You are on page 1of 1
5250-11AuF utes Harbour page 9 FM 200 sizing calculation Room to be protected T = 20°C room temperature (6% required design concentration) Room description Name: — FEC Telco Room Floor: Lower ground Gridine) GL4.5-C Room dimensions ~ Length: 65]m width: 3.8)m Height: 35]m Design calculations ‘The required agent quantity is based on the volume of protected area at the lowest expected ambient temperature and concentration required. To obtain the minimum agent quantity required, the following equation is used: W= (VIS) x (C/100 - C) where, W = weight of agent required V= volume of protected area S = specific vapour volume $= 0.1269 + 0.000513 x T C= Requited HFC-227ea Design concentration (% by volume) at design temperature (7) T = Design temperature in protected area (°C) W= volume x total flooding factor w volume x 0.6335 W Y ‘Weight used: 86 kg Cylinder sizes commonly available in the market b ¥g 10 45 20 9 40 18 70 an 125 56 200 90 0* 350 158 600 272V 900 408