GENERAL INFORMATION
The Chemetron Fire Systems MMX-101 Monitor
Module provides an interface between the Micro
200-I, 300-I, or 400-I Control Panel and the normally
open contact alarm initiating devices. While the
MMX-101 can be used to monitor an entire Style B
(Class B) initiating circuit, it is ideally suited for
monitoring single devices. The MMX-101 is small
enough to fit inside a single gang junction box
behind the device being monitored. The small size
and light weight allow it to be installed without the
need to be rigidly mounted.
FEATURES
P Built-in type identification automatically identi-
fies the device as a monitor module to the con-
trol panel.
P Powered directly by a 2-wire Micro 200-I, 300-I
or 400-I SLC loop. No additional power required. APPLICATIONS
P High noise immunity (EMF/RFI).
P Tinned, stripped leads provide ease of wiring. Use to monitor a single device or a zone of 4-wire
P Direct dial entry of DECADE address (01-99). smoke detectors, manual fire alarm pull stations,
waterflow devices, or other normally open dry-
CONSTRUCTION contact devices. May also be used to monitor nor-
mally open supervisory devices with special super-
visory indication at the control panel. Monitored
Controls include two rotary switches for Direct Dial circuit/device is wired as an NFPA Style B (Class B)
entry of DECADE Address (01-99). Initiating Device Circuit. A 47 K-ohm end-of-line
resistor (provided) terminates the circuit.
OPERATION
PRODUCT LINE INFORMATION
Each MMX-101 uses one of 99 available module
addresses on a Micro 200-I, 300-I, or 400-I SLC
MODEL DESCRIPTION
loop. It responds to regular polls from the control
panel and reports its type and the status (open/ MMX-101 . . Monitor Module.
normal/short) of its Initiating Device Circuit (IDC).
70100740 . . Surface mount backbox.
1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
MMX/101- 30198
1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
MMX/101- 30198
SPECIFICATIONS
Operating Voltage: 15 28 volts DC (Peak)
Standby Current: 230 FA maximum plus
supervisory current
Temperature Range: 0E to 49EC (32E to 120EF)
Humidity Range: 10% 95% Relative
Weight: 3.0 oz. (90 g)
Ordering Information
Shipping Weight
Stock Number Description lbs (kg)
70100724 MMX-101 Miniature Monitor Module .6 (.27)
70100740 Surface Mount Backbox .6 (.27)