You are on page 1of 16

Energy and Buildings 39 (2007) 166181

www.elsevier.com/locate/enbuild

Architectural design of an advanced naturally


ventilated building form
Kevin J. Lomas *
Institute of Energy and Sustainable Development, De Montfort University, Leicester LE1 9BH, UK
Received 3 April 2006; received in revised form 4 May 2006; accepted 24 May 2006

Abstract
Advanced stack-ventilated buildings have the potential to consume much less energy for space conditioning than typical mechanically
ventilated or air-conditioned buildings. This paper describes how environmental design considerations in general, and ventilation considerations in
particular, shape the architecture of advanced naturally ventilated (ANV) buildings. The attributes of simple and advanced naturally ventilated
buildings are described and a taxonomy of ANV buildings presented. Simple equations for use at the preliminary design stage are presented. These
produce target structural cross section areas for the key components of ANV systems. The equations have been developed through practice-based
research to design three large educational buildings: the Frederick Lanchester Library, Coventry, UK; the School of Slavonic and East European
Studies, London, UK; the Harm A. Weber Library, Elgin, near Chicago, USA. These buildings are briefly described and the sizes of the as-built
ANV features compared with the target values for use in preliminary design. The three buildings represent successive evolutionary stages: from
advanced natural ventilation, to ANV with passive downdraught cooling, and finally ANV with HVAC support. Hopefully the guidance, simple
calculation tools and case study examples will give architects and environmental design consultants confidence to embark on the design of ANV
buildings.
# 2006 Elsevier B.V. All rights reserved.

Keywords: Low energy buildings; Advanced natural ventilation; Ventilation areas; Case studies; Downdraught cooling

1. Background water and refrigerant) accounted for up to 50% of the emissions


associated with space heating and cooling. Because AC buildings
The imperative of reducing the emission of greenhouse gases, tend to be deep-plan, the CO2 emissions for artificial lights were
and in particular CO2, caused by the burning of fossil fuels has also substantial. Buildings which are particularly densely
stimulated interest in the design of low energy buildings. In the 20 occupied, with long periods of usage and with high internal
buildings monitored by Bordass et al., in the well known UK heat gains (e.g. from computers and other equipment) might
PROBE Studies [1] there was a factor of 6 difference in the CO2 justify the use of AC, but as the PROBE results show, some
emissions produced for space conditioning and lighting a given relatively lightly used buildings nevertheless had AC.
floor area (Fig. 1). Nine of the 10 highest CO2 emitters were air- NV and ANV buildings utilise naturally occurring wind
conditioned (AC) or mixed mode (MM) (these used chilled pressures, and/or the buoyancy force generated by internal heat
beams, with displacement ventilation, etc. rather than full AC), sources, to drive an air flow, thereby avoiding the use of fans.
and 9 of the 10 lowest emitters were naturally ventilated (NV) or Admitting cool night air into a building, to purge daytime heat
advanced naturally ventilated (ANV). The term advanced accumulated in exposed thermal mass, can avoid the need for
natural ventilation was coined to encompass buildings which mechanical cooling entirely or, in warmer locations, reduce
utilised the stack effect to drive an air flow and so has been cooling loads, energy use and associated CO2 emissions.
adopted for the buildings which are the subject of this paper. In Shallow-plans, which typify simple NV buildings, or the use of
the AC and mechanically ventilated buildings, the CO2 emissions atria and lightwells in deeper-plan buildings, can improve the
resulting from the fans and pumps required to move air (and use of natural light reducing the CO2 emission associated with
artificial lighting.
* Tel.: +44 116 257 7961; fax: +44 116 257 7977. Whilst global warming is seen as a treat to NV and ANV
E-mail address: klomas@dmu.ac.uk. buildings, the overheating risk can be overstated. Current

0378-7788/$ see front matter # 2006 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2006.05.004
K.J. Lomas / Energy and Buildings 39 (2007) 166181 167

Fig. 1. The CO2 emissions from 20 buildings and ECON19 [32] benchmarks.

evidence for the UK, although rather weak, suggests that ANV controlled, an air flow can be assured at all times when there is
can keep buildings comfortable though the next century in all an internal source of warmth, including at night. In fact, in an
but the hottest (London) region [2,3]. unconstrained displacement flow regimen, where heat sources
Conventionally conceived NV buildings are shallow plan generate isolated plumes of warm air, the flow rate is directly
with an extended perimeter, and facade openings which provide proportional to the strength of the source, and the interface
the fresh air inlet and exhaust air outlet (Table 1). These between the cooler air the warm air above remains fixed [4].
features can be incompatible with the planning constraints With heat sources distributed over a surface, the air flow is also
imposed by tight urban sights and the noise and pollution in city dependent on the source strength in steady state conditions [5].
centres. The use of manually operated windows can This happy coincidence, between heat input and air flow rate,
compromise security, increasing concerns about theft by enables rather simple but robust control of air flow and makes
building occupants (a particularly important consideration prediction of performance at the design stage comparatively
for library buildings of the type described in this paper). reliable. Further, the interface between the cool and warmer air
Mechanically controlled perimeter windows enable night can be designed to lie above head height.
ventilation but the building may then be vulnerable to break- The benefits of control-ability and predictability, which stack
in or other malicious acts. driven natural displacement ventilation offers, can be lost if wind
At the design stage an ability to reliably predict the likely pressures begin to dominate the flow. An inability to harness
internal conditions in a building, for example by using dynamic these pressures is not a disadvantage; after all it is during still
thermal models and computational fluid dynamics programs, warm summer conditions when it is most difficult to keep ANV
can be reassuring and it is important to have a clear idea of how buildings thermally comfortable. Therefore, designing the
the internal conditions in the finished building will be buildings to be wind neutral is a useful guiding principle.
controlled. Relying, as they do, on variable and ill defined In a recent paper [2] a taxonomy was proposed, in which
pressure differences set up across the building by the wind, the stack ventilated buildings were divided into four main types
likely performance of simple NV buildings is hard to predict (Fig. 2). The edge-in, centre-out approach (E-C) is exemplified
and control. by the Queens Building at De Montfort University, Leicester,
ANV buildings that utilise the stack effect, in which air UK [69] and the edge-in, edge-out strategy (E-E) by the UK
warmed by internal sources of heat drives the air flow, do not Building Research Establishments (BRE) Energy Efficient
necessarily rely on wind pressures. If properly designed and Office of the Future [10].
168 K.J. Lomas / Energy and Buildings 39 (2007) 166181

Table 1
Characteristics of different simple and advanced natural ventilation strategies (after [2])
Simple natural ventilation Advanced natural ventilation (ANV)
Single Cross Edge-in Edge-in Centre-in Centre-in
sided flow edge-out (E-E) centre-out (E-C) edge-out (C-E) centre-out (C-C)
Architectural implications
Air inlet objecta No No No No Yes Yes
Exhaust stacksb No No Yes Yes Yes Yes
Plan depthc 2.5 (5) 5 10d 10d 5
Deep plane No No No Yes Yes Yes
Indoor air quality provided
Occupant inlet control Yes Yes Yes Yes No No
Close control No No Possf Possf Yes Yes
Displacement vent possible No No Yes Yes Yes Yes
Draught control Poor Poor Poor Poor Good Good
Performance predictability Poor Poor Good Good Very good Very good
Protection from local environment
Urban noise attenuation Poor Poor Poor Poor Good Good
Perimeter security Poor Poor Poor Poor Good Good
Robustness to climate change
Night vent cooling Yes f Yesf Yesf Yes f Yes Yes
Possible mech vent assistg No No Yes Yes Yes Yes
Comfort cool Difficult Difficult Difficult Difficult Easy Easy
Heat recovery No No No No Noh Noh
a
Such as plenum and lightwell.
b
Might utilise other feature, such as an exhaust air lightwell.
c
Rules of thumb (e.g. CIBSE, 2001)based on multiples of the floor-to-ceiling height. For single sided vent this is the room depth, but for cross-flow vent it is the
floor plate width perimeter-to-perimeter.
d
With a row of centrally located stacks, exhausting both sides of the building (E-C), or a central air inlet shaft supplying both sides of the building (C-E), the
perimeter-to-perimeter depth may be 10.
e
Exceeding, about, 20 m perimeter-to-perimeter.
f
If mechanically controlled perimeter air inlets are used.
g
E.g. fan in a stack or fan pressurised supply.
h
However, since the air is exhausted through discrete vertical stacks, heat recovery is possible when a mixed mode variant of the building is operated in mechanical
mode (e.g. HAWL).

In both building types, cold winter air can be drawn in over ventilation). With centrally located stacks (E-C), deep-plan
perimeter heating elements to pre-warm it and in summer buildings are possible, as in the Queens Building. Whilst
operable windows can be used to enhance airflows, and create air centrally located atria can, in principle, assist buoyancy driven
movement, without disrupting the basic airflow strategy. flow, stacks require less space, have more reliable ventilation
Mechanically operated air inlets permit night ventilation (and performance, can have terminations which are less susceptible
in the Queens Buildings lecture theatres, also daytime to wind effects and can, if necessary, incorporate low-powered
axial fans to encourage airflow under particularly adverse
conditions (as in the BRE office). The disadvantage of the
edge-in strategy is that the perimeter inlets are susceptible to the
noise, pollution and security concerns associated with design on
urban sites (Table 1).
The three case study buildings described in this paper, for
which the author provided strategic design advice and
performance evaluations, on behalf of the client and the
architect, Short and Associates, all utilise a centre-in ANV
strategy: the centre-in, edge-out (C-E) strategy is exemplified
by the School of Slavonic and East European Studies building
(SSEES) building, London, UK [2,1113]; the larger, very
deep-plan, Frederick Lanchester Library (FLL), in Coventry,
UK employs both the C-E and C-C strategy [2,3,11,1319];
whilst the Harm A Weber Library (HAWL), in Elgin, near
Chicago, Illinois, USA [20,21] uses the C-E approach with
Fig. 2. Schematic diagrams of the different forms of stack ventilation. localised E-E ventilation of perimeter offices.
K.J. Lomas / Energy and Buildings 39 (2007) 166181 169

The centre-in strategy has a number of strategic design


advantages: it enables the external facade to be sealed, which
overcomes security, noise and pollution concerns; the air supply
route can become a lightwell if necessary, thereby introducing
daylight into a deep-plan; the air inlet can be protected from
wind effects, giving even greater confidence about the likely
airflows (than in buildings with perimeter openings); and the
fresh air can be pre-heated. Further, by locating the exhaust
stacks at the perimeter of the building, as in the three case study
buildings, the basic floor plate is left clear permitting more
flexible internal space planning.
Most interestingly, the supply air can be comfort cooled or
fully conditioned enabling the same basic, but versatile, plan
form to incorporate either an ANV or a mixed-mode (MM)
approach to ventilation without the overhead of having two
different air distribution systems (one for mechanical mode and
the other for natural mode), Table 1. This offers the prospect of
introducing measures to combat future climate change and for
applying the basic design strategy to a range of climate types
these advantages are illustrated by the case study buildings.

2. Common features of the three case study buildings

There are numerous geometrical differences between the


case study buildings, as dictated by the client, site, budget,
summer cooling strategy, etc., however, design considerations
imposed by the natural ventilation mode of operation have a
major impact on the overall built form and so there are strong
generic similarities between them: it is these on which this
paper concentrates. The geometry of the three buildings and the
intended ventilation strategies, are illustrated in Figs. 38 and
their key features, and dimensions, particularly those related to
the ventilation strategy, are tabulated in Appendix A.
Fig. 3. Floor plan of the Frederick Lanchester Library (after [13]).
All three case study buildings were for educational
establishments with clients who would own and operate the
buildings and so were concerned about whole of life operating 0.6%). Interestingly, the Chicago climate has a greater mean
costs and particularly energy consumption. The buildings diurnal swing in both spring and autumn than the UK climates
contain cellular offices for staff and teaching spaces and (over 9.5 K cf. under 8 K), which suggests that night ventilation
extensive areas for library books, which, for security reasons, cooling could be a useful energy saving resource. The diurnal
and because of the noisy sites, required the building facade to be swing for London is, in fact, likely to be less than the climate
sealed. file indicates due to the urban heat island effect [13,22].
The climate to which the UK buildings were exposed is, of To contend with these climatic differences, the three case
course, much less severe than that in the Chicago region (see study buildings illustrate a progressively more complex
Appendix A1). For example the UK sites have around 230 environmental control strategy: from pure ANV for the FLL
cooling degree days (CDD) to base 15.5 8C, compared to 766 (which is located in the UK Midlands); through ANV with
for Chicago; the mean daily maximum temperature (MDMa) in comfort cooling using passive downdraught cooling (PDC) in
the warmest month (July) is around 20 8C at the UK sites and the SSEES building (because of the reduced summer night
28.7 8C in Chicago; and there were under 3% of working hours cooling potential caused by the London urban heat island and
when the ambient temperature exceeded 25 8C (WH25) at the because the UK design guidelines relevant at the time [23]
UK sites and over 15% in Chicago. Comparing the two UK require the use of a near-extreme weather year for the design of
climates it is evident that London, even without considering the naturally ventilated buildings2); to ANV with full HVAC
urban heat island influence, is warmer than Manchester (CDD support in the HAWL (because of the severe Chicago climate).
229 cf. 77; MDMa 22.4 8C cf. 19.4 8C; and WH25 2.9% cf. As noted above, the summer-time mechanical cooling

1 2
Appendix A presents Manchester data for the FLL as this is the nearest TRY The third hottest year recorded in London (Heathrow) between 1976 and
site to Coventry. 1995: the London Design Summer Year is 1989.
170 K.J. Lomas / Energy and Buildings 39 (2007) 166181

Fig. 4. Frederick Lanchester Library showing air supply strategy (left) and air exhaust strategy (right) (after [13]).

equipment could be introduced into the SSEES and HAWL


without compromising the basic centre-in ANV strategy.
The buildings have a square (or in the case of the SSEES,
approximately square) footprint, which yields a low surface
area to volume ratio. This, together with the high insulation
standards used in the roofs and walls (Appendix A), produces
low specific fabric heat gains and losses. The windows are of
clear low-emissivity double glazing to admit natural light to
perimeter offices and work spaces, and the SSEES and FLL
have artificial lighting which responds to daylight levels. The
windows are well shaded to reduce perimeter heat gains: either
by deep window reveals (HAWL); by adjacent buildings
(SSEES); or by the stacks, stair towers and metal shading fins
(FLL). Concrete (SSEES) or steel (FLL and HAWL) columns
and beams support the exposed flat concrete ceilings, which are
essential for effective night ventilation cooling. Castellated
beams (FLL) or open trusses (HAWL) enable stratified warm
air to move across the ceiling soffit. The plan forms, insulation
standards and window designs represent good, energy efficient
practice, irrespective of how buildings are conditionedbut the
deep-plans are unusual for NV buildings.
The lightwells are, of course, a critical and distinctive feature
of the three buildings. These supply fresh air to each above-
ground floor via low level openings to encourage a displacement
ventilation flow. Higher floor-to-ceiling dimensions are advanta-
geous with such a flow regimen. The flow of air from the lightwell
Fig. 5. Floor plan of the School of Slavonic and East European Studies Building to occupied spaces is control by either dampers (FLL) or
(after [13]). windows (SSEES, HAWL) set below desktop level. Secondary
K.J. Lomas / Energy and Buildings 39 (2007) 166181 171

Fig. 6. School of Slavonic and East European studies building showing the
natural ventilation cooling strategy (after [13]).

