Professional Documents
Culture Documents
ENERGTICA
IDGE
POWER SOLUTIONS
ESTUDIOS DE OPERATIVIDAD
DE LA CTE IQUITOS
NDICE
1. INTRODUCCIN ........................................................................................................ 5
2. OBJETIVO .................................................................................................................. 6
3. INFORMACIN UTILIZADA ....................................................................................... 7
3.1. Descripcin del Proyecto .............................................................................................. 7
3.2. Periodo de Estudio ....................................................................................................... 10
3.3. Oferta del Sistema Elctrico Iquitos ........................................................................... 10
3.4. Demanda del Sistema Elctrico Iquitos ..................................................................... 11
4. METODOLOGA ....................................................................................................... 13
4.1. Tolerancia a la Circulacin de la Corriente de Secuencia Negativa ....................... 13
4.2. Anlisis de Flujo de Potencia ...................................................................................... 13
4.3. Anlisis de Cortocircuito ............................................................................................. 14
4.4. Determinacin del Tiempo Crtico de Despeje de Falla ........................................... 14
4.5. Anlisis de Estabilidad Transitoria ............................................................................. 14
5. CRITERIOS TCNICOS ............................................................................................ 15
6. EXIGENCIAS DE DISEO ........................................................................................ 16
6.1. Tolerancia a Corrientes de Secuencia Inversa .......................................................... 16
7. ANLISIS EN ESTADO ESTACIONARIO ................................................................. 18
7.1. Flujo de Potencia en Operacin Normal .................................................................... 18
7.1.1. Caso Base Sin Proyecto ......................................................................................... 18
7.1.2. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 19
7.1.3. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 20
7.2. Cortocircuito en Estado Estacionario ........................................................................ 22
7.2.1. Caso Base Sin Proyecto ......................................................................................... 22
7.2.2. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 22
7.2.3. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 23
7.2.4. Mxima Generacin 2024 .......................................................................................... 24
8. TIEMPOS CRTICOS DE DESPEJE DE FALLA ........................................................ 25
8.1.1. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 25
8.1.2. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 27
8.1.3. Resultados Tiempos Crticos de Despeje de Falla .................................................... 29
9. ESTABILIDAD TRANSITORIA ANTE FALLAS ......................................................... 30
10. ESTABILIDAD DE FRECUENCIA ............................................................................. 33
10.1. Eventos Importantes en el Ao 2015 .......................................................................... 33
10.2. Criterio para los Rels de Umbral de Frecuencia ..................................................... 35
10.2.1. Primer umbral de rechazo .......................................................................................... 35
10.2.2. Numero de etapas ..................................................................................................... 35
10.2.3. Temporizacin............................................................................................................ 35
NDICE DE CUADROS
NDICE DE FIGURAS
1. INTRODUCCIN
El proyecto comprende la instalacin de una central elctrica con una capacidad total de salida
de 12 MW a 10.5 kV - 60 Hz, 0.8 factor de potencia, Potencia Continua. Una mquina adicional
ser cmo reserva, para mantenimientos y/o reparaciones de cualquier de las otras mquinas.
Cables de MT
Todos los equipos tienen la capacidad para operar 24/7 (24 horas/7 das por semana), menos
durante mantenimiento, por lo que se usa la mquina de reserva. Los generadores operarn a
480 Volt 60Hz
2. OBJETIVO
3. INFORMACIN UTILIZADA
En la Figura 3.1, se muestra el diagrama unifilar del rea de influencia considerada en el estudio,
la C.T.E. Iquitos se encuentra encerrado con lneas de color azul.
El proyecto comprende la instalacin de 15 generadores con potencia nominal 1.25 MVA cada
uno, factor de potencia de 0.8 y tensin nominal 0.48 kV. Adems contar con dos
transformadores de 6.6 MVA (2x3.3 MVA) y un transformador de 3.3 MVA, la relacin de
transformacin es 10.5/0.48 kV en la C.T.E. Iquitos y la conexin al Sistema Elctrico Iquitos se
realizar en la celda de reserva BAO907 (Barra Wartsila G20MW) en 10.5 kV mediante cables
N2XSY de capacidad 354 A y 531 A.
Los transformadores elevadores de la C.T.E. Iquitos son de 3.3 MVA KNAF, 10.5 2x 4.76%/0.48
kV, con rangos de taps 9.52%. En el siguiente Cuadro se muestran los parmetros de los
transformadores del Sistema Elctrico Iquitos y de la C.T.E. Iquitos.
