Water Demand Final
Water Demand Final
The mean demand 177.5 gpm (mean demand = peak demand / peak factor )
Overhead tank size 5325 gallon ( Overhead tank size = (peak demand - mean demand) x duration }
20.13 m3
Transfer pump capacity 177.5 gpm ( Transfer pump capacity = mean demand , Assuming one pump
40.29 m3/h running & one standby)
11.19 l/s
ASHRAE Handbook
for Hot Water Gal/Hr @ 140F Final Temperature
Requirement. Apartment Industrial office private Fixture
club gym Hospital Hotel school YMCA gal/hr
house Plant building residence Qty
Wash basin-private 2 2 2 2 2 2 2 2 2 2 23 46
Wash basin-public 4 6 8 6 8 12 6 15 8 0
bath tub 20 20 30 20 20 20 30 0
Dish Washer 15 50-150 50-150 50-200 20-100 15 20-100 20-100 0
foot basin(bidet) 3 3 12 3 3 12 3 3 12 8 24
kitchen sink 10 20 20 30 20 20 10 20 20 3 30
Laundry 20 28 28 28 20 28 0
pantry sink 5 10 10 10 10 5 10 10 0
shower 30 150 225 75 75 225 30 30 225 225 14 420
service sink 20 20 20 30 20 20 15 20 20 3 45
hydrotherapeutic shower 400 0
hubbard bath 600 0
leg bath 100 0
arm bath 35 0
sitz bath 30 0
fcontinous flow bath 165 0
circular wash sink 20 20 30 20 30 0
semi circular wash sink 10 10 15 10 15
565 G/Hr
Demand Factor 0.3 0.3 0.4 0.25 0.25 0.4 0.3 0.3 0.4 0.4 169.5
Storage Factor 1.25 0.9 1 0.6 0.8 1 2 0.7 1 1 118.65 Gal
Calorifier capacity 444.9375 Litres 1D+1S
Domestic Chiller Capacity
Temp in 43 C
Temp out 25 C
Temp Diff 18 C