Fig. 8. Harm A Webber Library showing the natural ventilation strategy (after
[20]).

heating is provided by column radiators (SSEES, HAWL) or


trench heaters (FLL) at the point where the air leaves the
lightwell and enters the occupied spaces. Perimeter heating is
used in all buildings to offset any fabric heat loss.
The lightwells in the SSEES and HAWL are centrally located
to so that the flow path from the inlets to the perimeter air outlets
is approximately the same in all directions. In the larger
(50 m  50 m) FLL, four lightwells are used, one in the centre of
each quadrant, and a central lightwell acts like a large, glazed air
exhaust shaft. The use of a triangular lightwell in the SSEES
building was primarily an architectural choice, precipitated by
the shape of the building and constructional considerations,
rather than ventilation or environmental control considerations.
The lightwells have clear glazing in the walls and at the top
to admit natural light to the centre of the buildings and to
provide visual connectivity between the interior and the
outside. It is critical that the lightwell tops are sealed shut in
winter to prevent warmed buoyant air within them leaking
Fig. 7. Floor plan of the Harm A Webber Library (after [20]). away. They must also incorporate summertime solar radiation
172 K.J. Lomas / Energy and Buildings 39 (2007) 166181

control to stop the ambient air, and in the case of the SSEES and Exhaust air enters the stacks through dampered openings set
HAWL buildings the cooled air, being heated. The FLL and the below the ceiling soffit. The stacks are vertical and well
HAWL have an enclosed greenhouse formed by a horizontal insulated to keep the air in them warm and buoyant. They
glazed screen just above the air inlet to the top-most floor. The discharge above roof level to provide the necessary stack height
greenhouses have moving blinds and can be copiously and to position the terminations (which are to be neutral to wind
ventilated to remove solar-originated heat in summer. The effects) out of the turbulent airflow zone at roof level. The
SSEES building uses the same principle, but the greenhouse terminations are louvered to prevent the ingress of precipitation
takes the form of an upper and lower ETFE cushion. There is no and they contain bird or insect mesh. Above the roofline the
blind system, but the space between the cushions can be stacks have a rectangular cross section, which simplifies the
ventilated and the lightwell top is tilted towards the north. The design of the dampers which seal each stack at roof level.
lower ETFE layer has dampers around its perimeter with In the HAWL the stacks discharge into a sloped roof plenum
cooling batteries below. In spring and summer the dampers which exhausts via five ridge-mounted terminations: a position
admit ambient air for ventilation cooling and if necessary the air which the client preferred to the more dramatic perimeter
can be chilledpassive downdraught cooling. location for stacks.
In all three buildings air is supplied to the lightwell(s) via a Experience from CFD analyses has indicated that, unless
horizontal plenum located between the ground floor and the perimeter stacks extend above the level of the top floor inlet a
basement. The plenum feeds all sides of the lightwell, in the long way, which can be costly and impractical, stale air from
SSEES and HAWL, but just two sides of each lightwell in the lower floors can re-enter the top most floor [15]. Thus dedicated
FLL. Vertical drops from the plenum supply fresh air to top floor exhaust paths have become a feature of these ANV
basement areas in the SSEES and HAWL, which are exhausted buildings: separate short stacks in the HAWL; short stacks plus
by stacks. Because the basements are partially earth-bound and partitioned perimeter stacks in the FFL; and partitioned stacks
are poorly day lit, they tended to house unique (support) spaces at the rear, but dedicated partitioned chimneys at the front, in
(e.g. book archives and computer rooms), some of which may the SSEES.
require air conditioning. (For example, the whole of the FLL
basement is a 24 h access computing suite.) 3. Preliminary sizing of advanced natural ventilation
The plena are supplied with ambient air via dampered slots system components
at the buildings perimeter (FLL and HAWL) or by air supply
corridors and discreet inlets (SSEES). Each plenum has inlets 3.1. Preliminary design
located on more than one side of the building so that the
dampers at one or more inlets can be closed in adverse wind In the preliminary design phase the geometry of a building
conditions whilst retaining an open air inlet elsewhere. The can be extremely fluid as the architect grapples with a multitude
inlets are heavily louvered and incorporate either bird and of design constraints and design driversstructure, space
rodent mesh (SSEES, HAWL) or insect mesh (HAWL). Heater planning, fire, safety, cost, etc. This might include considering
batteries pre-heat the air and are located either across the base the number of storeys, the disposition of open plan and cellular
of the lightwell (FLL) or behind the air inlets (SSEES, HAWL). spaces and the external visual appearancein particular the
The latter strategy avoids insulating the plenum and enables the position, size and number of stacks and the style of the roof top
bottom of the lightwell to be clear glazing, thereby providing exhaust air terminations.
natural light to the basement. Under such circumstances it is helpful if the design team can
The perimeter stacks are an architecturally striking feature of work with simple equations and guidelines. In the context of
these ANV buildings and are crucial the ventilation strategy. In centre-in ANV buildings, these need to assist with sizing and
all three buildings they are reasonably uniformly distributed locating the main components: the plena; the lightwell(s); the
around the perimeter, which: assists with aesthetics; enables the stacks; and the air inlets and outlets to and from these. The
stacks to contribute to solar shading of windows; creates thermal critical measure is the free area available for air flow and so the
buffers between the inside and outside; helps to ensure zones of equations that follow generate target structural areas for
warm stale air do develop in the building; and offers planning preliminary design, i.e. the size of the opening to be created by
flexibility by enabling perimeter cellular spaces to be easily the architect (and into which any air flow control, heating and
locked into an exhaust stack. This latter benefit is fully other equipment will be inserted). The target areas are
exploited in the SSEES building, which has many offices: the rear expressed as a percentage of the floor area to be ventilated,
stacks, of triangular shape, cover the entire back wall and a which enables them to be used with buildings of arbitrary size
double facade runs right across the front face.3 There are draught and shape.
lobbies to entrance doors which prevent the stacks drawing in The air flow rates required to maintain thermal comfort
ambient air, which is particularly important in winter when the during warm, still summer conditions invariably dictate the
stack forces are greatest and the draught risk higher. maximum free area of opening required (some spaces have
higher ventilation needs, see e.g. [24], but in these specialist
buildings, natural ventilation is probably inappropriate).
3
The outer front facade was designed to harmonise with the Georgian Initially, the free areas are calculated on the basis of the
architecture of the surrounding area. overall expected internal heat gain in the particular building
K.J. Lomas / Energy and Buildings 39 (2007) 166181 173

Table 2
Estimated structural inlet and outlet areas for use at the preliminary design stage of advanced natural ventilation systems
Total heat gain Airflow rates Target structural areas as percentage of area of floors served (%)
(W/m2) 1 a 1 b
(ls ) (ach ) Lightwell Lightwell, plenum Plenum
outletsc outlet and stacks d inlete
20 2.4 2.5 1.6 0.5 1.0
30 3.6 3.7 2.4 0.7 1.4
40 4.8 4.8 3.2 1.0 2.0
50 6.0 6.0 4.0 1.2 2.4
60 7.1 7.4 4.8 1.4 2.8
Values in bold are target area for preliminary design purposes.
a
Air flow rate required for ventilation cooling per m2 of floor area.
b
Assumes 3.5 m floor to ceiling height.
c
Eq. (8) assumes gross structural area is twice the free area and the air speed is limited to 0.3 m/s.
d
Eqs. (3), (4), (9) and (10) presume no obstruction by grills, dampers, meshes, louvers, etc. and an air speed of 0.5 m/s.
e
Eq. (7) assumes gross structural area is twice the free area and the air speed is limited to 0.5 m/s.

