Professional Documents
Culture Documents
Abstract- Distribution system represents the final link between bulk generator into the distribution network. On the other hand,
power system and the consumers. Distributed generators or small- when operating at negative power factor, the generator will
scale energy sources are usually smaller than central energy sources consume reactive power. The power flow will be from the
and can produce electricity in the range of 10 kW to 10,000kW. It is
distribution network into the generator [9].
usually connected to the power system points close to the customer.
One of the problems faced when dealing with DG is to
Power loss in a distribution system consists of real and reactive
power loss. Real power loss is due to the transmission lines resistance determine the proper size. As the size of DG is increased, the
while reactive power loss is due to the inductive element, which total system loss will reduce up to a minimum point where if
allows the real power transfer in the distribution system. This paper the size of DG is further increase, the system loss will increase
presents the optimal allocation and sizing of multi-distributed [6]. Adnan in [6] verified that, location also affects the
generation (DG) in distribution system for minimum power loss. The reliability of DG. At different locations, DG would reduce
study involves the development of Gravitational Search Algorithm power loss differently. It can be said that DG is location-
(GSA) engine as an optimization technique. Comparison with dependent. The size of DG that will be allocated also need to
respect to Evolutionary Programming (EP) was conducted in order to
be equal or less to the summation of total systems load and
highlight its superiority. The developed algorithm has been validated
total systems loss [7]. This value will be the limit for the size
on 15-Bus IEEE Distribution System and the results revealed that
power loss is reduced. GSA outperformed EP in terms of achieving of DG to be allocated.
lower minimal power loss. The technique presented in this paper is to optimize the
total losses through the changes of loading condition at
Index Terms Gravitational Search Algorithm, Evolutionary selected buses using the Gravitational Search Algorithm
Programming, Allocation and sizing of DG (GSA). This technique was compared with Evolutionary
Programming (EP) to see which technique can offer better
I. INTRODUCTION results in minimizing power loss. The developed algorithm has
Renewable energy for electricity resource is gaining been tested on 15-Bus IEEE Distribution System. Study has
popularity in Malaysia. It can benefit the distribution system if revealed that the proposed algorithm has succeeded in
it is installed correctly. The main point of this research is to optimizing the power loss and offer better result compared to
have most minimum power loss. Power losses in the system EP.
mainly depend on the systems power flow [8].
Conventionally, distribution system was designed as a passive II. MECHANICS OF GRAVITATIONAL SEARCH ALGORITHM
network [7] and it has unidirectional power flow [12] purely Gravitational Search Algorithm (GSA) is an optimization
for delivering power [13]. By applying DG, the power flow algorithm based on the gravitation law. Based on Newtons
become active and it can either help reducing the loss or law of gravitation, each mass (of an object) attracts every
increasing it, depending on its size and location. Thus, DG is other mass with a gravitational force [1]. The force between
able to change the reactive power flow in the distribution the two masses can be formulated as follow:
network [9].
When operating at positive power factor, the generator (1)
will produce reactive power. The power will flow from the
(6)
(7)
365
2014 IEEE 8th International Power Engineering and Optimization Conference (PEOCO2014), Langkawi, The Jewel of Kedah,
Malaysia. 24-25 March 2014
366
2014 IEEE 8th International Power Engineering and Optimization Conference (PEOCO2014), Langkawi, The Jewel of Kedah,
Malaysia. 24-25 March 2014
have the same pattern as allocation for Bus 4 but with lesser Table VII, Table VIII and Table IX tabulate the optimal
load increment. sizing of DG for Case1 using EP. It is observed that the values
are consistently higher as compared to case 1 using GSA.
Table X, Table XI and Table XII shows the optimized location
TABLE I: OPTIMAL SIZING DURING LOAD INCREMENT AT BUS 6 and sizing of DG using EP. Same as case 1, using EP; the size
USING GSA
Qd6 Loss (MW) DG Sizing is almost consistent. The size of DG using EP is much higher
/ MVar Before After P1 P2 / Q2 than implementation using GSA.
/ MW MW / MVar For GSA, the size of DG for case 2 is much smaller as
2.0 0.2260 0.1120 0.4114 0.3290 0.4413
4.0 0.6607 0.3884 0.5024 0.3772 0.3990
compared to case 1. On the other hand, the size of DG for case
6.0 1.4860 0.8875 0.6425 0.4608 0.4104 2 is much bigger as compared to case 1 when EP was
8.0 3.0382 1.6896 0.8339 0.6052 0.6926 implemented. As mentioned in the introduction, DG is
location-dependent. The reason why EP is used, the sizing of
TABLE II: OPTIMAL SIZING DURING LOAD INCREMENT AT DG for case 2 is bigger which might be due to the location of
BUS 4 USING GSA
Qd4 / Loss (MW) DG Sizing DG is almost the same during load increment.
