LOAD SCHEDULE
CKT NO LOAD DESCRIPTION V VA A
1 LIGHTING OUTLET 4 - 100VA 230 400 1.30
2 CONVENIENCE OUTLET 3 - 200VA 230 600 2.60
3 STOVE (RANGE) OUTLET 1500VA 230 1500 6.52
4 SPARE 230 1500 6.52
TOTAL 230 4000 16.94
IL=□(64&4000/230) ×100% IL AT 100% DEMAND FACTOR:
IL=13.91 AMP USE: 2-5.5mm2 THHN + 1-5.5mm2 THHN IN 20mm
MAIN: 30AT/50AF, 2P, 240V
LP NEMA 1 ENCLOSURE, FLUSH MOUNTED
CIRCUIT BREAKER
WIRE SIZE CONDUIT SIZE
AT AF P
2-1.6mm2 THHN 20mm Ø PVC 15 50 2
2-3.5mm2 THHN 20mm Ø PVC 20 50 2
2-3.5mm2 THHN + 1-2.0mm2 THHN 20mm Ø PVC 20 50 2
20mm Ø PVC 20 50 2
ND FACTOR:
mm2 THHN + 1-5.5mm2 THHN IN 20mmØ RSC
CIRCUIT BREAKER
KAIC TYPE
10 BOLT-ON
10 BOLT-ON
10 BOLT-ON
10 BOLT-ON