AIRBUS

A318

ATA 26
Smoke Detection
System
Diff to A320

EASA Part 66 B1

A318 26 DIFF B1 E
For training purposes only.
 Copyright by Lufthansa Technical Training.
LTT is the owner of all rights to training documents and training
software.
Any use outside the training measures, especially reproduction
and/or copying of training documents and software − also extracts
thereof −in any format all (photocopying, using electronic systems
or with the aid of other methods) is prohibited.
Passing on training material and training software to third parties
for the purpose of reproduction and/or copying is prohibited without
the express written consent of LTT.
Copyright endorsements, trademarks or brands may not be re-
moved.
A tape or video recording of training courses or similar services is
only permissible with the written consent of LTT.
In other respects, legal requirements, especially under copyright
and criminal law, apply.

Lufthansa Technical
Training
Dept HAM US
Lufthansa Base Hamburg
Weg beim Jäger 193
22335 Hamburg
Germany

Tel: +49 (0)40 5070 2520


Fax: +49 (0)40 5070 4746
E-Mail: Customer-Service@LTT.DLH.DE
www.Luthansa-Technical-Training.com
Lufthansa Technical Training
FIRE PROTECTION A318

26

ATA 26 FIRE PROTECTION


For Training Purposes Only

FRA US/T KrU MAR 2005 Page: 1


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

26−17 LAVATORY SMOKE


GENERAL
Smoke detection
A318
A320 A smoke detection system is installed to detect smoke and/or fire in the lavato-
The lavatory smoke−detection system detects smoke in the lavatories and ries. The lavatory smoke detectors are connected to the related DEU B via a
sends a signal to the Smoke−Detection Control Unit (SDCU). The cargo Controller Area Network (CAN) bus. The DEU B transmits the information to
smoke-detection system detects smoke in the fwd and aft cargo compartment. both CIDS channels. If smoke is detected, the system gives a visual and aural
The detectors are of the ionization type. A safety bus system connects the de- warning to the flight crew.
tectors to the SDCU. This system is made−up of:
When the SDCU receives the smoke signal from one detector in a lavatory it  one smoke detector for each lavatory,
supplies a smoke warning signal to:
 a DEU B
 the Flight Warning Computer (FWC), it displays on the Engine/Warning Dis-
play (EWD) the applicable warning message (possible to disable by PIN-  the CIDS director (Cabin Intercommunication Data System), containing also
programming) the CIDS−SDF (CIDS Smoke Detection Function)
 the Cabin Intercommunication Data System (CIDS), it shows on several Smoke or fire in one of the lavatories causes a detector to signal this alarm
panels in the cabin in which lavatory the smoke is detected. condition to the CIDS director. This alarm condition is then forwarded to the
CIDS−SDF which provides the information to the Flight Warning computer.
The SDCU controls the cargo−compartment smoke−detection system. The
The FWC gives indications on:
SDCU Built−In Test Equipment (BITE) controls and monitors the systems and in-
terfaces with the Centralized Fault Display System (CFDS). It records the unsatis-  the ECAM upper display unit
factory components and system malfunctions. The CIDS gives indications on:
 In case of smoke warning the isolation valves of the cargo−compartment  the flight attendant panel
ventilation system close automatically. They remain closed independently  the area call panel
of the smoke warning signals.
 the attendant indication panel
The cargo−compartment smoke−detection system is installed in the cargo
For Training Purposes Only

compartment. It gives visual and aural warnings in the cockpit, if smoke or fire
is in the cargo compartment. The system includes:
 the smoke detectors,
 the smoke annunciator lights and a TEST pushbutton switch,
 the Smoke Detection Function of the Cabin Intercommunication Data Sys-
tem (CIDS−SDF)
If smoke in the cargo compartment is detected by the system, indications will
be given on the ECAM upper display unit and via smoke warning lights on the
overhead panel.

