PROTECTION PRODUCT SOLUTIONS

MiCOM Alstom
P14N, P14D, P94V

The P14N non-directional P40 Agile feeder management IEDs


feeder, P14D directional The footprints of both the device physical size and the lifecycle environmental impact
feeder and P94V voltage & have been minimised using state-of-the-art design, component, and process
selection. Agile solutions from Alstom are ideal for new-build and retrofit alike.
frequency IEDs bring the
design rigour and AGILITY, VERSATILITY THE PERFECT BALANCE:
technology of transmission MiCOM P40 Agile IEDs provide an STANDARDISED AND ADAPTABLE
integrated solution for the complete With a wide range of protection
applications to the entire protection, control and monitoring of functions as standard, MiCOM P14N,
electrical power systems. Application for
utility and industrial market. overhead lines, underground cables,
P14D and P94V IEDs also offer
additional pre-configured applications for
busbars, breakers, transformers, smaller generators and a choice of
reactors, distributed generation and functionality applicable to overhead lines.
motors is supported, right from This allows the user to conveniently scale
distribution (as primary protection) to the application, which is then readily
transmission voltage levels (as back-up). adapted via simple enable/disable feature
The IEDs are suitable for application in selection in the configuration menu.
solidly-earthed, resistance-earthed and
Petersen coil systems alike. The IEDs offer a universal wide-range
power supply, universal 1 A/5 A CT
inputs (software selectable), and
universal binary inputs the latter with
programmable pickup thresholds.
Harmonisation at just one ordering
option is often possible, easing the task
of creating standard cubicle designs and
strategic spares holding.

CUSTOMER BENEFITS
Novel | Draw-out | Versatile
Powerful logic, protection and
communications
Cost effective
IEC 61850 and DNP3 Ethernet
solution
High impedance downed
conductor element boosts the
safety of the public and livestock
Alstoms user-centric access tool
S1 Agile used as the single PC
tool for all MiCOM
(1) Only with sensitive earth fault CT option
NERC compliant cyber security (2) HIF high impedance (downed conductor) fault

Grid-SAS-L3-Agile-2759-2014_11-EN. Information contained in this document is indicative only. No representation or warranty is given or should be relied on
that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability
and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. Alstom
contributes to the protection of the environment. This leaflet is printed on environmentally friendly paper.
FUNCTIONAL OVERVIEW

The numbers in the table denote the number of elements or stages available
PROTECTION PRODUCT SOLUTIONS
MICOM ALSTOM P14N, P14D, P94V

INTUITIVE USER INTERFACES CYBER-SECURITY


The front-panel interface (shown in Figure 1) allows direct IED interaction. A USB The sophistication of protection schemes,
front port offers enhanced access by laptop computers. Integrated user function keys coupled with the advancement of
and tri-colour programmable LEDs provide a cost-effective solution for control and technology, increasingly leads to devices
annunciation. Numerous, optional, modern communication protocols, including IEC and substations being interconnected
61850, ensure interfacing to upper-level Supervisory, Control, Automation or Data with open networks, such as the internet
Acquisition systems. or corporate-wide networks. This
introduces a potential security risk
30TE (MiDOS SIZE 6) making the grid vulnerable to cyber-
attack, which could in turn lead to
Slot-in
electrical outage. To secure
user labelling
Additonal communication within such
four tri-colour environments, MiCOM P14N, P14D and
programmable
LEDs
P94V offer NERC-compliant cyber
security.

ASSET LIFE EXTENSION


In addition to new-build, P40 Agile IEDs
can be used to refurbish legacy protection
schemes. As MiCOM P14N and P14D
Function keys
with tri-
are pin-to-pin compatible with KCGG14x
colour status and KCEG14x respectively, they can
LEDs simply be plugged-in to the K relay cases
for an easy upgrade. This draw-out and
substitute strategy dramatically reduces
the refurbishment time and cost.
FIGURE 1 P40 Agile front panel interface
HARDWARE
All models offer:
Space-saving 4U height and 20TE (4)
or 30TE (6) case sizes
ENVIRONMENTAL RESPONSIBILITY A front USB port and a rear RS485 port
The IEDs are manufactured in a lead-free soldering process using lead-free Power-up diagnostics and continuous
components. Power dissipation is the lowest among comparable products, easing self-monitoring
concern on station batteries. Even the product weight (including packaging) has Wide choice of opto-isolated binary
been optimised to lessen the transit carbon footprint. All such actions boost the eco- inputs and output relays
responsibility demonstrated in the Product Environment Profile (PEP). The product N/O (form A) and N/C (form B)
does not require any resident battery. watchdog contacts

The PEP shows claims for raw material depletion, energy depletion, water depletion,
global warming potential, ozone depletion, photochemical ozone creation, air
acidification, and hazardous waste production.

