Professional Documents
Culture Documents
A. GENERAL 4. ALL THE CONCRETE SHOULD SATISFY THE DURABILITY CONDITION GIVEN BELOW FOR SUPER STRUCTURE CONCRETE ONLY.
A1. THE STRUCTURAL DRAWING SHALL BE READ IN CONJUNCTION WITH THE RELEVANT ARCHITECTURAL, REQUIREMENTS OF CONCRETE D. STRUCTURAL STEEL / SPACE FRAME
ELECTRICAL, MECHANICAL AND OTHER STRUCTURAL DRAWING IN PARTICULAR, CUT-OUTS IN SLAB NO TESTS TEST METHOD SPECIFICATION LIMIT GENERAL NOTE
D1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN OF THE PARAPETS & ARCHITECTURAL FEATURES.,
AND WALLS FOR BUILDING SERVICES SHALL BE READ IN CONJUNCTION WITH THE ELECTRICAL AND AND ANY STRUCTURAL STEEL WORK BY THE SPECIALIZED SUB CONTRACTOR. AND IN ACCORDANCE WITH THE DESIGN LOADS.
MECHANICAL DRAWINGS. 1. temperature ( at placement ) ASTM 1064 25° C max.
for all grades; ''' THE DESIGN CALCULATIONS SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
A2. FOR MAIN SETTING LINES AND LEVELS, REFER TO THE ARCHITECTURAL DRAWINGS. 2. slump mm ( at placement ) BS 1881; pat 102 150 ± 25 mm
ALL DIMENSIONS MUST BE VERIFIED ON SITE AND ANY DISCREPANCIES SHALL BE BROUGHT D2. THE SHOP DRAWINGS SPECIFICATION AND METHOD OF STATEMENTS FOR THE STEEL WORKS SHALL BE SUBMITTED
3. water permeability DIN 1048 18mm max.
TO THE ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION.
TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE PORTION OF WORK INVOLVED.
4. rapid chloride penetration ( RCP ) ASTM C1202 1500 col.. max.
D3. ALL BOLTS SHALL BE GRADE 8.8 TO BS 3692.
A3. ABBREVIATIONS 1.8% col.. max.
5. water absorption BS 1881; part 122
D4. THE PROTECTIVE POINT SYSTEM FOR THE STEEL WORK SHALL BE IN ACCORDANCE WITH THE SPECIFICATION.
EF = EACH FACE
B (B1 & B2) = OUTER & INNER BOTTOM BARS 6. chlorides by weight of cementations material BS 1881; part 124 0.3% max.
D5 ALL STRUCTURAL STEEL WORK SHALL BE GRADE 5275 TO BS EN10025.
T (T1 & T2) = OUTER & INNER TOP BARS 7. sulphates (503) by weight of cementations material BS 1881; part 124 4.0% max.
BW (EW) = BOTH WAYS (EACH WAY) D6 UNLESS SHOWN OTHERWISE ON THE DRAWING, ALL CONNECTIONS SHALL BE IN ACCORDANCE WITH
''' :- TO BE CONFIRMED BY THE SUPPLIER. THE FOLLOWING MINIMUM REQUIREMENTS :
= COLUMN CONTINUED
= COLUMN UNDER NOTE:-2 NOS CONCRETE TEST PRISMS 3m X 3m X 3m TO BE TESTED ON SITE PRIOR TO ANY CONCRETING, ONE FOR SUB STRUCTURE AND
I) ALL WELDS SHALL BE AT LEAST 6mm CONTINUOUS FILLET WELDS ALL ROUND.
= COLUMN TRANSFERRED OR PLANTED AT THIS LEVEL. (NO COLUMN UNDER) ONE FOR SUPER STRUCTURE WITH FULL TEMPERATURE MONITORING ON SITE ALONG WITH DURABILITY TESTS.
II) ALL BOLTS SHALL BE AT LEAST M20. WITH A MINIMUM OF 2 BOLTS OER CONNECTION.
= OPENING IN SLAB OR WALL C5. USE OF CONCRETE ADDITIVES PURLIN BOLTS TO BE IN ACCORDANCE WITH THE SUPPLIERS RECOMMENDATIONS.
EJ = EXPANSION JOINT CONCRETE ADDITIVES APPROVED BY THE ENGINEER SHALL BE USED TO IMPROVE CONSISTENCY, WORKABILITY, QUALITY
III) ALL GUSSET PLATES SHALL BE AT LEAST 10mm THICK.
AND STRENGTH OF CONCRETE
C/C = CENTRE TO CENTRE.
CHEMICAL ADMIXTURES MANUFACTURER SHALL PROVIDE CERTIFIED TEST REPORTS FROM QUALIFIED, INDEPENDENT, ACCREDITED IV) ALL CAP PLATES SHALL BE AT LEAST 12 MM THICK
A4. DRAWINGS.
