TESTING PROCEDURE FOR MICOM P64x/P63x TRANSFORMER PROTECTION ‘This tet procedure should be carted autby welltrained 2e'son. Individual furcton onlys considered for testing purposesand stable seting can be adonted and tested tis not necessary to test the relay atalleetting and ene cetting enough ar confirming lay operation. Sie Micom 64x, 62x16 numerical relays, scheme operation check ard load checkshould becarried out according te the manual Note: Test resutsare mageacording torelay settings provided atsie. tial Protection Testing Procedure: tha the various cures or apes of di Use Omicron Test. Set phase angle of Primary winding to 220! 1208 Set phase angle of Secondary winding 180% 60f and 69° 1 Thisistoaccount 186° phase shiftfor adjusting the current Fw of secondary into the rela. Keep the laa, ip bsettings in ‘Function Farameter~ Global Main ~to Standard. 4% Relay tobe sets: mi -03,m2~0,7, (diff -0.3and |, m2-1.5 > Testing involves verlication ofthe tripping characteristic which ha three part (Gen atove). > Thefist partis the dferental pick-up, which is tested as described earlier. Festa ofthe characteristic is verified as flows: 2 trctease the injected currents stowyfrom zero in Primary terminals keeping constant zero current in secondary. Find pict-up, twil beon 0.105(FLC"0.3) and read the dsplayed vale In the relay, Itillcead | dif -0.8| ref and |rest-0.45 [ret (Halfofthel it) Second part ofthe relay cure: > Make injeted curentsin Primary and Secondary FLC Amps respectively Reduce the seeotdary injected curtentslewly. Find pickup it wile on 0.43 and read the dsplayed value ‘nthe relay. It will ead diff -0.48 ref and | ret -0.751 re (Approx) Theoretical vale ofthe Iiffis calculated os fllows: Formule: eff = mt | rest ¢mi (-0.5'm3) aif = 0390.75 +0.3(140.5%0.3) .48- Which verifies the elay displayed value of lift. ‘Noted medel graph on second part curve trip: ‘Third part of the relay curve: > Make inpcted currentsin Primary and Secondary 2times that of FIC Amps Retuce the secordaryinlecedcurtent slow. Find pickup, itwillbe on 1 Ampsand read the value ‘dsplayed inthe ely. twill read as, | diff -0.81 ref and rest 1.6 |ref (Aporox.) Theoretical value of the ifs calculated as follows: Formula: {tt = m2 *| rest +4 if *(2-0.5¢mi) + m2 * (mt m2} la=0.7* 16r03" (1-05°03)7 15" (03-07) = 0.8- Which verifies he relay displayed valueof dif. "Noted model graph on second part curve trie: ‘SAMPLE TEST REPORT FOR OVFFERENTIAL: crozras, Winding pane [NEUTRAL CT AATIO-HV.CF- NAS) so = CTRATIO-LW.ET2 (ima) Nota = erRATO-Lu.CT3 [Amps] 100005 41. Metering check: Injected Current (A) Measured Current (Al Winding @Secondary side value interms of primary value R Y a tN R y 8 N AVC T from 1 1 1 60s | 60.9 | 602 Measurement-1 WC from 1 1 a | - | 603 | 609 | 2 Measurement-1 | WCIs. from 5 5 5 | - | so.0uK | 10.06 | 10.06% Measuroment-1 INJECTED VOLTAGE;Volts) ppt ‘Measured voltage Vx(KV) VOLTAGE'R,¥) 6asv n0.1v Note- HV-CT-11o be HY windingingut ‘TRAFO DETAILS iva sagomva ‘Adosted Voltage :2291/11.5Kv Vector arp nda Match Factor,¢T £1,609 (HVside) Match Factor, 12 :1.609 (IV-1 