Si CURRENT CARRYING CAPACITY GA ‘SINGLE CORE XLPE INSULATED PVC SQREL SHEATHED CABLE VOLTAGE 6001/1000 V : ‘AMBIENT TEMPERATURE 30°C CONDUCTOR OPERATING TEMPERATURE 90°C CUCM Gang 3 or 4 cables S-phase 2eables t-phase Jr cables 3:phase Zeables these ea ‘ac or de ac mee touching Tat ‘wofor Cm (amp) (amor ‘emp) emp) emp) 10 7 18 18 23 20 26 a 28 4 a2 37 6 64 48 10 75 66 16 100 88 25 133 117 161 141 135 35 164 148 200 476 169 50 198 175 242 216 207 70 253 222 310 279 268 95 308 268 377 342 328 120 354 312 437 400 383 150 393 342 04 464 444 186 449 384 875 533 510 240 528 450 679 634 607 300 603 514 783 736 703 ‘400 683 534 840 868 823 500 783 668 1083 998 948 630 900 764 1254 1151 1088 800 1358 1278 4214 +1000 1520 1436 1349 VOLTAGE DROP VOLTAGE DROP ( PER AMP PER METER ) Enclosed in ‘on cable tray, Enclosed in ‘on cablo tray, ‘on cablo tray ‘conduit touching ‘conduit flatand touching ‘wefoil Twain) Cimwrn) Twain) mwa) Conv 46 46 40 40 40 31 a 7 27 a 19 19 18 16 16 2 2 10 10 79 1 68 68 az az 40 40 29 29 28 28 1.90 1.88 165 1.60 138 138 118 148 1.08 1.00 0.90 087 075 on oss ost 088 0.82 0.60 0.45 048 043 oaz o37 043 0.36 07 031 037 0.30 032 026 033 0.25 0.29 022 031 022 o2t 0195 0.29 0.20 0.25 0.475 028 0.185 0.28 0.160 027 0.175 023 0.150 0.170 onas 0.165 0.140 Note : Correction factors for ambient temperature and group installation, please refer Page B-1