THE CONTRACTOR SHALL SUBMIT WORKSHOP DRAWINGS SHOWING ALL REQUIREMENTS FOR SERVICES, LABORATORIES SHOWING ACTUAL TEST RESULTS INDICATING MATERIALS COMPLY IN ALL RESPECTS WITH DURABILITY REQUIREMENTS
V) ALL BASE PLATES SHALL BE AT LEAST 12mm THICK.
PENETRATIONS ETC. FOR THE ENGINEER'S APPROVAL. MODIFICATION NECESSITATED BY DETAILED PLANT HIGH RANGE WATER REDUCING ADMIXTURE SHALL BE NAPHTHA LENE SULPHONATE POLYMER BASED MATERIAL LIKE
INFORMATION SHALL BE SUBJECT TO THE ENGINEER'S APPROVAL. CONPLAST SP 2000, OR CONPLAST SP 432 OR EQUAL APPROVED BY THE ENGINEER SHALL BE USED D7 THE STEEL FABRICATOR SHALL BE RESPONSIBLE FOR DESIGN OF CONNECTION IN ACCORDANCE
WATER REDUCING AND RETARDING ADMIXTURE SHALL CONFIRM TO BS EN-934-2 OR ASTM AT 494 TYPE FOR G WITH THE FACTORED DESIGN LOADS GIVE ON THE DRAWING. THE CONNECTION DESIGN CALCULATION
A5. STRUCTURE IS DESIGNED FOR RESIDENTIAL BUILDING (2B + G +3P.+ 23TYP.FLRS) SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF FABRICATION.
B. EARTHWORKS AND FOUNDATIONS D8 THE PURLIN SUPPORTING THE CLAD AREAS OF THE ROOF STEEL STRUCTURE SHALL BE
COLD FORMED Z TYPE PURLINS SELECTED FROM APPROVED SUPPLIER, AND SHALL BE
B1. GRANULAR FILL UNDER FOUNDATIONS AND SLAB CAST-ON-GROUND SHALL BE SELECTED GRANULAR MATERIAL CAPABLE OF RESISTING THE FOLLOWING UNFACTORED WIND LOADS.
LAID IN 200 mm LAYERS AND MECHANICALLY COMPACTED TO AT LEAST 95% OF ITS MAXIMUM DRY DENSITY. C6. CONCRETE FORM WORK - DOWNWARD PRESSURE =2.0 KN/m²
B2. THE BACK FILLING MATERIAL SHALL BE SELECTED GRANULAR MATERIAL COMPACTED AT LEAST 95% OF ITS MINIMUM PERIODS IN DAYS FOR STRIKING OTHER FORM WORK SHOULD BE IN ACCORDANCE WITH THE FOLLOWING TABLE - UPWNWARD PRESSURE =2.0 KN/m²
MAXIMUM DRY DENSITY AND IN ACCORDANCE WITH THE SPECIFICATIONS.
B3. TESTS:- CPT TEST TO BE DONE ON BACK FILLING. AT LEAST 1/150m² SLAB ( PROPS LEFT UNDER ) 7 D9 THE FABRICATION AND ERECTION OF THE STRUCTURAL STEEL WORK SHALL BE
AREA. SUPERVISED BY QUALIFIED PERSONNEL TO ENSURE THAT ALL DESIGN REQUIREMENTS
BEAM SOFFITS ( PROPS LEFT UNDER ) 10
ARE MET. DETAILS OF ERECTION SEQUENCE SHALL BE SUBMITTED TO THE ENGINEER
C. REINFORCED CONCRETE PROPS TO SLABS 16 FOR APPROVAL PRIOR TO COMMENCEMENT OF ERECTION.
-DEAD LOAD-
THE TENSION LAP LENGTH SHOULD BE AT LEAST EQUAL TO THE DESIGN ANCHORAGE SELF WEIGHT + 2.0 KN/m² FLOOR FINISHING + 2.5 KN/m² PARTITION WALLS.
NOTE:- 1. MIX DESIGN TO BE PROPOSED FOR ALL MIXES BY THE SUPPLIER TO THE CONSULTANT FOR APPROVAL . SERVICES 0.5 KN/m²
LENGTH OR EQUAL TO 50 TIMES THE BAR DIAMETER.