side) Match Factor,¢T3—:1.346 (WV side) APH 2PH cK UP TEST: 3H = Actual 1 PH actual pk wire | way | eon) rica | fa Y | 8 m8 sine 1 | ow | ax | oss ans wise 3 | tae | aan | ze a8 Was s | 1a [aa | uae a TRPPING TMETEST: ‘Winding Iref(A) wae i wa spe 5 We sb 5 ‘iranevTAL PROTECTION sevnnes a 200-3 PU Trans ot Enabled sethode ‘vance i 1000 PU a 30.00% 2 an x ores oe istst 400 Pu 52 Status Enabled Zerosea tH Eabed ists 200 Pu daroseq Ly Disabled dndham Hocked ——txabed ina > ‘00% CsatandNocae sated Cros boeing Dated Sthham ded Exabed ines > 35.00% Cia Fal sable Figure? Treping charecteiatc of iferental protection + Gemma ay eter cont eo = a WK) =a, (tH ae a2) ep = #162 2 a, a = 2) SLOPE CHARACTERISTICS STABILIY: ‘CHECKING STABLE CONDITION ATFULL LOAD CURRENT: Fullload Current AtHY side: 372,8A Frimary 0.6224 Secondary Fullload Curent at LV sie: 7229.6 Primary 3.715 ASeconday Fullload Current at LV sie: 7229.6 Primary 3.735 ASacondary LLOUTZONE FAULT @ 1 TIMES FIC 2, INZONE FAULT @ 1 TIMES FLC 3. QUTZONE FAULT @ 2°TIMES Fic 4: INZONE FAULT @ 2°TIMES FIC STABILITY CHECKS: foe Injected current (A) Expeciedvalues | Measured Vites | oy, | Tine vsibe WSOF | dau | iRpU | idou | pu (Ses) asmuo | a7i5.2x7 | ac00 | 200 | 00s | 100 | Sabie 1 [Tem var[smscar | oco0 [20 [aoe [soe] | no.mp | omaao | snscsar | coo | 100 | 0008 | 100 | rerun aeaio | amsiar | 20 | 10 | 2007 | 1009 | Unstable 2 [fomano [ansiam | 20 | 10 | 20 | aon | mm? |e | osm.en0" | anscaso | 20 | 10 | 2007 | 1005 | regen imc" | 7aczie | cos | 20 | e019 | 2001 | suble ». [acne [ase | oon | 20 | ona | 200]? | no-ip ramon | 7asasr | aces | 20 | 001i | 2008 | regun uaaco | 749137 | 400 | 20 | 402 | 2008 | Unstbe «. [awecaa [pacar | sao [a0 [aon | am | mm? |e __ [Rawccaze | aacase | a00 | 20 | «02 | 2008 | region ety found stable for though faultat1* times fll badcurrent Reley found Unstablefor inzone fault at 1* times full oad current. Relzy found stable for through faultat2* times full adcurrent Relzy found Unstablefor inzone fault at 2* times full load current \VERIFYING SLOPE CHARECTERSTICS ‘SLOPE mi and m2 VERIFICATION: aN Injected current (A) Expected values | Measured Values a *N stope svavus | (B05 HV SIDE Wwside | idPU | iRPU | idPU | IRPU cassia” | 2ooc20 | 02 | oss | 0199 | 068 | yictanle ; inmt | Tap 1 | mi | oassie-no | 200.97 | 02 | 0038 | 0199 | oo | Smt | Ie, oasri+i20" | 2o0casr | 02 | o«se | 0.199 | ose | rie | ossive roam [a0 | 09s | 0287 | 0955 |unsunie : im | top 2) om | osteam | ao.sr | 29 | oss | oe | oss | 2m | [Ob ossiiee | soca | a29 | 09s | 0287 | 0956 | “ser aano | raacaoe | aaa | 2005 | 1425 | 2925 | yctanie inme | Tip a) om | ames | sas | a1 | aso | see | 29m | 9 | OE zavvi | rasa | 1a: | 2905 | 1aza | 2am | ‘een sara | anova | 274 | 40s | 2758 | 406 | yissabie : nm | Tip 4) mz | ax75uam | rors | 27 | aos | 255 | aor | 2m? | Te amsiene | anova | 274 | 405 | 2055 | 406 | reeion Note - Whete testing carved out inital to check stability current, after that HV current increase unt felay operates with respect to LV side current HARMONICS BLOCK: SAE ‘OPERATE VALUE ‘Operated TinelSec) STATUS = FAULT ATS0 Hz TRIPPED = Figo. AT 100 TRIPPED. = TFigia>0.2 AT 100 He BLOCKED = “FAULT AT SO Hz TRIPPED = ifisacoasar250He TRIPPED = Tiis/a>0asar250He BLOCKED where 2 Harmonies Frequency (10082) & fundamental normal frequency (S0Hs according to standard) are sipprossodat HV winding co fer testing purpose V/FTest 98: v/HeTip | V/HeSet | V/HeDelay | Treset v/Mesage | v/iaStates aes _| a Fue w/t) (ee) (See) ‘VWyazAlaim | Enabled oF 251 7600 = Viie>t Enabled or 2330 10.00 Via Enabled or 2.840 ‘e000 Wiiz>3 nabled oF 2.60 300. Vio Enabled of 3.08 1.00 ‘Alarm Check Pekupy/fkaio—— SC sac Time [Alar Operating TimeSech 23H Tose 12005 ‘TRIPPING TME TEST ‘Sage Tnjecied /F Rat ‘AciualOperating | Remar Timeisee) Saget 220% 22.48 or Stage ait 175.35 ot ‘Staged 2a $5.06 ‘ol 261 4.085 ‘oh 3 as [ok ‘Checking LED's Output Relays (As per drawing which sass ned in PSL configuration) ‘etal | Sorected runction | txpected Relays | Opented | "PRCT Osersead te | Status Leo's elay's DitaTrip | nipaznisne | ainizargra | Le02 te: | veritedok pi eTrip | RiRizAiaRs | aifizargra | Ue02 toa | Veriiedok purctrip | Ripisnis.Ae | ninisarera | Le03 tos | veritedon weve: ] 1234 | mipiaaieas | myersarges | ow tos — | Veriiedox TAP Wos | napss.ets.as | na,fizar4re | E05 us — | Veriiedok srawmusy | FARIA RIBAS eos | verieaor | PROTRP(2) | RIAI3,RI6,R9 | ma,fi3AreRG | LEDS tvs | vermesox oritap(isy | aiaizriaer | eieizaige7 | 1607 up? Verified ok sroTmp(a) | RIAIRIRs | ALAIZAIgRE | LEDS Los Verified ok BUCH THIPLS) | 1A23,R14,RIO | RI,RI3AI4,RI0 | FoKey-2 | Frey | YeriNedok ‘rant Fre(t6) mas ns Fikey-2 | Frkey2 | Yeritedok ‘964x oPTD : Faker? Frey | Veritedok TBIXoPTD a - Frkevt | Frkey-t | Verinedok 30 PTD oe: Fakes Frey | YVeritedok Bie Tan Temp Vary Fokey-6 | Frey | Verifedok [wien | Spare ~ Faker? | Frkey7 | Yerifeok Spare - Fokey-® Frey | VerinedOk Spare ~ Frkevs | Frkey9 | Yeritedok Reset ee = Frkey-10 | Friey10 | VeriiedOk TeSTRESULT: FUNCTION ‘STATUS OF CHECKING weir ‘MEASUREMENT CHECKS Dyes |Owa FOUND OK PROTECTION FUNCTION CHEEKS Dyes [OWA FOUND OK Dc LoGie Dyes |ON/a FOUND OK ‘OUTPUT RELAY CHECKS Dyes (Ona FOUND OK BREAKER TRIPPING CHECES Dyes |Qwa FOUND OK ‘OPTO INPUT CHECKS Dyes |Dwa FOUND OK DISTURBANCE RECORDER TRIGGER Dyes [OWA FOUND OK FAUIT RECORDER Dye [Qwa FOUND O¢ EVENT RECORDER Dyes [Qwa FOUND O« {eb CHECK Dyes (Qwa FOUND Ox "ANNUNCIATION CHECK ‘WATCH 0% RELAY CHECK ‘COMMUNICATION FRONT SAMPLESETTING WITH TESTREPORT: Rated Inputeurrent: 3/5 4 2 SIDE REFHVSIDE) fay setting ‘Parameters Function parameters/Parameter subset /REF_A REI Enable Pst-ves REELI Operatingmede PS1-high impedance era its 1.00 iret REET ifs» Blocked REED mt 20 RELA m2 0 RELL IRm2 Dire! J [iis [Measured OperaingVaue amp] | Gaimea vane [No_| setting | ______ | tame) (02 let | Taio aliatod asta (03 et | Tobe akslated 0.285 0 0.335, (05 rt | Tobe cakslated 0.475 10 0.595. (OF et | Tobe caleslated 0.665 0 0.735 LD lef | Tobe cakulated 0.35 101.05 SIDE REF(LVSIDE) fey Setting ‘/Parameters/Funeton parametes/Parameter subset REF_2 REE2 Enable st Yes REE? Operating mode PS1~ High impedance REE 2 itp S1- 0.20 ref REE2 