type, tabulated values for which can be found in design guides close to the ceiling could be about 3 K, or in the case of higher
(e.g. [24]). ceilings, 4 K above the mid-height temperature [24,25]. Thus
Assumptions about the likely internal temperature differ- an assumption that the overall temperature difference, DT, is
ential and air speeds have to be made and, for preliminary 7 K is reasonable. Given this, the volume flows necessary for
design, values are chosen such that the calculated ventilation different heat gains can be found (Table 2, cols 2 and 3).
opening areas are conservative, i.e. over, rather than under, The allowable temperatures rise, DT, could be varied from
sized. Experience indicates that areas set aside for ventilation the value used here, for example 5 K might be more appropriate
(stacks, lightwells, etc.) at preliminary design, can be readily in buildings with a lower ceiling height (and vice-versa). The
surrendered for other purposes as the design evolves, but trying effect would be to proportionally increase (or decrease) the
to reclaim space, to compensate for under sizing early in the target volume flows of air, and hence the target opening areas,
design process, can be very difficult. required.
The target areas calculated are, of course, merely the starting The mass flow rate can be converted into a free area of
point. As the design evolves, the free areas can be refined, by re- ventilation opening, A, via:
using the equations but with the improved knowledge about the m
use which will be made of spaces and thus the likely heat gains. A m2 (2)
v
Detailed design can involve more accurate manual calcula-
tions, such as the application of stack effect equations (see, for where v (m/s) is the assumed air speed.
example [24]), and, later in the design process, the use of The achievable air speed will decrease as the stack height
sophisticated computer-based methods such as thermal decreases, all other factors being equal. Assuming that
simulation and computational fluid dynamics analysis (see dedicated ventilation provision is made for the top floor of
Appendix A for the analyses used in designing the case study the building (as in the case studies) then the top-but-one floor
buildings). Indeed, it is experience gained through the use of will have the shortest stack height, say 6 mthe height of the
these methods that has informed the development of the simple floor above plus the height from the roof level to the stack
equations and guidelines presented here. termination. Using this value, and a DT of 7 K, it can be shown
(e.g. equations in [24], pp. 411) that a value for v of 0.5 m/s is
3.2. Displacement and stack ventilation reasonable. Experience from CFD analysis corroborates this
rough assumption (e.g. [21]).
The sizing equations are based on considerations of a simple
stack-driven displacement ventilation regimen; that is, a low 3.3. Location and size of lightwell
level inlet supplying the space to be cooled and a high level
outlet into a stack. The volume flow of air, m (m3/s), required to It is generally most appropriate to position the lightwell in
provide ventilation cooling for different internal heat gains is the middle of the floor plates which are to be ventilated:
given by: although circumstances can arise which dictate otherwise, for
example when a building abuts its neighbours so that exhaust
QA
m m3 =s (1) stacks cannot be located on all sides.
C c DT
The volume flow of air required up the lightwell, ml, can be
where Q is the heat gain (W/m2), A (m2) the floor area, DT (K) calculated on the basis of total area of the building to be
the allowable temperature rise, and Cc is the volumetric heat ventilated from the lightwell, Ab, and the expected daily
capacity of air (1200 J/m3 K). average heat gain density in these areas, Qb. A building-average
Typically, the supply air temperature would be 23 K below heat gain is appropriate for lightwell sizing even if peak gains in
the target temperature for the occupied zone. The temperature individual spaces are known, because, whilst some zones might
174 K.J. Lomas / Energy and Buildings 39 (2007) 166181

be at full occupancy, it is unlikely that all spaces will be so determines the plenum depth, Dp:
simultaneouslypeople move around redistributing the heat
Apo
sources (and the stack system will automatically draw more Dp m (6)
air to the more densely occupied, and thus warmer, zones). Pl
Periods of particularly dense occupancy also tend to be short where P1 (m) is the length of the lightwells perimeter. Because
lived (especially at the whole building level) and a thermally a shallow plenum is desirable, as this reduces the overall
massive building, in which occupants can radiate heat to a building height (and increases the head height in a basement
night-cooled ceiling slab, can simply ride out periods of dense below), it is advantageous to make maximum use of the
occupation (the time history of thermally massive buildings can perimeter available by connecting the plenum to all sides of
be in the order of several days). the lightwell (as in the SSEES and the HAWL).
The lightwell cross sectional area, Al , can be expressed as a The plenum can be supplied with ambient air either by a slot
percentage of the whole building floor area by combining around the buildings perimeter (FLL, HAWL) or by air
Eqs. (1) and (2): corridors (e.g. SSEES). The structural opening to these should
be sufficiently large that the necessary obstructions, dampers,
Al Qb
 100 % (3) heater batteries and bird or insect meshes, do not inadvertently
Ab vC c DT reduce the free area. Therefore, the structural area of inlet to the
Using the values of 0.5 m/s, 1200 J/m3 K, and 7 K for v, Cc plenum is given by:
and DT, respectively, yields the ratio of the lightwell area to that Api Qb
of the total floor area ventilated (Table 2), e.g. 0.7% and 1.2%,  100 % (7)
Ab vC c DTbpi
for heat densities of 30 and 50 W/m2, respectively.
For a lightwell fed by a plenum (as in the FLL and HAWL), where bpi is the proportion of the plenum inlet that is
the cross sectional area calculated is, in fact, for the bottom of obstructed.
the lightwell. From an air supply standpoint, a bottom-fed For preliminary design purposes, it is reasonable to assume
lightwell could taper because the air volume to be carried that bpi is 0.5. Methods of reducing blockage at the air inlet
diminishes floor-by-floor. However, from an interior day- include: raking the heater batteries (SSEES and HAWL) or
lighting standpoint, it is better to have a lightwell with a large enlarging the mouth of the plenum (HAWL). Whilst the plenum
aperture at the top (and a larger aperture is almost certainly can carry services these should not unduly restrict the free area
needed if the lightwell is (also) to be fed by from above in or hinder maintenance.
ventilation cooling mode, e.g. the SSEES building). Also, as If the air entering the plenum serves only the lightwell (and
will be seen later, it tends to be the available area of lightwell not, for example, the basement below) then Qb and Ab are the
perimeter, rather than the cross sectional area of the lightwell, same as in Eqs. (3) and (4). However, if some of the air entering
which begins to dictate its size. Therefore, in practice, air the plenum is used to ventilate a basement (as in the HAWL and
supply lightwells (even those fed with air from the bottom only) the SSEES) or other areas (such as the perimeter offices, in the
tend to have vertical sides: this can also be less costly than HAWL) then the value of Ab in Eq. (7) will be larger than the
sloping sides. value used in Eqs. (3) and (4). To produce the target areas in
Table 2 it has been assumed that all air entering the plenum
3.4. Sizing the air inlet plenum supplies only the lightwell.

If the lightwell is fed only from the bottom, the plenum 3.5. Sizing air outlets from lightwell
needs to be able to deliver all the air the building needs. Thus,
The gross structural area of the outlets from the lightwell to
Apo Qb each floor, Alo, can be given by:
 100 % (4)
Ab vC c DTbpo
Alo Qf
 100 % (8)
where bpo is the proportion of the plenum outlet that is blocked Af vo C c DTblo
(0, fully blocked; 1, no blockage), Apo the free cross-sectional
area of the plenum outlet into the lightwell and v and DT are where Af is the area of the floor to be ventilated; Qf the heat load
again 0.5 m/s and 7 K, respectively. If there is no obstruction at density on the floor (W/m2); blo the proportion of the inlet that
the interface between the lightwell and plenum and, in fact, no is blocked by obstructions; and vo is the speed of the air leaving
airflow control device is needed at this point, the free cross- the outlets (m/s). At preliminary design stage the value of Qf
sectional area Apo is equal to the gross structural area, giving: might simply be taken as Qb and refined as the occupancy for
each floor becomes better defined.
Apo Al (5) The air outlets from the lightwell are located adjacent to
occupied areas. In fact, the available daylight and fresh air,
Because the building perimeter, which is the location for the together with a structure (the lightwell) on which to mount
plenum inlet, is longer than the lightwell perimeter, it tends to services, makes the lightwell perimeter an ideal place to locate
be the outlet from the plenum into the lightwell which work surfaces. Care must be taken, therefore, to avoid cold
K.J. Lomas / Energy and Buildings 39 (2007) 166181 175

draughts, especially in winter. Thus the air speeds must be whole building (Ast) will be given by
limited (and, in winter, the air temperatures not too low) but a
Ast Qb
displacement flow regimen, supplying all the occupied floor  100 % (10)
Ab vC c DT
area, must be achieved. In general, guides (e.g. [24]) suggest an
upper value of air speed of about 0.15 m/s. However, in summer values for different Qb are given in Table 2.
cooling mode, which is the design condition being considered Ideally, the stacks should be vertical and straight and
here, the speed can be higher (because the supply air terminate above the roof line; as noted above, the top floor may
temperature will be elevated) therefore, for these sizing need to be ventilated separately and/or the stacks might be
purposes a value for the air speed, vo , of 0.3 m/s has been internally partitioned.
assumed (Table 2). The stack-top terminations can become rather large because
The structure associated with the lightwell, the reheating they must provide the same free area as the stacks which they
devices, and the dampers with their framing and louvers (or surmount but also: prevent rain penetration; and include insect
other flow control objects), will introduce blockage. This might or bird mesh, dampers and devices to overcome unwanted wind
mean that only 50% of the structural opening is actually free pressures. They must also have a suitable aesthetic appearance
area so a reasonable value for blo at preliminary design stage is as they may be the most striking visual feature of stack-
0.5. ventilated buildings.
The calculated free area for outlets, e.g. 2.4% of floor The inlets to each stack will be located at high level, just
area for an internal heat gain of 30 W/m2 (Table 2) does not below the ceiling soffit in order to drain warm, stale stratified
seem large. However, the inlets serving an entire floor will air, and they will contain dampers to control the airflow. Thus
cluster around the perimeter of the lightwells and the top of the structural area of the openings into each stack will exceed
the inlet may need to be no more than about 0.7 m above the the area of stacks calculated from Eq. (9) in proportion to the
floorto ensure a displacement flow and to fit below work degree of blockage caused by the dampers, e.g. by 50%. At
surfaces. Thus, the length of a lightwells perimeter may preliminary design stage it is unnecessary to size these
limit the free inlet area achievable, which can lead to the openings; however, if the number of stacks provided on a given
lightwells being enlarged to accommodate the outlet areas floor is small and if the stacks present a narrow face towards the
required.4 In very deep-plan buildings, the lightwell space, it may be difficult to get the necessary outlet area into the
perimeter may be insufficient and so multiple smaller stack. The stacks in the HAWL and especially the SSEES
lightwells may be used, rather than a single large lightwell building overcome such difficulties by presenting a wide stack
(e.g. the FLL). face towards the occupied spaces.

