Introduction 4.1
References 4.7
• 4 • Fault Calculations
4.1 INTRODUCTION
A power system is normally treated as a balanced
symmetrical three-phase network. When a fault occurs,
the symmetry is normally upset, resulting in unbalanced
currents and voltages appearing in the network. The only
exception is the three-phase fault, which, because it
involves all three phases equally at the same location, is
described as a symmetrical fault. By using symmetrical
component analysis and replacing the normal system
sources by a source at the fault location, it is possible to
analyse these fault conditions.
For the correct application of protection equipment, it is
essential to know the fault current distribution
throughout the system and the voltages in different
parts of the system due to the fault. Further, boundary
values of current at any relaying point must be known if
the fault is to be cleared with discrimination. The
information normally required for each kind of fault at
each relaying point is:
i. maximum fault current
ii. minimum fault current
iii. maximum through fault current
To obtain the above information, the limits of stable
generation and possible operating conditions, including
the method of system earthing, must be known. Faults
are always assumed to be through zero fault impedance.
4 . 2 T H R E E - P H A S E F A U LT C A L C U L AT I O N S
Three-phase faults are unique in that they are balanced,
that is, symmetrical in the three phases, and can be
calculated from the single-phase impedance diagram
and the operating conditions existing prior to the fault.
A fault condition is a sudden abnormal alteration to the
normal circuit arrangement. The circuit quantities,
current and voltage, will alter, and the circuit will pass
through a transient state to a steady state. In the
transient state, the initial magnitude of the fault current
will depend upon the point on the voltage wave at which
the fault occurs. The decay of the transient condition,
until it merges into steady state, is a function of the
parameters of the circuit elements. The transient current
may be regarded as a d.c. exponential current
E' E''
V
Figure 4.2: Reduction of typical
power system network
— — —
V = 0.97 E’ - 1.55 I
N
1.2 × 2.5
V = 0.99 E '' + + 0.39 I
2.5 + 1.2
Figure 4.1: Network with fault at F — —
For practical working conditions, E’ 〉〉〉1.55 I and
— — — — —
— E’’ 〉〉〉1.207 I . Hence E’≅ E’’≅ V.
The voltage V at F before fault inception is: — —
— — —— — —— Replacing the driving voltages E’ and E’’ by the load
• 4• V = E - I Z‘ = E’’ + I Z’’ —
voltage V between A and N modifies the circuit as shown
— in Figure 4.3(a).
After the fault the voltage V is zero. Hence, the change
—
in voltage is - V . Because of the fault, the change in the The node A is the junction of three branches. In practice,
current flowing into the network from F is: the node would be a busbar, and the branches are
∆I = −
V
= −V
Z1' + Z1'' ( ) feeders radiating from the bus via circuit breakers, as
shown in Figure 4.3(b). There are two possible locations
Z1 Z1' Z1'' for a fault at A; the busbar side of the breakers or the
and, since no current was flowing into the network from line side of the breakers. In this example, it is assumed
F prior to the fault, the fault current flowing from the that the fault is at X, and it is required to calculate the
network into the fault is: current flowing from the bus to X.
If = −∆I = V
( Z1' + Z1'' ) The network viewed from AN has a driving point
impedance |Z1| = 0.68 ohms.
Z1' Z1''
The current in the fault is V
By applying the principle of superposition, the load Z1 .
currents circulating in the system prior to the fault may
A
The circuit of Figure 4.4 (b) has been included because
X
the Protection Engineer is interested in these equivalent
parameters when applying certain types of protection
relay.
(b) Typical physical arrangement of node A with a fault shown at X
4 . 3 S Y M M E T R I C A L C O M P O N E N T A N A LY S I S
Figure 4.3: Network with fault at node A OF A THREE-PHASE NETWORK
Fa u l t C a l c u l a t i o n s
The Protection Engineer is interested in a wider variety of
1.55Ω A 1.21Ω faults than just a three-phase fault. The most common
fault is a single-phase to earth fault, which, in LV
systems, can produce a higher fault current than a three-
V phase fault. Similarly, because protection is expected to
operate correctly for all types of fault, it may be
necessary to consider the fault currents due to many
N
(a) Impedance viewed from node A
different types of fault. Since the three-phase fault is
unique in being a balanced fault, a method of analysis
that is applicable to unbalanced faults is required. It can
1.1Ω X 1.79Ω be shown [4.2] that, by applying the 'Principle of
Superposition', any general three-phase system of
vectors may be replaced by three sets of balanced • 4•
V (symmetrical) vectors; two sets are three-phase but
having opposite phase rotation and one set is co-phasal.
These vector sets are described as the positive, negative
N
(b) Equivalent impedances viewed from node X
and zero sequence sets respectively.
The equations between phase and sequence voltages are
Figure 4.4: Impedances viewed from fault given below:
of unbalanced vectors voltages in the system due to the fault are greatest at the
source, as shown in the gradient diagram, Figure 4.6(b).
