You are on page 1of 8

Volume VI Issue 1 A publication for the engineering community Fa11 2004/Winter 2005

Multiple Fan Systems - Fans in Series and Parallel


In most fan systems a single fan is critical, especially at very rated as a single unit in order for
is selected for the required low flow rates for long time AMCA rating definitions and
system design rating. Various intervals. practices to apply. To simplify
methods of control are employed selection and control, two fans of
3. Supply and exhaust fans
such as dampers, variable inlet the same size are typically used
operating on opposite ends of
vanes, variable pitch blades or with the required flow rate
a system decrease the pressure
variable speed to meet other defined by the inlet conditions of
build-up in a duct or space
operating points defined by the the first fan. The combined total
compared to a single fan. It is
system duty cycle. This may pressure across both fans will be
usually easier to control a zero
even include an allowance for the sum of the individual total
point location or maintain low
future expansions. pressure of each fan. Total
pressures (such as the draft
pressures are used instead of
Sometimes it is advantageous to over a fire in a boiler) if supply
static pressure because the fans
use more than one fan in a and exhaust fans are used.
can actually be different sizes
system. The fans may be located
4. Critical systems are often and a change in fan or
in close proximity to each other
equipped with redundant or connecting duct areas has an
such as mounted on a common
back-up fans in case of a fire influence upon static pressure
shaft, or separated by quite a
or accident in a tunnel or some values.
distance such as a supply and
other emergency that requires
exhaust fan. Most often there is There may also be by-pass
a sudden increase in flow.
some compelling reason to use ductwork around the second fan
Redundant fans are also used
more than one fan in a single if only one fan is run for a period
to eliminate down-time during
system. of time. These losses must be
fan maintenance.
added to the normal system
1. One fan may be too large and
5. Some systems for process resistance requirements.
not fit into the desired space,
applications may require
or it may weigh too much if
pressures that are greater than INSIDE THIS ISSUE
supported on upper levels.
a single fan can produce or
2. The required operating range when noise may be a special
of the system may necessitate concern. When this occurs, Silica Gel Desiccant . . . . . . . . . .5
multiple fans instead of one two fans are placed in series
large fan controlled over a with each taking about one-
wide operating range. half of the pressure. Metric Conversion Factors
Multiple fans for capacity
control may be more Rating Two Fans in Series for Fan Application Per
economical if cost of operation Two fans in series are normally
AMCA Standard . . . . . . . . . . . . .6

Whats New at Greenheck . . .8

P.O. Box 410 Schofield, WI 54476


715.359.6171 Fax 715.355.2399 www.greenheck.com
Copyright 2005 Greenheck Fan Corp.
2 Engineering Update Fall 2004/Winter 2005

Multiple Fan Systems - Fans in Series and Parallel, continued from page 1

What is the quickest and easiest Two fans in series


way to select two fans in series?
1. Establish the system
requirements in terms of total
pressure. If they are known only
in terms of static pressure, total 10
pressure values may be
calculated by adding the velocity 8
pressure corresponding to the Total of
velocity passing through the Total Pressure 2 Fans
outlet of the second stage fan to 6
the system static pressure
requirements. 4

2. If axial fans or inline fans are Curve for


being considered, select each fan 2 each Fan
for the flow rate required and
one-half of the system total 0
pressure requirements. 0 2 4 6 8 10 12 14 16
If centrifugal fans are being Flow
considered, select each fan for of total pressure and that the involved, parallel fan
the flow rate required and one- fans are selected using total applications may use multiple
half of the system total pressure pressure. fans. In this case the selection
requirements plus an allowance process is straight forward in
for interconnecting ductwork Rating Fans in Parallel that each fan will be selected for
losses, typically one inch of total In most instances fans in parallel the same static or total pressure
pressure. will be in some form of plenum with the flow rate being the total
application. Unlike fans in series flow divided by the number of
It must be realized that the above
when typically only two fans are fans. Use care when selecting
selection process is approximate
in that the actual individual o Fans in parallel
Parallel
Two fans in
performance of each fan is not
the same. Both fans will handle
the same mass flow of air but not
10
volumetric flow rate. This is the
result of differences in the inlet
densities of each fan caused by 8
differences in the inlet absolute
Total Pressure

pressures and differences in the 6


temperatures resulting from the Do not rate above this line
possible heat of compression or
motor heating etc. by the first 4
stage fan. Curve for Total of
2 each Fan 2 Fans
The greatest significance is that
the rating process can be
simplified by making sure the 0
0 2 4 6 8 10 12 14 16
system requirements are in terms Flow


Engineering Update Fall 2004/Winter 2005 3

Multiple Fan Systems - Fans in Series and Parallel, continued from page 2

fans in parallel to ensure that the operation, consideration must be together. It may be advisable to
system resistance remains on a given to those times when only close inlet vanes or dampers
stable portion of the fan curve at one fan is running. This may be during start-up to minimize
all times. This is particularly true during start-up, during repairs horsepower requirements. Once
when the fans have a or as part of a flow control the fans are up to speed, the
pronounced surge area or a dip scheme based upon the number controls may be opened.
in the fan curve and some form of fans running.
Variable pitch vane axials, which
of control is applied. A good rule
1. Start-up conditions - In have a dip in the fan curve,
of thumb is to ensure that the
general, as long as the system should be started with the blade
operating point with all fans
curve and the fan curve always pitch reduced and then opened
running is no higher than the
up once at speed. If the first vane
lowest pressure in the dip. This
axial has been started, it is best
minimizes the possibility that the Fan Curve
Total Pressure

to reduce its blade pitch and start


fan will hunt back and forth
the next fan at the same pitch.
across the peak of the curve
When both fans are up to speed
looking for an operating point.
rve and aerodynamically balanced,
This policy also minimizes the Cu
te m increase the blade pitch of both
likelihood that the fans will Sy
s
fans to the desired operating
experience unequal loading
condition.
causing differences in motor load
Flow
or creating unequal velocity Fans in parallel should have
intersect at a stable operating
profiles within the plenum which some form of isolation damper to
point, no problem should be
may result in a system effect. prevent the air from an
encountered during start-up or
energized fan from going back
Additional Considerations during continuous operation.
through a fan that is not
When a system depends upon Centrifugal fans or fixed pitch
energized. The damper also
more than one fan for proper vane axial fans should be able to
serves to minimize the shock
be started individually or
Vane Axial Fans in Parallel Double Width Centrifugal Fans in Parallel

Airflow
1.5 D 1.5 D

Airflow

2D 2D

Airflow

Airflow

1.5 D 1.5 D


4 Engineering Update Fall 2004/Winter 2005

Multiple Fan Systems - Fans in Series and Parallel, continued from page 3

during start-up of bringing a problem. The motors of the fans What is the relative location of
windmilling fan to a stop and left running must be sized the rating point on each fan
then up to speed again. This is properly by taking into account curve under all operating
not good for the fan, motor or the shape and slope of the conditions? Does the operating
system. A mechanical back stop horsepower curve further out to point remain on a stable
clutch can also be used to the right. With fewer fans portion of the curve?
eliminate windmilling of fans running, the system line will
Does the location of the rating
installed in parallel. intersect the fan curve further
point allow the use of the fan
out to the right than with all the
The type of isolation damper control desired and the range
fans running. As an example,
used will vary with the type of of flow desired?
with a vane axial fan the power
fan. Backdraft or opposed-blade Taking into account the range
may drop off but with a forward
control dampers are used at the of operation and numbers of
curved fan the power will
discharge on double width fans, do the motors satisfy the
increase due to the constantly
centrifugal fans. Butterfly power required?
rising horsepower characteristic.
dampers are commonly used at
Are there properly designed
the discharge of tubular inline For close-coupled fans in series,
isolation dampers or other
fans (axial, centrifugal, and it is not advisable to run one fan
provisions in case some fans
mixed flow). Isolation dampers with the other off. Obviously, an
are shut down? Are leakage
for plenum fans should be isolation damper will stop the air
requirements satisfied?
located farther away from the entirely. Without an isolation
fan, either up stream or down, in damper, the fan shut down will Are the system requirements
order to minimize the loss windmill, but the pressure drop satisfied under all operating
through the dampers. across it when added to the conditions?
reduction in pressure having Are sound levels acceptable
2. Continuous operation with
only one fan running will likely under all operating
one fan - All equipment will
make the system useless. conditions?
need periodic maintenance and
repair. This means that at least Summary Satisfactory applications require
one fan is shut down while the When more than one fan is used satisfactory answers to all of the
others are running. For fans in in a system, whether in series or above.
parallel equipped with isolation parallel, the following questions
dampers, this is generally no must be answered.

Free for the asking!


Greenheck Product Application Binder
Greenheck would be pleased to send you an Application Binder that
includes all our published articles. And, every 6 months we will send
you printed copies of any additional published articles.

To order an Application Binder fax your company information to


715-355-6564 or e-mail cheryl.aderhold@greenheck.com

Application articles can also be found on our web site


www.greenheck.com Click on the Application Info button, click on
Application Articles.


Engineering Update Fall 2004/Winter 2005 5

Silica Gel Desiccant


Silica gel is a highly porous solid (typically between
adsorbent material that 40 and 60%). 40

structurally resembles a rigid When the Silica Gel


sponge. It has a very large airstream with the

Adsorption - Lb. H20 per 100 Lb. Adsorbent


internal surface composed of higher relative 30
Alumina
myriad microscopic cavities and humidity passes (Sph erical)

a vast system of capillary over the silica gel Molecular Sieves


channels that provide pathways coated wheel, 20
connecting the internal moisture is
microscopic cavities to the adsorbed from the Alumina (Granular)
outside surface of the sponge. airstream into the 10

The characteristic curve for silica gel. Then


adsorption of water on silica gel when the
is shown in Figure 1 as % weight airstream with the 0

adsorbed versus relative lower relative 0 20 40 60


Relative Humidity (%)
80 100

humidity of the airstream in humidity contacts


Source: Davison Chemical Co. Figure 1
contact with the silica gel. The the silica gel,
amount of water adsorbed rises moisture is used to mitigate excessive
almost linearly with increasing desorbed (removed) from the formaldehyde levels in mobile
relative humidity until RH silica gel and put into the homes, concern was expressed by
reaches about 60%. It then airstream. some people that enthalpy type
plateaus out at about 40% In this ventilation energy heat exchangers that transferred
adsorbed as relative humidity recovery application, the silica moisture as well as heat might
approaches 100%. The curve for gel has all of its surface area also transfer excess amounts of
molecular sieves, by contrast, covered with at least a formaldehyde gas due to its high
rises rapidly to plateau at about monomolecular layer of water solubility in water. Accordingly,
20% adsorbed at 20% relative because it has a greater affinity tests were conducted by the
humidity. This helps to explain for water than any other chemical Lawrence Berkeley Laboratories
why the molecular sieve is an species.With all of the adsorption of the U.S.D.O.E., on two
excellent choice for regenerated sites occupied by water, the silica enthalpy type exchangers to
applications such as desiccant gel will not be able to transfer determine whether this suspicion
cooling and dehumidification other chemical species by was justified. Results were
systems which are designed to adsorption and desorption in its presented in ASHRAE paper No.
reduce processed airstreams to normal form. Species that are CH85-03 No. 3 which reported
very low relative humidities. On soluble in water could become that the rotary type enthalpy heat
the other hand, silica gel has dissolved in the adsorbed water exchanger (using lithium chloride
superior characteristics for the and then released when the as desiccant) transferred
recovery of space conditioning water is desorbed but this formaldehyde with only 3-6%
energy from exhaust air. process is limited by kinetics and efficiency. They concluded that
The use of silica gel on rotary does not present a very efficient formaldehyde transfer between
regenerators for energy recovery mechanism for contaminant airstreams by processes other
ventilation applications involves transfer. than air leakage does not
a process cycle where the silica An example of this phenomenon seriously compromise the
gel is alternately exposed to is formaldehyde, a gas which is performance of these enthalpy
airstreams having nearly equal very highly soluble in water. In exchangers.
relative humidities somewhere in the early 1980s when energy
the mid range of this curve recovery ventilators were being


6 Engineering Update Fall 2004/Winter 2005

Metric conversion Factors for Fan Application per AMCA


Standard

Quantity "English" Unit Metric Unit Conversion Factor


Volume cubic feet per minute cubic meter per second 0.00047195
CFM m3/S
cubic meter per minute 0.028317
m3/min
cubic meter per hour 1.6990
m3/hr
liter per second 0.47195
l/s
Pressure inches of water gauge pascal 248.36
in. wg Pa or N/m2
millimeters 25.4
mm
Power horsepower watt 745.70
hp, BHP W or J/s
Kilowatt 0.7457
kw
Torque pound-inch newton meter 0.11298
lb-in. N-m
Density pounds per cubic feet kilogram per cubic meter 16.018
lb/ft3 kg/m3
Speed revolutions per minute revolution per second 0.01667
RPM rps
Velocity, Tip Speed feet per minute meter per second 0.00508
fpm m/s
Dimensions inch millimeter 25.4
in. mm

Multiply "English" Unit by conversion factor to obtain Metric Unit.


For example: 5000 CFM x 0.00047195 = 2.360 m3/s
Divide Metric Unit by conversion factor to obtain "English" Unit.
For example: 62.1 Pa / 248.36 = 0.250 in. wg


Engineering Update Fall 2004/Winter 2005 7

Metric conversion Factors for Fan Application per AMCA Standard, continued
from page 6

Quantity "English" Unit Metric Unit Conversion Factor


Area square foot square meter 0.0929
m2
square inch square millimeter 645.16
mm2
Length foot millimeter 304.8
mm
foot meter 0.3048
m
yard meter 0.9144
m
Mass (weight) ounce gram 28.350
g
pound kilogram 0.4536
kg
Velocity feet per second meters per second 0.3048
m/s
feet per minute meters per second 0.00508
m/s
miles per hour meters per second 0.44704
m/s
Volume (capacity) cubic inch cubic centimeter 16.3871
cm3
cubic yard cubic meter 0.7646
m3
gallon (U.S.) liter 3.785
l
gallon (imperial) liter 4.546
l

Multiply "English" Unit by conversion factor to obtain Metric Unit.


For example: 5000 CFM x 0.00047195 = 2.360 m3/s
Divide Metric Unit by conversion factor to obtain "English" Unit.
For example: 62.1 Pa / 248.36 = 0.250 in. wg


8 Engineering Update Fall 2004/Winter 2005

Whats new at Greenheck

Tamper Resistant Centrifugal Roof Exhaust Fans From


Greenheck
Greenheck's Model NYD and NYB tamper-resistant centrifugal roof
exhaust fans prevent entry into the fan unit or building. Constructed of
galvanized steel, the fans hinged hood provides easy access to all
internal components. Belt drive Model NYB and direct drive Model NYD
feature a backward inclined wheel and are available in 10 different sizes,
with capacities from 169 to 8,080 cfm and up to 1.25 in. wg of static
pressure. Greenheck Models NYD and NYB are licensed to bear the
AMCA Seal for Air Performance.

Greenheck Offers Indirect Gas-Fired Make-Up Air Units


Greenheck's new line of Model IG Indirect Gas-Fired Make-Up Air units
feature a single-piece design for maximum weather resistance. Model IG
features a power vented 80% efficient gas fired furnace and is ETL
labeled to ANSI Standards Z83.3 and CGA 2.6. The IG units are supplied
with double width, double inlet Greenheck forward curved blowers
tested to AMCA standards for high efficiency and low sound levels.
Airflow volumes range from 800 to 7,000 cfm with heating capacities up
to 400,000 BTU/hr input.
Greenheck's Model IG features large access panels for ease of inspection
and maintenance, and is factory assembled and wired to minimize field
installation costs. Units are available in horizontal and down discharge
arrangements with optional evaporative cooling section and mixing box
for recirculation.

Greenheck Presorted Standard


P.O. Box 410 U.S. Postage
Schofield, WI 54476 PAID
Greenheck

Change of address?
Please help us keep our
mailing list up to date. If
you have any changes,
additions or deletions,
please note them on this
page and fax it to:
715-355-6564
Thank you.

You might also like