You are on page 1of 1

CURRENT IN AMPERES

100000
10000

20000

30000

40000

50000

60000
70000
80000
90000
1000

2000

3000

4000

5000

6000
7000
8000
9000
100

200

300

400

500

600
700
800
900
5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900

100E

125E
150E
175E
200E
250E
800 800

50E

65E
80E
700 700

600 600

500 500

400 400

300 300

200 200

100 100
90 90
80 80
70 70
60 60

50 50

40 40

30 30

20 20

10 10
9 9
8 8
7 7

6 6

5 5
TIME IN SECONDS

TIME IN SECONDS
4 4

3 3

2 2

1 1
.9 .9
.8 .8
.7 .7
.6 .6

.5 .5

.4 .4

.3 .3

.2 .2

.1 .1
.09 .09
.08 .08
.07 .07

.06 .06

.05 .05

.04 .04

.03 .03

.02 .02

.01 .01
5 6 7 8 9 10 20 30 40 50 60 70 80 90
100

200

300

400

500

600
700
800
900
1000

2000

3000

4000

5000

6000
7000
8000
9000
10000

20000

30000

40000

50000

60000
70000
80000
90000
100000

CURRENT IN AMPERES

TOTAL CLEARING TIME-CURRENT CHARACTERISTIC CURVES


SMD® FUSE UNITS—S&C VERY SLOW SPEED
BASIS—These fuse units are tested in accordance with the proce- COORDINATION—These curves represent the total time required for Sometimes a selected ampere rating will fail to meet the coordi-
dures described in ANSI Standard C37.41-1981, and they are rated a fuse unit to melt and interrupt a fault current, and should be fol- nation requirements in any available speed. In this case the selec-
to comply with ANSI Standard C37.46-1981. As required by these lowed in coordination problems where fuses are applied as “pro- tion of another ampere rating for either the protecting or protected
standards, the minimum melting current is not less than 200% of tecting” devices. fuse usually will satisfy all requirements.
fuse-unit ampere rating, and the minimum melting and total clearing
Any preloading reduces melting time. With respect to the “pro- Do not assume that other fuses that do not employ S&C’s silver,
curves are based on tests starting with the fuse unit at an ambient
tected” fuse, the effect of preloading must be determined and adjust- helically coiled fusible element construction can better resolve a
temperature of 25°C and no initial load.
ments made to its minimum melting curve: coordination impasse than the use of another ampere rating in one
CONSTRUCTION—Fusible elements are silver, helically coiled, and 1. When close coordination is required; of the S&C speed options. Such other fuses, including “time-lag”
of solderless construction. 2. When, regardless of the preciseness of coordination, the pro- speeds, “super-slow” speeds, and “high-surge” speeds, require the
tected fuse is subjected to temporary overloads. use of “safety-zone” or setback allowances and, in addition, they
TOLERANCES—Curves are plotted to maximum test points. All varia-
have larger construction tolerances (plus 20% in current; plus 40%
tions are minus. There are cases where the coordination requirements may be
in terms of time). The application of these two factors will give a time
very exacting, for example, in coordinating a transformer primary
APPLICATION—S&C Very Slow Speed fuse units are for application interval between the adjusted minimum melting curve and the total
fuse with a secondary breaker and a source-side breaker. The time
in circuits where additional time margin in the “protected” fuse is clearing curve greater than in the case of S&C speed options.
interval between the operating characteristics of the two breakers
necessary for coordination, but where load conditions do not
may be very narrow. Under these circumstances there must be an
require fuses of a larger ampere rating.
extremely short time interval between the minimum melting and the
FUSE UNITS AVAILABLE—
Like all high-voltage fuses, these fuse units are intended to total clearing characteristics of the fuse.
accommodate overloads, not to interrupt them. Accordingly, they Type Kv Nom. Ratings Ampere Ratings
The fuse units represented by these curves possess this short
feature fusible elements which are designed with a minimum melting SMD-1A . . . . . . . . . . . . . . . . 115/138 . . . . . . . . .50E through 100E
time interval feature, since—having a nondamageable fusible ele-
current of 200% of the fuse-unit ampere rating (for fuse units rated SMD-2B . . . . . . . . . . . . . . 115 and 138 . . . . . . .50E through 250E
ment of precise construction—they require:
100 amperes or less) or 220% of the fuse-unit ampere rating (for
1. As little as 10% total tolerance in melting current—compared to
fuse units rated over 100 amperes). As a result, these fuse units
the 20% tolerance of many fuses (20% and 40% respectively
have considerable peak-load capabilities; however, they should
in terms of time).
never be exposed to loading in excess of the peak-load capabilities
2. No “safety-zone” or setback allowances.
listed in S&C Data Bulletin 210-190.
This narrow time band normally will provide the desired coordi-
Since these fuse units have silver element construction which is
nation. If the selected S&C Very Slow Speed fuse unit does not meet
not subject to damage by aging or transient overcurrents, it is unnec-
the coordination requirements, check to see if the same ampere
essary to replace unblown fuse units in single-phase or three-phase
rating in the S&C Slow Speed or S&C Standard Speed will satisfy.
installations when one or more fuse units have blown.

Supersedes TCC No. 176-1-9 dated 1-25-88 c1988


TCC NUMBER 176-1-9
s S&C ELECTRIC COMPANY • Chicago
S&C ELECTRIC CANADA LTD. • Toronto
Page 1 of 1
August 29, 1988

You might also like