3.6. Sizing the stacks and air outlets 4. Comparison of as-built and target opening areas

The stacks themselves are likely to be free of blockage and, It is instructive to compare the as-built areas of the openings
as noted above, it is reasonable to assume an air speed in them, in the three case-study buildings with the target areas suggested
during ventilation cooling operation, of 0.5 m/s. Therefore the by the above sizing method for a number of reasons: to
total area of the stacks As exhausting a floor can be given by: understand which of the target opening areas are, in practice,
the most difficult to achieve; to illustrate the extent to which
As Qf opening areas deviate from the target figures; to illustrate how
 100 % (9) design ingenuity can enable the desired free inlets to be
Af vC c DT
achieved in difficult circumstances; and, finally, to act as a
As noted above Qf might simply be taken as Qb for springboard for discussion of the finer points of these buildings
preliminary design. The required area can be distributed designs.
around a number of equally sized stacks or in some other way From the as-built dimensions (as given in Appendix A) it is
(the FLL has stacks and a central lightwell, the HAWL stacks possible to obtain: the total floor area to be ventilated from the
of differing cross-section and the SSEES stacks and a double lightwell, Ab; the cross-sectional area of the lightwell, Al; the
facade). feasible maximum area of the outlets from the lightwell, Alo; the
As successive floors exhaust into each stack, the volume area of the outlet from the plenum into the lightwell, Apo; the
flows of air to be carried increases, thus the cross-sectional gross area available for ambient air to enter the plenum, Api; and,
areas could increase up the building. The central lightwell of finally, the cross-sectional area of the stacks available to exhaust
the FLL visibly illustrates this; it enlarges from 36 m2 on the the air from the building, Ast (see Table 3). These as-built areas,
ground floor to 82 m2 at the roof topa form which is expressed as a percentage of Ab, are compared with the target
consistent with daylighting considerations. At the level of the areas intended for preliminary architectural design (Table 2) in
stack terminations, the total area of all the stack outlets from the Table 4. The target areas are calculated using Qb values of 30 W/
m2 for the FLL and SSEES and 45 W/m2 for the HAWL, which
4
The authors and architect have considered articulating lightwell perimeters were the values adopted at the preliminary design stage.
to artificially increase their perimeter lengthbut this can be costly, construc- It is evident (Table 4) that, in all three buildings, the as-built
tionally difficult and in conflict with interior planning ideas. cross-sectional area of the lightwells exceeds the target free
176 K.J. Lomas / Energy and Buildings 39 (2007) 166181

Table 3
As-built areas of main airflow apertures in the three case study buildings
FLL SSEES HAWL
2
Building Gross floor area of building (m ) 8161 3380 3468
Gross areas of floors 2228 m2 (G-2) 303 m2 (G) 665 m2 (14) 1165 m2 (G-2)
Lightwells Total building floor area serveda (m2) 4  1858 2936 2283
Cross sectional area (m2) 4  38 36 73
Perimeter lengthb 24.4 m (G-2) 12.2 m (3) 24 m (G-4), 19 (5) 34 m (G-2)
Total feasible maximum outlet areac (m2) 4  60 76 71
Plenum Depth at outlet into lightwell (m) 1.5 0.80 0.93
Gross area at outletd (m2) 4  18 19 h 32
Depth at inlet at building perimetere (m) 1.4 n/a 1.45
Gross area at inletf (m2) 4  36 15 55
Stacks Cross sectional areasg (m2) 160 33 47.4
2
Values in bold, rounded to the nearest 1 m , are used to calculate as-built statistics for comparison with preliminary design target values in Table 4.
a
Excludes the lightwell itself and all areas not ventilated from the lightwell(s), e.g. stair wells, mechanically ventilated areas (e.g. WCs), the basements and, in the
HAWL, perimeter offices directly ventilated from the facade.
b
Stated perimeter length includes curved corners of SSEES lightwell, length excluding corners is 18 m (G-4).
c
Presumes inlet heights are a maximum of 0.7 m (i.e. below desktop). Curved lightwell corners are not a feasible outlet location in the SSEES building. E.g. FLL
0.7  (3  24.4 + 1  12.2) = 60 m2; 24.4 m perimeter on G, 1 and 2 and 12.2 m perimeter on floor 3.
d
E.g. FLL = 1.5  12.2 = 18.3 m2 as only two sides of each lightwell served from plenum. The perimeter, excluding the curved corners, is used for SSEES.
e
Depth of plenum slot at the perimeter of the building for FLL and HAWL, not applicable at SSEES which has discrete air corridors and apertures as inlets.
f
Structural area, i.e. excluding any obstruction from louvers, dampers, grills, mesh, etc.
g
Area of all stacks at level of terminations, except HAWL which is area at entry to roof plenum, FLL includes area of the central lightwell.
h
Additionally there is 26 m2 of inlet at the head of the lightwell.

area by a considerable amount. For example, in the HAWL, the The air supply lightwells in the FLL occupy about 6.8%, of
target area for preliminary design is 1.1% of the floor area the gross area of the ground to second floor, the SSEES
ventilated, whereas the actual cross-section of the lightwell is lightwell occupies 12% of the (reduced area) ground floor and
3.2% of the area ventilated. The target free areas presume that 5.4% of floors one to four, and the HAWL lightwell 6.3% for all
there is no obstruction to airflow, however in the FLL, the heater above ground floors. In addition to providing fresh air, the
batteries across the base of the lightwell reduce the effective lightwells admit daylight which brings both functional and
free area by about 50%, i.e. to 1.0% of the floor area ventilated, physiological benefits to otherwise deep plan spaces.
which is much closer to the target of 0.7%. Nevertheless, it is The feasible maximum area of outlets from the lightwells
evident that the cross-sectional area of these lightwells should are much closer to the target areas, with the HAWL actually
not, in practice, act as a constraint to the flow of ventilation air. having a maximum feasible opening area that is less than the

Table 4
Comparison of as-built areas and target structural areas for use in preliminary design
Gross areas as percentage of floor area served (%) a
FLL SSEES HAWL
b c b c
As-built Target As-built Target As-builtb Targetc
Lightwell Gross cross sectional aread 2.0 i 0.7 1.2 0.7 3.2 1.1
Feasible maximum area of outletse 3.2 2.4 2.6 2.4 3.1 3.6
Plenum Outlets into lightwellf 1.0 0.7 0.7j 0.7 1.4 1.1
Inlet from ambientg 1.9 1.4 0.5j 1.4 2.4 2.2
Stacks Cross sectional area at terminationsh 2.2 0.7 1.1 0.7 2.0 1.1
a
Areas rounded to nearest 0.1%.
b
Areas used to calculate as-built values taken from Table 3, methods of calculation are given below.
c
Target areas from Table 2 using whole building design heat loads of 30 W/m2FLL and SSEES and 45 W/m2 HAWL. These do not, necessarily, concur with the
heat loads used later in the design process when occupancy had been more accurately defined.
d
As percentage of floor area served, e.g. FLL 38/1858 = 2.0%.
e
Excludes curved lightwell corners in the SSEES, e.g. FLL 60/1858 = 3.2%.
f
Outlet from plenum to lightwell as percentage of floor area served by lightwell(s), e.g. FLL 18/1858 = 1.0%.
g
E.g. FLL 36/1858 = 1.9%.
h
Includes central lightwell in FLL, e.g. FLL = 160/(4  1858) = 2.2%.
i
But the horizontal heater batteries reduce the free cross-sectional area by 50%, to 1% of the floor area served.
j
Additional 26 m2 of inlet in the head of the lightwell for ventilation cooling giving an extra inlet area of 0.9% of the floor area served.
K.J. Lomas / Energy and Buildings 39 (2007) 166181 177

