3/03
Report of Inspection, Testing & Maintenance
of Fire Pump Assemblies
ALL QUESTIONS ARE TO BE ANSWERED AND ALL BLANKS TO BE FILLED
(Weekly inspection tasks are NOT included in this report)
Y N/A N Y N/A N
G.7.2 Pump maintenance of peak load performance G.11.2 *Operate emergency manual starting means
verified (without primary power)
G.7.3 Power failure condition removed G.11.3 *Exhaust system tested for excessive back
G.7.4 Pump reconnected to normal power source pressure
after a time delay G.12.0 Pertinent parties notified of test conclusion
G.8.0 Alarm conditions simulated G.13.0 ALARM PANEL CLEAR
G.8.1 Local or remote alarm indicating devices G.14.0 SYSTEM RETURNED TO SERVICE
(visual and audible) observed for operation
G.15.0 COMMENTS:
G.8.2 Legally required safety precautions taken
during inspecting, testing, and maintaining
electric controllers
G.8.3 After water-flow portions of annual testing or
fire protection system activations, suction
screens inspected and cleared of debris
or obstructions
G.8.4 Engine generator sets supplying emergency or Five-Year Items for Fire Pump Assemblies
standby power to fire pump assemblies tested
H.1.0 System in service before conducting tasks
in accordance with NFPA 110
G.8.5 Automatic transfer switches tested in H.2.0 Pertinent parties notified before conducting tasks
accordance with NFPA 110 H.3.0 Check valves internally inspected
G.8.6 Pump room environmental heating equipment H.3.1 Check valve internal components operate
automatic operation verified correctly
G.8.7 Pump room environmental illumination H.3.2 Check valve internal components move freely
equipment manual operation verified H.3.3 Check valve internal components in good
G.8.8 Pump room environmental ventilation condition
equipment automatic operation verified H.3.4 Check valve internal components
G.8.9 Parallel and angular alignment of pump and cleaned/repaired/replaced as necessary
driver checked H.3.5 Check valve internal inspection/maintenance
G.8.10 Parallel and angular misalignment corrected date:
TEST RESULTS AND EVALUATION: H.4.0 Adequate drainage provided before flow testing
G.9.0 Theoretical rated speed correction factors H.4.1 Pressure control valves full flow tested
not applied to determine pump compliance
per testing H.4.2 Supply side static pressure psi
G.9.1 Engine speed not increased beyond pump H.4.3 System side static pressure psi
speed rating at rated condition to achieve
H.4.4 Supply side residual pressure psi
rated pump performance
G.9.2 Fire pump assembly considered acceptable H.4.5 System side residual pressure psi
because test matches initial unadjusted field H.4.6 Results compared to previous full flow test
acceptance test curve
H.4.7 Adjustments made as necessary
G.9.3 Fire pump assembly considered acceptable
because test performance matches H.5.0 Fire pump assembly maintenance performed
performance characteristics on nameplate in accordance with mfg. recommendations
G.9.4 Investigation initiated where degradation in H.6.0 Obstruction investigation conducted
excess of 5 percent of initial acceptance test (required at 5 year intervals regardless of
pressure or nameplate pressure obstruction evidence) (see AFSA Form 114A)
G.9.5 Voltage readings at motor within 5 percent H.7.0 Pertinent parties notified after conclusion of tasks
below or 10 percent above rated voltage H.8.0 ALARM PANEL CLEAR
G.9.6 Abnormalities observed during inspection, H.9.0 SYSTEM RETURNED TO SERVICE
testing, and maintenance promptly reported
to responsible party H.10.0 COMMENTS:
G.10.0 Circulation relief valve verified to close in
accordance with mfg. spec.
G.11.0 Fire pump assembly maintenance performed
in accordance with mfg. recommendations
G.11.1 *Circuit breaker tripped (if provided)
Signature and Title of Person Making Test Company Name & Address
150%
Volts Lead#1 Lead #2 Lead #3 Amps Lead #1 Lead #2 Lead #3
Address:
Churn
City/State/Zip 100%
150%
DATE _______________
Page 6 of 6
(AFSA Form 110A)