QUALITY BUILT-IN
Quality Built-In methodology is applied throughout the development and
manufacturing of the IEDs. Parts stress analysis in R&D, rigorous component supplier
selection, and a shipping carton compliant with ISTA protection requirements all are
examples of best-practice to maximise long-life reliability. All circuit boards have
harsh environmental coating, to resist moisture, salt, corrosive atmosphere and
industrial ambient pollution as standard. Circuit board production uses in-circuit
tests, boundary scanning, built-in self-test, automated optical inspection, and X-ray
scanning to achieve maximum test coverage.

Figure 2 depicts the software scalability of models, within the overall superset of the
range functionality. The strong P40 family identity offers high customer familiarity,
with minimal training requirements.
FIGURE 2 P40 Agile application scalability
FIGURE 3 Example P40 Agile standard hardware (P14D)

HARDWARE OVERVIEW

*Ethernet models will have 8DI / 8DO


PROTECTION PRODUCT SOLUTIONS
MICOM ALSTOM P14N, P14D, P94V

PROTECTS ASSETS, PROTECTS PERSONNEL, PROTECTS THE PUBLIC, PROTECTS THE ENVIRONMENT
30TE models can accommodate: The profile can be chosen to optimise the
An optional IRIG-B port for time synchronising protection, without constraining the
An additional RS485/K-Bus port feeders loadability. If a standard curve
An optional Ethernet port for IEC 61850 or DNP3.0 protocol is not suitable for the application, the
Optional additional binary I/O: 5 inputs/4 outputs, or 3 inputs/4 outputs user can program and upload a custom
(for H7 TCS schemes) - model dependent variant.

There are two standard earth fault


elements, each with four independent
stages. The first is the EF1 Measured
element which operates from the
quantity flowing directly into the relays
earth (IN) input.

The second standard earth fault element


(EF2) operates from a residual current
that is derived internally by a
mathematical summation of the three
phase currents. The sensitive earth fault
(SEF) order option fits a sensitive CT,
designed for systems whose earth fault
current is constrained. A core balance
CT should be used to drive this SEF CT
input.

FIGURE 4 Example hardware options available in case size 30TE

All CT connections have integral shorting,


when the IED is withdrawn from the
case. This affords additional safety to
personnel who may be working near live
apparatus.

FEEDER PROTECTION
Ethernet, graphical programmable logic
and proven protection, measurement
and control algorithms from Alstoms
modular MiCOM P40 are native in the
new range.

Phase and Earth Fault Overcurrent


Six independent stages are available for
each phase overcurrent element. In
addition to definite time and predefined
IDMT curve selection, P14N and P14D
support user programmable curves for
customised operation and resetting. FIGURE 5 IEC and ANSI/IEEE inverse-time curve profiles
Special applications
Load encroachment (blinder), cold load pick-up logic, second harmonic inrush
blocking, broken conductor protection, RMS thermal overload protection, wattmetric
earth fault, fault locator, auto reclose and check synchronising are built-in.

High Impedance Earth Fault (HIF)


Innovative high impedance earth fault algorithms improve the detection of downed
conductors which have fallen on surfaces with high resistivity (eg. sand, dry
scrubland, trees). This helps the utility to save human lives, protect nearby animals
and lessen the risk of vegetation fires caused by prolonged arcing. Prior to the advent
of HIF, such faults may not have been detectable by conventional earth fault
methods, due to the extremely low and/or sporadic current flow. FIGURE 6 Typical current waveform trace
recorded for a downed conductor
Wattmetric Directional Earthfault (WDE)
An earth fault in an unearthed 3-phase system causes the phase voltage in the other
two phases to increase. This in turn will cause arcing at the fault location. Many
distribution systems use a Peterson coil to compensate, thus eliminating the arcing The wide range of setting options
problem. The introduction of a Peterson coil creates difficulties for determining the permits application of any frequency
direction of the fault. Standard directionalising techniques used by conventional based load shedding or islanding
feeder protection devices are not adequate. Wattmetric Directional Earthfault (WDE) scheme. Four stages of rate of change
is used in this scenario to protect compensated networks. of voltage protection elements are also
available, which offer an alternative
DISTRIBUTED GENERATION PROTECTION approach to implement load-shedding
Voltage controlled and voltage restrained overcurrent schemes.
Voltage-dependent protection boosts sensitivity and reduces tripping times for faults
on weaker systems, such as those with a high prevalence of distributed generation. LOGIC AND CONTROL CAPABILITIES
The timing characteristic can be set as either definite time or IDMT. All aspects of MiCOM P40, and MiCOM
Power P40 Agile IED configuration are
Two stages of power protection are provided and each stage can be independently managed using the MiCOM S1 Agile
configured to operate as over power or under power, forward or reverse directional software.
and active or reactive. Two stages of sensitive power protection are provided and
these can be independently selected as reverse power, over power or low forward
power.
Under / Over voltage
Under/over voltage protection may be configured to operate from either phase-phase
or phase-neutral quantities. Three independent stages with definite time elements are
available; one of the stages can also be configured with an inverse characteristic.

