GENERAL INFORMATION
The Chemetron Fire Systems MMX-101 Monitor
Module provides an interface between the Micro
200-I, 300-I, or 400-I Control Panel and the normally
open contact alarm initiating devices. While the
MMX-101 can be used to monitor an entire Style B
(Class B) initiating circuit, it is ideally suited for
monitoring single devices. The MMX-101 is small
enough to fit inside a single gang junction box
behind the device being monitored. The small size
and light weight allow it to be installed without the
need to be rigidly mounted.

FEATURES
P Built-in type identification automatically identi-
fies the device as a monitor module to the con-
trol panel.
P Powered directly by a 2-wire Micro 200-I, 300-I
or 400-I SLC loop. No additional power required. APPLICATIONS
P High noise immunity (EMF/RFI).
P Tinned, stripped leads provide ease of wiring. Use to monitor a single device or a zone of 4-wire
P Direct dial entry of DECADE address (01-99). smoke detectors, manual fire alarm pull stations,
waterflow devices, or other normally open dry-
CONSTRUCTION contact devices. May also be used to monitor nor-
mally open supervisory devices with special super-
visory indication at the control panel. Monitored
Controls include two rotary switches for Direct Dial circuit/device is wired as an NFPA Style B (Class B)
entry of DECADE Address (01-99). Initiating Device Circuit. A 47 K-ohm end-of-line
resistor (provided) terminates the circuit.
OPERATION
PRODUCT LINE INFORMATION
Each MMX-101 uses one of 99 available module
addresses on a Micro 200-I, 300-I, or 400-I SLC
MODEL DESCRIPTION
loop. It responds to regular polls from the control
panel and reports its type and the status (open/ MMX-101 . . Monitor Module.
normal/short) of its Initiating Device Circuit (IDC).
70100740 . . Surface mount backbox.

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
MMX/101- 30198

MMX-101 Monitor Module

ARCHITECTURAL/ENGINEERING contact device, including 4-wire smoke detectors), to


one of the Fire Alarm Control Panel Signalling Line
SPECIFICATIONS Circuit (SLC) Loops. The monitor module shall be
small enough to fit inside a single gang junction box
behind the device being monitored or directly into the
Monitor modules shall be provided to connect one
Fire Alarm Control Panel. The monitor module shall be
supervised Initiating Device Circuit (IDC) zone of
small enough in size and light enough in weight to
conventional alarm initiating devices (any N.O. dry-
allow it to be installed without the need to be rigidly

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
MMX/101- 30198

mounted. The IDC zone may be wired for Style B


operation. The monitor module shall provide address-
INSTALLATION
setting means using rotary decimal switches and shall
also store an internal identifying code that the Fire The MMX-101 Monitor Module mounts inside a single
Alarm Control Panel shall use to identify the type of gang junction box behind the device being monitored.
device. The small size and light weight allow it to be installed
without the need to be rigidly mounted. Alternately,
the MMX-101 Monitor Module may be mounted to the
surface mount backbox, Part No. 70100740. Mounting
hardware and installation instructions are provided
with each module.

SPECIFICATIONS
Operating Voltage: 15 28 volts DC (Peak)
Standby Current: 230 FA maximum plus
supervisory current
Temperature Range: 0E to 49EC (32E to 120EF)
Humidity Range: 10% 95% Relative
Weight: 3.0 oz. (90 g)

Ordering Information

Shipping Weight
Stock Number Description lbs (kg)
70100724 MMX-101 Miniature Monitor Module .6 (.27)
70100740 Surface Mount Backbox .6 (.27)

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847

You might also like