S-03
Cab_S-04
B_CATMAK-05
0.0400 km tr2_AuxWartsilaG20MW
1.5MVA 10.5/0.4KV Dyn11_5.92% Cab_AuxWartsilaG20MW
N2XSY 8.7/15KV 3x240 mm2
S-04
0.0400 km tr2_AuxCATMAK-05
1.6MVA 10.5/0.4KV Dyn11_6%
tr2_AuxCATMAK
1.6MVA 10.5/0.4KV Dyn11_6% Cab_ServAuxi
0
N2XSY 3-1x185 mm2
0.0300 km Cab_WARTSILA-N05
0
AuxWARTSILAG20MW
AuxCAT MAK-05
0.1200 km Cab_CATMAK-05
0
~
N2XSY 6/10KV 3x120 mm2
AuxCAT MAK
SG
0.0400 km
B_CATMAK 01-02
0.0500 km
WARTSILA-N05
~
CAT MAK-05
SG
Cab_WARTSILA-N06
N2XSY 8.7/15KV 3x240 mm2
Cab_CATMAK-N02 0.1150 km
~
N2XSY 3-1x240 mm2
SG
Breaker/Switch
0.0500 km
~
SG
WARTSILA-N06
WARTSILA-WARTSILA G20MW
N2XSY 8.7/15KV 3x240 mm2
S-07
SG
0.0260 km
DESARROLLO
WARTSILA-N07
1.0MVA 10.5/0.4KV Dyn11_7.20% 6/10KV-1992 3x500 mm2 ALU
AuxSKODA
B_W ARTSILA
WARTSILA-N04
Cab_S-08
N2XSY 3-1x70 mm2
1250 A 0.0400 km
S-08
GESTIN ENERGTICA
Max353.8Amp(1)
N2XSY 8.7/15KV 3x185 mm2
0.0700 km
Cab_PSE NORTE
N2XSY 3-1x70 mm2
PSE NORTE 0.0400 km
~
B_G1-G3
G01
SG
tr2_CTE-IQUITOS01 Cab_WARTSILA-N03
3.3MVA 10.5/0.48KV Dyn11_9.73% 6/10KV-1992 3x300 mm2 ALU
GR_01
EPLI SAC_01 0.0400 km
3.0MVA 10.5/0.4KV Yd5_5.81%
B_G1-G6
~
~
~
G02
SG
SG
SG
1
CAT 3516-N01
WARTSILA-N03
0 Cab_RESERVA
~
~
N2XSY 3-1x70 mm2
G03
SG
SG
RESERVA 0.0400 km
B_SKODA
CAT 3516-N05
0.0150 km
GR_02
0.5000 km
~
~
B_G4-G6
G04
SG
SG
tr2_CTE-IQUITOS02 0.0400 km
N2XSY 8.7/15KV 3x240 mm2
CAT 3516-N06
1
~
~
G05
SG
SG
Cab_S-02
WARTSILA-N02
1
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
CAT 3512B-PM16
~
GR_03
G06
S-02
SG
EPLI SAC_03
2.5MVA 10.5/0.4KV Dyn11_5.81%
~
SG
Cab_WARTSILA-N01
6/10KV-1992 3x70 mm2 ALU
GRUPOS RAPIDOS
0.0300 km
CAT 3512B-PM17
1
~
~
SG
SG
~
B_G7-G9
G07
SG
tr2_CTE-IQUITOS03
0.0350 km
Cab_S-10
WARTSILA-N01
CAT 3512B-PM19
Max530.7Amp
3.3MVA 10.5/0.48KV Dyn11_9.73% N2XSY 8.7/15KV 3x120 mm2
0.0400 km
B_G7-G12
0.5000 km
~
G08
N2XSY 8.7/15KV 3x240 mm2
S-10
SG
T-3
SKODA-CAT-N3
1
N2XSY 8.7/15KV 3x120 mm2
~
G09
Pgina 9
SG
0
~
SG
T-4 T-6
1.0MVA 10.1/0.4KV Dyn11_7.11% 1.5MVA 10.5/0.4KV Dyn11_5.4%
CAT 3516-N03
~
~
B_G10-G12
G10
SG
SG
0.0600 km
POWER SOLUTIONS
CAT 3516-N02
GENERAL MOTOR
(1)
~
~
G11
SG
SG
T-6(1)
GM-N1
Line(2)
N2XSY 8.7/15KV 3x120 mm2
~
G12
SG
0.0400 km
0.0400 km
Max353.8Amp
1
~
SG
T-6(2)
1.0MVA 10.5/0.4KV Dyn11_7.14%
CAT 3516-N04
Cab_S-11
N2XSY 8.7/15KV 3x185 mm2
~
B_G13-G15
B_G13-G15(1)
G13
SG tr2_CTE-IQUITOS05 0.0400 km
3.3MVA 10.5/0.48KV Dyn11_9.73%
1
S-11
TR2_CUMMINSN1
2.0MVA 10.5/0.4KV Dyn11_6%
~
G14
SG
Cab_S-06
N2XSY 8.7/15KV 3x120 mm2
1
~
0.0400 km
SG
1
~
C.T.E. IQUITOS
G15
CUMMINS-N1
S-06
SG
Figura 3.1 Diagrama Unifilar del Proyecto
tr2_AuxWartsila Cab_AuxWartsila
0.2540 km
AuxWARTSILA
SR522.9KV
Breaker/Switch(1)
Tr2-SR5 Cab_S-01
7.0MVA 22.9/10KV Ynd5_5.85% N2XSY 8.7/15KV 3x120 mm2
0.0400 km
S-01
SR-5
Cab_SR-4
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
PowerFactory 15.1.7
SR-4
SANTA_ROSA60KV
T-03
BARRA_A_10.5KV
Z_SR
T-04
7.5MVA 60/10KV Ynd5_7.20%
Serv.Aux
-4
SR-2
Cab_SR-2
IQUITOS60KV
0.0400 km T-01
C.T .E. IQUIT OS
Cab_T-01
IQUITOS10.5KV
0.0380 km
N2XSY 8.7/15KV 3x500 mm2
BARRA ALSTOM-SET IQUITOS
Cab_SR-6
060_CT Iquitos - Iquitos
0
0.0540 km
Cab_SR-1
0
Annex:
Cab_SR-9
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
SR-9
BARRA_B_10.5KV
Project: EOCTEIQ
9/16/2015
Graphic: RED_IQUIT OS
DIgSILENT
INGENIERA
DESARROLLO
GESTIN ENERGTICA
La demanda de los alimentadores del sistema Elctrico Iquitos para el ao 2015, fue
proporcionada por la Empresa Electro Oriente, esta informacin se detalla en el siguiente cuadro.
4. METODOLOGA
Segn la norma ANSI, la capacidad trmica de corto tiempo del rotor se calcula de acuerdo a la
siguiente expresin:
(I2)2 x t = n
Siendo:
De acuerdo a la Norma ANSI C37.102.1987, las maquinas con potencias nominales menores a
800 MVA pueden soportar en forma permanente corrientes de secuencia negativa del orden del
10% de la corriente nominal.
