Measuring Current transformer: This is also known as
Metering CT ,it should confirm to IS:27O5-2 or IEC-60044-1 The cross section area of the cores are so designed that ,the core saturates at about 5 times the rated current (with low saturation current) .This would facilitate safety to the instruments, while heavy fault current flows in the Primary circuit. Before going into the details of characteristic / duty to be performed by the metering CTs, one should be aware of some definitions / terminology relevant to the equipment. 7.1 Instrument Security Factor (IFS/FS): The ratio of instrument limit primary Current to the rated primary current. Note: In the event of system fault current flowing through the primary winding of a CT, the safety of the apparatus supplied by the CT is greatest when the value of the instrument security factor (SF) is small. . Rated Instrument Limit Primary Current (IPL): The Value of the minimum primary current at which the composite error of the measuring CT is equal to or greater than 10%,while the secondary burden is equal to the rated burden. Note: The composite error should be greater than 10%, in order to protect the apparatus supplied by the CT against the high current produced in the event of system fault. 8.0 Accuracy classes;
accuracy limits are defined from 5% of current onwards, however the declared accuracy limits ie 0.1,0.2,0.5 & 1.0% respectively and 5,10,30,60 minutes respectively would be at 100% to 120% of rated current at 25% to 100% of rated burden. {Ref:IS:2705(part-2)} (b)Special Application Accuracy classes: 0.2S and 0.5S are used for special applications. The accuracy limits are defined from1% of rated current, however the declared accuracy limits ie 0.2% & 0.5%and 10&30 minutes respectively would be at 20% to 120% rated current at 25% to 100% of rated burden. Precision metering of High value HT consumers and Tariff meters etc are categorized as special application metering and need �S� class CTs. {Ref:IS:2705(part-2)or IEC:60044-1}.