target value (i.e. 3.1% compared to the target of 3.6%). This offices enable these spaces to be ventilated directly from
arises because the single lightwell is supplying air to a large ambient, thereby overcoming any restriction imposed by the
surrounding floor plate. (Note, that in the HAWL the maximum plenum inlet.
horizontal air inlet to outlet distance is 15.7 m, but in the other Because the plenum inlet area was barely large enough in the
two buildings it is only 12 m, see Appendix A.) The HAWL also SSEES and HAWL, particular care was taken to reduce the
has a higher design internal heat gain, i.e. 45 W/m2 compared to blockage caused by heater batteries, by positioning them at a
30 W/m2 in the other two buildings. To overcome the limitation raked angle (e.g. Fig. 8). In the HAWL, the potentially severe
in available area, top-hung canopy windows operated by long restriction of the insect mesh, rather than bird/rodent mesh, was
push bars are used at the outlets from the lightwell. limited by folding the mesh (effectively extending the plan
Additionally, the top-floor, a design studio, has operable length over which it was distributed).
clerestory windows, so that it can be ventilated with cool air In all three buildings, the cross-sectional area of the stacks at
directly from ambient (see Fig. 8). the level of the terminations (and in the case of the FLL, the
Overall, these results illustrate the more general point that it stacks plus the central lightwell) are in excess of the target
tends to be the length of the lightwell perimeter necessary to areas; in the FLL by a factor of 3 (2.2% compared to a target
achieve a desired outlet area, rather than the cross-sectional value of 0.7%). These larger cross-sectional areas are the result,
area of the lightwell itself, that determines the overall lightwell in part, of adjusting the areas in line with the stack ventilation
dimensions. Put another way, at the preliminary design stage calculationsby enlarging the outlets, relative to the inlets, the
the size of the lightwell is likely to be determined by the area of neutral pressure level can be encouraged to settle higher up the
outlet needed around the perimeter (Eq. (8)) rather than the free stacks reducing the likelihood of back flow into upper floors.
area required for the lightwell itself (Eq. (3)). This was a particular concern during the design of the FLL.
In all three buildings, the area of the outlet from the plenum Whilst the stacks in the HAWL seem amply sized, they also
into the lightwell is close to, or in excess of, the target area. In ventilate the basement and the perimeter offices, which are fed
the SSEES building, the as-built area only just meets the target with fresh air directly from the plenum rather than from the
value (0.7% of floor area), but this free area was difficult to lightwell.
attain because the level of the basement and ground floor were Overall, it is evident that the as-built structural opening areas
set by the site levels and, of course, head height had to be in the SSEES building and the HAWL are rather closely aligned
retained within the basement. to the target areas proposed for preliminary design purposes,
The inlets to the plenum at the building perimeter were whereas in the FLL, the opening areas are conservatively larger.
larger than the target value in the FLL and HAWL but much This general difference results, in part, from the growth in
smaller in the SSEES building (0.5% as-built, compared to the confidence of the design team with successive buildings. The
target value of 1.4%); again, this was due to the difficult site SSEES and HAWL also have supporting mechanical summer-
configuration. The vehicle delivery route at ground level, which time cooling systems which can be activated when the natural
loops round the back of the building (see Fig. 6), prevented the displacement ventilation cooling fails to achieve the desired
use of a slot-type plenum inlet (as used in the FLL and HAWL); internal temperatures.
so air corridors were used at the back of the building and four
large apertures at the front. The restricted area of inlet is 5. Design development
overcome when the building is in natural ventilation cooling
mode through the provision of air inlets at the head of the The forgoing sections have shown how to calculate the
lightwellthese inlets provide an additional 26 m2 of opening, overall sizes of the components of the ANV systems at the
equivalent to 0.9%, of the floor area ventilated by the lightwell. preliminary design stage. However, as designs develop, other
Thus the total inlet area in this mode of operation is 1.4%, factors must also be considered, for example: the provision of
which is comparable to the target area. The area of inlets to the air transfer ducts, or labyrinths, to enable air to flow into (at low
SSEES plenum is, in fact, just sufficient to meet the fresh air level) or out of (at high level) cellular spaces, as in all three of
needs of occupants and it is during this winter time mode of the buildings discussed here (Figs. 4, 6 and 8); the introduction
operation that the air needs pre-heating before delivery to the of acoustic absorbers, especially between spaces with different
lightwell.5 noise level expectations (e.g. in the stacks of the HAWL
Although, in the HAWL, the as-built gross inlet area to the between the design studio (floor 2) and the library and office
plenum is marginally larger than the target value, not all the air floors below); and, of course, the fine adjustment of the areas of
serves the lightwell; some ventilates the basement and some is inlets and outlets, to and from, individual spaces to reflect their
fed up to perimeter offices (Fig. 8). However, when the building individual design heat loads and the different stack heights.
is in natural ventilation cooling mode, the clerestory windows These area adjustments can be made by recalculating the target
to the top floor studio and the operable windows to perimeter areas in Table 2 using the actual heat loads in the individual
spaces (in conjunction with the floor area of the space). The
5 outlet areas into the stacks can be further refined by, in effect,
Assuming a ventilation requirement of 10 l/s per person, and that each
person occupies 10 m2 of building floor area, the target gross area of inlet using more realistic air flow velocities for the stacksthese can
required is 0.4% of the floor area served; which is comparable to the area be calculated using the well known stack ventilation equations
provided of 0.5% (Table 4). (e.g. [24]).
178 K.J. Lomas / Energy and Buildings 39 (2007) 166181

