From the Driver pull down menu select Modbus RTU Slave
Leave the Baud as 19200
Leave the Parity as NONE
Leave the Stop Bits as 1
Leave the Data Bits as 8
Change the Node Address to 2
On the Modbus Data Table File Numbers modify the Holding Registers (4XXXX) to 9.
This number is the file number that we have created earlier and named it as WIRELESS.
Press Apply and then press OK to close this window.
6. On the Data Files menu double click on the N9 WIRELESS, it will open a new window: