You are on page 1of 16

High impedance differential relay 7VH80

Fig 1. High impedance differential protection relay 7VH80


Features 1. The individual connections static measurement circuit from
are marked sequentially from left the main current transformers.
l Robust solid state design. to right (viewed from the rear).
l Inrush stabilization through See fig. 3. The AC measured current is
filtering. band pass filtered and rectified
l Auxiliary dc supply monitor. Mode of Operation to a proportional dc voltage.
l Fast operating time (15ms). This voltage is monitored by a
l Voltage operated target The 7VH80 relay is a single pole Schmidt trigger circuit. If the set
indicator. sensitive current relay. The AC dc voltage, equivalent to the
l Simple voltage setting. input impedance of the relay is relay nominal operating current
adjusted by means of a series of of 2OmA is exceeded, then the
Applications high wattage resistors. The trigger operates to energise the
relay setting is a voltage pick-up command output relay as well as
The 7VH80 relay is designed for value that is set by means of the operation indicator.
fast and selective differential connecting pins that are inserted
protection based on the high in the front of the relay module. The auxiliary dc supply is
impedance circulating current When the pin is inserted, the connected to terminals 4A1(+ve)
principle. It is used for the corresponding series resistor is and 4A2(-ve). An auxiliary dc
protection of machine stator shorted out and when the pin is supply monitoring circuit
windings, busbars and withdrawn, the resistor is in consisting of a green LED and a
transformer and reactor circuit. Each pin socket has a N/C relay contact is provided to
windings against phase to phase voltage value. The relay voltage indicate the status of the dc
and phase to earth short circuits. setting is determined by adding supply.
up the socket value all of the
Design withdrawn pins (series resistors The relatively simple electronic
in circuit) plus the minimum base design of the 7VH80 provides a
The withdrawable module is voltage setting. These series robust and reliable relay suitable
housed in a 7XP2010 metal resistors are termed stabilizing for all high impedance circulating
case suitable for flush mounting. resistors and the setting on the current protection applications.
The plug connector at the rear of relay determines the steady
the case has one screw and one state rms voltage required for The employ of a solid state
snap on terminal for each relay operation. measurement circuit ensures a
connection point. The plug relatively constant and fast
connector is marked with a co- The input from the CTs is operating time.
ordinated system depending on connected to terminals 1A1 and
the mounting location e.g. 4A1 1A2. The relay input transformer See fig. 2 for the connection
denoted row 4, block 1, column galvanically isolates the relay diagram.
High impedance differential relay 7VH80

Fig 2. Connection diagram for 7VH80 relay

Fig 3. 7VH80 relay in flush mount case

2
High impedance differential relay 7VH80

Technical Data

CT Circuits
Normal Frequency 50 Hz or 60 Hz

Thermal Withstand
1 sec 5 x setting (volts)
Continous 2 x setting (volts)

Measuring Circuit

Setting Range:
24 Volt version 24+24+24+24+24+120 Max 240 Volt
6 Volt version 6+6+6+6+6+30 Max 60 Volt

Tripping Time
2 x setting 30 ms
3 x setting 20 ms
5 x setting 13 ms

Pick up to drop out ratio 0.95

Reset Time 20 ms

Supply and Reset voltages


24V dc 20%
3OV dc 20%
48V dc 20%
110/125V dc 20%
22OV dc 20%

Supply Burden (at rated voltage)

For all voltages


Quiesent 4W
Picked up 5W

Contacts Command Output Alarm

Number of Contacts 2 N/O 1 N/C


Make 1 000 W/VA 3OW/VA
Break 3OW/VA 3OW/VA
Carry 30A for 0,5s and 5A continuous
Max. Switching Voltage 25OV AC/dc

Indication 1 off voltage operated target indicator

Environmental Withstand

Max. Temperatures, during


Service - 10C to + 55C
Storage - 25C to + 55C
Transport - 25C to + 70C

Humidity, acc. to DIN 40 040 class F

3
High impedance differential relay 7VH80

Vibration, service 0.5g between


60 to 500 Hz
0.035 mm amplitude
between 1 0 to 60 Hz

Vibration, transport 2 g between


8 to 500 Hz
7,5 mm amplitude
between 5 to 8 Hz

Insulation Tests
HV Test IEC 255-5 2kV (rms)., 50/60 Hz; 1 min
Impulse Test IEC 255-5 5kV (peak); 1,2/50 s; 0,5J; sec
3 positive and 3 negative
shots at intervals of 5s

High Frequency Test 2,5 kV (pea k); 1 MHz;


IEC 255-22-1 = 1,5 s; 400 shots/s
Class Ill duration 2s

EMI Test

IEC 801-3 20 MHz to 1000 MHz at 10V/m field


ANSI/IEEE C37.90.2 strength

Weight Dimensions

Withdrawable Module 3U; 12 slots of 5.08 mm

Case

Standard metal case for 7XP2010-2C


flush mounting

Size 1/6 of 19" rack

Extra frame for surface 7XP21


mounting

Enclosure protection IP51


Mass Approx. 1kg

Modular Terminal Block


2
Each terminal provides one snap-on 1.5 mm wire
connection one tunnel type screw
connection

4
High impedance differential relay 7VH80

Ordering Data

Order No.
High impedance differential relay 7VH80 - C A
Supply Frequency
50 Hz 0
60 Hz 1
Voltage Range
24V Steps with Flag 0
6V Steps with Flag 1

Auxiliary Supply Voltage (Not Isolated)


24V dc 1
30V dc 2
48V dc 3
110/125V dc 4
220V dc 5
Case Option
Module in Case C

With Varistor 0
Without Varistor 1
Reset Voltage
24V dc 1
30V dc 2
48V dc 3
110/125V dc 4
220V dc 5

ORDERING DATA
Please specify the varistor type required for your application or consult your nearest Siemens office.

5
High impedance differential relay 7VH80

Fig 4. Restricted earth fault protection of power transformer windings

6
High impedance differential relay 7VH80

Fig 5. Phase and earth fault protection of a generator

Relay setting
7
High impedance differential relay 7VH80

List of abbreviations

IE = Current transformer exciting current at relay setting voltage.


(referred to the CT secondary current)
IF = Maximum value of primary through fault current for which protection must remain stable.

IFM = Maximum value of primary fault current for internal fault.

lp = Primary current for operation of protection.

IR = Relay operating current.

ISH = Current in shunt resistor at relay setting VR.

N = Turns ratio of current transformer.

n = No. of current transformers in parallel with relay.

RCT = Secondary resistance of current transformer.

RL = Lead resistance between furthest current transformer and relay connection point.

RR = Relay impedance.

RSH = Value of shunt resistor.

VF = The theoretical voltage which would be produced across the relay circuit
under internal fault conditions.
I FM
VF ( RCT + 2 RL + RR )
N

VK = Knee point voltage of current transformer.

VP = Peak voltage across relay circuit under maximum internal fault conditions.

VS = Minimum Setting voltage. (Calculated)

VR = Relay setting voltage.

K = Varistor constant.

B = Varistor constant.

8
High impedance differential relay 7VH80

Calculation of relay setting

The minimum setting voltage to point voltage must be VK 2VR. including the varistor is given in
ensure stability is The operating current of the the table below (Fig 1.). It must
I FM be appreciated that varistors
VS ( RCT + 2RL ) relay is 20mA irrespective of the
voltage selected excluding the have large tolerances and these
N
The relay plug setting voltage VR current drawn by the external figures are given for guidance
must be set to the nearest tap varistor. When a standard only.
above Vs. The minimum knee varistor is included with the
relay, the relay operating current

Setting Voltage VR 24 48 72 96 120 144 168 192 216 240


in volts
Relay current IR 20 20 20 22 22 23 25 26 28 30
(including varistor) in mA

