You are on page 1of 39

FIRE SAFETY REQUIREMENTS

FOR PERSONS WITH


DISABILITIES
Fire Code Seminar 2013
By
Goh Siam Imm (Ms)
Building and Construciton Authority
Member of Fire Code Review Committee
6 March 2013
Implementation
Fire Safety Requirements for Persons with
Disabilities
Released by SCDF in Jan 2011
Implemented on 1 Nov 2011
Amendment (8 Jan 2013)
Appendix 20 item 7 - Means to Alert the Hearing
Impaired
Take effect on 15 July 2013
To be read with Requirements on Using lifts for
evacuation of building occupants during
emergency
Implementation
Fire Safety Requirements for Persons with
Disabilities

Not Applicable for


Purpose group I and II (residential
development)
Non-residential standalone buildings intended
as ancillary use within the residential
development, eg. carpark buildings and
clubhouses
Health Care Occupancy (eg. Hospitals, Nursing
Home etc.)
Scope of the Guidelines
Fire Safety Requirements for Persons with
Disabilities covers
Essential fire Safety provisions to
facilitates the evacuation of PWDs during
the fire emergencies
Escape Route
Holding point for Person with Disabililites (PWD)
Evacuation lift
Communication
Planning strategies to manage the
evacuation of PWDS
Persons with Disabilities
Persons with Disabilities (PWD) are
persons whose mobility and use of a building
are affected as a consequence of one or
more of the following physical or sensory
disabilities or impairments:
(a) Ambulant disabled
(b) Wheel-bound
(c) Hearing impairment or deafness
(d) Visual impairment or blindness
Emergency

Building Owner

Evacuation Persons With Disabilities


Concept
PWD Holding Point

Evacuation lift

Place of Safety
PWD Holding Point
A temporarily safe space for PWDs to await
assistance for their evacuation

To be provided on all storeys including


basement level (except for first storey or storey
at grade level)

At least 2 PWD Holding Points for every storey


except for building with a single exit staircase
PWD Holding Point

PWD Holding PWD Holding


Point Point
At least two designated PWD Holding Points for
every storey of building except for building designed
with single exit staircase
PWD Holding Point

PWD Holding Point

Single PWD Holding Point for building designed with


single exit staircase allowed under:
Cl.2.6.1 Office, shop, factory & warehouse not exceeding
15m in habitable height and not exceeding 4 storeys
PWD Holding Point
Safe waiting areas for
short period of time
Enclosed with fire-
resisting construction
and served directly by a
safe route to a storey
exit, evacuation lift or
final exit
PWD Holding Point
Located within fire
fighting lobby,
smoke stop lobby
or external corridor

Free of obstruction
Located away from
Point of occupant
egress
PWD Holding Point

Min 2000mm

PWD Holding Point designated in an external corridor


shall be positioned at least 2000mm away from the
edge of exit staircase
PWD Holding Point

Min
500mm

PWD Holding Point within fire fighting lobby and


smoke stop lobby
shall be positioned at least 500mm away from
the edge of exit staircase and from the
occupant escape path
PWD Holding Point
PWD Holding Point
inside exit staircase
Only permitted for
buildings not more
than 4 storeys above
ground or without lift PWD Holding Point

provision

The PWD Holding Point shall not obstruct or


disrupt the escape flow within the staircase
PWD Holding Point
Wheelchair space of at least
900mm X 1400mm to allow
manoeuvring of wheelchair
PWD Holding Point,
Dotted rectangle marking
and symbol of access for
PWD on the floor
Mandatory sign PWD
Holding Point-Keep
Clear prominently
displayed
Escape Route
The corridor serving as escape route
shall have a minimum width of
1200mm

Rationale
In line with the minimum clear width or
1.2 m specified in the Code on
accessibility in the Built Environment
The width would facilitate wheelchair
bound person to manouevre and to gain
access to the nearest PWD Holding
Point
Escape Route

Corridor width at least 1200mm

The corridor serving as escape route shall have a


minimum width of 1200mm
Minimum 1.2m
Escape Route
The requirement for travel distance similar
to that stipulated in the Fire Code (see Table
2.2A in the Fire Code).
Evacuation Lift
Evacuation Lift
A lift provided for the evacuation of PWD
during emergencies assisted by
authorized personnel.
Located within a protected lobby such
as smoke stop lobby, external exit
passageway or external corridor.
Installed in accordance with SS 550
Code of Practice for Installation,
Operation and Maintenance of Electric
Passenger and Goods Lifts
Evacuation Lift
Evacuation Lift designated to facilitate
evacuation for PWDs
Fire lift shall not be designated as
evacuation lift unless there is more than 1
fire lift provided in the building
Fire lift intended to provide a vertical means of
access for fire fighting and rescue operation
Evacuation Lift

