WO# 952236

WORK REPORT
TAG #

LOCATION
WORK SUMMARY.

REPLACED MPCB (MOTOR PROTECTION CIRCUIT BREAKER) fan

1.Take the MPCB from work shop and tested at two times of 1.3 amps. It was ok and trip time 98.42 sec. Motor
FLC is 1.3 A at 400 Volt.
2.New MPCB details. Type: 3RV1021/1AA15, Range 1.1 to 1.6 Amps.
3.Measure the IR value of motor UVW/E = 278 M Ohms and WR 25.9 Ohms balanced.
4.After normalized power start the unit and measure the motor current as U = 1.5A, V = 1.47A, W = 1.45A.
5.After discussion with supervisor, change the relay setting from 1.3 Amps to 1.5 Amps. Motor working normal.
6.Old MPCB details: Type: 3RV1011-1AA10, Range: 1.1 1.6 Amps.

PERFORMER ENGINEER
WORK STARTED WORK COMPLETED
NAME:

11/08/2017 11/08/2017 SIG : SIG :