Table 1
The primary current for Two types of configuration from which the magnetizing
operation is given by are generally provided: current curve versus the
lP = N (IR + nIE) secondary voltage is shown.
If the resultant value of lP is too single phase faults; requiring From this curve, it is easy to
low it may be increased by the one 7VH80 relay determine the magnetizing
addition of a shunt resistor RSH polyphase faults; requiring a current IE for a secondary
to give a current of grouping of three (3) 7VH80 voltage of V.
ISH = VR / RSH relays
The new increased value of Current transformer CT supervision circuit
primary current supervision, if called for,
lP = N (IR + nIE + ISH) protects against the accidental If the CTs have broken or
opening of a CT connection. shorted connections, the
Setting advice This occurrence normally protective relay may detect this
causes a fault current that is condition as a busbar fault and
With particular reference to too low to activate the relay therefore trip all the circuit
high impedance busbar circuits, however the condition breakers in that zone.
protection, the plant and should be signalled before the If several CTs are associated
equipment should have appearance of an actual fault. in the zone, the disconnection
protection with the following The supervision would register of one of them (corresponding
features: the low unbalanced current and perhaps to a lightly loaded
adequate sensitivity control a time delayed output feeder) will result in a very low
fast response time alarm. fault current measurement.
stability, when external faults If this unbalance is lower than
occur Knee-point voltage of current the 7VH80 setting, this
selectivity to allow transformers condition will not be detected.
disconnection of only the Therefore a more sensitive
faulted section The CTs will not be saturated monitoring circuit is required for
CT supervision.
permanent supervision of the by the short-circuit current if the
current transformers knee-point voltage is greater
than twice the maximum This supervision circuit
(optional)
voltage likely to be applied operates with a time delay to
across the terminals of the avoid a false alarm signal in
Relay operation shall not
relay during the fault. case of a busbar fault. When
occur on: choosing a setting the following
VRMAX = 2 2VK (VF VK ) rule should generally be
saturation of the CTs by the At the maximum secondary adopted:
transient dc component through fault current the The supervision relay must be
when a serious fault occurs varistor should limit the voltage sensitive to an unbalance
outside the zone to 1 5OOV rms if possible. corresponding to a busbar
accidental open or short current of 25A or to 10% of the
circuit of the secondary of Determination of current in the least loaded
one or more CTs magnetizing current IE ingoing or outgoing feeder. The
highest current value will be
The manufacturer of the adopted.
current transformer supplies Further details may be provided
the magnetic characteristics on request.

9
High impedance differential relay 7VH80

Ammendment 1 to page 10 of 7VH80 Publication G 53300-Y33-U19-1-18

Varistor Selection

Each 7VH80 relay is normally relationship between resistance If the current transformer
applied with an external varistor and applied voltage is non-linear, secondary voltage is to be
which must be connected i.e. an increase in the applied limited to a safe level
across the relay input terminals. voltage will result in a decrease during maximum internal fault
The varistor limits the voltage in the resistance and hence an conditions then a varistor may
developed across the CT and increase in the current. The be required. Generally if
relay terminals under fault change in resistance occurs VRMAX > 2KV
conditions. instantaneously. then a varistor is required
A varistor is a non-linear or The electrical characteristics can
B
voltage dependent resistor. It is be expressed as V = KI where
a ceramic semi-conducting K and B are constant for any one
VRMAX = 2 2VK (VF VK )
resistance material in which the varistor.

Relay Voltage Setting K B Varistor type


Up to 125V rms 450 0.25 600A/S1/S256
125 - 240 rms 900 0.25 600A/S1/S1088

Table 2

K Characteristic Max.Continuous Rating - rms


450 2OOV
900 35OV
Varistor Assembly Type Unit K Value Short Time Rating
Standard 600A/S1/S256 450 22A for 3 seconds
30A for 2 seconds
45A for 1 second
Standard 600A/S1/S1088 900 17A for 3 seconds
30A for 1.5 seconds
39A for 1 second

Table 3

Installation and
Commissioning Instructions
Installation
Protective relays, although The relays are either despatched sustained in transit. If damage
generally of robust construction, individually or as part of a due to rough handling is
require careful treatment prior to panel/rack mounted assembly in evident, a claim should be
installation. By observing a few cartons specifically designed to made to the Transport
simple rules the possibility of protect them from damage. Company concerned
premature failure is eliminated Relays should be examined immediately and the nearest
and a high degree of immediately they are received to Siemens Office should be
performance can be expected. ensure that no damage has been promptly notified. Relays which
are supplied unmounted and
not

10
High impedance differential relay 7VH80

intended for immediate Commisioning preliminaries tests, must subsequently be


installation should be returned to replaced.
their protective cartons. Inspection
It is only necessary to check the
Care must be taken when Carefully examine the module relay at the setting on which it is
unpacking and installing the and case to see that no damage to be used. The relay must not
relays so that none of the parts has occurred during transit. be used at any setting other than
are damaged or their settings Check that the relay serial that for which the setting has
altered and must at all times be number on the module, case been calculated.
handled by skilled persons only. and cover are identical, and that
the model number and rating Commissioning Tests
Relays which have been information are correct. Test Equipment
removed from their cases should
not be left in situations where Check that the external wiring is 1 Secondary injection test
they are exposed to dust or correct to the relevant relay equipment capable of
damp. This particularly applies diagram or scheme diagram. providing an AC voltage
to installations which are being supply of up to at least
carried out at the same time as Particular attention should be 120% of the relay setting.
construction work. paid to the correct wiring and 1 Test plug for use with test
value of any external resistors block if fitted.
If relays are not installed indicated on the wiring 3 Calibrated multimeters 0-10
immediately upon receipt they diagram/relay rating information. amp AC 0 - 400 volt AC.
should be stored in a place free 1 Set of primary injection
from dust and moisture in their Note that shorting switches testing equipment
original cartons and where shown on the relay diagram are .
dehumidifier bags have been fitted internally across the
included in the packing they relevant case terminals and General
should be retained. close when the module is
withdrawn. It is essential that If the relay is wired through a
The action of the dehumidifier such switches are fitted across test block it is recommended
crystals will be impaired if the all CT circuits. that all secondary injection tests
bag has been exposed to damp should be carried out using this
ambient conditions and may be If a test block is provided, the block.
restored by gently heating the connections should be checked
bag for about an hour, prior to to the scheme diagram, Ensure that the main system
replacing it in the carton. particularly that the supply current transformers are shorted
connections are to the live side before isolating the relay from
Dust which collects on a carton of the test block. the current transformers in
may, on subsequent unpacking, preparation for secondary
find its way into the relay; in injection tests.
Earthing
damp conditions the carton and
packing may become Danger
Ensure that the case earthing
impregnated with moisture and
connection at the rear terminal
the de-humidifying agent will Do not open circuit the
block, is used to connect the
lose its efficiency. secondary circuit of a current
relay to a local earth bar.
The storage temperature range transformer since the high
is -25 and +55C. Insulation voltage produced may be
lethal and could damage
The installation should be clean,
The relay, and its associated insulation.
dry and reasonably free from
wiring, should be insulation
dust and excessive vibration.
tested between: Secondary injection testing
The site should preferably be
all electrically isolated circuits
well illuminated to facilitate
inspection. The relay should be all circuits and earth Connect the circuit as shown in
mounted in the cut-out or rack Figure 6 and ensure that the
provided (Fig 3.) and wired An electronic or brushless current transformer primary is
according to Figure 2 or the insulation tester should be used, open circuit and that if any
relevant drawing or schematic having a dc voltage not earthing connections are fitted,
diagram. exceeding 1000V. Accessible they do not short out the
terminals of the same circuit primaries of any current
should first be strapped transformers.
together. Deliberate circuit
earthing links, removed for the Increase the voltage until the
relay just operates.

