WORK REPORT
TAG #
LOCATION
WORK SUMMARY.
1.Take the MPCB from work shop and tested at two times of 1.3 amps. It was ok and trip time 98.42 sec. Motor
FLC is 1.3 A at 400 Volt.
2.New MPCB details. Type: 3RV1021/1AA15, Range 1.1 to 1.6 Amps.
3.Measure the IR value of motor UVW/E = 278 M Ohms and WR 25.9 Ohms balanced.
4.After normalized power start the unit and measure the motor current as U = 1.5A, V = 1.47A, W = 1.45A.
5.After discussion with supervisor, change the relay setting from 1.3 Amps to 1.5 Amps. Motor working normal.
6.Old MPCB details: Type: 3RV1011-1AA10, Range: 1.1 1.6 Amps.
PERFORMER ENGINEER
WORK STARTED WORK COMPLETED
NAME: