You are on page 1of 4

Key Factors for Maintaining

Battery Performance
Michael Nispel and Al Williamson, C&D Technologies, Bluebell, Pennsylvania

A well-maintained and monitored battery system will pro- commonly assumes that the battery’s
runtime will simply be reduced by 20%.
vide the owner with the most reliable and cost effective Unfortunately, the reality is much more
dramatic. Table 1, examines the effect
power source – one that isn’t likely to be an expensive dis- on a typical UPS battery installation:
Table 2 details the effect on run time,
appointment, due to the inevitable changes that occur at a due to an increase in discharge current
battery site. To guarantee that a facility’s backup battery for this battery. As the table shows, the
effect of an increase in current on the
power system will operate as designed, routine maintenance run time is quite dramatic.
This effect on run time is also evi-
should also include procedures to examine external factors dent as a battery ages. As the capacity
of a battery decreases with age, its run
to the battery system. This article outlines many of the key time decreases at a much higher rate.
factors external to the battery itself that will increase the The result is similar to the one described
above: a 15-minute battery that is near-
performance and the reliability of your battery-based power ing its end-of-life, and has lost 20% of
its initial capacity, will lose 50% of its
system. original run time. The result is even
Battery owners know that a lot of sized, and explains how changes in these more severe for a 5-minute battery.
thought and energy went into the selec- factors can critically affect the battery’s When the same battery used in the pre-
tion of their UPS battery system, since performance. vious example is sized for a 5-minute
it was originally sized to provide backup load, it will not be able to sustain its load
power for some specified time period. Required Duty Cycle – at all – if it has lost more than 12% of
Many battery owners perform careful The most obvious factor that can af- its initial capacity.
maintenance on their system year after fect the battery’s performance is the re-
year, feeling confident that by keeping quired duty cycle. The effect of a change Load Change
their battery in peak condition they will in current on the battery’s performance If the load changes over the years to
be protected from a power outage. But is often underestimated. To illustrate this a level significantly greater than the
it turns out that their well-maintained point, consider the example where the original installation, the increased
battery may leave them just as unpre- load on a UPS battery has increased by power loss in the connecting cables must
pared for an outage as it would if their 20% over the years. The battery user also be reconsidered. Resistive power
battery was run-down, improperly main-
tained or undersized.
This potential problem exists be-
cause external changes that occur over
time at a battery site, although they may
seem trivial and minor when they hap-
pen, may cumulatively push the battery
system to the point of being insufficient.
This article reviews the factors that are
considered when a battery is originally Table 1. Specifications of a typical battery.
loss in a connector or cable is a func- shedding (loose particles of plate mate- quires new equipment, it is not unusual
tion of the square of the current. This rial) of the positive, and collection of for a new boiler, compressor or a pump
means that if the load has doubled over this material in the sediment space at to be installed in the same room as the
the years, the power loss and tempera- the bottom of the cells. As this material battery. All of this equipment generates
ture rise in these connectors is not sim- accumulates, it will eventually cause an significant heat, and will cause the
ply doubled, but will rise by a factor of internal short when its level reaches the room’s ambient temperature to rise. The
four. In high current discharges, this bottom of the plates. The effect of the good news is that one can expect higher
power loss may be significant. This is glass retention mat on the cycle life of a capacity from the battery with an in-
especially true for long cable runs,
where the UPS system is not located im-
mediately adjacent to the battery. In all
cases, whenever a battery’s performance
is being evaluated, the total cable run
of the entire UPS and battery loop (in-
cluding cross-aisle connections) must be
considered.

Battery Type Table 2. The effects of increased current on the run time.
In terms of battery type, the change
in cycle activity may also be significant.
If the original expectation was for long typical flooded battery is shown in Fig- crease in temperature (Figure 2). If dis-
periods of float, with a moderate cycle ure 1. For VRLA applications which re- charged at this higher temperature, the
(50% depth-of-discharge) every two quire frequent, high-rate discharges, the battery will deliver more energy. How-
months, a light-duty, flooded battery gelled-electrolyte type of VRLA battery ever, what is much more important than
may have been specified. These battery is often selected. These gelled cells are this short-term gain, is the long-term
types typically have insufficient active inherently better at heat dissipation due loss in life that results from this higher
material retention for frequent, high-rate to the larger volume of electrolyte mass temperature. More specifically, a bat-
cycles. If the cycle activity has increased and the improved heat transfer to the cell tery will lose one-half of its life if it is
over the years, the plate without reten- container. Local spill containment regu- kept at 95°F instead of 77°F (and half
tion may no longer be appropriate. In lations may also be relaxed with the again for every 18°F above this). This
this case, a more appropriate battery gelled-type electrolytes. factor alone is probably responsible for
design would be one with a thicker glass a significant portion of the disappoint-
mat for active material retention (ex. Temperature ments in the life of lead-acid batteries.
0.020 inch vs. 0.010 inch thick), in ad- Aside from changes in the load, the It is critically important to a battery’s
dition to a separator that will shield the most important factor in the battery’s life to regulate the temperature in its en-
bottoms of the plates. If the original performance is the temperature. Batter- vironment.
battery continues to be cycled at the ies are often installed in mechanical On the other hand, low temperatures
higher rate, it is destined for early fail- rooms with other maintenance are also important to consider, since
ure. Signs of failure would be excessive equipment. As a company grows and re- batteries will experience reduced capac-

Figure 1. The effect of glass mat retainer on cycle life: Flooded UPS Figure 2. Relative correction factors used for determining the proper
battery at 15 minute rate of discharge. cell size based on discharge temperature.
ity as the temperature drops. In this case, capacity and early life failures. VRLA millivolts per degree F per flooded cell
it is not the average temperature that batteries that are not charge-compen- applies. For example, a flooded battery
needs to be considered, but the tempera- sated for high temperatures are at an on float at 2.200 volts per cell at 77°F
ture at the time of the discharge. Because even greater risk of failure. VRLA bat- should be adjusted to 2.228 volts per
of this relationship, the sizing of the teries normally operate at higher tem- cell at 67°F.
battery becomes questionable if the bat- peratures internally than a flooded bat-
tery room temperature is allowed to tery due to the internal heat of gas re- Ventilation
appreciably shift over time from the combination, the lower thermal mass of One of the considerations made in
the original battery installation is the
general type of battery – flooded or
valve-regulated – and how its environ-
ment will affect it. When a traditional
flooded battery is installed, the under-
standing is that the room must have suf-
ficient ventilation to evacuate the hy-
drogen gas generated. It is important to
realize that changes in the room usage
may be critical in the battery selection
– to the point that the original flooded
Table 3. It is critical to compensate the charge voltage if the temperature drifts in the battery room. battery would no longer be appropriate
for the installation. The IEEE 484, Rec-
ommended Practice for Installation
original temperature. The battery will the acid-starved element and the re- Design and Installation of Vented Lead-
also be affected if there are changes in duced heat transfer (as compared to a Acid Batteries for Stationary Applica-
the winter heating conditions, or even flooded battery container). Should the tions states, “The battery area shall be
if the building heat is turned down on temperature rise without the voltage ventilated...to prevent accumulation of
weekends for energy conservation rea- being lowered to compensate, the bat- hydrogen and to maintain design oper-
sons. tery will be forced to generate additional ating temperature. The ventilation sys-
gas, which will recombine and add more tem shall limit hydrogen accumulation
Voltage Regulation heat to an already warm battery. Should to less than 2% of the total volume of
While we’re on the subject of tem- the battery reach the point where more the battery area.” Critical to this percent-
perature, it is important to note voltage heat is generated internally than can be age is the free air volume of the room.
regulation. If the temperature of the bat- dissipated to the surrounding air, the If, over time, the room’s open-air vol-
tery room is allowed to drift either batteries will reach a point of thermal ume is decreased by one-half – due to
higher or lower after installation, it is runaway. At this point, the batteries will additional items being placed in the
critical to compensate the charge volt- almost certainly be damaged beyond room – the hydrogen gas accumulation
age. A flooded, lead-calcium battery repair, and may generate enough heat rate will be doubled. If the maximum
that was originally sized for 77°F and to damage surrounding equipment. This hydrogen level approaches 2%, either
is later kept at 87°F, should have its is an extreme example, but it is impor- additional ventilation must be installed
charge voltage reduced by 0.028 volts tant to consider the ramifications of al- or the flooded battery must be replaced
per cell, or 2.8 millivolts per degree F lowing a battery room’s temperature to with a VRLA battery. Note that VRLA
per cell (or 5mV/°C per cell). A VRLA climb, while not compensating the float batteries typically operate at well over
cell should be compensated in the same voltage. 95% efficiency of gas recombination,
manner by 0.002 volts per degree F per and so gas evolution is less than 5% of
cell (or 3.6mV/°C per cell). For a total Charge Compensation a similar flooded battery.
battery, this actual voltage change can Charge compensation is another criti-
be significant, as shown in Table 3. cal factor if the battery temperature Equalization Charge
drops after its initial installation. In this Another item that must be considered
Thermal Runaway case, the uncompensated float voltage for flooded batteries is the equalization
The result of not compensating the is too low to maintain the full state-of- charge. One important function of this
float voltage on flooded batteries that charge of the battery. If the cell is al- charge is to combat stratification of the
operate at high temperatures is exces- lowed to remain in this sulfated state for acid. As the acid electrolyte participates
sive gas evolution, greatly increased an extended period of time, even an in the chemical reactions within the cell,
water loss, excessive shedding of posi- equalization charge may not be suffi- it will change in density. The higher
tive active material and increased posi- cient to recover the capacity of the cell. density acid will slowly migrate toward
tive grid corrosion – all factors in low Again, the same rule-of-thumb of 2.8 the bottom of the cell, resulting in a
range of acid specific gravities within
it. In extreme cases, the low gravity acid
at the top of the cell will result in poor
discharge capacity. Conversely, the
higher gravity at the bottom of the cell
will result in higher grid corrosion, pos-
sible negative expander damage and
higher positive active material usage. To
avoid these adverse effects later on, it
is important to equalize a battery when
the per-cell voltage readings warrant it.
Any changes in this procedure may dra-
matically affect the performance of the
battery.

©1999 Reprinted from Power Quality Maga-


zine March/April 1999 issue.

You might also like