Understanding Ground Fault

and Leakage Current Protection


Ground-fault circuit interrupters (GFCIs) have been in use for over 40 years,
and have proven themselves to be invaluable in the protection of
personnel from the hazard of electric shock. Other types of leakage
current and ground fault protective devices have been introduced
for various applications since the introduction of GFCIs. The use
of some protective devices is specifically required in the National
Electrical Code® (NEC)®. Others are a component of an appliance, as
required by the UL standard covering that appliance. This article will
help to differentiate the various types of protective devices used today
and clarify their intended uses.
GFCIs and kitchens. Article 680 of the NEC current
The definition of a ground-fault circuit covering swimming pools has additional levels less
interrupter is located in Article 100 of the GFCI requirements. than that of
NEC and is as follows: “A device intended In almost every new edition of the NEC a supply
for the protection of personnel that functions since 1968, new GFCI requirements were circuit overcur-
to de-energize a circuit or portion thereof added. See the sidebar on page 2 for rent protective
within an established period of time when a examples of when the NEC first required device. This type
current to ground exceeds the values GFCIs for various applications. Please note of device is
established for a Class A device.” Following that this list does not include all locations designed typically
this definition, a Fine Print Note provides where GFCI protection is required. to trip in the 30 mA
additional information on what constitutes a or higher range, and
Class A GFCI device. It states that a Class A UL Guide Information for Ground-Fault therefore is not used for
GFCI trips when the current to ground has a Circuit Interrupters (UL Product Category personnel protection. This
value in the range of Code KCXS) can be found in the UL White type of device may be provided as required
Book or online at www.ul.com/database. by Section 230.95 of the NEC. Additional
4 milliamps to 6 milliamps, and references
UL 943, the Standard for Safety for Ground- Other Types of Leakage Current and information for Ground-Fault Sensing and
Fault Circuit-Interrupters. Ground Fault Protective Devices Relay Equipment may be located under the
The following describes various types UL Product Category KDAX.
Section 210.8 of the NEC covers specific
of leakage current or ground fault LCDI (Leakage Current Detector
applications where GFCI protection for
protective devices: Interrupter) — LCDIs are permitted as an
personnel is required. In dwelling units,
GFCIs are required in all 125-volt, single GFPE (Ground-Fault Protection of alternative to AFCIs in accordance with
phase, 15- and 20-ampere receptacles Equipment) — Intended for the protection Section 440.65 of the NEC. LCDI power
installed in locations such as bathrooms, of equipment by disconnecting all supply cord assemblies use a special cord
garages, outdoors, unfinished basements, ungrounded conductors of a circuit at employing a shield around the individual
continued »

01
Understanding Ground Fault
and Leakage Current Protection (continued)
conductors, and are designed to interrupt IDCI (Immersion Detection Circuit
the circuit when leakage current occurs Interrupter) — A component device that
between a conductor and the shield. interrupts the supply circuit to an immersed
Additional information for Leakage-Current appliance. When a conductive liquid enters
Detection and Interruption may be located the appliance and contacts both a live part
under the UL Product Category ELGN. and an internal sensor, the device trips when
EGFPD (Equipment Ground-Fault current flow between the live part and the
Protective Device) — Intended for sensor exceeds the trip current value. The
applications such as fixed electric deicing trip current may be any value below 6 mA
and snow melting equipment, as well as sufficient to detect immersion of the
fixed electric heating equipment for connected appliance. The function of an
pipelines and vessels, in accordance with IDCI is not dependent on the presence of a
Articles 426 and 427 in the NEC. This grounded object. Listed products that
device operates to disconnect the electric contain IDCIs or ALCIs have been investi-
circuit from the source of supply when the gated for installation in applications in
ground-fault current exceeds the ground- accordance with Section 422.41 of the NEC.
fault pick-up level marked on the device, Proven Benefit of Leakage Current
typically 6 mA to 50 mA. Additional and Ground Fault Protection
information for Ground-Fault Protective To help mitigate electrical shock hazards,
GFPE Circuit Breaker Devices may be located under the UL UL has been at the forefront of detector
Product Category FTTE. research, technology and standards
NEC Edition Where GFCI The following types of devices are UL development. Statistics have shown that
devices described in this article have
Component Recognized, and not intended
Protection Was First for general sale or use. They are intended proven to be an effective means to improve
Required for use as factory-assembled components safety in residential occupancies and other
of specific appliances where the suitability electrical installations. Proper application
1968 — Swimming pool underwater of the installation is determined by UL. They and use of these protective devices is
lighting have not been investigated for installation in critical to coordinating required protection
1971 — Outdoor receptacles and near the field, and may or may not satisfy for safe installations.
swimming pools requirements in the NEC.
1975 — Bathroom receptacles and ALCI (Appliance Leakage Current
construction sites Interrupter) — A component device on
1978 — Garage receptacles electrical appliances, ALCIs are similar to
GFCIs, as they are designed to interrupt the
1981 — Spas or hot tubs circuit when a ground fault current exceeds
1984 — Bathrooms of hotel or motel 6 mA. An ALCI is not intended to replace
guest rooms the use of a GFCI device, where GFCI
1987 — Basements, receptacles near protection is required in accordance with
kitchen sinks, and boathouses the NEC.

1990 — Unfinished basements and


crawl spaces
1993 — Wet bar sinks
1996 — All kitchen countertop recep-
tacles, unfinished accessory buildings,
rooftops
2005 — Near laundry and utility room
sinks, outdoors in public spaces
2008 — All sinks (other than dwelling
units), electric water drinking fountains

02 Copyright © material from the 2009 January Issue of The Code Authority: Electrical Connections newsletter.