laifb>> S1- Blocked FEE2 omit 1-020 fen2 m2 rst 150 Fer? hme 51- 1.001eF T]Tais | Measured Operating Vaue Amal] Caimed Vahe No_| Setting (amp) (02 let | Tobe cakslated ‘a18t0021 (03 lef | Tobe caleslated 0.285 6 0.315, (05 let | Tobe cakslated 0.475 to 0.525, 07 leet | Tobe caleslated 0.665 t0 0.735, [inet [Tobe caleslated f098to105 TOC FUNCTION TEST: Procedure: Input energizing quantity current) is increased slowly atl relay contact operates SAMPLESETTING WITH TESTREPORT: Rated Inputeurrent: 3/5 A Relay seine /Parameters/Function paramaters/Parameter subset Y/DTOC DTOCL Enable PSL-Yes IOC Block um st.1N PSL-wwthout DTOCL Gen.starting medePS1-W/o sant. IN/Ineg proc. ts PSi-a.00 DTOCL Rushrestrenabl PSL-No DTOG = —— PS~LO0Inem DToc’ b> PS1-3000inom DIO. >> #S1-3000inom TOCA lpdynamic FSi-2.00 irom TOCA fssdyamie $11.00 hom TOCA 555 dynamic PS1~1.00 nom DTOCL th ——PSI-.00s DTOc th> — Psi-o.ms DTOCL th>> — PS1-0.005, TOC Ineg> —PS1-0.25 nom TOCA Ineg>> —_PS1-8.001nom TOCA Inegss> —_PSL-£.00 inom DTOCL Ineg> dynamic PS1--1.00Inom DTOCL Ineg>> dynamic PS1-1.00 Inom TOCA Ineg>>> dynamic PS1-1.00Inom DIOCL tineg> —PS1-0.005 DTOG@ thep> —PSI--000s TOC thhep>> —PS2-0.002 TOC) I> PS2-0.25Inam DTOC. I> 81-800 hom DTOCL IN PSt-=800 inom DTOCL IN>damic PS1~100 nom DIOCL IN>>dyrame PS1-LOd inom TOCA INz>dynamlePS1~1.00 Inom procs ts FS1-Q00= DTOCI tiNs> —PSt-0.00 DTOCL tIN>>> —PS1-0.005 Forshasefault(AB.Cl>: tb 0 sec bSating | Value(AAC) | Tnom | Measured operating | Caimed operating value value ac} ‘ach [eh [CPh OSinom [95 7 ‘OA75= 0525 Sinem | 5 i AIS 525 201 nom | 20 1 wm Forphase fault(A.,0) b>; t1> Ose b>Sattng | Value(AC) | tom | Measured operating | Caimed operating value value (aac ‘APh [BPR [CPh a Oa7S— 0.535 1 475 — 525 ee bbo>Setiing | Value(AAC) [Taom | Measured operating | Claimed operating value value (aac ‘eh [BPR | CPh ‘GSinom [os ir aa7s—0525 ‘Sinom [5 r 475-525 2lnom | 20 Z w-0 Forearth faultIN>; tIN> 0 se Tw>seting [Value(a AC) [Tnom [Measured operating | Caimed operating value | neutea> value (AAC) a2Inem [d2 7 ais- O24 [itnom [10 1 L 085-105 [80Inon [80 1 760-840 Forearth faultiN>> ; UN>> Osec >> Setting Value AC) [inom | Measured ‘Caimed operating ‘operating value | value (AAC) Ineutras> 2i nom on t 019-024 nom 10 t (095-105 BOI nom a0 t 760-840 Far earthfaultiNsss : tbs 0 TWs>> Setting ValugAAC) [Thom | Measured Cairsed operating ‘operating value | value(AAC) Ineutra>>> ‘inom ar T as on I nam ia r 035-105 ‘BO inom a T 7650-840 Fae NEGATIVE SEQUENCE In Procedure: ‘Apply 3 ahase Negative sequence curent and increase til the fu tinog> 0: ction asigned contact closes TWEG> Seting | Vobe(AAC) [nom | Measured Chaired operating operating value | value (AAC) neg Sinan [os i ars 083 SI nem = i [ars -8.25 Adinon | 80 1 70-80 West >> iting >> [EGS Sting | ValuetA —[Tnam [Measured Caimed eperatieg aq) operating valve | value (AAC) Ineg>> Osa os 7 oars 0535 5A 5 T 475 -5.25 Eo a0 7 70-80 For NEGATIVE SEQUEMCE Ineg >>>: thneg >>> Ose ‘BOinom [80 TWESS>—Value® AQ) [Tnom | Measured Caimed operating song operating value! | value (AAC) its | negos jee ‘GSinom i ouins— 