.978 10.4 0.989
SANTA_ROSA60KV 60 60.1 1.001 60.7 1.011 60.4 1.007

Del cuadro anterior se observa que las tensiones en el sistema, estn dentro de los rangos
aceptables de operacin normal 5%.

d) Respecto a las sobrecargas del Sistema Elctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, lneas de transmisin y transformadores:

Cuadro 7.6 Niveles de Carga (%) Periodo 2 con C.T.E. Iquitos 12 MW

Tensin PERIODO 2
Lnea / Transformador Nominal Mxima Media Mnima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.27 9.34 22.89
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.72 17.34
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.93 4.62 35.36
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.89 39.75 9.16 20.56
Max353.8Amp(1) N2XSY 8.7/15KV 3x185 mm2 5.26 64.32 5.26 64.33 5.26 64.30
Max530.7Amp N2XSY 8.7/15KV 3x240 mm2 7.90 83.49 7.90 83.50 7.89 83.46
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 18.47 65.12 16.35 57.66 9.60 33.84
T-01 14MVA 60/10KV Ynd5_8.7% 11.08 75.66 9.32 63.56 4.72 32.67
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.29 4.62 32.01
tr2_CTE-IQUITOS01 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.87 2.77 83.87 2.77 83.84
tr2_CTE-IQUITOS02 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.87 2.77 83.87 2.77 83.84
tr2_CTE-IQUITOS03 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.82 2.77 83.83 2.77 83.79
tr2_CTE-IQUITOS04 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.82 2.77 83.83 2.77 83.79
tr2_CTE-IQUITOS05 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.95 2.77 83.96 2.77 83.92

Del cuadro anterior se observa que las sobrecargas en lneas y transformadores son menores al
100%.

En el Anexo A3, se puede observar los resultados de las simulaciones de flujo de potencia con
proyecto para el ao de ingreso.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 21
INGENIERA
DESARROLLO
GESTIN ENERGTICA

7.2. Cortocircuito en Estado Estacionario

Las simulaciones se realizaron con el programa Digsilent Versin 15.1.7, para las situaciones
con proyecto y sin proyecto, en las condiciones de mxima, media y mnima demanda para el
ao 2015.

En el Anexo B, C y D, se pueden observar los resultados de las simulaciones del clculo de las
corrientes de cortocircuito, para fallas bifsicas a tierra, monofsicas y trifsicas respectivamente.

7.2.1. Caso Base Sin Proyecto

Se ha realizado el clculo de las corrientes de cortocircuito para la configuracin sin la C.T.E.


Iquitos, para los escenarios de mxima, media y mnima demanda. En el siguiente cuadro se
presenta los resultados en mxima y mnima demanda los cuales se consideran de mayor
importancia:

Cuadro 7.7 Niveles de Cortocircuito Caso Base 2015

Nombre Tensin BASE - 2015


Subestacin Barra Nominal Mxima Mnima
Digsilent [kV] 2-T 3 1 2-T 3 1
SKODA B_SKODA 10.5 22.51 25.86 0.90 11.25 12.81 0.61
CATMAK 01-02 B_CATMAK 01-02 10.5 22.51 25.86 0.90 11.25 12.81 0.61
WARTSILA B_WARTSILA 10.5 22.53 25.88 0.90 11.29 12.85 0.61
B_ALSTOM 10.5 22.53 25.88 0.90 11.29 12.85 0.61
B_CATMAK-05 10.5 22.53 25.88 0.90 11.29 12.85 0.61
WARTSILA G20MW B_WARTSILA G20MW 10.5 22.55 25.90 0.90 11.26 12.82 0.61
CAT-N3 10.5KV 10.5 17.74 20.24 0.88 9.95 11.29 0.60
GENERAL MOTOR GENERAL MOTOR 10.5 21.94 25.18 0.89 11.12 12.66 0.61
GRUPOS RAPIDOS 10.5 18.85 21.55 0.88 10.07 11.44 0.61
IQUITOS IQUITOS10.5KV 10.5 21.26 24.40 0.89 10.96 12.48 0.61
IQUITOS60KV 60 2.27 1.80 2.31 1.69 1.25 1.68
SANTA ROSA BARRA_A_10.5KV 10.5 4.90 5.60 0.22 4.03 4.59 0.22
BARRA_B_10.5KV 10.5 3.56 4.12 0.00 3.07 3.55 0.00
SANTA_ROSA60KV 60 2.05 1.61 2.08 1.57 1.15 1.55

De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifsicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.9 kA, el cual supera la capacidad de ruptura de 25 kA.

En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentaran
problemas con el equipo existente de 31.5 kA.

7.2.2. Periodo 1 con C.T.E. Iquitos 9 MW

En el siguiente cuadro se presentan los resultados de las simulaciones del clculo de las
corrientes de cortocircuito para la situacin con proyecto en el periodo 1:

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 22
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Cuadro 7.8 Niveles de Cortocircuito Periodo 1 con C.T.E. Iquitos 9 MW

Nombre Tensin PERIODO 1


Subestacin Barra Nominal Mxima Mnima
Digsilent [kV] 2-T 3 1 2-T 3 1
C.T.E. IQUITOS B_G1-G6 10.5 21.27 24.55 0.89 9.47 10.93 0.45
B_G7-G12 10.5 21.24 24.51 0.89 9.46 10.92 0.45
B_G13-G15(1) 10.5 21.57 24.91 0.90 9.51 10.99 0.45
SKODA B_SKODA 10.5 21.81 25.19 0.90 9.55 11.03 0.45
CATMAK 01-02 B_CATMAK 01-02 10.5 21.82 25.20 0.90 9.55 11.03 0.45
WARTSILA B_WARTSILA 10.5 21.83 25.21 0.90 9.56 11.03 0.45
B_ALSTOM 10.5 21.83 25.21 0.90 9.56 11.03 0.45
B_CATMAK-05 10.5 21.83 25.21 0.90 9.56 11.03 0.45
WARTSILA G20MW B_WARTSILA G20MW 10.5 21.85 25.24 0.90 9.56 11.04 0.45
CAT-N3 10.5KV 10.5 17.16 19.66 0.88 8.59 9.88 0.44
GENERAL MOTOR GENERAL MOTOR 10.5 21.23 24.50 0.89 9.44 10.89 0.45
GRUPOS RAPIDOS 10.5 17.65 20.25 0.88 8.68 9.99 0.45
IQUITOS IQUITOS10.5KV 10.5 20.64 23.80 0.89 9.32 10.76 0.45
IQUITOS60KV 60 2.25 1.78 2.28 1.56 1.13 1.53
SANTA ROSA BARRA_A_10.5KV 10.5 4.86 5.56 0.22 3.79 4.34 0.22
BARRA_B_10.5KV 10.5 3.55 4.10 0.00 2.93 3.39 0.00
SANTA_ROSA60KV 60 2.03 1.59 2.06 1.46 1.05 1.43

De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifsicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.24 kA, el cual supera la capacidad de ruptura de 25 kA.

En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentaran
problemas con el equipo existente de 31.5 kA.

7.2.3. Periodo 2 con C.T.E. Iquitos 12 MW

En el siguiente cuadro se presentan los resultados de las simulaciones del clculo de las
corrientes de cortocircuito para la situacin con proyecto en el periodo 2:

Cuadro 7.9 Niveles de Cortocircuito Periodo 2 con C.T.E. Iquitos 12 MW

Nombre Tensin PERIODO 2


Subestacin Barra Nominal Mxima Mnima
Digsilent [kV] 2-T 3 1 2-T 3 1
C.T.E. IQUITOS B_G1-G6 10.5 21.47 24.82 0.89 7.99 9.29 0.37
B_G7-G12 10.5 21.46 24.81 0.89 8.00 9.29 0.37
B_G13-G15(1) 10.5 21.80 25.21 0.90 8.03 9.33 0.37
SKODA B_SKODA 10.5 22.03 25.48 0.90 8.05 9.35 0.37
CATMAK 01-02 B_CATMAK 01-02 10.5 22.04 25.49 0.90 8.05 9.35 0.37
WARTSILA B_WARTSILA 10.5 22.04 25.49 0.90 8.04 9.35 0.37
B_ALSTOM 10.5 22.04 25.49 0.90 8.04 9.35 0.37
B_CATMAK-05 10.5 22.04 25.49 0.90 8.04 9.35 0.37
WARTSILA G20MW B_WARTSILA G20MW 10.5 22.07 25.53 0.90 8.05 9.36 0.37
CAT-N3 10.5KV 10.5 17.29 19.83 0.88 7.36 8.51 0.36
GENERAL MOTOR GENERAL MOTOR 10.5 21.41 24.73 0.89 7.96 9.24 0.37
GRUPOS RAPIDOS 10.5 17.79 20.44 0.88 7.42 8.60 0.37
IQUITOS IQUITOS10.5KV 10.5 20.83 24.05 0.89 7.88 9.15 0.37
IQUITOS60KV 60 2.26 1.79 2.29 1.42 1.02 1.37
SANTA ROSA BARRA_A_10.5KV 10.5 4.87 5.58 0.22 3.53 4.05 0.22
BARRA_B_10.5KV 10.5 3.55 4.11 0.00 2.77 3.21 0.00
SANTA_ROSA60KV 60 2.04 1.60 2.07 1.34 0.95 1.29

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 23
INGENIERA
DESARROLLO
GESTIN ENERGTICA

De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifsicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.53 kA, el cual supera la capacidad de ruptura de 25 kA.

En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentaran
problemas con el equipo existente de 31.5 kA.

7.2.4. Mxima Generacin 2024

En el siguiente cuadro se presentan los resultados de las simulaciones del clculo de las
corrientes de cortocircuito para la situacin de mxima generacin (todos los generadores
operando) en la situacin con y sin proyecto:

Cuadro 7.10 Niveles de Cortocircuito Mxima Generacin

Nombre Tensin Mxima Generacin


Subestacin Barra Nominal CC TRIFSICO
[kV]
Digsilent SIN C.T.E CON C.T.E
C.T.E. IQUITOS B_G1-G6 10.5 - 35.08
B_G7-G12 10.5 - 35.04
B_G13-G15(1) 10.5 - 35.90
SKODA B_SKODA 10.5 32.65 36.51
CATMAK 01-02 B_CATMAK 01-02 10.5 32.68 36.53
WARTSILA B_WARTSILA 10.5 32.72 36.56
B_ALSTOM 10.5 32.72 36.56
B_CATMAK-05 10.5 32.72 36.56
WARTSILA G20MW B_WARTSILA G20MW 10.5 32.73 36.61
CAT-N3 10.5KV 10.5 23.98 25.88
GENERAL MOTOR GENERAL MOTOR 10.5 31.67 35.22
GRUPOS RAPIDOS 10.5 25.76 27.94
IQUITOS IQUITOS10.5KV 10.5 31.72 35.33
IQUITOS60KV 60 2.02 2.11
SANTA ROSA BARRA_A_10.5KV 10.5 5.91 6.02
BARRA_B_10.5KV 10.5 4.29 4.35
SANTA_ROSA60KV 60 1.78 1.85

Considerando la operacin de todos los generadores, se deber considerar para el diseo de los
equipos la corriente de cortocircuito de 37 kA en la barra de 10.5 kV (celdas resaltadas de color
rojo).

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 24
INGENIERA
DESARROLLO
GESTIN ENERGTICA

8. TIEMPOS CRTICOS DE DESPEJE DE FALLA

Secuencia de Simulacin:

Se aplic una falla trifsica en el punto de conexin de la C.T.E. Iquitos en 10.5 kV durante 100
ms, luego se procedi a incrementarlo hasta que el generador perdiese el sincronismo. El anlisis
se realiza para las situaciones de mxima, media y mnima demanda para el periodo 1 (con
C.T.E. 9 MW) y periodo 2 (con C.T.E. 12 MW).