FRA US/T KrU MAR 2005 Page: 2


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

A320 A318
ECAM
LAVATORY FWC‘s
smoke
LAVATORY
sensors
SMOKELAV H

smoke
sensors CIDS

CAN BUS
DIR 2
DEU B DIR 1
SDF
SDCU
SDF

MIDDLE CFDIU
LINE

CARGO VENT
For Training Purposes Only

CONTROLER

CARGO
smoke
CAN BUS
sensors

wd Cargo Fire Exting. Bottle Contr. Mon. Sys.


ptional
Figure 1 Smoke detection general
FRA US/T KrU MAR 2005 Page: 3
Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

CABIN SMOKE DETECTION INDICATION


FAP smoke detection page
The FAP smoke detection page indicates cabin related smoke alerts and
smoke sensor faults. In the case of smoke alert the page will come up auto-
matically regardless of any other previous selected page or FAP function.
The following messages shall be indicated:
 Smoke alerts with location,
 Sensor faults with location,
 Smoke signal reset.
A system configuration by plug−in memory cassette, the Cabin Assignment
Module (CAM), is installed in the front of the FAP. It defines the smoke detec-
tion properties:
 Definition of chime distribution,
 Definition of AIP indications,
 Assignments of call lights,
 Assignments of ACP indications,
 Assignments of smoke zone reset commands,
 Assignments of flashing modes for smoke indications.
For Training Purposes Only

FRA US/T KrU MAR 2005 Page: 4


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17
For Training Purposes Only

Figure 2 Smoke detection FAP


FRA US/T KrU MAR 2005 Page: 5
Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
SMOKE DETECTOR
26−16

26−16 SMOKE DETECTOR


SMOKE DETECTOR PRINCIPLE

On A320:
On A318:
All smoke detectors are based on the ionization principle. They ionizes the air
The smoke detectors operates on the principle of scattered light. The light
particles that pass between the electrodes. As smoke causes the electrical re-
source, the labyrinth and the photocell are set out in a horizontal plane so that
sistance of the circuit to increase, the voltage in the measurment chamber in-
the photocell cannot receive light. But when there is smoke, the smoke par-
crease to a higher level than the reference chamber. At a set difference level
ticles reflect and scatter a part of the light beam. The photocell receives this
the detector sends a signal to the AEVC.
light and gives an analog signal and set of the alarm.
For Training Purposes Only

FRA US/T KrU MAR 2005 Page: 6


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
SMOKE DETECTOR
26−16

A320 A318

FET
For Training Purposes Only

-
DC
+

Figure 3 Smoke detector


FRA US/T KrU MAR 2005 Page: 7
Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

CFDS MCDU PAGES


Bite test
Because the SDCU is replaced by the CIDS−SDFs, the SDCU menu page has
been modified:
 SDCU title becomes CIDS−SDF1 or 2,
 ON GROUND FAULT has been replaced by a GND SCANNING line key,
 WIRING REPORT line key has been replaced by TROUBLE SHOOT DATA
line key,
 PRINT line key has been replaced by SMOKE WARN TEST line key,
 A CLASS 3 FAULT line key is added,
 A SYSTEM TEST line key is added,
 A GROUND REPORT line key is added,
 SPECIFIC DATA line key is added.
For Training Purposes Only

FRA US/T KrU MAR 2005 Page: 8


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

CFDS SYSTEM REPORT/TEST

< LAST LEG REPORT < AIRCOND F/CTL >


< LAST LEG ECAM REPORT < AFS FUEL >
< PREVIOUS LEG REPORT < COM ICE&RAIN >
< AVIONICS STATUS < ELEC INST >
< SYSTEM REPORT/TEST < FIRE PROT L/G >
POST
* PRINT SEND* < RETURN NAV >
FLIGHT REPORT

NEXT
PAGE

SYSTEM REPORT/TEST CIDS - SDF 1 1/2 CIDS - SDF 1 2/2


FIRE PROT
SDCU FUNCTION LAST LEG CLASS 3
< FDU 1 <REPORT FAULTS >
IS INTEGRATED IN PREVIOUS LEGS SYSTEM
< FDU2 <REPORT TESTS >
CIDS DIRECTORS
< FDU APU 101RH & 102RH <LRU IDENT
For Training Purposes Only

SMOKE WARN
< SDCU <GND SCANNING TESTS >
CALLED CIDS - SDF 1 TROUBLE SHOOT GROUND
<DATA REPORT >
SPECIFIC
< RETURN < RETURN < RETURN DATA >