0835 SI nem i 495 -5.38 7 70-8. {DMT FUNCTION Te SAMPLESETTING WITH TEST REPORT: Rated Inputcurrent 3/5 4 olay seting ‘PParameters/Function parameters/Parameter subset {/IOMTE IDMIa Enable PSL Yes TDMA Block umat. IV PSL~ Without DME Gen.starting modest Wo start. IN/Ineg DMT2 1s SI 0.008 DMT Rush estrenabl #S2- No OMT tel PSI 1.001nom DMT IrelP dynamic PS4~ 3.00 nom IDMTA —CharaderisticP PS1-- Definte Time [Mra FactorkyP PS1- 1.00 DMT Min. tip LP PSS. 0005 IDMTi Holl tmeP Pst. 0.005 IDM Release P _PSi- Without delay DMT Irefneg_PS1~ 0.80 inom IDMT1 rele dynamic?Si-- Blocked DMA Charader.neg. S1~ Definite Time IMT Facorktsveg PSt~ 1.60 IDMTE Min. tip t nog PS1~ 1.00 © DMT. Hod tmenes Psi 0.005 DMT Releaseneg PS1~ Without delay DMT IretN-PS1-- 0.80 nom IDM tet dynamic FS1-- Biocked IDMT2—Characeristicn PS1~ Definite ime DMT. Factarkt.N Si 1.00 DMT Min. tip tN PSI~ 1.005 OMIA Hold tmeN Pst- 0.005 DMT ReleaceNPSI- Forghase fault(A8.0:; Min.tript.P= Ose Tih | Ware 0) [Toon [Mmorpg] Sad spars Stine vai tea ok [BR [CR| azinon [a2 | [ors-21 nom 10 fa [095-105 ‘ivan [40 [Sanaa Fae NEGATIVE SEQUENCE Irafnag Min. tript. nog: 0 Procedure: ‘Apply3 ahase Negative sequence current and crease til the Function assigned contact closes iietaee We(AAC) [Tnom [Measured Claimed operating setthg operating value | value (AAC) Ing ‘G2inam [aa 7 ai-33 ‘Odinom [oa 1 0380.49 O8inom | 08 1 (0.76 - 0.84 Forearth faultirel§N: Mn. tp t.N=Osec Teh NSetting | Vaue(AAC) ]Tnom | Measured Chaired operating operatng value! | value (AAC) nevtral Co CE i Gis-33 Gainom [oa i o3—0.42 8inon | 08 1 (0.76 -0.88 ‘Vs >(UNDER/OVER VOLTAGE} Procedure: ‘Apply 3eh- voltage (62.5V) and increase one phase valtage or over voltage or decrease one phase ‘altage for under voltage function tl the function acegnad contact lovee RELAY SETTING /Parameters/Function parameters/Parameter subset /Vo> Vo Enable st. Yer vo v> PS1= 1, nom Vo ve PSL 1.Vnom ve Ww Psi 0.005 Vo We »S1-000s vo vs PS1--0.80 Voom Vo Vx Psi-agovnem Vo Vins Psi- 025 nem vo we PSi- Blocted Vo We PS1- Blocked Vo transient PSi~ 4005 Veo Hyst.Ve>meas, PSI- 1% OVER VOLTAGE V> i> 0 see WS Seting |Vauewy | Vnom | Measured operating value VS | Clamed operating Ac) AW aN cK |vaue WAC) Liveew | so.sso/mt [aioBv 776-1. 125Vaom | 79.388/337 |1103V 7700381766 5 TSVnen | 95.268/i65 [TI0V sao =38. DE ‘OVER VOLTAGE vo> j1v> > 0: VS> Siting | Value” | Vnam | Measured operating vai Vb>_| Claimed operating ac) AW BN [CN |vaue VAC) Livrem [59459 [a10hV 6776-1155 125Vnom | 79.385 [210/43 L5Vnom /95.268 (210/93 LUNDER VOLTAGE V- V0 26 Ve Setting [ValueWAG |Vnon [Menswed operating valueVe | aimed operating a [BN CN | vane VAG) 3Vnon | 19.05 10/33 18478193. 