11
High impedance differential relay 7VH80

Record the current at which the operates. The voltage at which connections are correct. A high
relay operates (A2). It should be the relay operates should be reading (twice the injected
approximately 2OmA at setting. within 10% of the relay setting current, referred through the
voltage VR. The primary current current transformer ratio)
Note also the voltage at which for operation and relay current indicates that one of the current
the relay operates which should should be noted. transformers polarity is reversed.
correspond to the setting VR of
the relay with a tolerance of In the case of machine Injection should be carried out
10%. The total secondary protection similar tests must be through each phase to neutral.
current for operation will be carried out by injecting first into
given on ammeter A1.This test each current transformer in turn Where primary injection is not
should be repeated for each to determine the primary fault practicable as in the case of
pole of the relay. setting. restricted earth fault protection
on a transformer it may be
Record the value at which the For large machines the machine possible to check stability by
relay picks up and then reduce itself can be used to provide the means of back energising the
the voltage until it drops off. fault current to check the primary transformer from a low voltage
From these two values calculate fault setting as shown in Figure supply as shown in Figure 9.
the drop off/pick up value. It 10. The machine should be run (eg. 38OV)
should be approximately 0,95. up to speed with no excitation. In the case of machine
The excitation should then be protection similar stability tests
Primary injection testing increased until the relays have must be carried out by injecting
all operated. The primary into one and out of another
It is essential that primary current, relay current and relay current transformer connected
injection testing is carried out to voltage should be noted as each on the same phase.
prove the correct polarity of relay operates.
current transformers. For large machines, the machine
Before commencing any primary Through fault stability itself can be used to provide the
injection testing it is essential to fault current, but the short circuit
ensure that the circuit is dead, With any form of unbalanced must now be fitted as shown in
isolated from the remainder of protection it is necessary to Figure 11. The machine should
the system and that only those check that the current be run up to normal speed and
earth connections associated transformers are correctly the excitation increased until the
with the primary test equipment connected. For this purpose primary current is approximately
are in position. with a restricted earth fault full load, when the spill current
scheme the circuit shown in should be checked.
Primary fault setting Figure 6 may be used. During
this test the relay is shorted out All other types of balanced
The primary fault setting of any and the spill current through the protection should be tested in a
balanced scheme can be relay circuit A2 is measured. similar manner.
checked using the circuit shown The current is increased up to as
in Figure 7. The primary current near full load as possible and At the conclusion of the tests
is injected into each current the spill current noted. The spill ensure that all connections are
transformer in turn and current should be very low, only correctly restored and any
increased until the relay a few milliamps if the shorting connections removed.

ADDENDUM COMMISSIONING TEST RECORD DATE


HIGH STABILITY
CIRCULATING CURRENT RELAY
TYPE 7VH80
STATION CIRCUIT
RELAY MODEL NO. SERIAL NO.
SETTING RANGE CT RATIO
SETTING VOLTAGE RELAY SETTING
SHUNT RES.
OHMS (if fitted)
TYPE OF EXT. CALCULATED PRI.
VARISTOR OP CURRENT

12
High impedance differential relay 7VH80

High impedance differential relay 7VH80

TEST RESULTS
Relay CT Shorting Switch
Secondary Voltage to operate relay

Phase Total Current (A1) Relay Current (A2) P.U. Volts D.O. Volts
A
B
C

Drop off / Pick up ratio check

Table 5

Primary Current to operate relay


Phase Primary Current A1 Relay Current A2 Relay Voltage
A
B
C
N

Table 6

Stability check by primary injection

Restricted Earth Fault


Phases Primary Current Spill Current
A1 A2
A-N
B-N
C-N

Table 7

Circulating Current between two or more sets of current transformers

Phases Primary Current Spill Current


A1 A2
Al -A2
Bl - B2
Cl -C2

Table 8

Where more than two sets of


current transformers are
involved, injection should be
carried out between set 1 and
each other set in turn.

Maintenance

Periodic maintenance is not mounted in poor environmental


necessary. However, periodic conditions.
inspection and test is Repeat secondary injection tests
recommended. This should be to prove correct operation,
carried out every 12 months or making sure the circuit breaker
more often if the relay is trips when the relay operates.
operated frequently or is
13
High impedance differential relay 7VH80

Fig 6. Secondary injection test

Fig 7. Primary fault setting test


14
High impedance differential relay 7VH80

Fig 8. Through fault stability test

Fig 9. Through fault stability test

15
High impedance differential relay 7VH80

Fig 10. Primary fault setting test

Fig 11. Through fault stability test

The information contained in this publication is subject to change without prior notice.

Siemens Limited
P O Box 207 lsando 1600
South Africa
Telephone (011) 921-7000

Issued by Energy and Automation Group - Power Transmission and Distribution

16

You might also like