Igualmente, la misma norma especfica que la constante de tiempo (I2/I0)2.t de los generadores
con potencias menores a 800 MVA es de 40 s.
durante el proceso de clculo. La solucin del problema de flujo de potencia permite obtener
principalmente los siguientes resultados:
Los anlisis de flujo de potencia, se realizan en condiciones normales de operacin con la C.T.E.
Iquitos en los Periodo 1 con 9 MW y Periodo 2 con 12 MW.
El clculo de las corrientes de cortocircuito se realiza segn la norma IEC60909 2001, para fallas
bifsicas a tierra, monofsicas y trifsicas en las barras del Sistema Elctrico Iquitos. Este
anlisis se realizar para las situaciones de mxima, media y mnima demanda para el ao 2015.
Los resultados del anlisis de cortocircuito, se presentan en cuadros y salidas graficas del
DIGSILENT. Asimismo se simula el escenario de mxima generacin, con todos los generadores
operando, con el fin de calcular las mayores corrientes de cortocircuito.
Para ello, se aplic una falla trifsica en la barra de alta tensin del transformador elevador de la
C.T.E. Iquitos durante 100 ms, luego se procedi a incrementarlo hasta que el generador
perdiese el sincronismo.
El anlisis se realiza para las situaciones de mxima, media y mnima demanda en los periodos
1 y 2.
Para encontrar desde el punto de vista dinmico, el impacto que puede producir sobre el sistema
la ocurrencia de disturbios de magnitud importante, tales como cortocircuitos, se analizan los
siguientes casos:
Falla monofsica con recierre exitoso en la lnea Iquitos Santa Rosa 60 kV, al 1% de
la lnea desde la S.E. Iquitos.
5. CRITERIOS TCNICOS
Los criterios tcnicos para el anlisis en estado estacionario se describen a continuacin y han
sido obtenidas del documento Procedimiento tcnico del COES, PR-20 - Ingreso, modificacin
y retiro de instalaciones del SEIN, aprobado mediante Resolucin OSINERGMIN N 035-2013-
OS/CD del 14 de marzo de 2013.
Tensin
Estado Normal: debe estar dentro del rango 5 % de las tensiones nominales de los
equipos instalados en las subestaciones, principalmente transformadores de potencia.
Asimismo, en el caso de las barras del sistema de transmisin, las tensiones en Estado
Normal deben estar en el rango de 2.5 % de las tensiones de operacin.
Sobrecargas
Estado Normal: no se admite sobrecargas ni en lneas ni en transformadores de
potencia.
6. EXIGENCIAS DE DISEO
Se simula una falla bifsica sin contacto a tierra en los bornes de generacin 0.48 kV y en el lado
de alta tensin del generador elevador 10.5 kV, determinndose el cual de los casos se obtiene
una mayor corriente de secuencia inversa.
DIgSILENT
2.323
0.002 s
Y = 2.212 p.u.
1.836
1.350
0.863
0.376
-0.111
-0.100 0.119 0.339 0.558 0.777 [s] 0.997
G01: Negative-Sequence Current, Magnitude in p.u.
G04: Negative-Sequence Current, Magnitude in p.u.
G07: Negative-Sequence Current, Magnitude in p.u.
G10: Negative-Sequence Current, Magnitude in p.u.
G13: Negative-Sequence Current, Magnitude in p.u.
SEC_INVERSA Date:
Annex: /1
DIgSILENT
1.466
0.002 s
Y = 1.396 p.u.
1.159
0.852
0.545
0.237
-0.070
-0.100 0.119 0.339 0.558 0.777 [s] 0.997
G01: Negative-Sequence Current, Magnitude in p.u.
G07: Negative-Sequence Current, Magnitude in p.u.
G10: Negative-Sequence Current, Magnitude in p.u.
SEC_INVERSA Date:
Annex: /1
I2 tiempo
Falla en: Tensin (kV)
(p.u.) (segundos)
Lado de Baja Tensin 0.48 2.212 8.18
Lado de Alta Tensin 10.5 1.396 20.53
En el cuadro anterior se observa, que la falla que produce mayor incremento de corriente de
secuencia negativa, es la falla bifsica en 0.48 kV y ste tolerar dicha corriente de 2.212 p.u.
por 8.18 segundos.
De acuerdo a los resultados este tiempo de tolerancia de 8.18 segundos, an bajo la hiptesis
que la corriente inversa no decrece con el tiempo, supera ampliamente cualquier tiempo
razonable que pudiera ser asignado para un esquema de respaldo.
Las simulaciones se realizaron utilizando el programa Digsilent Versin 15.1.7, los anlisis
incluyen las situaciones con proyecto y sin proyecto (Periodo 1 y 2), en las condiciones de
mxima, media y mnima demanda para el ao 2015.
Se ha simulado los flujos de potencia para la configuracin sin la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:
Del cuadro anterior se observa que las tensiones en el sistema, estn dentro de los rangos
aceptables de operacin normal 5%.
b) Respecto a las sobrecargas del Sistema Elctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, lneas de transmisin y transformadores:
Del cuadro anterior se observa que las sobrecargas en cables, lneas y transformadores son
menores al 100%.
En el Anexo A1, se puede observar los resultados de las simulaciones de flujo de potencia sin
proyecto.