MVar P1 / P2 Q2 /
Before After
MW / MW MVar
2.0 0.2973 0.0533 0.3681 0.3870 0.4454 TABLE VII: OPTIMAL SIZING DURING LOAD INCREMENT
4.0 0.9957 0.1555 0.3946 0.4991 0.4935 AT BUS 6 USING EP
6.0 2.8894 0.3237 0.4376 0.6483 0.4657 Loss (MW) DG Sizing
Qd6 /
MVar P1 / P2 / Q2 /
Before After
TABLE III: OPTIMAL SIZING DURING LOAD INCREMENT AT MW MW MVar
BUS 13 USING GSA 2.0 0.2260 0.1820 0.7564 0.9910 0.3653
Qd13 / Loss (MW) DG Sizing 4.0 0.6607 0.4458 0.7564 0.9910 0.3653
MVar P1 / P2 / Q2 4.5 0.8229 0.5500 0.0291 0.0471 0.5257
Before After 6.0 1.4860 0.9825 0.0304 0.0478 0.5263
MW MW / MVar
0.5 0.1088 0.0241 0.3685 0.3135 0.3071 8.0 3.0382 1.8843 0.0312 0.0493 0.5260
1.0 0.2174 0.0554 0.3998 0.3134 0.4564
1.5 0.4013 0.1089 0.4363 0.3307 0.5579 TABLE VIII: OPTIMAL SIZING DURING LOAD INCREMENT
2.0 0.6978 0.1867 0.5310 0.3135 0.3601 AT BUS 4 USING EP
2.5 1.2043 0.2919 0.6362 0.3135 0.4495 Qd4 / Loss (MW) DG Sizing
MVar Before After P1 / P2 / Q2 /
MW MW MVar
TABLE IV: OPTIMAL LOCATION AND SIZING DURING LOAD
2.0 0.2973 0.1187 0.7564 0.9910 0.3653
INCREMENT AT BUS 6 USING GSA
4.0 0.9957 0.2072 0.0285 0.0471 0.5260
Qd6 / Loss (MW) DG Location DG Sizing
MVar before after DG1 DG2 P1 P2 Q2 6.0 2.8894 0.4086 0.0288 0.0494 0.5257
Bus Bus (MW) (MW) MVar
2.0 0.226 0.058 11 4 0.074 0.206 0.583 TABLE IX: OPTIMAL SIZING DURING LOAD INCREMENT
4.0 0.661 0.253 4 4 0.351 0.132 0.515 AT BUS 13 USING EP
6.0 1.486 0.632 5 11 0.113 0.106 0.695 Loss (MW) DG Sizing
Qd13 /
8.0 3.038 1.182 10 4 0.091 0.072 0.409 P1 / P2 / Q2 /
MVar Before After
MW MW MVar
0.5 0.1088 0.0976 0.7564 0.9910 0.3653
TABLE V: OPTIMAL LOCATION AND SIZING DURING LOAD
INCREMENT AT BUS 4 USING GSA 1.0 0.2174 0.1254 0.7564 0.9910 0.3653
1.5 0.4013 0.1731 0.7564 0.9910 0.3653
Loss (MW) DG Location DG Sizing
Qd4 / 2.0 0.6978 0.2436 0.7564 0.9910 0.3653
DG1 DG2 P1 / P2 Q2 /
MVar before after 2.5 1.2043 0.3482 0.0291 0.0471 0.5259
Bus Bus MW / MW MVar
2.0 0.297 0.064 8 8 0.245 0.056 0.463
4.0 0.996 0.313 8 8 0.193 0.104 0.387 TABLE X: OPTIMAL LOCATION AND SIZING DURING LOAD
6.0 2.889 0.737 8 8 0.482 0.090 0.684 INCREMENT AT BUS 6 USING EP
Qd6 / Loss (MW) DG Location DG Sizing
MVar before After DG1 DG2 P1 / P2 / Q2 /
TABLE VI: OPTIMAL LOCATION AND SIZING DURING LOAD
Bus Bus MW MW MVar
INCREMENT AT BUS 13 USING GSA
2.0 0.226 0.211 4 15 0.756 0.991 0.365
Loss (MW) DG Location DG Sizing
Qd13 / 4.0 0.661 0.474 4 15 0.756 0.991 0.365
DG1 DG2 P1 / P2 / Q2 /
MVar before After 6.0 1.486 0.963 14 12 0.653 0.414 0.700
Bus Bus MW MW MVar
1.5 0.401 0.109 6 6 0.376 0.007 0.537 8.0 3.038 1.855 14 12 0.649 0.410 0.696
2.0 0.698 0.191 6 6 0.300 0.007 0.492
2.5 1.204 0.308 7 7 0.393 0.134 0.218
367
2014 IEEE 8th International Power Engineering and Optimization Conference (PEOCO2014), Langkawi, The Jewel of Kedah,
Malaysia. 24-25 March 2014
368