6Vnam—|38.10 110/837 36957-38208 ‘aavnen [5755 Of 35435 Ses Ve Seting | ValueQVAC)—[Wnom [Vex Opt Gained operating AN_[aN [oR | alee AAC 3Vn0m 1905 TORBV 1678196 6V nom 2.0 ov 36857--39.208 03Veon | 57.15 110/43 55435-5865 ‘s:(unp oven raequency, Procedure: ‘Apply3 phase voltage 63.V} with ratedfrequency and increase or decrease the frequency tl the functionassigned contact closes RELAY SETTING [Parameters/Funetion paramaters/Generalfunctions/fe> ‘General enable USER -- Yes Seledion meas vott~-Vohage AG Evaluation ime 4Periods LUndervet black, Ve 0.65 vnomU/%3) (Other functions in General functions - Generalenable USER - No /Parameters/Confi.parameters/OUTP Fet.assignn.k7 =~ fe Tri signaif2 /Parameters/Function parameters/Parameter subset i/fe> fnable Ves Oper. mode ft f a wa0he nh 0.005, anjat LoHz/s belts 020K Delta t2 ome Oper. mode 2 1 2 woke n 0.005 arzpat 2OHz/s betta o.30H2 Delt «2 ome Oper. mode ‘ 8 = 69.0 He 8 0.005, a/at 2OHz/s betta o.30n2 Delta 2 ous per. mode fa ‘ i 0.80 He 4 0.005 raat 2OHz/s Delta 4 0.30H2 Delta 4 ons Frequency setting i> Function Tr Setting | Weasired operating vaue( Hi) | Caimedoperaingvaue Hz 45H 8.65—16.35 ‘are 6.55 44 2H wat 53.56 VJ RUNCTION-ALARM /Parameters/Function pramaters/Parameter subset I/VIF Ps ves 'I-- 1.05 Voor farm PSL Blocked PSI~ Blocked Pstas, Relay Setting vt Enable Vit Vf (alarm) writs Vi Vib> vit wwe Vit tatv/ten0s Vi tat/s1.10 vit tatv/isnas Vi tatv/tes20 vi tates 25 Vi tatvitet 30 Vi tatyien 35 Vi tates 40 vA tatiana wr tanya ss Vi tates 60 Vit Resettime Vit wib> Procedure: ‘Apply AC veltage (SOHe) less than siting and increase the voltage with time delayof 200mSec til it ‘neratex Racor tho valu (Operating valu sttng X supply Frequency) SING] Wi Garay] Valuelv AC) MeasuredOperating | Clamed Value Setting Value (Volt) {Watt {Vnon/inom) 1.00 [1300 Tou TOVo 11830 140 [1210 1173710 12463 FEC} 109 R97 wi. Cperating tine toxt Low SET OPERATING TIME: Relay Setting SETTINGS(a) Sik> 200.0e3Pu Procedure: Apply Sphcurcent with 5 times setting value & measure operating time Wwsivet ‘SNe | Measured Operating Tine Claimed Overating Te ‘ADHASE | WPHASE | CPHASE 3010 # msec HIGH SET OPERATING TIME: Relay Setting sernes(a) Sikb>5fu ‘Procedure: Apply Sphcurrent with § times settingvalue & measure operating time Ww SioEt ‘S'No. | Measured Operating Tine Claimed Overating Tme ‘ADHASE —[&-PHASE | CPHASE Tove msec EF OPERATING TIME: Alay Setting sermmes(a) StlosHV 20000-29U Silo>Ivi_ 100e-3PU Stlo>LV2 — 100.0e-3PU Procedure: Apply Iphcurtent with Stimes setting valve & measure operating time 'S'No | Measured Operating Tine Clamed Operating Tme HY wi We Baie wmsec ‘OVERFLUX OPERATING TIMEITRI); Relay Setting SETTINGS(3) SLV/ITrip}Char OT SIV/ (ip) 220 ‘Procedure: Apgly voltage 121VAC (110% OF SETTING) S0H1z and measure operating time SNe] AVIF (Trip) setting | Measured Operating Time | Claimed Operating Time (Sec) (Sec) ny T0w2IS_ 208 190 to 2108 508 47510525 olay Setting SETTINGSI3) S1V/fTep) 1OMT SiV/t(Tip) 220- SLIMS 1 Procedure: Apaly woltage 121VAC (110% OF SETTING) 50H and measure operating time ‘SNe ] Applied Vote | Meured Operating Time | Claimed Operating Time Sec) Bed nav [isavte 2088 130 4770 19583 av 2520 19308 ‘OVERFLUX OPERATING TIME[ALARM): Relay Setting seTmnes(t) SLVi(Taip\char OF SLV/"UMARM) 220. Procedure: Apply voltage 121VAC (110% OF SETTING), SOM and measure operating time ‘S'No | {Vit (ALARM) setting Measured Operating Tine | Clarmed Operating Time (Sec) (See) ay 1a0t@ 25 20S 19.0 210 30s W7St0S25

You might also like