Se ha simulado los flujos de potencia para la configuracin con la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:
Del cuadro anterior se observa que las tensiones en el sistema, estn dentro de los rangos
aceptables de operacin normal 5%.
b) Respecto a las sobrecargas del Sistema Elctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, lneas de transmisin y transformadores:
Tensin PERIODO 1
Lnea / Transformador Nominal Mxima Media Mnima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.26 9.33 22.85
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.71 17.31
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.92 4.62 35.30
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.88 39.74 9.15 20.52
Max353.8Amp(1) N2XSY 8.7/15KV 3x185 mm2 5.02 61.39 5.02 61.36 5.02 61.30
Max530.7Amp N2XSY 8.7/15KV 3x240 mm2 5.01 53.02 5.01 53.00 5.01 52.95
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 17.45 61.54 15.67 55.25 6.76 23.81
T-01 14MVA 60/10KV Ynd5_8.7% 11.08 75.66 9.32 63.55 4.71 32.61
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.28 4.62 31.96
tr2_CTE-IQUITOS01 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS02 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS03 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS04 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS05 3.3MVA 10.5/0.48KV Dyn11_9.73% 0.02 0.46 0.02 0.46 0.02 0.46
Del cuadro anterior se observa que las sobrecargas en lneas y transformadores son menores al
100%.
En el Anexo A2, se puede observar los resultados de las simulaciones de flujo de potencia con
proyecto para el ao de ingreso.
Se ha simulado los flujos de potencia para la configuracin con la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:
Del cuadro anterior se observa que las tensiones en el sistema, estn dentro de los rangos
aceptables de operacin normal 5%.
d) Respecto a las sobrecargas del Sistema Elctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, lneas de transmisin y transformadores:
Tensin PERIODO 2
Lnea / Transformador Nominal Mxima Media Mnima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.27 9.34 22.89
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.72 17.34
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.93 4.62 35.36
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.89 39.75 9.16 20.56
Max353.8Amp(1) N2XSY 8.7/15KV 3x185 mm2 5.26 64.32 5.26 64.33 5.26 64.30
Max530.7Amp N2XSY 8.7/15KV 3x240 mm2 7.90 83.49 7.90 83.50 7.89 83.46
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 18.47 65.12 16.35 57.66 9.60 33.84
T-01 14MVA 60/10KV Ynd5_8.7% 11.08 75.66 9.32 63.56 4.72 32.67
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.29 4.62 32.01
tr2_CTE-IQUITOS01 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.87 2.77 83.87 2.77 83.84
tr2_CTE-IQUITOS02 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.87 2.77 83.87 2.77 83.84
tr2_CTE-IQUITOS03 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.82 2.77 83.83 2.77 83.79
tr2_CTE-IQUITOS04 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.82 2.77 83.83 2.77 83.79
tr2_CTE-IQUITOS05 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.95 2.77 83.96 2.77 83.92
Del cuadro anterior se observa que las sobrecargas en lneas y transformadores son menores al
100%.
En el Anexo A3, se puede observar los resultados de las simulaciones de flujo de potencia con
proyecto para el ao de ingreso.
Las simulaciones se realizaron con el programa Digsilent Versin 15.1.7, para las situaciones
con proyecto y sin proyecto, en las condiciones de mxima, media y mnima demanda para el
ao 2015.
En el Anexo B, C y D, se pueden observar los resultados de las simulaciones del clculo de las
corrientes de cortocircuito, para fallas bifsicas a tierra, monofsicas y trifsicas respectivamente.
De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifsicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.9 kA, el cual supera la capacidad de ruptura de 25 kA.
En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentaran
problemas con el equipo existente de 31.5 kA.
En el siguiente cuadro se presentan los resultados de las simulaciones del clculo de las
corrientes de cortocircuito para la situacin con proyecto en el periodo 1:
De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifsicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.24 kA, el cual supera la capacidad de ruptura de 25 kA.
En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentaran
problemas con el equipo existente de 31.5 kA.
En el siguiente cuadro se presentan los resultados de las simulaciones del clculo de las
corrientes de cortocircuito para la situacin con proyecto en el periodo 2:
De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifsicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.53 kA, el cual supera la capacidad de ruptura de 25 kA.
En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentaran
problemas con el equipo existente de 31.5 kA.
En el siguiente cuadro se presentan los resultados de las simulaciones del clculo de las
corrientes de cortocircuito para la situacin de mxima generacin (todos los generadores
operando) en la situacin con y sin proyecto:
Considerando la operacin de todos los generadores, se deber considerar para el diseo de los
equipos la corriente de cortocircuito de 37 kA en la barra de 10.5 kV (celdas resaltadas de color
rojo).
Secuencia de Simulacin:
Se aplic una falla trifsica en el punto de conexin de la C.T.E. Iquitos en 10.5 kV durante 100
ms, luego se procedi a incrementarlo hasta que el generador perdiese el sincronismo. El anlisis
se realiza para las situaciones de mxima, media y mnima demanda para el periodo 1 (con
C.T.E. 9 MW) y periodo 2 (con C.T.E. 12 MW).