2. (*) SUPPLIER SHOULD CONFIRM THE MIX DESIGN FOR CONCRETE WITH NO SHRINKAGE CRACKS. AND THE QUANTITIES -LIVE LOAD-
GIVEN ABOVE ARE TENTATIVE. 5.0 KN/m² & 10.0KN/m.2 ENG. ADNAN SAFFARINI
ALL CONDUITS SHALL RUN ABOVE BOTTOM REINFORCEMENT AND BELOW TOP REINFORCEMENT OF SLAB,
NOTE:- 1. MIX DESIGN TO BE PROPOSED FOR ALL MIXES BY THE SUPPLIER TO THE CONSULTANT FOR APPROVAL INSIDE BEAM AND COLUMN LINK AND BETWEEN WALL EXTERNAL REINFORCEMENT LAYERS. 3) PODIUM FLOOR DESIGN, SUPERVISON & CONSULT
MECHANICAL COUPLERS TO BE USED FOR 40 mm,32 mm AND 25 mm DIA BARS. -DEAD LOAD-
2. MAXIMUM PEAK TEMPERATURE OF CONCRETE TO BE NOT MORE THAN 70° C & THE MAXIMUM DIFFERENTIAL TEMPERATURE SELF WEIGHT + 1.0 KN/m² FLOOR FINISHING. HEAD OFFICE , POST BOX - 4000 DUBAI : 04-2222002
SHOULD NOT BE MORE THAN 18° C. ( SPECIFICATION OF COUPLERS WRITTEN ON FOUNDATION PLAN ALSO. ) SERVICES 0.5 KN/m² ABUDHABI:02-626050,SHJ:06-5733100,ALAIN:03-668970
3. ALL THE CONCRETE SHOULD SATISFY THE DURABILITY CONDITION GIVEN BELOW FOR SUBSTRUCTURE CONCRETE PARALLEL THREADED COUPLERS WITH BAR BREAK GUARANTEE TO BE USED -LIVE LOAD-
ONLY. 5.0 KN/m².
C9. COVER TO REINFORCEMENT. 4) TYPICAL FLOOR SLAB
REQUIREMENTS OF CONCRETE ARCHITECT Ar. AHMED SAFFARINI SIGN
COVER TO REINFORCEMENT SHALL BE FOLLOWS UNLESS SHOWN OTHERWISE ON THE DRAWING :- -DEAD LOAD-
NO TESTS TEST METHOD SPECIFICATION LIMIT PILES =75mm SELF WEIGHT + FINISHES(2.0 KN/m²) & PARTITION WALLS = 2.5 KN/m² STRUCTURE ENG. SHAKEEB SIGN
PERIPHERAL WALL LINE LOAD = 7.5 KN/m
PILE CAP BOTTOM =AS/SKETCH SERVICES 0.5 KN/m²
1. 30° C max. " ELECTRICAL ENG. ----- SIGN
temperature ( at placement ) ASTM 1064 PILE CAP SIDES & TOP =75mm EXTERNAL -LIVE LOAD-
for all grades; ''' GROUND BEAMS =40mm INTERNAL / 75mm EARTH FACES 2 KN/m² MECH. ENG. ----- SIGN
2. slump mm ( at placement ) BS 1881; pat 102 150 ± 25 mm SUSPENDED SLAB =25mm INTERNAL 40mm EXTERNAL 5) TERRACE FLOOR SLAB
3. 10mm max. BEAMS, LINTELS & CAPPING BEAMS =30mm INTERNAL 40mm EXTERNAL -DEAD LOAD- CAD BY: SYED SHAMEEM SIGN
water permeability DIN 1048
COLUMNS =30mm INTERNAL 40mm EXTERNAL /60mm EARTH FACES SELF WEIGHT + 3.5 KN/m² FINISHING + PARAPETS + ARCHITECTURAL FEATURES
4. 1500 col.. max. R.C. WALLS =30mm INTERNAL 50mm EXTERNAL /60mm EARTH FACES SERVICES 0.5 KN/m²
rapid chloride penetration ( RCP ) ASTM C1202 CHECKED BY : DATE: MAY 2016
WATER TANK =50mm INTERNAL 50mm EXTERNAL -LIVE LOAD-
5. BS 1881; part 122 1.8% col.. max. 5 KN/m² +30KN/m² (WATER TANK )
water absorption EXTERNAL RELATES TO CONCRETE FACES EXPOSED TO THE EXTERNAL ENVIRONMENT. REVIEWED BY : DATE:
SEISMIC ZONE - 2B AS/ UBC 97
6. chlorides by weight of cementations material BS 1881; part 124 .15% max. C10. JOINT FILLER/SEALANT SOIL PROFILE TYPE - SC.
EMIRATES: CITY: LOCATION: PLOT NO.:
7. sulphates (503) by weight of cementations material BS 1881; part 124 4.0% max. JOINTS FILLER SHALL BE FLEXL BY FOSROC OR EQUIVALENT APPROVED. JOINT SEALANT SHALL BE
DUBAI DUBAI BUSINESS BAY 346-572
THIOFLEX 600 BY FOSROC OR EQUIVALENT APPROVED. ALL APPLICATIONS ARE TO BE CARRIED OUT BB.A05.032
" :- 10° C FOR RAFT
''' :- TO BE CONFIRMED BY THE SUPPLIER. STRICTLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTION.
PROJECT No.: DATE: SCALE: SHEET NO: