You are on page 1of 1

Space Design Load Summary for CORRIDOR 4a

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CORRIDOR 4a '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.2 C / 29.8 C HEATING OA DB / WB 12.0 C / 10.0 C
OCCUPIED T-STAT 21.0 C OCCUPIED T-STAT 20.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 313 m 4164 - 313 m 2538 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 211 m 5253 - 211 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 11738 W 8216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 52 4512 6954 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 8% / 5% 1772 348 0% 0 0
>> Total Zone Loads - 23916 7302 - 2538 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CORRIDOR 4a '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 313 1.014 - 4164 - 2538

Hourly Analysis Program v4.50 Page 1 of 1

You might also like