Figura 8.1 Tiempo Crtico de Despeje de Falla Mxima Demanda (9 MW) tc=180 ms
DIgSILENT
90.32 115.5
55.56
73.65
-4.333
56.98
-64.23
40.31
-124.1
23.64 -184.0
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
6.968 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg CATMAK-N02: Rotor angle with reference to reference machine angle in deg
G11: Rotor angle with reference to reference machine angle in deg CUMMINS-N1: Rotor angle with reference to reference machine angle in deg
1.381 10.39
7.036
1.083
3.681
0.784
0.326
0.486
-3.030
0.187 -6.385
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: Total Active Power in MW
-0.111 WARTSILA-N03: Total Active Power in MW
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N04: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-N05: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-N06: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-N02: Total Active Power in MW
G13: m:Psum:bus1 CUMMINS-N1: Total Active Power in MW
Figura 8.2 Tiempo Crtico de Despeje de Falla Media Demanda (9 MW) tc=190 ms
DIgSILENT
300.00 159.5
119.2
200.00
78.86
100.00
38.53
0.00
-1.800
-100.00 -42.13
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
-200.00 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg CATMAK-N02: Rotor angle with reference to reference machine angle in deg
G11: Rotor angle with reference to reference machine angle in deg CUMMINS-N1: c:firel
1.004 22.44
14.47
0.779
6.508
0.554
-1.459
0.329
-9.425
0.105 -17.39
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: Total Active Power in MW
-0.120 WARTSILA-N03: Total Active Power in MW
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N04: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-N05: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-N06: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-N02: Total Active Power in MW
G13: m:Psum:bus1 CUMMINS-N1: m:Psum:bus1
Figura 8.3 Tiempo Crtico de Despeje de Falla Mnima Demanda (9 MW) tc=200 ms
DIgSILENT
186.9 97.03
69.45
148.9
41.88
110.9
14.30
72.91 -13.28
-40.86
34.93 -0.100 1.920 3.940 5.960 7.980 [s] 10.000
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
WARTSILA-N03: c:firel
-3.057 WARTSILA-N04: c:firel
-0.100 1.920 3.940 5.960 7.980 [s] 10.000 WARTSILA-N05: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg CATMAK-N02: c:firel
G10: Rotor angle with reference to reference machine angle in deg CUMMINS-N1: c:firel
1.003 13.22
8.610
0.764
4.003
0.525
-0.605
0.286
-5.212
0.047 -9.819
-0.100 1.920 3.940 5.960 7.980 [s] 10.000
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: Total Active Power in MW
-0.191 WARTSILA-N03: m:Psum:bus1
-0.100 1.920 3.940 5.960 7.980 [s] 10.000 WARTSILA-N04: m:Psum:bus1
G01: Total Active Power in MW WARTSILA-N05: m:Psum:bus1
G04: Total Active Power in MW WARTSILA-N06: m:Psum:bus1
G07: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-N02: m:Psum:bus1
G13: m:Psum:bus1 CUMMINS-N1: m:Psum:bus1
Figura 8.4 Tiempo Crtico de Despeje de Falla Mxima Demanda (12 MW) tc=180 ms
DIgSILENT
150.5 55.60
35.15
122.1
14.69
93.83
-5.762
65.52
-26.22
37.21
-46.67
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
8.900 WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg CATMAK-N02: Rotor angle with reference to reference machine angle in deg
1.321 16.15
10.69
1.001
5.235
0.681
-0.223
0.362
-5.681
0.042
-11.14
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
-0.278 WARTSILA-N01: Active Power in MW
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N02: Active Power in MW
G01: Active Power in MW WARTSILA-N03: Active Power in MW
G04: Active Power in MW WARTSILA-N04: Active Power in MW
G07: Active Power in MW WARTSILA-N05: Active Power in MW
G10: Active Power in MW WARTSILA-N06: Active Power in MW
G13: Active Power in MW WARTSILA-N07: Active Power in MW
Figura 8.5 Tiempo Crtico de Despeje de Falla Media Demanda (12 MW) tc=185 ms
DIgSILENT
132.0 34.03
20.95
106.9
7.866
81.74
-5.217
56.61
-18.30
31.48
-31.38
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
6.354 WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg CATMAK-N02: c:firel
1.345 12.41
8.489
1.012
4.568
0.679
0.648
0.346
-3.273
0.013
-7.194
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
-0.320 WARTSILA-N01: Total Active Power in MW
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-N02: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-N03: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-N04: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-N05: Total Active Power in MW
G10: Total Active Power in MW WARTSILA-N06: Total Active Power in MW
G13: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
Figura 8.6 Tiempo Crtico de Despeje de Falla Mnima Demanda (12 MW) tc=190 ms
DIgSILENT
169.1 52.82
36.66
136.3
20.49
103.6
4.326
70.80
-11.84
38.04
-28.01
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
5.275 WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N02: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N03: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: c:firel
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: c:firel
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: c:firel
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
0.962 9.810
6.239
0.744
2.667
0.525
-0.904
0.307
-4.475
0.089
-8.046
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
-0.130 WARTSILA-N01: Total Active Power in MW
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-N02: m:Psum:bus1
G01: Total Active Power in MW WARTSILA-N03: m:Psum:bus1
G04: Total Active Power in MW WARTSILA-N04: m:Psum:bus1
G07: Total Active Power in MW WARTSILA-N05: m:Psum:bus1
G10: Total Active Power in MW WARTSILA-N06: m:Psum:bus1
G13: Total Active Power in MW WARTSILA-N07: Total Active Power in MW
De las simulaciones se concluye que el menor valor del tiempo crtico de despeje de falla es de
180 ms en el escenario de mxima demanda, y se encuentra entre 185 ms-190 ms en el
escenario de media demanda y entre190 ms-200 ms en el escenario de mnima demanda, los
tiempos obtenidos son mayores al tiempo normal de operacin de las protecciones, igual a 100
ms.
Tiempo Crtico
CASO Escenario Conclusin
(ms)
Mxima Demanda 180 >100ms
Con CT.E Iquitos 9 MW Media Demanda 190 >100ms
Mnima Demanda 200 >100ms
Mxima Demanda 180 >100ms
Con CT.E Iquitos 12 MW Media Demanda 185 >100ms
Mnima Demanda 190 >100ms
Falla monofsica con recierre exitoso en la lnea Iquitos Santa Rosa 60 kV, al 1% de
la lnea desde la S.E. Iquitos.
