DSEGenset
TEMPERATURE
BS EN 60068
The DSE8610 is an easy to use The event log will record 250 events KEY LOAD SHARE FEATURES: Ab/Ae Cold Test -30oC
Synchronising Auto Start Control to facilitate easy maintenance. An • Peak lopping/sharing (with BS EN 60068-2-2
Bb/Be Dry Heat +70oC
Module suitable for use in a extensive number of fixed and DSExx60)
multi-generator loadshare system, flexible monitoring, metering and • Sequential set start VIBRATION
designed to synchronise up to 32 protection features are included • Manual voltage/frequency BS EN 60068-2-6
Ten sweeps in each of three major axes
generators including electronic and as well as comprehensive adjustment 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
non-electronic engines. communication and system • R.O.C.O.F. and vector shift
expansion options. protection HUMIDITY
BS EN 60068-2-30
The DSE8610 monitors the • Generator load demand Db Damp Heat Cyclic 20/55oC @ 95% RH
generator and indicates operational Using the DSE PC Configuration • Automatic hours run balancing 48 Hours
status and fault conditions, Suite Software allows easy • Mains (Utility) de-coupling BS EN 60068-2-78
Cab Damp Heat Static 40oC @ 93% RH
automatically starting or stopping alteration of the operational • Mains (Utility) de-coupling 48 Hours
the engine on load demand or fault sequences, timers and alarms. With test mode
SHOCK
condition. all communication ports capable of • Dead bus sensing BS EN 60068-2-27
being active at the same time, the • Bus failure detection Three shocks in each of three major axes
System alarms are annunciated on DSE8610 is ideal for a wide variety • Direct governor and AVR control 15gn in 11mS
the LCD screen (multiple language of demanding load share • Volts and frequency matching DEGREES OF PROTECTION
options available), illuminated LED applications. • kW and kV Ar load sharing PROVIDED BY ENCLOSURES
BS EN 60529
and audible sounder. • Dead bus synchronising IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
+
ETHERNET
DEUTZ
DSE8610 MSC
ISUZU
PERKINS
CATERPILLAR
MTU
7 55xx 75xx 8xxx VOLVO
OTHER
CUMMINS
SCANIA
BUS VOLT FREE GENERATOR SENSING FUEL & START CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
CURRENT VOLTS
D+
+ W/L
ISSUE 3
®
DSEGenset
DSE8610 SPECIFICATION
CRANKING DROPOUTS
FEATURES Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
• Independent earth fault protection alarms expansion capability via DSENet® OFFSET VOLTAGE
• Advanced integral PLC editor • Multiple date and time run • Licence-free PC software +/- 10 V DC
Fully isolated
• 11 Configurable inputs scheduler • IP65 rating (with supplied gasket)
• 8 Configurable outputs • Manual fuel pump control offers increased resistance to water BUILT-IN AVR CONTROL
• Configurable flexible sensor inputs • Fuel usage monitor and low fuel ingress MINIMUM LOAD IMPEDANCE
1000Ω
• DSENet® expansion compatibility level protection • Advanced Internal PLC editor allows Fully isolated
• User configurable RS232, RS485 • Charge alternator failure user configurable functions to meet
GAIN VOLTAGE
and Ethernet communications protection specific application requirements. 0 V to 10 V DC
• Remote SCADA monitoring via • Load switching (load shedding Fully isolated
various DSE software applications and dummy load control) EXPANSION DEVICES
• DSE124 CAN/MSC Extender OFFSET VOLTAGE
• MODBUS RTU & TCP support • Configurable event log (250) +/- 10 V DC
• User configurable MODBUS • Backed up real time clock • DSE2130 Input Expansion Module Fully isolated
• DSE2131 Ratio-metric Input Expansion
pages
Module DIMENSIONS
• Advanced SMS control and fault • DSE2133 RTD & Thermo-couple OVERALL
messaging (additional GSM Expansion Module 240 mm x 181 mm x 42 mm
9.4” x 6.8” x 1.6”
modem required) • DSE2152 Ratio-metric Output
• Easy access diagnostic pages Expansion Module PANEL CUTOUT
including modem diagnostic pages • DSE2157 Output Expansion Module 220 mm x 160 mm
8.7” x 6.3”
• Data logging and trending • DSE2548 LED Expansion Module
MAXIMUM PANEL THICKNESS
8 mm
RELATED MATERIALS 0.3”
TITLE PART NO’S OPERATING TEMPERATURE RANGE
DSE8610 Installation Instructions 053-069 -30 oC to +70 oC
DSE8610 Operator Manual 057-115
DSE8600 PC Configuration Suite Manual 057-119 STORAGE TEMPERATURE RANGE
DSE8660 Date Sheet 055-086 -40 oC to +85 oC