URGA sectnigues trate rvture, Transformer Manufacturer IG/EARTHING TRANSFORMER Date : 29/11/2017 Amb. Temp : 32°C CUSTOMER : M/s. Rongxin Electronics Pvt, Ltd P.O NO : RIPL-RX-106-PO-005 Dated on 13/06/2016 Project + 400 kV Solapur Substation for STATCOM Station Transformer Detais- Voltage Neutral current” | vector Group | SSRN 38.5 kV 7 50 HZ, 900 A for 30 sec through neutral and 300 A for 30 ZNO UM-1730/2057 hla Perce Bec see 1) IR TEST :~ net [HV Earn measures ae Sm “rea ea core Ear Nesured 50 ————~e's9 a] 2) HIGH VOLTAGE TEST ;- HV - & Earth 3) NO LOAD TEST After Hy :- Conducted from 38.5 KV side by Putting 400 V / 40000 intermediate transformer = 5 KV for 1 minute withstood - OK Voliage im i *h th T_Na fea ale Toe eda Tas 4) INDUCE OVER VOLTAGE TEST :- ‘Two times the normal voltage at 150 Hz for 40 Sec. withstood — OK. 5) OIL TEST :- BDV of it at 2.5 mm gap = 65 kv Witnessed By Nitesh Kashyap 4067050008 e-mail: response@urjatranstormers.com, Tel. £+91-22-2769 1001/02 e-mail : admin@urjatransformers.com, Road, Wadala, Mumbai ~ 400 031 Works | R-476, TTC, M.LD.C, Thane Belapur Road, Rabale, Navi Mumbai - 400 701 Office | B-17,Shri Ram Ind, Estaie, GD, Ambekar ie