8.1.1. Periodo 1 con C.T.E. Iquitos 9 MW

Figura 8.1 Tiempo Crtico de Despeje de Falla Mxima Demanda (9 MW) tc=180 ms

DIgSILENT
90.32 115.5

55.56
73.65

-4.333

56.98

-64.23

40.31
-124.1

23.64 -184.0
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
6.968 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg CATMAK-N02: Rotor angle with reference to reference machine angle in deg
G11: Rotor angle with reference to reference machine angle in deg CUMMINS-N1: Rotor angle with reference to reference machine angle in deg

1.381 10.39

7.036
1.083

3.681

0.784

0.326

0.486
-3.030

0.187 -6.385
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: Total Active Power in MW
-0.111 WARTSILA-N03: Total Active Power in MW
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N04: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-N05: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-N06: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-N02: Total Active Power in MW
G13: m:Psum:bus1 CUMMINS-N1: Total Active Power in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 9 MW ANGULO_GPOTENCIA Date:


TIEMPOS CRTICOS DE DESPEJE DE FALLA MAXIMA_DEMANDA_2015 Annex: E1. /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 25
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 8.2 Tiempo Crtico de Despeje de Falla Media Demanda (9 MW) tc=190 ms

DIgSILENT
300.00 159.5

119.2
200.00

78.86

100.00

38.53

0.00
-1.800

-100.00 -42.13
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
-200.00 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg CATMAK-N02: Rotor angle with reference to reference machine angle in deg
G11: Rotor angle with reference to reference machine angle in deg CUMMINS-N1: c:firel

1.004 22.44

14.47
0.779

6.508

0.554

-1.459

0.329
-9.425

0.105 -17.39
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: Total Active Power in MW
-0.120 WARTSILA-N03: Total Active Power in MW
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N04: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-N05: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-N06: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-N02: Total Active Power in MW
G13: m:Psum:bus1 CUMMINS-N1: m:Psum:bus1

ESTUDIO DE OPERATIVIDAD - C.T.E. 9 MW ANGULO_GPOTENCIA Date:


TIEMPOS CRTICOS DE DESPEJE DE FALLA MEDIA_DEMANDA_2015 Annex: E2. /1

Figura 8.3 Tiempo Crtico de Despeje de Falla Mnima Demanda (9 MW) tc=200 ms

DIgSILENT
186.9 97.03

69.45
148.9

41.88

110.9
14.30

72.91 -13.28

-40.86
34.93 -0.100 1.920 3.940 5.960 7.980 [s] 10.000
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
WARTSILA-N03: c:firel
-3.057 WARTSILA-N04: c:firel
-0.100 1.920 3.940 5.960 7.980 [s] 10.000 WARTSILA-N05: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg CATMAK-N02: c:firel
G10: Rotor angle with reference to reference machine angle in deg CUMMINS-N1: c:firel

1.003 13.22

8.610
0.764

4.003

0.525

-0.605

0.286
-5.212

0.047 -9.819
-0.100 1.920 3.940 5.960 7.980 [s] 10.000
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: Total Active Power in MW
-0.191 WARTSILA-N03: m:Psum:bus1
-0.100 1.920 3.940 5.960 7.980 [s] 10.000 WARTSILA-N04: m:Psum:bus1
G01: Total Active Power in MW WARTSILA-N05: m:Psum:bus1
G04: Total Active Power in MW WARTSILA-N06: m:Psum:bus1
G07: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-N02: m:Psum:bus1
G13: m:Psum:bus1 CUMMINS-N1: m:Psum:bus1

ESTUDIO DE OPERATIVIDAD - C.T.E. 9 MW ANGULO_GPOTENCIA Date:


TIEMPOS CRTICOS DE DESPEJE DE FALLA MINIMA_DEMANDA_2015 Annex: E3. /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 26
INGENIERA
DESARROLLO
GESTIN ENERGTICA

8.1.2. Periodo 2 con C.T.E. Iquitos 12 MW

Figura 8.4 Tiempo Crtico de Despeje de Falla Mxima Demanda (12 MW) tc=180 ms

DIgSILENT
150.5 55.60

35.15
122.1

14.69
93.83

-5.762

65.52

-26.22

37.21
-46.67
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
8.900 WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg CATMAK-N02: Rotor angle with reference to reference machine angle in deg

1.321 16.15

10.69
1.001

5.235
0.681

-0.223
0.362

-5.681

0.042

-11.14
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
-0.278 WARTSILA-N01: Active Power in MW
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N02: Active Power in MW
G01: Active Power in MW WARTSILA-N03: Active Power in MW
G04: Active Power in MW WARTSILA-N04: Active Power in MW
G07: Active Power in MW WARTSILA-N05: Active Power in MW
G10: Active Power in MW WARTSILA-N06: Active Power in MW
G13: Active Power in MW WARTSILA-N07: Active Power in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW ANGULO_GPOTENCIA Date:


TIEMPOS CRTICOS DE DESPEJE DE FALLA MAXIMA_DEMANDA_2015 Annex: E4. /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 27
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 8.5 Tiempo Crtico de Despeje de Falla Media Demanda (12 MW) tc=185 ms

DIgSILENT
132.0 34.03

20.95
106.9

7.866
81.74

-5.217

56.61

-18.30

31.48
-31.38
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
6.354 WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg CATMAK-N02: c:firel

1.345 12.41

8.489
1.012

4.568
0.679

0.648
0.346

-3.273

0.013

-7.194
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
-0.320 WARTSILA-N01: Total Active Power in MW
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N02: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-N03: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-N04: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-N05: Total Active Power in MW
G10: Total Active Power in MW WARTSILA-N06: Total Active Power in MW
G13: Total Active Power in MW WARTSILA-N07: Total Active Power in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW ANGULO_GPOTENCIA Date:


TIEMPOS CRTICOS DE DESPEJE DE FALLA MEDIA_DEMANDA_2015 Annex: E5. /1

Figura 8.6 Tiempo Crtico de Despeje de Falla Mnima Demanda (12 MW) tc=190 ms

DIgSILENT
169.1 52.82

36.66
136.3

20.49
103.6

4.326
70.80

-11.84

38.04

-28.01
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
5.275 WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N02: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N03: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: c:firel
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: c:firel
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: c:firel
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg

0.962 9.810

6.239
0.744

2.667
0.525

-0.904
0.307

-4.475

0.089

-8.046
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
-0.130 WARTSILA-N01: Total Active Power in MW
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N02: m:Psum:bus1
G01: Total Active Power in MW WARTSILA-N03: m:Psum:bus1
G04: Total Active Power in MW WARTSILA-N04: m:Psum:bus1
G07: Total Active Power in MW WARTSILA-N05: m:Psum:bus1
G10: Total Active Power in MW WARTSILA-N06: m:Psum:bus1
G13: Total Active Power in MW WARTSILA-N07: Total Active Power in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW ANGULO_GPOTENCIA Date:


TIEMPOS CRTICOS DE DESPEJE DE FALLA MINIMA_DEMANDA_2015 Annex: E6. /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 28
INGENIERA
DESARROLLO
GESTIN ENERGTICA

8.1.3. Resultados Tiempos Crticos de Despeje de Falla

De las simulaciones se concluye que el menor valor del tiempo crtico de despeje de falla es de
180 ms en el escenario de mxima demanda, y se encuentra entre 185 ms-190 ms en el
escenario de media demanda y entre190 ms-200 ms en el escenario de mnima demanda, los
tiempos obtenidos son mayores al tiempo normal de operacin de las protecciones, igual a 100
ms.

Cuadro 8.1 Tiempos Crticos de Despeje de Falla

Tiempo Crtico
CASO Escenario Conclusin
(ms)
Mxima Demanda 180 >100ms
Con CT.E Iquitos 9 MW Media Demanda 190 >100ms
Mnima Demanda 200 >100ms
Mxima Demanda 180 >100ms
Con CT.E Iquitos 12 MW Media Demanda 185 >100ms
Mnima Demanda 190 >100ms

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 29
INGENIERA
DESARROLLO
GESTIN ENERGTICA

9. ESTABILIDAD TRANSITORIA ANTE FALLAS

En el presente captulo, se realizar el anlisis de estabilidad transitoria ante eventos de fallas


monofsicas y trifsicas con la desconexin de la C.T.E. Iquitos. Los casos analizados se
describen a continuacin.

Falla monofsica con recierre exitoso en la lnea Iquitos Santa Rosa 60 kV, al 1% de
la lnea desde la S.E. Iquitos.

La secuencia de simulacin es la siguiente:

0 ms: Cortocircuito monofsico al 1% de la lnea desde la S.E. Iquitos.

100 ms: Despeje de falla y apertura de la fase en falla.

600 ms: Recierre monofsico exitoso luego de 500 ms.

Figura 9.1 Falla 1 con Recierre Exitoso LT Iquitos Sta. Rosa en Mxima Demanda

DIgSILENT
18.23 5.562

3.049
18.10

0.537
17.97

-1.975
17.84

-4.488

17.71

-7.000
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
17.57 WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg

60.66 2.468

2.204
60.52

1.940

60.38
1.675

60.24 1.411

1.146
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
60.11
WARTSILA-N01: Active Power in MW
WARTSILA-N02: Active Power in MW
WARTSILA-N03: Active Power in MW
WARTSILA-N04: Active Power in MW
59.97 WARTSILA-N05: Active Power in MW
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N06: Active Power in MW
B_WARTSILA G20MW: Electrical Frequency in Hz WARTSILA-N07: Active Power in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW ANGULO_GPOTENCIA Date:


RECIERRE MONOFSICO EXITOSO EN LNE IQUITOS-STA ROSA 60 KV MAXIMA_DEMANDA_2015 Annex: F1. /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 30
INGENIERA
DESARROLLO
GESTIN ENERGTICA

DIgSILENT
1.05 23.00

1.01

19.00

0.97

15.00

0.93

11.00

0.89

0.85 7.00
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
BARRA_A_10.5KV: u1, Magnitude in p.u.
BARRA_B_10.5KV: u1, Magnitude in p.u.
B_ALSTOM: u1, Magnitude in p.u.
B_CATMAK 01-02: u1, Magnitude in p.u.
B_CATMAK-05: u1, Magnitude in p.u.
B_G1-G6: u1, Magnitude in p.u.
B_G13-G15(1): u1, Magnitude in p.u.
B_G7-G12: u1, Magnitude in p.u. 3.00
B_SKODA: u1, Magnitude in p.u. -0.100 1.919 3.938 5.956 7.975 [s] 9.994
B_WARTSILA: u1, Magnitude in p.u. BARRA ALSTOM-SET IQUITOS: Total Active Power/Terminal i in MW
B_WARTSILA G20MW: u1, Magnitude in p.u. IQUITOS-SANTA ROSA 60KV: Total Active Power/Terminal i in MW
CAT-N3 10.5KV: u1, Magnitude in p.u. Max353.8Amp: Total Active Power/Terminal i in MW
GRUPOS RAPIDOS: u1, Magnitude in p.u. Max353.8Amp(1): Total Active Power/Terminal j in MW
IQUITOS10.5KV: u1, Magnitude in p.u. Max530.7Amp: Total Active Power/Terminal i in MW
IQUITOS60KV: u1, Magnitude in p.u. WARTSILA G20MW-SET IQUITOS: m:Psum:bus2
PCONEX_CTE: u1, Magnitude in p.u. WARTSILA-CATMAK: Total Active Power/Terminal j in MW
SANTA_ROSA60KV: u1, Magnitude in p.u. WARTSILA-WARTSILA G20MW: Total Active Power/Terminal j in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW TENSION_POTENCIA Date:


RECIERRE MONOFSICO EXITOSO EN LNE IQUITOS-STA ROSA 60 KV MAXIMA_DEMANDA_2015 Annex: F1. /2

Figura 9.2 Falla 1 con Recierre Exitoso LT Iquitos Sta. Rosa en Mnima Demanda

DIgSILENT
15.09 0.472

-1.605
15.01

-3.682
14.94

-5.759
14.86

-7.837

14.78

-9.914
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
14.71 WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N02: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N03: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: c:firel
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: c:firel
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: c:firel
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg

60.41 6.574

6.005
60.33

5.435

60.24
4.866

60.15 4.296

3.727
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
60.07
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: m:Psum:bus1
WARTSILA-N03: m:Psum:bus1
WARTSILA-N04: m:Psum:bus1
59.98 WARTSILA-N05: m:Psum:bus1
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N06: m:Psum:bus1
B_WARTSILA G20MW: Electrical Frequency in Hz WARTSILA-N07: Total Active Power in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW ANGULO_GPOTENCIA Date:


RECIERRE MONOFSICO EXITOSO EN LNE IQUITOS-STA ROSA 60 KV MINIMA_DEMANDA_2015 Annex: F2. /1

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 31
INGENIERA
DESARROLLO
GESTIN ENERGTICA

DIgSILENT
1.04 12.00

1.02

10.00

1.00

8.00

0.98

6.00

0.96

0.94 4.00
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
BARRA_A_10.5KV: u1, Magnitude in p.u.
BARRA_B_10.5KV: u1, Magnitude in p.u.
B_ALSTOM: u1, Magnitude in p.u.
B_CATMAK 01-02: u1, Magnitude in p.u.
B_CATMAK-05: u1, Magnitude in p.u.
B_G1-G6: u1, Magnitude in p.u.
B_G13-G15(1): u1, Magnitude in p.u.
B_G7-G12: u1, Magnitude in p.u. 2.00
B_SKODA: u1, Magnitude in p.u. -0.100 1.919 3.938 5.956 7.975 [s] 9.994
B_WARTSILA: u1, Magnitude in p.u. BARRA ALSTOM-SET IQUITOS: Total Active Power/Terminal i in MW
B_WARTSILA G20MW: u1, Magnitude in p.u. IQUITOS-SANTA ROSA 60KV: Total Active Power/Terminal i in MW
CAT-N3 10.5KV: u1, Magnitude in p.u. Max353.8Amp: Total Active Power/Terminal i in MW
GRUPOS RAPIDOS: u1, Magnitude in p.u. Max353.8Amp(1): Total Active Power/Terminal j in MW
IQUITOS10.5KV: u1, Magnitude in p.u. Max530.7Amp: Total Active Power/Terminal i in MW
IQUITOS60KV: u1, Magnitude in p.u. WARTSILA G20MW-SET IQUITOS: m:Psum:bus2
PCONEX_CTE: u1, Magnitude in p.u. WARTSILA-CATMAK: Total Active Power/Terminal j in MW
SANTA_ROSA60KV: u1, Magnitude in p.u. WARTSILA-WARTSILA G20MW: Total Active Power/Terminal j in MW

ESTUDIO DE OPERATIVIDAD - C.T.E. 12 MW TENSION_POTENCIA Date:


RECIERRE MONOFSICO EXITOSO EN LNE IQUITOS-STA ROSA 60 KV MINIMA_DEMANDA_2015 Annex: F2. /2

De las simulaciones observamos que el ngulo del rotor, potencia de los generadores, potencia
en lneas y tensiones se estabilizan en el periodo de simulacin de 10 segundos.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 32
INGENIERA
DESARROLLO
GESTIN ENERGTICA

10. ESTABILIDAD DE FRECUENCIA

En el presente captulo, se realizar el anlisis de estabilidad de la frecuencia ante la


desconexin de la C.T.E. Iquitos.

El anlisis comprende la implementacin de un Esquema de Rechazo de Carga por Mnima


Frecuencia (ERCMF), el esquema ser implementado con rels de mnima frecuencia. La
operacin de estos equipos, se produce cuando la frecuencia est por debajo de cierto valor
(umbral) durante cierto tiempo (temporizacin).

10.1. Eventos Importantes en el Ao 2015

De acuerdo a la informacin proporcionada por ELOR se realiza el anlisis de la frecuencia de


operacin normal y durante los eventos de mayor importancia.

En el primer caso, evaluaremos la salida del generador Wartsila N 6, en la siguiente figura se


muestra la evolucin en el tiempo de la frecuencia:

Figura 10.1 Salida Automtica GT Wartsila N 6

De acuerdo al evento la generacin total pre-falla es 27.75 MW, el cual corresponde al escenario
de mnima demanda. Antes de ocurrir algn rechazo automtico de generacin o carga la
frecuencia es mayor a 59.8 Hz y menor a 60.02 Hz.

En el segundo caso, evaluaremos la salida del generador GT Cat Mak N 2, en la siguiente figura
se muestra la evolucin en el tiempo de la frecuencia:

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 33
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 10.2 Salida Automtica de GT Cat Mak N 2

De acuerdo al evento la generacin total pre-falla es 22.8 MW, el cual corresponde al escenario
de mnima demanda. Antes de ocurrir algn rechazo automtico de generacin o carga la
frecuencia es mayor a 59.5 Hz y menor a 60.02 Hz.

Por ltimo, tenemos algunos de los eventos importantes, en la siguiente figura se muestra la
evolucin en el tiempo de la frecuencia:

Figura 10.3 Otros Eventos Importantes

Al igual que los primeros eventos podemos verificar que la frecuencia pre-falla se encuentra entre
59.6 Hz y 60.1 Hz.

Por tanto, concluimos que la frecuencia pre-falla (operacin normal) es mayor a 59.5 Hz.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 34
INGENIERA
DESARROLLO
GESTIN ENERGTICA

10.2. Criterio para los Rels de Umbral de Frecuencia

Un ERCMF se caracteriza por el primer umbral de frecuencia, el nmero de etapas, la


temporizacin y la cantidad de carga a ser rechazada.

10.2.1. Primer umbral de rechazo

El primer umbral de frecuencia no debe estar cercano a la frecuencia nominal del sistema,
permitiendo de esta manera la respuesta natural del sistema ante la variacin de la generacin.
Tambin se debe considerar que los umbrales de disparo de las protecciones de baja frecuencia
de las unidades de generacin es la frecuencia de 57 Hz.