Figura 9.1 Falla 1 con Recierre Exitoso LT Iquitos Sta. Rosa en Mxima Demanda
DIgSILENT
18.23 5.562
3.049
18.10
0.537
17.97
-1.975
17.84
-4.488
17.71
-7.000
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
17.57 WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N02: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N03: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
60.66 2.468
2.204
60.52
1.940
60.38
1.675
60.24 1.411
1.146
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
60.11
WARTSILA-N01: Active Power in MW
WARTSILA-N02: Active Power in MW
WARTSILA-N03: Active Power in MW
WARTSILA-N04: Active Power in MW
59.97 WARTSILA-N05: Active Power in MW
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N06: Active Power in MW
B_WARTSILA G20MW: Electrical Frequency in Hz WARTSILA-N07: Active Power in MW
DIgSILENT
1.05 23.00
1.01
19.00
0.97
15.00
0.93
11.00
0.89
0.85 7.00
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
BARRA_A_10.5KV: u1, Magnitude in p.u.
BARRA_B_10.5KV: u1, Magnitude in p.u.
B_ALSTOM: u1, Magnitude in p.u.
B_CATMAK 01-02: u1, Magnitude in p.u.
B_CATMAK-05: u1, Magnitude in p.u.
B_G1-G6: u1, Magnitude in p.u.
B_G13-G15(1): u1, Magnitude in p.u.
B_G7-G12: u1, Magnitude in p.u. 3.00
B_SKODA: u1, Magnitude in p.u. -0.100 1.919 3.938 5.956 7.975 [s] 9.994
B_WARTSILA: u1, Magnitude in p.u. BARRA ALSTOM-SET IQUITOS: Total Active Power/Terminal i in MW
B_WARTSILA G20MW: u1, Magnitude in p.u. IQUITOS-SANTA ROSA 60KV: Total Active Power/Terminal i in MW
CAT-N3 10.5KV: u1, Magnitude in p.u. Max353.8Amp: Total Active Power/Terminal i in MW
GRUPOS RAPIDOS: u1, Magnitude in p.u. Max353.8Amp(1): Total Active Power/Terminal j in MW
IQUITOS10.5KV: u1, Magnitude in p.u. Max530.7Amp: Total Active Power/Terminal i in MW
IQUITOS60KV: u1, Magnitude in p.u. WARTSILA G20MW-SET IQUITOS: m:Psum:bus2
PCONEX_CTE: u1, Magnitude in p.u. WARTSILA-CATMAK: Total Active Power/Terminal j in MW
SANTA_ROSA60KV: u1, Magnitude in p.u. WARTSILA-WARTSILA G20MW: Total Active Power/Terminal j in MW
Figura 9.2 Falla 1 con Recierre Exitoso LT Iquitos Sta. Rosa en Mnima Demanda
DIgSILENT
15.09 0.472
-1.605
15.01
-3.682
14.94
-5.759
14.86
-7.837
14.78
-9.914
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
14.71 WARTSILA-N01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N02: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-N03: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-N04: c:firel
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-N05: c:firel
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-N06: c:firel
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-N07: Rotor angle with reference to reference machine angle in deg
60.41 6.574
6.005
60.33
5.435
60.24
4.866
60.15 4.296
3.727
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
60.07
WARTSILA-N01: Total Active Power in MW
WARTSILA-N02: m:Psum:bus1
WARTSILA-N03: m:Psum:bus1
WARTSILA-N04: m:Psum:bus1
59.98 WARTSILA-N05: m:Psum:bus1
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-N06: m:Psum:bus1
B_WARTSILA G20MW: Electrical Frequency in Hz WARTSILA-N07: Total Active Power in MW
DIgSILENT
1.04 12.00
1.02
10.00
1.00
8.00
0.98
6.00
0.96
0.94 4.00
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
BARRA_A_10.5KV: u1, Magnitude in p.u.
BARRA_B_10.5KV: u1, Magnitude in p.u.
B_ALSTOM: u1, Magnitude in p.u.
B_CATMAK 01-02: u1, Magnitude in p.u.
B_CATMAK-05: u1, Magnitude in p.u.
B_G1-G6: u1, Magnitude in p.u.
B_G13-G15(1): u1, Magnitude in p.u.
B_G7-G12: u1, Magnitude in p.u. 2.00
B_SKODA: u1, Magnitude in p.u. -0.100 1.919 3.938 5.956 7.975 [s] 9.994
B_WARTSILA: u1, Magnitude in p.u. BARRA ALSTOM-SET IQUITOS: Total Active Power/Terminal i in MW
B_WARTSILA G20MW: u1, Magnitude in p.u. IQUITOS-SANTA ROSA 60KV: Total Active Power/Terminal i in MW
CAT-N3 10.5KV: u1, Magnitude in p.u. Max353.8Amp: Total Active Power/Terminal i in MW
GRUPOS RAPIDOS: u1, Magnitude in p.u. Max353.8Amp(1): Total Active Power/Terminal j in MW
IQUITOS10.5KV: u1, Magnitude in p.u. Max530.7Amp: Total Active Power/Terminal i in MW
IQUITOS60KV: u1, Magnitude in p.u. WARTSILA G20MW-SET IQUITOS: m:Psum:bus2
PCONEX_CTE: u1, Magnitude in p.u. WARTSILA-CATMAK: Total Active Power/Terminal j in MW
SANTA_ROSA60KV: u1, Magnitude in p.u. WARTSILA-WARTSILA G20MW: Total Active Power/Terminal j in MW
De las simulaciones observamos que el ngulo del rotor, potencia de los generadores, potencia
en lneas y tensiones se estabilizan en el periodo de simulacin de 10 segundos.
De acuerdo al evento la generacin total pre-falla es 27.75 MW, el cual corresponde al escenario
de mnima demanda. Antes de ocurrir algn rechazo automtico de generacin o carga la
frecuencia es mayor a 59.8 Hz y menor a 60.02 Hz.
