5250-11AuF utes Harbour page 9
FM 200 sizing calculation
Room to be protected
T = 20°C room temperature
(6% required design concentration)
Room description
Name: — FEC Telco Room
Floor: Lower ground
Gridine) GL4.5-C
Room dimensions ~
Length: 65]m
width: 3.8)m
Height: 35]m
Design calculations
‘The required agent quantity is based on the volume of protected area at the
lowest expected ambient temperature and concentration required. To obtain the
minimum agent quantity required, the following equation is used:
W= (VIS) x (C/100 - C)
where,
W = weight of agent required
V= volume of protected area
S = specific vapour volume
$= 0.1269 + 0.000513 x T
C= Requited HFC-227ea Design concentration (% by volume) at design temperature (7)
T = Design temperature in protected area (°C)
W= volume x total flooding factor
w volume x 0.6335
W Y
‘Weight used: 86 kg
Cylinder sizes commonly available in the market
b ¥g
10 45
20 9
40 18
70 an
125 56
200 90 0*
350 158
600 272V
900 408