You are on page 1of 3

2

CALCULATION COVER SHEET PAGE NUMBER:


1 1 OF 2
CLIENT : CALCULATION NO.
SUBJECT : NET ALLOWABLE BEARING CAPACITY (NABC) OF FOUNDATION
LOCATION : GENERIC
CALCULATION TITLE:
SOIL BEARING CAPACITY OF SUBMERGED FOUNDATION.

OBJECTIVE:
TO DETERMINE THE NET ALLOWABLE SOIL BEARING CAPACITY OF FOUNDATION WITH PRESENCE OF
WATER TABLE.

INPUTS:
GEOTECHNICAL REPORT

ASSUMPTIONS:
SEE CALCULATIONS FOR ASSUMPTIONS

ASSUMPTIONS REQUIRING CONFIRMATION:

BASIS OF CALCULATION, METHOD, OR SOFTWARE TO BE USED:


MoPTT STANDARDS (BS-02 and BS-03)

CONCLUSION:

SOIL BEARING CAPACITY IS DETERMINE WITH GIVEN DEPTH OF FOUNDATION AND WATER TABLE.

REMARKS:

REVISION 0 1 2 3 4 5 6
PREPARED BY:
DATE
CHECKED BY:
DATE
Page No. 2 of 2
CALCULATION SHEET Rev. No. 0
Client: J.O. No. 0
Project Name: Prepared By: Date: 1/8/1997
Location : Generic Checked By: Date: 1/8/1997

NET ALLOWABLE BEARING CAPACITY (NABC) OF FOUNDATIONS


FOUNDATION ENGINEERING DESIGN CALCULATION
INTRODUCTION

For evaluating net allowable bearing capacity of shallow foundations on granular soils:

Shear Considerations
Adopting a factor of safety of 3 against shear failure, net safe bearing capacity, q, from shear consideration:

For square or circular foundations: q = 0.105N²BRw' + 0.314(100+N²)DRw (1)


For strip foundations: q = 0.157N²BRw' + 0.262(100+N²)DRw (2)

Settlement Considerations
Net permissible bearing capacity, q, for 25mm settlement is computed using Meyerhof equation modified by
Teng.

q = 34.5(N-3)[(B+0.305)/(2B)]²kdRw' (3)

Where: kd = depth factor = (1+D/B) <= 2


B & D = Foundation width & depth, respectively
L = Foundation length
Rw & Rw' = Reduction factors for water table effect
N = Standard penetration resistance in blows/300mm

From both shear and settlement considerations, the least value of q obtained from equations (1), (2) & (3) is
considered as the Net Allowable Bearing Capacity (NABC).

GIVEN/ASSUMED FIGURE h
B = 5.00 m Water
L = 5.00 m level
D = 1.50 m D=
da = 0.00 m 1.50 m da = 0.00
db = 1.85 m
N = 17 blows/300mm
PARAMETERS: B= db = 1.85
Rw = 1-0.50(da/D) = [1-(0.05)(0.00)/(1.50)] = 1.00 5.00
Water
Rw' = 0.50(1+db/B) = (0.05)[1+(1.85)/(5.00)] = 0.69 level
kd = (<=2) =1+D/B = [1+(1.50)/(5.00)] = 1.30 B= 5.00 m
NET ALLOWABLE BEARING CAPACITY
Shear Consideration:
(Square or Circular Foundation)
q= [(0.105N²BRw') + 0.314(100+N²)DRw]
q= [(0.105(17.00)²)(5.00)(0.69)+ 0.314(100+17.00²)(1.50)(1.00)] = 287 kN/m²
(Strip Foundation)
q= [(0.157N²BRw') + 0.262(100+N²)DRw]
q= [(0.157(17.00)²)(5.00)(0.69)+ 0.262(100+17.00²)(1.50)(1.00)] = 308 kN/m²
Settlement Consideration:
q= {(34.5)(N-3)[(B+0.305)/(2B)]²(kd)(Rw')}
q= 34.5(17.00-3)[(5.00+0.305)/(2x5.00)]²(1.30)(0.69) = 121 kN/m², Governs
Hence, the Net Allowable Bearing Capacity q all = 121 kN/m²
kN/m², Governs