Other building, climate and client-specific factors might also 6. Conclusions


need to be considered, for example, in the HAWL: the desire for
operable office windows (which led to offices having dedicated The attributes of two different forms of simple natural
stack outlets and inlets directly from the plenum); and the need ventilation and four generic building types for exploiting
to integrate the HVAC system, and thus the provision of a return advanced natural ventilation (ANV) have been summarised,
air path from the exhaust stacks to the plant room (which led to highlighting, for each one: the architectural implications; the
the use of the roof plenum). indoor air quality provision; the degree of protection from the
Once the design is rather well developed, the likely surrounding environment; and the likely tolerance to climate
temperatures and airflows need to be determined using more change. ANV buildings, with a central air supply and perimeter
sophisticated analyses methods. Typically, as with the three exhaust stacks, seem to offer benefits in each of these four
buildings described here, this will involve dynamic thermal areas. Such centre-in, edge-out (C-E) buildings can, in
simulation modelling, to understand the time-varying principle, be designed so they are essentially wind neutral,
behaviour of the building, and CFD analyses to evaluate that is, wind pressures will not hinder, or assist, the airflow; this
airflows and temperatures under chosen critical conditions gives added reliability to predictions of their likely, as-built,
(e.g. [15], FLL; [21], HAWL). Other computer models might performance.
be used to evaluate solar heat gains and daylight levels and Three case-study buildings which use the C-E ventilation
physical models might be used for wind tunnel tests (e.g. of strategy are described: the Frederick Lanchester Library,
termination designs) or for water-bath modelling of internal Coventry, which uses ANV; the School of Slavonic and East
airflows. Such analyses can reveal critical design flaws, for European studies, which uses ANV with passive downdraught
example in the SSEES building it was found that the larger cooling to combat the warmer central London micro-climate;
stacks at the rear of the building could draw air into the top of and the Harm A Webber library, being built near Chicago, USA,
the double facade and across the floor plates, thus turning the which integrates and HVAC system within the ANV concept.
double facade into an inlet rather than an outletwhich They each have a central air-supply lightwell, fed with fresh air
would generate very cold draughts, especially in winter, when by a low level plenum and exhaust stacks arranged around the
the condition was most likely to occur. In the final design a building perimeter. The sizes and other characteristics of these
glazed screen separates the front of the building from the rear components are tabulated, along with synoptic climate data for
(see Fig. 5). each site.
The building geometry and opening areas, as described Based on experience gained through the design of these
above, are determined by the volume flows of air necessary for buildings, simple equations, for use at the preliminary
effective natural ventilation cooling in warm summer condi- architectural design stage, to roughly size the lightwell,
tions under normal occupancy. Under other circumstances the plenum and stacks are presented. The sizes are determined
openings required for airflow can be much smaller: e.g. in by the volume flows of air needed for summertime NV
winter when pre-heated air to heat only the fresh air cooling. The target structural areas to be provided at the
requirements is needed; at times when the internal heat loads preliminary design stage, expressed as a percentage of the
are low, outside of occupied periods; to provide appropriate total building floor area to be ventilated from the lightwell(s)
night-time ventilation; when the spread of fire and smoke must are presented.
be controlled; and, in hybrid buildings, to control mechanically Finally, the as-build structural areas in the case study
driven airflows. A building energy management (BMS) system buildings are compared with the target values. These
is, of course, the most appropriate system for effecting such comparisons illustrate that it is relatively straightforward to
control. It would take inputs from air (and possibly thermal design a central supply route (e.g. lightwell) of sufficient great
mass) temperature sensors, CO2 (or volatile organic compound cross-sectional area but that it can be difficult, particularly with
(VOC)) sensors, smoke detectors, and, in some hybrid deeper floor plans and densely occupied buildings, to achieve
buildings, possibly humidity sensors, and send output signals the target structural opening areas for air supply around the
to control the dampers, windows (and possible shading perimeter of such lightwells. On constrained sites it can also be
devices): some insight into the control strategy from the difficult to achieve the target structural opening areas for the
HAWL is given in [20]. The definition of a suitable BMS plenum inlets. With design ingenuity, however, such difficulties
control strategy, its programming, and its subsequent refine- can be overcome and strategies for doing this in two of the case-
ment during the commissioning and early post occupancy study buildings are described.
period, is an area of ANV building design which would benefit The equations and tabulated structural opening areas are
from further research. only a rough target for use at the preliminary design stage: more
Preliminary data from the FLL illustrates the good sophisticated analyses should be undertaken as the design
summertime cooling performance and low energy consump- develops.
tion that is possible [3]. It also confirms the need for more It is hoped that this paper will give architects and engineers
post-occupancy performance data collection and analysis. the added confidence necessary to embark on the design of
And this exemplifies a rather more general pointthat there is ANV buildings. Their low energy consumption, relative to
rather little post-occupancy performance data for ANV typical air-conditioned buildings, is valuable in attempts to
buildings. combat global warming.
K.J. Lomas / Energy and Buildings 39 (2007) 166181 179

Acknowledgements fruitful working relationship, and without whose assistance this


paper would not have been possible. The environmental design
The architects of the buildings described were Short and analyses were led by Dr. Malcolm Cook of the Institute of
Associates, with whom the author has had a long-standing and Energy and Sustainable Development.

Appendix A. Comparison of key features of the three advanced naturally ventilated buildings

Building name Frederick Lanchester School of Slavonic and East Harm A Webber
Library (FLL) European Studies (SSEES) Library (HAWL)

Client and context


Client Coventry University University College London Judson College
Location Coventry, UK Bloomsbury, London, UK Elgin, Nr Chicago, Il, USA
Site City center City centre Green campus
ANV Type C-E, C-C C-E C-E, E-E
Cooling method Natural Natural and PDC Natural and HVAC
Number of levels Basement + Ground + 3 Basement + Ground + 5 Basement + Ground + 2
Completion date September 2000 November 2005 Winter 2006
Structure Steel frame Concrete Steel frame
U-values
Roof 0.18 W/m2 0.20 W/m2 0.25 W/m2 K
Wall 0.26 W/m2 0.30 W/m2 0.25 W/m2 K
Window 2.00 W/m2 2.00 W/m2 2.60 W/m2 K
Footprint 50 m  50 m 31.5 m  27 m 34 m  34 m

Gross floor areas 8161 m2 (G + 1 + 2 + 3) 3380 m2 (G-5) 3468 m2 (G + 1 + 2)


942 m2 (B) 695 m2 (B) 1192 m2 (B)
Floor to ceiling height 3.9 m (G, 1, 2, 3) 3.2 m (G), 2.9 m (14), 2.6 to 4.9 m (5) 3.35 m (G, 1), 3.86.5 m (3)
Window shading Perimeter stacks, metal fins Adjacent buildings External window reveals
Approximate cost 20 m 10 m $13.5 m
Publications
By designers [2,3,11,1315] [2,1113] [20,21]
By others [1619]

Air supply lightwells


Type 4 no Lightwells Lightwell Lightwell
Levels serveda G, 1, 2, 3 G, 15 G, 1, 2
Shape Square Triangular Square
Top Sealed, glazedb Operable/ETFE Sealed, glazedb
Shading Moveable blind None Moveable blind
Bottom Opaque-heater battery Clear single glazing Clear single glazing
Sides Clear single glazing Clear single glazing Clear single glazing
Air outlet type Dampers Bottom hung windows Top hung windows
Secondary heating Trench heaters Column radiators Linear finned emitters
Cross-sectional area 4 no 38 m2 36 m2 73 m2
Gross perimeter lengthc 4  [25 m (G, 1, 2), 12 m2 (3)]d 24 m (G, 1, 2, 3, 4), 19 m (5) 34 m2 (G, 1, 2)
Floor area servede 1858 m2 per lightwell 2926 m2 2283 m2
Gross area of air inletf 18.6 m2 per lightwell 19 m2 bottom and 26 m2 top 32 m2
Maximum airflow distanceg 12 m 12 m 15.7 m
Air inlet plena
Air inlet type Perimeter slots Corridors (side) and four apertures (front) Two perimeter slots
Inlet depthh 1.4 m n/ai 1.45 m
Outlet depth 1.5 m 0.8 m 0.93 m
Gross plenum inlet area 36 m2 per lightwell 8.7 m2 (corridors), 6 m2 (apertures) 55.2 m2
Air preheating Horizontal heater coils Raked heater battery Raked heating battery
180 K.J. Lomas / Energy and Buildings 39 (2007) 166181

Appendix A (Continued )
Air exhaust pathsj

Lightwell Stacks Stacks Double Stacks and


Facade roof plenum
Rear stacks Front chimneys

Shape Square Square Triangular Rectangular Rectangular slot Rectangular


Cross-sectional areask 81 m2 20 no 3.28 m2 10 no 2.1 m2 4 no 1.2 m2 1 no 7.2 m2 10 no1.64 m2
(G, 1, 2) (15)l (3 and 4)m (G, 1, 2) and 10 no1.05 m2
(G, 1)
4 no 3.28 m2 (3) 3 no 6.5 m2 (2)
Total outlet areas 160 m2 33 m2 47.4 m2 n
Minimum and maximum stack height 7 m (2) 4.5 m (3) 6 m (5) 3.9 m (3)
15.5 m (G) 18.5 m (G) 23 m (1) 12.5 m (G)