En el segundo caso, evaluaremos la salida del generador GT Cat Mak N 2, en la siguiente figura
se muestra la evolucin en el tiempo de la frecuencia:
De acuerdo al evento la generacin total pre-falla es 22.8 MW, el cual corresponde al escenario
de mnima demanda. Antes de ocurrir algn rechazo automtico de generacin o carga la
frecuencia es mayor a 59.5 Hz y menor a 60.02 Hz.
Por ltimo, tenemos algunos de los eventos importantes, en la siguiente figura se muestra la
evolucin en el tiempo de la frecuencia:
Al igual que los primeros eventos podemos verificar que la frecuencia pre-falla se encuentra entre
59.6 Hz y 60.1 Hz.
Por tanto, concluimos que la frecuencia pre-falla (operacin normal) es mayor a 59.5 Hz.
El primer umbral de frecuencia no debe estar cercano a la frecuencia nominal del sistema,
permitiendo de esta manera la respuesta natural del sistema ante la variacin de la generacin.
Tambin se debe considerar que los umbrales de disparo de las protecciones de baja frecuencia
de las unidades de generacin es la frecuencia de 57 Hz.
Del anlisis de los eventos importantes ocurridos en ELOR se concluye que la frecuencia pre-
falla es mayor a 59.5 Hz, por tanto como primer umbral se utilizar la frecuencia de 59.0 Hz.
Siendo el primer umbral 59 Hz, el paso entre etapas ser fijo e igual a -0.1 Hz, es decir el umbral
para la segunda etapa es 58.9 Hz, para la tercera etapa es 58.8 Hz, para la cuarta etapa es 58.7
Hz, para la quinta etapa es 58.6 Hz. El valor de -0.1 Hz es muy usual en sistemas de potencia y
puede considerarse estndar.
10.2.3. Temporizacin
La temporizacin es igual para todas las etapas, con el fin de permitir que el efecto causado por
el rechazo de cada etapa en la dinmica del sistema se efectivice antes de que actu la siguiente
etapa. Se ha seleccionado una temporizacin de 150 ms, en la seleccin de esta temporizacin
se tiene en cuenta la demora de los interruptores en abrir efectivamente (85 ms).
En el anlisis se buscar rechazar la menor carga hasta que el sistema sea estable y la
frecuencia final se encuentre entre 59.5 Hz y 60.5 Hz.
Las caractersticas del rechazo de carga por derivada de frecuencia son similares a las de umbral
de frecuencia, con la diferencia de que para todas las etapas se tiene un umbral de frecuencia
comn. El coordinamiento entre etapas se establece mediante los valores de la pendiente.
respuesta natural del sistema Iquitos, con este valor se esperara una rpida accin de rechazo,
el cual se verifica en las simulaciones realizadas
Generacin 9 MW Generacin 12 MW
Indicador Mxima Media Mnima Mxima Media Mnima
Demanda Demanda Demanda Demanda Demanda Demanda
Total Carga (MW) 53.46 48.30 22.02 53.46 48.30 22.02
Total Generacin (MW) 54.14 48.85 22.35 54.14 48.85 22.35
Prdida de Generacin (MW) 9.00 9.00 9.00 12.00 12.00 12.00
% Prdida Generacin/Carga 16.8% 18.6% 40.9% 22.4% 24.8% 54.5%
La salida de la C.T.E. Iquitos en mnima demanda representa el 40.9% y 54.5%, en estos casos
donde se presentan gran dficit de generacin es necesario realizar rechazar ms del porcentaje
para que el sistema pueda recuperar la frecuencia.
Nmero de Porcentaje de Rechazo Rles por Umbral Rles por Derivada de Frecuencia
Etapa en cada Etapa (*) Umbral (Hz) Temporizacin (s) Umbral (Hz/s) Temporizacin
1 8% 59.0 0.15 -0.9 0.12
2 5% 58.9 0.15 -0.7 0.12
3 4% 58.8 0.15 -0.7 0.12
4 4% 58.7 0.15
5 30% 58.6 0.15
(*) Porcentaje de carga para cualquier escenario (mxima, media y mnima demanda)
A continuacin se verificar la actuacin del ERCMF ante la salida de la C.T.E. Iquitos en los
caos de salida de la CTE con 9 MW y 12 MW en mxima, media y mnima demanda.