Figure 4 Smoke MCDU menu


FRA US/T KrU MAR 2005 Page: 9
Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17
FIRE PROTECTION CFDS MENU
On ground, SMOKE WARN TESTS can be selected on the SDCU menu of the
MCDU.
If submenu SMK WARN TEST is selected, a submenu with all smoke detectors
installed is displayed. A test for each smoke detector can be selected by the
line key.
During the test of the lavatory smoke detectors the active CIDS channel sends
a test request to the relative lavatory smoke detector via the DEU B and the
CAN bus.
If the smoke detector is operative it transmits a test−alarm information to the
DEU B. The DEU B transmits the information to the CIDS−SDF via the CIDS
internal bus.
The CIDS starts the cabin indications (chime, FAP, AIP, ACP) and the CIDS−
SDF sets the ARINC 429 outputs to the FWC.
The lavatory smoke warning is displayed on ECAM together with a repetitive
chime and master warning. The test finishes when all indications are con-
firmed or when the MCDU line key RETURN is selected.
NOTE: THE ”SMK DET AVIONICS TEST” IS A PIN−PROGRAMMED OP-
TION.
For Training Purposes Only

FRA US/T KrU MAR 2005 Page: 10


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

SYSTEM TEST

CIDS - SDF 1 CIDS - SDF 1


SYSTEM TEST SYSTEM TEST

TEST OK

< START TEST


< RETURN PRINT * < RETURN PRINT *

SMOKE WARNING TESTS

CIDS - SDF 1 1/2 CIDS - SDF 1 2/2


SMOKE WARNING TESTS SMOKE WARNING TESTS

< SMK DET AVIONICS TEST < SMK DET VCC TEST
< SMK DET FWD LDCC TEST NEXT
For Training Purposes Only

< SMK DET AFT LDCC TEST PAGE


< SMK DET LAVATORY TESTS
< RETURN PRINT * < RETURN PRINT *

Figure 5 Smoke bite test


FRA US/T KrU MAR 2005 Page: 11
Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17
SPECIFIC DATA
If the key ”SPECIFIC DATA” is pressed the system shall transmit a ”SMOKE
WARNING REPORT” page. In case of smoke warning, if ”SMOKE WARNING
REPORT” is pushed, the ”SMOKE WARNINGS REPORT” page layout charac-
teristics shall be identical to the
”PREVIOUS LEGS REPORT” except that:
 The title displayed shall be ”SMOKE WARNINGS REPORT”,
 No failure ”CLASS” shall be displayed,
 In case of a smoke warning during the last leg the leg counter shall indi
cate ”00”,
 In case of a smoke warning on ground the leg counter shall indicate ”GD”.
For Training Purposes Only

FRA US/T KrU MAR 2005 Page: 12


Lufthansa Technical Training
SMOKE DETECTION SYSTEM A318
LAVATORY SMOKE
26−17

CIDS - SDF
SPECIFIC DATA1 2/2
LAST LEG CLASS 3
<INFORMATION:
REPORT FAULTS >
PREVIOUS LEGS SYSTEM
<REPORT
THE SMOKE WARNINGS TESTS >
REPORT INDICATES SMOKE
<LRU IDENT
DETECTORS WHICH HAVE
LED TO A SMOKESMOKE
WARNINGWARN
<GND SCANNING TESTS >
TROUBLE SHOOT REPORT
GROUND
<<DATA
SMOKE WARNING
REPORT >
SPECIFIC
<RETURN DATA >

CIDS - SDF 1 CIDS - SDF 1


SPECIFIC DATA
SMOKE WARNINGS REPORT

INFORMATION:
NO SMOKE WARNING OCCURED
THE SMOKE WARNINGS
REPORT INDICATES SMOKE
DETECTORS WHICH HAVE
LED TO A SMOKE WARNING
For Training Purposes Only

<SMOKE WARNINGS REPORT


<RETURN PRINT * <RETURN PRINT *

Figure 6 Smoke MCDU warning report


FRA US/T KrU MAR 2005 Page: 13
A318 26 DIFF B1 E

TABLE OF CONTENTS
ATA 26 FIRE PROTECTION . . . . . . . . . . . . . . . . . . . . 1
26−17 LAVATORY SMOKE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
CABIN SMOKE DETECTION INDICATION . . . . . . . . . . . . . . . . . . . . . . 4
26−16 SMOKE DETECTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SMOKE DETECTOR PRINCIPLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CFDS MCDU PAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

FRA US/T-5 Kremer JUN 2005


Page i
A318 26 DIFF B1 E

TABLE OF FIGURES
Figure 1 Smoke detection general . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 2 Smoke detection FAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 3 Smoke detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 4 Smoke MCDU menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 5 Smoke bite test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 6 Smoke MCDU warning report . . . . . . . . . . . . . . . . . . . . . . . 13