At least one of the lifts shall be designated as


Evacuation Lift
Readily visible sign marked Evacuation Lift for
PWDs affixed onto the wall adjacent to the lift door at
every landing of the evacuation lift
Evacuation Lift
Evacuation Lift
Clear platform size of
minimum 1200mm
width X 1400 mm
Min 11200
2 0 0 m in
mm

0
15
ax

1 4 0 0 m mm
m

Min 1400 in
Evacuation Lift
Evacuation Lift
Switching device
installed next to each
evacuation lift landing
door on the designated
floor.
housed in a breakable
glass-fronted cover box
marked evacuation
switch.
Evacuation Lift
Provided with standby power supply
For continuous operation during power failure
and/or fire emergencies (routing of cables for
evacuation lift similar to fire lift)

Lift shall
Be brought to the
designated floor
Park there with its doors
closed, after discharging
all the passengers
Other provision in lieu of lift
Ramps can serve as alternative means of
escape
Internal and external exit ramps
comply with current Fire Code
cl.2.3.3 (Exit staircase) & cl.2.3.8 (exit
ramp gradient)
Ramp designs conform to
requirements spelled out in Code on
Accessibility in the Built Environment
Management of Evacuation
Evacuation procedures have to be pre-planned by
the building owner/facilities manager
Management of Evacuation
The building owner
must plan, identify and make arrangements
for assistance during emergency
keep the following information :
Number of PWDS
Location of the PWDs
Nature of their disabilities
PWD Holding point in which they are allocated.
Management of Evacuation

Staff designated to
help PWD are to be
fully trained to execute
the evacuation
procedures

Horizontal and vertical


evacuation
procedures to be
tested at least once a
year.
Building with Evacuation Lift
Alarm activation
PWDs move or directed to the PWD Holding
Point in the evacuation lift lobby

Trained staff pick


up PWDs from
designated PWD
Holding point and
direct them to the
final exit
Building without Evacuation Lift
Alarm Activation
PWD move or directed to the PWD Holding
Point inside exit staircase
Trained staff continue
their search
procedure
Completed search
procedure and assist
PWD Holding Point the PWD down the
stair to the final exit.
Suitable means of communication
To be provided between the PWD holding point
and Fire Command Centre (FCC) or any 24-
hourly manned station
In the form of a distress button or voice
communication
Located between 800mm and 1200mm above
ground level
Appropriately labeled
Prominently displayed clear instruction sign on its
operation; and
Shall generate a clear visual indication to indicate
that the distress signal has been relayed, when the
device for communication is activated.
Visual Alarm System
To alert persons with hearing impairment
Location of visual alarm
In isolation spaces
Toilet cubicles, car park and lift lobbies.
Designated bedroom in buildings with stay-
in facilities such as hotel, service
apartments, hostels, dormitories
At least 10% of the guestrooms or
accommodation units shall be provided
with visual alarm
Visual Alarm System
Visual alarm devices can take the
form of flashing beacon or strobe
light for use in conjunction with
conventional fire alarm system

Visual indicator to be
provided where alarm
bells are located.
Visual Alarm System
Visual Alarm signal Visual Alarm Devices
Sufficient in number and
distribution to be visible from all
accessible locations
Visual indicator shall be mounted
at appropriate height such that it
is visible from all corners of the
floor
Visual alarm indicating device
shall be labelled with the word
Intensity of light signal should be
Fire and is legible from the
normal standing position
sufficient to draw the attention of
people in the vicinity Flashing or strobe lights of visual
alarm system shall be
Flash at a rate within the range
synchronized with the flash rate
of 30 to 130 flashes per minute
of such multiple fixture
Appreciation
The following Associations have been invited to
comment on the PWD Fire Safety Guidelines:
Handicaps Welfare Association (HWA)
The Society For The Physically Disabled (SPD)
Singapore Association Of The Visually
Handicapped (SAVH)
Singapore Association For The Deaf (SADeaf)
Disabled Peoples Association of Singapore
Thank you

You might also like