You are on page 1of 2

JOB NO

첨부 #1
PROJECT TEST PROJECT
Attachment - 1.
VESSEL PROCESS DATA DOC. NO.
( METRIC UNITS ) ITEM NO TEST-V-4902
CLIENT GS PETROCHEMICAL CO., LTD. SERVICE PAGE REV.
LOCATION YEOSU, KOREA CUMENE FLARE K.O DRUM 1 OF 1
01
02
03
04
SAMPLE
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23 NO. REQUIRED One (1) MARK SIZE Q'TY SERVICE REMARKS
24 NOMINAL / NET VOLUME , m3 65.86 51.65 NO. inch 2
25 FLUID NAME Flare K.O I1 24" 1 Flare Relief Inlet
26 SP.Gr @ Oper. Temp. 0.81 O1 3" 1 Flare K.O Liquid Outlet
27 OPER. PRESS., kg/cm2g (Nor./Max.) 0.15 V1 24" 1 Vapor Outlet
28 OPER. TEMP. , ℃ (Nor./Max./Min.) 140.8/ 228/ 84 PG1 Note 2 1 Pressure Guage
29 DESIGN PRESS. / VAC., kg/cm2g 3.5 SO1 2" 1 Steam Out
30 DESIGN TEMPERATURE , ℃ 250 LT1,2 Note 2 2 Level Transmitter
31 VESSEL DIA.(ID) / LEN.(T/T) mm 3300 6600 LG1,2 Note 2 2 Level Gauge
32 MAX. LIQUID LEVEL, mm MH1 24" 1 Manhole
33 INSULATION REQUIRED TYPE Personal Protection I2 1 1/2" 1 Minimum Flow 2
34 FIRE PROOF ■ YES □ NO PI1 Note 2 1 Pressure Indicator 1
35 SHELL CS TI1 Note 2 1 Temperature Indicator 1
36 MATERIAL HEAD CS
37 SELECTION INTERNAL PIPE COILS CS
38 LINING OR CLADDING -
39 CORROSION ALLOWANCE , mm 3
40 HEAD TYPE 2:1 Ellip.
41 LETHAL □ YES ■ NO
42 CHARACTERISTICS CORROSIVE □ YES ■ NO
43 FLAMMABLE ■ YES □ NO
44 CYCLIC SERVICE □ YES ■ NO ( )
45 NOTES :
46 1. The revision is marked with cloud mark.
47 2. By Instrument.
48
49
50
51
52
###
REVISION 0 1 2
DATE 08, Oct. '03 19, Dec. '03 20th, MAY.'04
BY/CHECKED SJS / YSL ETJ / YSL ETJ / YSL / / / /

LTM-B110-32A Quality, Speed and Trust