VT Tutorials
VT Tutorials

Power System
Protection
S.A.Soman

Problem 1

Problem 2

1 Problem 1

2 Problem 2
VT Tutorials

Power System
Protection Problem 1
S.A.Soman Design a CCVT for a 132kV transmissiion line using the
Problem 1
following data. Resistive burden (3)=150VA, frequency
Problem 2
deviation to be subjected to, f = 3Hz, phase angle error
= 40minutes. Consider four choices of V2 as 33kV, 11kV,
6.6kV and 3.3kV. Transmission line voltage V = 132kV. The
standardized VT secondary voltage is 110 volts(L-L).
VT Tutorials

Power System
Protection
S.A.Soman
Problem 2
Problem 1 The equivalent circuit of a CCVT is shown in figure. The
Problem 2
values of C1 and C2 are 0.0018F and 0.0186F
respectively. Tuning inductor has an inductance of 497H
and a resistance of 4620. Xm of the VT referred to 6.6kV
side is 1M, core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current
drawn by Xm is equal to 3.183 109 F.
(a) Verify the appropriateness of choice of L and Cm .
(b) Find out the nominal value of V /V2 .
(c) If the frequency drops from 50Hz to 47Hz, what would be
the values of ratio error and phase angle error?