Climateo

Latitude/longitude 52.378/1.338W 51.488/0.08 42.038/88.278W


HDDp (10 8C) 765 656 1745
HDD (15.5 8C) 2163 1896 1274
CDDq (18.3 8C) 13 69 426
CDD (15.5 8C) 77 229 776
Working hours
Over 25 8Cr 0.6% 2.9% 15.2%
Over 28 8C 0.0% 0.6% 7.3%
Mean diurnal swing
Springs 7.2 K 7.8 K 9.6 K
Autumn 5.6 K 6.4 K 10.1 K
MDMat 19.4 8C 22.4 8C 28.7 8C
MDMau 7.2 8C 7.3 8C 0.4 8C
Thermal analysis
Summer design targetv 5%/27 8C 5%/25 8C Comfort envelope
Weather filew Kew 67 London DSY Chicago TRY
Dynamic thermal Sim x ESP-r ESP-r ESP-r
Ventilation analysisy CFX CFX and Water-bath model CFX
Solar gain/daylightingz None Radiance Radiance
a
Basements either independently mechanically ventilated (FLL) or ventilated from plenum (SSEES, HAWL).
b
Ventilated greenhouse arrangement the bottom of which is sealed.
c
Length around the lightwell, in SSEES curved corners are not useable for supplying air length of straight sides is 18 m (G-4).
d
Only two sides of lightwell adjoin floor 3.
e
Excludes the lightwell itself and areas not ventilated from ite.g. stair wells, mech vented areas (e.g. WCs), and directly ventilated perimeter offices (HAWL).
f
Area of inlet from plenum to lightwells, and for SSEES also inlet at top.
g
Ie maximum air flow distance from lightwell to a perimeter stack.
h
Ie free height between insulation layers, in HAWL occurs at restricting downstand at lightwell edge.
i
Inlet is air corridors and apertures, not a plenum slot.
j
Excludes basement exhaust stacks (SSEES, HAWL).
k
Plan areas at termination of stack/lightwell/double facade (SSEES, HAWL), at entry to roof plenum (HAWL).
l
Internally divided stacks: Floors 1 and 2 combine, floors 3 and 4 combine and floor 5 linked separately.
m
Floor 3 offices and floor 4 offices internally partitioned chimney
n
Excludes exhaust from perimeter offices fed from perimeter (E-E) rather than the lightwell.
o
Data for FLL is Manchester TRY; for SSEES, London TRY; and for HAWL, Chicago TRY.
p
E.g. heating degree days to base 10 8C.
q
E.g. cooling degree days to base 18.3 8C.
r
E.g. annual percentage of hours between 8:00 and 18:00 over 25 8C.
s
Average of daily temperature swing (maximum to minimum) in March/April and October/November.
t
Mean of daily maxima for month of July for all climates.
u
Occurs in February for London (SSEES) and Manchester (FLL) and in January for Chicago (HAWL).
v
E.g., no more than 5% of occupied hours over 27 8C, for ANSI/ASHRAE comfort envelope, see eg [26].
w
See reference: [27] for Kew 67; [23] for London DSY; and [28] for Chicago TRY.
x
For all buildings, combined thermal and airflow modelling was used, for ESP-r, see [29].
y
CFX is a CFD code, see [30] for the water bath modelling see e.g. [4,5].
z
See e.g. [31] for description of radiance.
K.J. Lomas / Energy and Buildings 39 (2007) 166181 181

References Conference, vol. 2, Brisbane, Australia, (1999), pp. 597602, ISBN: 1


86499 3480.
[1] B. Bordass, R. Cohen, M. Standeven, A. Leaman, Assessing building [16] A. McDonald, Celebrating outstanding new library buildings. SCONUL
performance in use: energy performance of the PROBE buildings, Build- (Society of College, National and University Libraries). 2002, http://
ing Research and Information 29 (2) (2001) 114128. www.sconul.ac.uk/pubs_stats/newsletter/27/ARTICL27.PDF.
[17] J. Field, Breeze blocks. Building Services Journal, December, Architects:
[2] K.J. Lomas, M.J. Cook, Sustainable buildings for a warmer World, in:
Proceedings of the World Renewable Energy Congress, Aberdeen, May Short & Associates, Consulting Engineers: Environmental Design Part-
2227, Elsevier, (2005), p. 26, ISBN: 0-080-44671-X. nership, 2000, pp 1822 + front cover.
[3] B. Krausse, M.J. Cook, K.J. Lomas. Environmental performance of a [18] S. Pidwell. Deep heat in Lanchester Library by Short and Associates.
Architecture Today, No. 115, 2001, pp. 3849, ISSN 0958-6407
naturally ventilated city centre library, in: Proceedings of the Conference
Comfort and Energy Use in BuildingsGetting Them Right, Windsor, [19] T. Monk, 2001. Cunning Plan, Brick Bulletin, Summer, pp 810 and front
UK, p. 12. cover.
[20] C.A. Short, K.J. Lomas. Exploiting opportunities for natural displacement
[4] P.F. Linden, G.F. Lane-Serff, D.A. Smeed, Emptying filling boxes; the
ventilation in a US continental climate, Building Research and Informa-
fluid mechanics of natural ventilation, Journal for Fluid Mechanics 22
(1990) 309335. tion, in press.
[5] C. Gladstone, A.W. Woods, On buoyancy-driven natural ventilation of a [21] K.J. Lomas, M.J. Cook, D. Fiala., 2006. Low energy architecture for a
severe US climate: design and evaluation of a hybrid ventilation strategy,
room with a heated floor, Journal of Fluid Mechanics 441 (2001) 293314.
[6] R. Asbridge, R. Cohen, Probe 4: Queens Building, Building Services Energy and Buildings, in press.
Journal 18 (4) (1996) 3538, ISSN 0951-9270. [22] H. Graves, R. Watkins, P. Westbury, P. Littlefair, Cooling buildings in
[7] BRECSU, The Queens Building De Montfort UniversityNew Practice London: overcoming the heat island, Report BR431, BRE Centre for
Environmental Engineering/DETR, 2001, 32 pp.
Final Report, vol. 102, Department of the Environment, 1997.
[8] M. Swenarton, Low energy gothic: Alan Short and Brian Ford at Leicester. [23] CIBSE, Guide J; Weather Solar and Illuminance Data, Chartered Institu-
Architecture Today, No. 41, 1993, pp. 2030, ISSN 0958-6407 tion of Building Services Engineers, 2002.
[9] R. Bunn, Will natural ventilation work? Building Services Journal 15 (10) [24] CIBSE, Ventilation and air conditioning, CIBSE Guide B2, Chartered
Institution of Building Services Engineers, 2002, , ISBN: 0 900953 96 9.
(1993) 4142, ISSN 0951-9270.
[10] BRECSU, A Performance Specification for the Energy Efficient Office of [25] REHVA, Displacement ventilation in non-industrial premises, in: H.
the Future, BRECSU, for the DOE Energy Efficient Office of the Future Skistad (Ed.), Guidebook No. 1, Federation of European Heating and
Air-conditioning Associates, 2000, 95 pp.
(EOF) project, General Information Report 30, 1995, 24 pp.
[11] M.J. Cook, C.A. Short, Natural ventilation and low energy cooling of [26] ANSI/ASHRAE, Thermal Conditions for Human Occupancy, American
large. Non-domestic buildingsfour case studies, The International National Standards Institute (ANSI), American Society of Heating,
Journal of Ventilation 3 (4) (2005) 283294, ISSN 1473-3315. Refrigeration and Air-conditioning Engineers (AHSRAE), Standard 55,
2004 170 pp.
[12] C.A. Short, Q.M. Pop, M.J. Cook, D. Fiala, K.J. Lomas, Passive down-
draught evaporative cooling of a Central London institutional building, in: [27] M.J. Holmes, E.R. Hitchin, An example year for the calculation of energy
Proceedings of the 20th Conference on Passive and Low Energy Archi- demands in buildings, Building Services Engineering 45 (1978) 186190.
tecture (PLEA), Santiago, Chile, 912 November, (2003), p. 5. [28] W. Marion, K. Urban, Users Manual for TMY2s, Typical Meteorological
Years, National Renewable Energy Laboratory, 1995 49 pp. approx.
[13] C.A. Short, K.J. Lomas, A. Woods, Design strategy for low-energy
ventilation and cooling within an urban heat island, Building Research [29] ESRU, ESP a building and plant simulation system, user guide. Energy
and Information 32 (3) (2004) 187206, ISSN 0961-3218. Systems Research Unit, University of Strathclyde, Glasgow, 1998.
[30] CFX International, CFX 4.4 User Manual, AEA Technology, Didcot,
[14] M.J. Cook, K.J. Lomas, H. Eppel, Design and operating concept for an
innovative naturally ventilated library, in: Proceedings of the CIBSE 99 Oxfordshire, UK, 2001.
National Conference, Harrogate, UK, (1999), pp. 500507, ISBN: [31] G. Ward Larsen, R. Shakespeare, Rendering with Radiance: The Art and
0900953977. Science of Lighting Visualisation, Morgan Kaufmann, San Francisco, 1998.
[32] BRECSU, Energy Use in Offices, Energy Consumption Guide 19, Build-
[15] M.J. Cook, K.J. Lomas, H. Eppel, Use of computer simulation in the
design of a naturally ventilated library, in: Proceedings of the PLEA 99 ing Research Energy Conservation Support Unit, Energy Efficiency Best
Practice Programme, 2000, p. 24.

You might also like