Del anlisis de los eventos importantes ocurridos en ELOR se concluye que la frecuencia pre-
falla es mayor a 59.5 Hz, por tanto como primer umbral se utilizar la frecuencia de 59.0 Hz.

10.2.2. Numero de etapas

Siendo el primer umbral 59 Hz, el paso entre etapas ser fijo e igual a -0.1 Hz, es decir el umbral
para la segunda etapa es 58.9 Hz, para la tercera etapa es 58.8 Hz, para la cuarta etapa es 58.7
Hz, para la quinta etapa es 58.6 Hz. El valor de -0.1 Hz es muy usual en sistemas de potencia y
puede considerarse estndar.

10.2.3. Temporizacin

La temporizacin es igual para todas las etapas, con el fin de permitir que el efecto causado por
el rechazo de cada etapa en la dinmica del sistema se efectivice antes de que actu la siguiente
etapa. Se ha seleccionado una temporizacin de 150 ms, en la seleccin de esta temporizacin
se tiene en cuenta la demora de los interruptores en abrir efectivamente (85 ms).

10.2.4. Cantidad de carga rechazada

En el anlisis se buscar rechazar la menor carga hasta que el sistema sea estable y la
frecuencia final se encuentre entre 59.5 Hz y 60.5 Hz.

10.3. Criterio para los Rels de Derivada de Frecuencia

Las caractersticas del rechazo de carga por derivada de frecuencia son similares a las de umbral
de frecuencia, con la diferencia de que para todas las etapas se tiene un umbral de frecuencia
comn. El coordinamiento entre etapas se establece mediante los valores de la pendiente.

El umbral de frecuencia se selecciona cerca a la frecuencia de operacin, para el caso de ELOR


se utilizar 59,5 Hz porque los valores de pendiente antes de este valor corresponden a la

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 35
INGENIERA
DESARROLLO
GESTIN ENERGTICA

respuesta natural del sistema Iquitos, con este valor se esperara una rpida accin de rechazo,
el cual se verifica en las simulaciones realizadas

10.4. Resultados del ERCMF

La C.T.E. Iquitos presenta dos periodos de evaluacin, en el primer periodo la generacin es 9


MW y en el segundo periodo la generacin es 12 MW. En el siguiente cuadro el porcentaje de
prdida de generacin con respecto a la demanda en los escenarios de mxima, media y mnima
demanda:

Cuadro 10.1 Indicadores ERCMF

Generacin 9 MW Generacin 12 MW
Indicador Mxima Media Mnima Mxima Media Mnima
Demanda Demanda Demanda Demanda Demanda Demanda
Total Carga (MW) 53.46 48.30 22.02 53.46 48.30 22.02
Total Generacin (MW) 54.14 48.85 22.35 54.14 48.85 22.35
Prdida de Generacin (MW) 9.00 9.00 9.00 12.00 12.00 12.00
% Prdida Generacin/Carga 16.8% 18.6% 40.9% 22.4% 24.8% 54.5%

La salida de la C.T.E. Iquitos en mnima demanda representa el 40.9% y 54.5%, en estos casos
donde se presentan gran dficit de generacin es necesario realizar rechazar ms del porcentaje
para que el sistema pueda recuperar la frecuencia.

Cuadro 10.2 Indicadores ERCMF

Nmero de Porcentaje de Rechazo Rles por Umbral Rles por Derivada de Frecuencia
Etapa en cada Etapa (*) Umbral (Hz) Temporizacin (s) Umbral (Hz/s) Temporizacin
1 8% 59.0 0.15 -0.9 0.12
2 5% 58.9 0.15 -0.7 0.12
3 4% 58.8 0.15 -0.7 0.12
4 4% 58.7 0.15
5 30% 58.6 0.15
(*) Porcentaje de carga para cualquier escenario (mxima, media y mnima demanda)

El ERCMF propuesto consiste de 5 etapas, el porcentaje total de carga rechazada es 51% de la


demanda de cada escenario, para los rels por umbral el primer umbral de frecuencia es 59 Hz
y la temporizacin en todas las etapas es 150 ms, el tiempo de apertura de los interruptores es
85 ms.

A continuacin se verificar la actuacin del ERCMF ante la salida de la C.T.E. Iquitos en los
caos de salida de la CTE con 9 MW y 12 MW en mxima, media y mnima demanda.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 36
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 10.4 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) Mxima Demanda

DIgSILENT
60.25

2.686 s
59.987 Hz
60.00

59.75

45.568 s
59.558 Hz

0.831 s
0.161 s Y = 59.500 Hz
59.50

59.25

0.332 s Y = 59.100 Hz
0.351 s
59.059 Hz
Y = 59.000 Hz
59.00
-0.100 9.920 19.94 29.96 39.98 [s] 50.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz

La frecuencia final es 59.558 Hz, la mnima frecuencia es 59.059 Hz y se activa la etapa 3.

Figura 10.5 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Media Demanda

DIgSILENT
60.30

60.00
57.666 s
60.147 Hz

59.70

1.150 s
0.145 s Y = 59.500 Hz

59.40

0.532 s
0.281 s Y = 59.100 Hz
59.10

Y = 59.000 Hz
0.350 s
58.956 Hz Y = 58.900 Hz

Y = 58.800 Hz
58.80
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz

La frecuencia final es 60.147 Hz, la mnima frecuencia es 59.956 Hz y se activa la etapa 3.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 37
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 10.6 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Mnima Demanda

DIgSILENT
63.25
Y = 63.000 Hz

2.706 s
62.957 Hz

62.00

60.75
0.977 s 11.513 s Y = 60.500 Hz

52.658 s
59.871 Hz

0.737 s
0.008 s Y = 59.500 Hz
59.50
0.656 s
0.092 s Y = 59.100 Hz
Y = 59.000 Hz
Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
0.492 s
58.25 0.196 s Y = 58.200 Hz

0.365 s
57.477 Hz

57.00
-0.100 11.92 23.94 35.96 47.98 [s] 59.99
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz

DIgSILENT
63.25
Y = 63.000 Hz

62.00

60.75
0.977 s Y = 60.500 Hz

0.049 s
0.020 s
0.008 s 0.737 s Y = 59.500 Hz
59.50

0.092 s 0.656 s Y = 59.100 Hz


Y = 59.000 Hz
Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz

58.25 0.196 s 0.492 s Y = 58.200 Hz

0.369 s
57.473 Hz

57.00
-0.100 0.485 1.071 1.656 2.241 [s] 2.827
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz

La frecuencia final es 59.871 Hz, la mnima frecuencia es 57.477 Hz y se activa la etapa 5. La


frecuencia es menor a 58.2 Hz durante (0.492s-0.196s) = 0.296 s, lo cual indica que el rel por
mnima frecuencia del alimentador R-5 no acta.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 38
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 10.7 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mxima Demanda

DIgSILENT
60.20

59.90
55.873 s
59.733 Hz

59.60

0.108 s 8.193 s Y = 59.500 Hz

59.30

2.626 s
0.205 s Y = 59.100 Hz

Y = 59.000 Hz
59.00

Y = 58.900 Hz

Y = 58.800 Hz
0.309 s
58.780 Hz
Y = 58.700 Hz
58.70
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz

La frecuencia final es 59.733 Hz, la mnima frecuencia es 58.780 Hz y se activa la etapa 3.

Figura 10.8 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Media Demanda

DIgSILENT
60.30

56.996 s
59.90 59.757 Hz

0.090 s 3.572 s Y = 59.500 Hz


59.50

1.321 s
0.167 s Y = 59.100 Hz
59.10
Y = 59.000 Hz

Y = 58.900 Hz

Y = 58.800 Hz

Y = 58.700 Hz
58.70
Y = 58.600 Hz
0.470 s
58.570 Hz Y = 58.500 Hz

58.30
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz

La frecuencia final es 59.757 Hz, la mnima frecuencia es 58.750 Hz y se activa la etapa 4.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 39
INGENIERA
DESARROLLO
GESTIN ENERGTICA

Figura 10.9 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mnima Demanda

DIgSILENT
61.00

Y = 60.500 Hz

3.851 s
59.932 Hz
60.00
48.168 s
59.588 Hz
1.881 s
0.007 s Y = 59.500 Hz

1.450 s
0.009 s Y = 59.100 Hz
Y = 59.000 Hz
59.00 Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
0.906 s
0.120 s Y = 58.200 Hz

58.00

57.00

0.306 s
56.478 Hz

56.00
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz

DIgSILENT
61.00

Y = 60.500 Hz

60.00

0.007 s 1.881 s Y = 59.500 Hz

0.056 s
0.009 s 1.450 s Y = 59.100 Hz
Y = 59.000 Hz
59.00 Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz

0.120 s 0.906 s Y = 58.200 Hz

58.00

57.00

0.306 s
56.478 Hz

56.00
-0.100 0.570 1.240 1.910 2.580 [s] 3.250
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz

La frecuencia final es 59.588 Hz, la mnima frecuencia es 56.478 Hz y se activa la etapa 5. La


frecuencia es menor a 58.2 Hz durante (0.906s-0.120s) = 0.786 s, lo cual indica que el rel por

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 40
INGENIERA
DESARROLLO
GESTIN ENERGTICA

mnima frecuencia del alimentador R-5 actuara. Se recomienda cambiar la temporizacin del
rel por mnima frecuencia del alimentador R-5 a 0.8 s.

Cuadro 10.3 Resultados ERCMF


Prdida de Rechazo de Etapa
Frecuencia Frecuencia Rechazo de Carga
Evento Generacin Carga ltima
Mnima (Hz) Final (Hz) (% de demanda)
(MW) (MW) Activada
Mxima Demanda 9 59.059 59.558 17.0% 9.09 3
Media Demanda 9 59.956 60.147 17.0% 8.21 3
Mnima Demanda 9 57.477 59.871 51.0% 11.23 5
Mxima Demanda 12 58.780 59.773 17.0% 9.09 3
Media Demanda 12 58.750 59.757 21.0% 10.14 4
Mnima Demanda 12 56.478 59.588 51.0% 11.23 5

De las simulaciones se concluye lo siguiente:

Ante la prdida de generacin igual a 9 MW se debe rechazar 9.09 MW, 8.21 MW y 11.23 MW
en el escenario de mxima, media y mnima demanda respectivamente.

Cuando se pierda 12 MW de generacin se debe rechazar 9.09 MW, 10.14 MW y 11.23 MW en


el escenario de mxima, media y mnima demanda respectivamente.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 41
INGENIERA
DESARROLLO
GESTIN ENERGTICA

11. CONCLUSIONES Y RECOMENDACIONES

a) La falla bifsica en 0.48 kV produce una mayor corriente de secuencia negativa y ste
tolerar dicha corriente de 2.212 p.u. por 8.18 segundos. De acuerdo a los resultados este
tiempo de tolerancia de 8.18 segundos, an bajo la hiptesis que la corriente inversa no
decrece con el tiempo, supera ampliamente cualquier tiempo razonable que pudiera ser
asignado para un esquema de respaldo.

b) Luego de la operacin de las nuevas instalaciones que conforman el proyecto, se observa


una mejora en el control de las tensiones alcanzando los valores permitidos segn la Norma
Tcnica de Calidad de los Servicios Elctricos (NTCSE).

c) El nivel de carga de los Transformadores de Potencia instalados, se encuentran dentro de


los valores permitidos de operacin normal (menor al 100%), excepto el transformador T-04
de 7.5 MVA en la S.E. Santa Rosa, el cual se encuentra en sobrecarga aun en la situacin
sin la C.T.E. Iquitos.

d) En la operacin normal de la Central Iquitos, en la barra Wartsila G20MW se observa que la


corriente de cortocircuito alcanza valores de 25.9 kA, 25.24 kA y 25.53 kA para el caso base
(Sin C.T.E. Iquitos), periodo 1 (C.T.E. Iquitos 9 MW) y periodo 2 (C.T.E. Iquitos 12 MW)
respectivamente. Estos valores superan la capacidad de ruptura existente de 25 kA.

