Comments
Load report conatin comparision , please remove comparision as
ADA/RMTC is not interested in comparision. It may be your internal
discussion. Only put some note in analysis part to justify difference.
explain why the support in fixed in all direction with bending stiffness in Z
direction !
How do you control temparature effect of structure if it is fixed all around,
why to stress the structure when we can relive temparature stress by
allowing movement.
pl provide expansion joint in the canopy
Provide detailed load calculations , not provided in current package
provide a list of assumptions and deviation for your design.
please enhance your wind load for 100 years period for 100 years design
life.
Please provide design criteria report for ICE review
Please provide ref of lateral deflction limit
Ref Item 2, review the displcement limits adopted. It should be limited to
L/240 as per ER
your support condition and general structural concept dont match and
contracdictory ( ref item 3.1 and 3.3) . Please explain !!
Please provide a overall diagram to understand better with respect to actual
structure.
Need to verify with NFPA ICE for fre issues
Provided joint is hinged in one direction , verify with your design
methodology
Provided joint is hinged in one direction , verify with your design
methodology
Plesse rovide connection design and details all members
ref section AA, how you are catering local ecentricity in connection in your
design and analyisi. Explain
deflection limitation for faade to check with design and ensure it does not
affect faade