Check synchronising
The check synchronising feature has predictive close control, to ensure that the CB
contacts touch at the instant of synchronism, minimising the stress on plant assets
when parallelling.

TRANSFORMER PROTECTION
P14N and P14D devices offer the required current protection with second harmonic FIGURE 7 MiCOM S1 Agile:
blocking, thermal overload protection and instantaneous restricted earth fault element a powerful and intuitive PC-toolsuite
(REF). REF detects transformer winding earth faults, and may be configured as high
impedance or low impedance biased differential. Negative sequence overcurrent Circuit breaker control
protection can be set non-directional or directional (forward/reverse) and offers Circuit breaker control is available from
detection of remote phase-phase and phase earth faults the front panel user interface, optically
isolated inputs and remotely via the
BUSBAR PROTECTION
Phase fault over current can be applied in a high impedance differential protection substation communications. Three
scheme for busbars, fitted with external stabilising resistors and non-linear resistors function keys are available for direct
(Metrosils). Alternatively, a peer-to-peer hard-wired or Ethernet scheme can achieve actions instigated by users. The F-keys
blocked overcurrent unit protection for busbars. operate in two modes, normal and
toggled, and activate associated signals
LOAD SHEDDING AND RESTORATION in PSL that are used to customise the
Nine stages each of frequency protection are available (except P14N). Each may application or operative mode.
measure in over-, under-, rate of change, frequency supervised rate of change or
average rate of change mode.
PROTECTION PRODUCT SOLUTIONS
MICOM ALSTOM P14N, P14D, P94V

Programmable Scheme Logic (PSL)


Powerful graphical logic allows the user
to customise the protection and control
functions. It is also used to program the
optically isolated inputs, relay outputs
and LEDs. The logic includes OR, AND
and MAJORITY gates, timers, and
set/reset latch functions, with the ability
to invert the inputs and outputs, and
provide feedback. The PSL imposes no
delay on logic throughput, using
concurrent processing being used
instead of sequential equations and
avoiding any logic race issues. FIGURE 8 Programmable Scheme Logic

SUPERVISORY AND CONDITION The internal disturbance recorder has Any of the protocols listed below can be
MONITORING FUNCTIONS up to 9 analogue channels, 32 digital chosen at the time of ordering:
Depending on the hardware base, two channels and 1 time channel. The Courier / K-Bus
stage circuit breaker failure protection, memory capacity is approximately 50 Modbus
CT / VT supervision, circuit breaker records for a typical 0.5 s duration. IEC 60870-5-103
condition monitoring and trip circuit DNP 3.0 (RS485 serial or Ethernet)
supervision are available. The measurements provided, which IEC 61850 (100 Mbit/s Ethernet)
Supervision of the trip circuit in both may be viewed in primary or secondary
circuit breaker open and closed states values, can be accessed via the front IEC 61850 or DNP 3.0 over Ethernet are
can be realised using the optically panel LCD display, or the available when the optional Ethernet
isolated inputs and programmable communications ports. port is ordered in 30TE models. The
scheme logic. Full compliance to the copper physical link option uses RJ45
benchmark H7 supervision scheme is LOCAL AND REMOTE connectors, the fibre option uses LC
available as a hardware option. COMMUNICATIONS connectors. IEC 61850 offers high-
Two communication ports are standard: speed data exchange, peer-to-peer
MEASUREMENTS, RECORDING, a rear port providing remote communication, reporting, disturbance
AND POST-FAULT ANALYSIS communications and a front port for record extraction and time
All events, fault and disturbance records substation staff. The front USB port synchronisation. MiCOM P40 Agile
are time tagged to a resolution of 1ms. allows the programming of settings, offers 32 virtual inputs, and best-in-class
Up to 2048 time-tagged event records configuration of the programmable GOOSE performance.
are stored in the flash memory and can scheme logic, extraction and viewing of An optional second rear Courier port is
be extracted using the communication event, disturbance and fault records, available, designed typically for local
ports or viewed on the front panel viewing of measurements and the engineering workstation access, or for
display. Records of the last 10 faults are instigation of control functions. dial-up modem access when the main
stored in the flash memory. port is reserved for SCADA.

THE INCLUSION OF FUNCTION KEYS, ANCILLARY SUPERVISION AND


TRI-COLOUR LED ANNUNCIATION SAVES CUBICLE SPACE
PROTECTION PRODUCT SOLUTIONS
MICOM ALSTOM P14N, P14D, P94V

For more information


please contact Alstom Grid:

Alstom Grid Worldwide Contact Centre


www.alstom.com/grid/contactcentre/

Phone: +44 (0) 1785 250 070

Visit us online: www.alstom.com


MiCOM P40 Agile: Novel | Draw-out | Versatile
Grid-SAS-L3-Agile-2759-2014_11-EN. Information contained in this document is indicative only. No representation or warranty is given or should be relied on
that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability
and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. Alstom
contributes to the protection of the environment. This leaflet is printed on environmentally friendly paper.