Statement of distribution pipe losses between the design points and te installation valves

Hazard Group: Flowrate: 1000 L/min

Name and Address: Floor to ceiling height 4m= 400mbar


Design Pipe Pipe No. Eqv Total Pipe Static Nett Mbar
point size Length Turns Lgth Eqv L losses GainX
alarm (mm) (mbar) (mbar)
valve
1A-2A 65 10 1 3 13 455
2A-3A 80 5 1 3 8 128
3A-4A 80 10 2 6 16 256
4A-AV 100 2 2 6 8 35.2
874.2 400 474.2

1A-2A 65 10 1 3 13 455
2A-3A 80 5 1 3 8 128
3A-4A 80 10 2 6 16 256
4A-AV 100 2 2 6 8 35.2
874.2 400 474.2