11kV Outdoor 1250A VCB

Type of Equipment Outdoor VCB


Make & Model To be filled by Manufacturer
Equipment conforms to specification IS:13118/ IEC: 62271-100
Rated voltage 12kV
Rated frequency 50Hz
Rated continuous current 1250A
Rated short time withstand current 26.3kA for 3 Sec
Rated short ckt Breaking current 26.3kA
Rated short ckt making current 65.75kAp
Total creepage distance 300mm min
Rated operating sequence 0-0.3s-co-3 min-co
Rated insulation level 12kV/28kV/70kVp
Degree of protection IP-55
Vacuum interrupter type To be filled by Manufacturer
Type of operating mechanism To be filled by Manufacturer
Aux switches 12No+12NC
Spring charge motor supply 240V AC
Tripping Supply 220V DC
Closing supply 220V DC
Heater supply 240V AC
Paint shade Light grey, shade 631 of IS-5
Local/Remote Selector switch 16A, 240V AC
TNC control switch 16A, 240V AC
Toggle switch 10, 240V AC
Heater 80W
Thermostat 15A, 240V
Illumination lamp LED
Push to OFF type door switch 2A, 240V AC
Socket with ON/OFF switch 6-Pin, 5/15A, 240V
Plug in type relay for anti pumping 24V/220V DC , 2-C/O contacts
Control terminal box
Operation counter Mechanical
MCB DP 10A