Figura 10.4 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) Mxima Demanda
DIgSILENT
60.25
2.686 s
59.987 Hz
60.00
59.75
45.568 s
59.558 Hz
0.831 s
0.161 s Y = 59.500 Hz
59.50
59.25
0.332 s Y = 59.100 Hz
0.351 s
59.059 Hz
Y = 59.000 Hz
59.00
-0.100 9.920 19.94 29.96 39.98 [s] 50.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz
Figura 10.5 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Media Demanda
DIgSILENT
60.30
60.00
57.666 s
60.147 Hz
59.70
1.150 s
0.145 s Y = 59.500 Hz
59.40
0.532 s
0.281 s Y = 59.100 Hz
59.10
Y = 59.000 Hz
0.350 s
58.956 Hz Y = 58.900 Hz
Y = 58.800 Hz
58.80
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz
Figura 10.6 Verificacin del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Mnima Demanda
DIgSILENT
63.25
Y = 63.000 Hz
2.706 s
62.957 Hz
62.00
60.75
0.977 s 11.513 s Y = 60.500 Hz
52.658 s
59.871 Hz
0.737 s
0.008 s Y = 59.500 Hz
59.50
0.656 s
0.092 s Y = 59.100 Hz
Y = 59.000 Hz
Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
0.492 s
58.25 0.196 s Y = 58.200 Hz
0.365 s
57.477 Hz
57.00
-0.100 11.92 23.94 35.96 47.98 [s] 59.99
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz
DIgSILENT
63.25
Y = 63.000 Hz
62.00
60.75
0.977 s Y = 60.500 Hz
0.049 s
0.020 s
0.008 s 0.737 s Y = 59.500 Hz
59.50
0.369 s
57.473 Hz
57.00
-0.100 0.485 1.071 1.656 2.241 [s] 2.827
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz
Figura 10.7 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mxima Demanda
DIgSILENT
60.20
59.90
55.873 s
59.733 Hz
59.60
59.30
2.626 s
0.205 s Y = 59.100 Hz
Y = 59.000 Hz
59.00
Y = 58.900 Hz
Y = 58.800 Hz
0.309 s
58.780 Hz
Y = 58.700 Hz
58.70
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz
Figura 10.8 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Media Demanda
DIgSILENT
60.30
56.996 s
59.90 59.757 Hz
1.321 s
0.167 s Y = 59.100 Hz
59.10
Y = 59.000 Hz
Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
58.70
Y = 58.600 Hz
0.470 s
58.570 Hz Y = 58.500 Hz
58.30
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: Electrical Frequency in Hz
WARTSILA-N06: Electrical Frequency in Hz
WARTSILA-N07: Electrical Frequency in Hz
Figura 10.9 Verificacin del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mnima Demanda
DIgSILENT
61.00
Y = 60.500 Hz
3.851 s
59.932 Hz
60.00
48.168 s
59.588 Hz
1.881 s
0.007 s Y = 59.500 Hz
1.450 s
0.009 s Y = 59.100 Hz
Y = 59.000 Hz
59.00 Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
0.906 s
0.120 s Y = 58.200 Hz
58.00
57.00
0.306 s
56.478 Hz
56.00
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz
DIgSILENT
61.00
Y = 60.500 Hz
60.00
0.056 s
0.009 s 1.450 s Y = 59.100 Hz
Y = 59.000 Hz
59.00 Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
58.00
57.00
0.306 s
56.478 Hz
56.00
-0.100 0.570 1.240 1.910 2.580 [s] 3.250
WARTSILA-N05: n:fehz:bus1
WARTSILA-N06: n:fehz:bus1
WARTSILA-N07: Electrical Frequency in Hz
mnima frecuencia del alimentador R-5 actuara. Se recomienda cambiar la temporizacin del
rel por mnima frecuencia del alimentador R-5 a 0.8 s.
Ante la prdida de generacin igual a 9 MW se debe rechazar 9.09 MW, 8.21 MW y 11.23 MW
en el escenario de mxima, media y mnima demanda respectivamente.
a) La falla bifsica en 0.48 kV produce una mayor corriente de secuencia negativa y ste
tolerar dicha corriente de 2.212 p.u. por 8.18 segundos. De acuerdo a los resultados este
tiempo de tolerancia de 8.18 segundos, an bajo la hiptesis que la corriente inversa no
decrece con el tiempo, supera ampliamente cualquier tiempo razonable que pudiera ser
asignado para un esquema de respaldo.
e) De las simulaciones se concluye que el menor valor del tiempo crtico de despeje de falla es
180 ms, el tiempo determinado es mayor al tiempo normal de operacin de las protecciones,
igual a 100 ms.
f) Ante una falla monofsica con recierre exitoso en la lnea Iquitos-Santa Rosa 60 kV, no se
pierde sincronismo de las centrales, las tensiones, potencia y velocidad se estabilizan en el
periodo de simulacin de 10 segundos.
i) Por lo mencionado, de los anlisis elctricos se concluye que las nuevas instalaciones que
conforman el proyecto C.T.E. IQUITOS, cumplen con el objetivo principal de brindar el
suministro de energa adicional de manera continua y confiable y no afecta la operacin
actual de las dems instalaciones del proyecto.
12. ANEXOS
================================================
Anexo A Flujo de Potencia
================================================
A1 Caso Base
A1.1 Mxima Demanda
A1.2 Media Demanda
A1.3 Mnima Demanda
A2 Periodo 1 Con C.T.E. Iquitos 9 MW
A2.1 Mxima Demanda
A2.2 Media Demanda
A2.3 Mnima Demanda
A3 Periodo 2 Con C.T.E. Iquitos 12 MW
A3.1 Mxima Demanda
A3.2 Media Demanda
A3.3 Mnima Demanda
================================================
Anexo B Cortocircuito Caso Base Sin CTE Iquitos
================================================
B1 Cortocircuito Bifsico a Tierra
B1.1 Mxima Demanda
B1.2 Media Demanda
B1.3 Mnima Demanda
B2 Cortocircuito Monofsico
B2.1 Mxima Demanda
B2.2 Media Demanda
B2.3 Mnima Demanda
B3 Cortocircuito Trifsico
B3.1 Mxima Demanda
B3.2 Media Demanda
B3.3 Mnima Demanda
================================================
Anexo C Cortocircuito Con CTE Iquitos 9 MW
================================================
C1 Cortocircuito Bifsico a Tierra
C1.1 Mxima Demanda
C1.2 Media Demanda
C1.3 Mnima Demanda
C2 Cortocircuito Monofsico
C2.1 Mxima Demanda
C2.2 Media Demanda
C2.3 Mnima Demanda
C3 Cortocircuito Trifsico
C3.1 Mxima Demanda
================================================
Anexo G - Escenario de Mxima Generacin
================================================
G1 Cortocircuito Trifsico
G1.1 Sin C.T.E. Iquitos
G1.2 Con C.T.E. Iquitos
================================================
Anexo H Base de Datos Digsilent
================================================