e) De las simulaciones se concluye que el menor valor del tiempo crtico de despeje de falla es
180 ms, el tiempo determinado es mayor al tiempo normal de operacin de las protecciones,
igual a 100 ms.

f) Ante una falla monofsica con recierre exitoso en la lnea Iquitos-Santa Rosa 60 kV, no se
pierde sincronismo de las centrales, las tensiones, potencia y velocidad se estabilizan en el
periodo de simulacin de 10 segundos.

g) El Esquema de Rechazo de Carga por Mnima Frecuencia (ERCMF), ha sido implementado


en 5 etapas, primer umbral 59 Hz y paso de 0.1 Hz, la temporizacin es 150 ms en todas las
etapas y el tiempo de apertura de los interruptores es 85 ms. Los rels por derivada de
frecuencia debern ser implementado en las tres primeras etapas.

h) El ERCFM ha sido verificado satisfactoriamente en los escenarios de mxima, media y


mnima demanda cuando se pierde la generacin de la C.T.E. Iquitos para 9 MW y 12 MW.

i) Por lo mencionado, de los anlisis elctricos se concluye que las nuevas instalaciones que
conforman el proyecto C.T.E. IQUITOS, cumplen con el objetivo principal de brindar el
suministro de energa adicional de manera continua y confiable y no afecta la operacin
actual de las dems instalaciones del proyecto.

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 42
INGENIERA
DESARROLLO
GESTIN ENERGTICA

12. ANEXOS

================================================
Anexo A Flujo de Potencia
================================================
A1 Caso Base
A1.1 Mxima Demanda
A1.2 Media Demanda
A1.3 Mnima Demanda
A2 Periodo 1 Con C.T.E. Iquitos 9 MW
A2.1 Mxima Demanda
A2.2 Media Demanda
A2.3 Mnima Demanda
A3 Periodo 2 Con C.T.E. Iquitos 12 MW
A3.1 Mxima Demanda
A3.2 Media Demanda
A3.3 Mnima Demanda
================================================
Anexo B Cortocircuito Caso Base Sin CTE Iquitos
================================================
B1 Cortocircuito Bifsico a Tierra
B1.1 Mxima Demanda
B1.2 Media Demanda
B1.3 Mnima Demanda
B2 Cortocircuito Monofsico
B2.1 Mxima Demanda
B2.2 Media Demanda
B2.3 Mnima Demanda
B3 Cortocircuito Trifsico
B3.1 Mxima Demanda
B3.2 Media Demanda
B3.3 Mnima Demanda
================================================
Anexo C Cortocircuito Con CTE Iquitos 9 MW
================================================
C1 Cortocircuito Bifsico a Tierra
C1.1 Mxima Demanda
C1.2 Media Demanda
C1.3 Mnima Demanda
C2 Cortocircuito Monofsico
C2.1 Mxima Demanda
C2.2 Media Demanda
C2.3 Mnima Demanda
C3 Cortocircuito Trifsico
C3.1 Mxima Demanda

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 43
INGENIERA
DESARROLLO
GESTIN ENERGTICA

C3.2 Media Demanda


C3.3 Mnima Demanda
================================================
Anexo D - Cortocircuito Con CTE Iquitos 12 MW
================================================
D1 Cortocircuito Bifsico a Tierra
D1.1 Mxima Demanda
D1.2 Media Demanda
D1.3 Mnima Demanda
D2 Cortocircuito Monofsico
D2.1 Mxima Demanda
D2.2 Media Demanda
D2.3 Mnima Demanda
D3 Cortocircuito Trifsico
D3.1 Mxima Demanda
D3.2 Media Demanda
D3.3 Mnima Demanda
================================================
Anexo E Tiempos Crticos de Despeje de Falla
================================================
E1 Periodo 1 en Mxima Demanda Con C.T.E. Iquitos 9 MW
E1.1 ngulos de los Rotores y Potencia de los generadores
E1.2 Tensin en Barras y Potencia en Lneas
E2 Periodo 1 en Media Demanda Con C.T.E. Iquitos 9 MW
E2.1 ngulos de los Rotores y Potencia de los generadores
E2.2 Tensin en Barras y Potencia en Lneas
E3 Periodo 1 en Mnima Demanda Con C.T.E. Iquitos 9 MW
E3.1 ngulos de los Rotores y Potencia de los generadores
E3.2 Tensin en Barras y Potencia en Lneas
E4 Periodo 1 en Mxima Demanda Con C.T.E. Iquitos 12 MW
E4.1 ngulos de los Rotores y Potencia de los generadores
E4.2 Tensin en Barras y Potencia en Lneas
E5 Periodo 1 en Media Demanda Con C.T.E. Iquitos 12 MW
E5.1 ngulos de los Rotores y Potencia de los generadores
E5.2 Tensin en Barras y Potencia en Lneas
E6 Periodo 1 en Mnima Demanda Con C.T.E. Iquitos 12 MW
E6.1 ngulos de los Rotores y Potencia de los generadores
E6.2 Tensin en Barras y Potencia en Lneas
================================================
Anexo F Recierre Monofsico Exitoso en Lne Iquitos-Sta. Rosa 60 kV
================================================
F1 Periodo 1 en Mxima Demanda Con C.T.E. Iquitos 12 MW
F1.1 ngulos de los Rotores y Potencia de los generadores
F1.2 Tensin en Barras y Potencia en Lneas

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 44
INGENIERA
DESARROLLO
GESTIN ENERGTICA

F2 Periodo 2 en Mnima Demanda Con C.T.E. Iquitos 12 MW


F2.1 ngulos de los Rotores y Potencia de los generadores
F2.2 Tensin en Barras y Potencia en Lneas

================================================
Anexo G - Escenario de Mxima Generacin
================================================
G1 Cortocircuito Trifsico
G1.1 Sin C.T.E. Iquitos
G1.2 Con C.T.E. Iquitos

================================================
Anexo H Base de Datos Digsilent
================================================

Estudio de Operatividad para la Conexin de la CTE en el Sistema Elctrico ELOR


POWER SOLUTIONS
Pgina 45