When a fault occurs in a power system, the phase
impedances are no longer identical (except in the case of X
three-phase faults) and the resulting currents and Figure 4.6 ZS1 ∆Z '1 F Z ''1
voltages are unbalanced, the point of greatest unbalance
I '1 I ''1
being at the fault point. It has been shown in Chapter 3
Z '1 I1
that the fault may be studied by short-circuiting all
normal driving voltages in the system and replacing the E' V1 E ''
fault connection by a source whose driving voltage is
equal to the pre-fault voltage at the fault point. Hence, N
(a) System diagram
the system impedances remain symmetrical, viewed from
• 4• the fault, and the fault point may now be regarded as the N
I '1
Fa u l t C a l c u l a t i o n s
X
a. Single-phase-earth (A-E)
V2
V2 + I'2∆Z'1 Ib = 0
N Ic = 0
(b) Gradient diagram
V a = 0 …Equation 4.7
Figure 4.7: Fault at F:
Negative sequence diagram b. Phase-phase (B-C)
Ia = 0
4.3.3 Zero Sequence Network
The zero sequence current and voltage relationships Ib = −Ic
during a fault condition are the same as those in the V b = V c …Equation 4.8 • 4•
negative sequence network. Hence:
— —— c. Phase-phase-earth (B-C-E)
V0 = - I0 Z0 …Equation 4.6
Ia = 0
Also, the zero sequence diagram is that of Figure 4.7,
— —
substituting I0 for I2 , and so on. Vb = 0
The currents and voltages in the zero sequence network V c = 0 …Equation 4.9
are co-phasal, that is, all the same phase. For zero
sequence currents to flow in a system there must be a d. Three-phase (A-B-C or A-B-C-E)
return connection through either a neutral conductor or
Ia + Ib + Ic = 0
the general mass of earth. Note must be taken of this
fact when determining zero sequence equivalent circuits. Va = Vb
— — —
Further, in general Z1 ≠ Z0 and the value of Z0 varies
Vb = Vc …Equation 4.10
according to the type of plant, the winding arrangement
and the method of earthing. It should be noted from the above that for any type of
fault there are three equations that define the fault
conditions.
Consider a fault defined by Equations 4.7 and by Figure Again, from Equation 4.9 and Equations 4.1 and 4.2:
4.8(a). Converting Equations 4.7 into sequence — — —
I1 = -( I2 + Io ) …Equation 4.18
Fa u l t C a l c u l a t i o n s
V0 = V a
I1
P1
I2
P2
I0
P0
V1 = V 2 = 0 …Equation 4.23 N1 +ve
Sequence ν1
N2 -ve
Sequence ν2
N0 Zero
Sequence ν0
and Network Q1 Network Q2 Network Q0
—
I0 = 0 …Equation 4.24
— (b) Equivalent circuit
Substituting V2 = 0 in Equation 4.5 gives:
—
I2 = 0 …Equation 4.25 Figure 4.12: Open circuit on phase A
Fa u l t C a l c u l a t i o n s
—
and substituting V1 = 0 in Equation 4.4:
— —— 4.4.6 Cross-country Faults
0 = V1 - I1 Z1
A cross-country fault is one where there are two faults
or
— —— affecting the same circuit, but in different locations and
V = I1 Z1 …Equation 4.26
— possibly involving different phases. Figure 4.13(a)
Further, since from Equation 4.24 Io = 0 , it follows from illustrates this.
— —
Equation 4.6 that Vo is zero when Zo is finite. The
equivalent sequence connections for a three-phase fault The constraints expressed in terms of sequence
are shown in Figure 4.11. quantities are as follows:
a) At point F
A F Va
F1 F2 F0 I b + I c = 0
Vb 4•
B
Vc Z1 Z2 Z0 Va = 0 …Equation 4.29
•
C
N2 N0
Figure 4.11 I Ib Ia N1 V Therefore:
c
I a1 = I a 2 = I a 0
Ia+Ib+Ic=0
Va+Vb+Vc=0 V a1 + V a 2 + V a 0 = 0 …Equation 4.30
a-e b-e
Ia1 I'a1
F1 F'1
Va1 V'a1
N1 N'1
2
a I'a2
F2 Ia2 I'a2 F'2 1 2
a
2
a V'a2
Va2 V'a2
N2 N'2
Fa u l t C a l c u l a t i o n s
aI'a0
F0 Ia0 I'a0 F'0 1
a
aV'a0
Va0 V'a0
N0 N'0
• 4• ’ = aI a2
a2 I a1 ’ = I ’a0 4.5 CURRENT AND VOLTAGE DISTRIBUTION
IN A SYSTEM DUE TO A FAULT
or
’ = a2I a2
I a1 ’ = aI ’a0 …Equation 4.33 Practical fault calculations involve the examination of
the effect of a fault in branches of network other than
and, for the voltages the faulted branch, so that protection can be applied
V ’b1 + V ’b2 +V ’b0 = 0 correctly to isolate the section of the system directly
involved in the fault. It is therefore not enough to
Converting:
calculate the fault current in the fault itself; the fault
’ + aV a2
a2V a1 ’ +V ’a0 = 0 current distribution must also be established. Further,
or abnormal voltage stresses may appear in a system
because of a fault, and these may affect the operation of
’ + a2V a2
V a1 ’ + aV ’a0 = 0 …Equation 4.34 the protection. Knowledge of current and voltage
The fault constraints involve phase shifted sequence distribution in a network due to a fault is essential for
quantities. To construct the appropriate sequence the application of protection.
networks, it is necessary to introduce phase-shifting The approach to network fault studies for assessing the
transformers to couple the sequence networks. This application of protection equipment may be summarised as
is shown in Figure 4.13(b). follows:
Fa u l t C a l c u l a t i o n s
4.5.1 Current Distribution
I ' b = a 2 C1 I1
The phase current in any branch of a network is
determined from the sequence current distribution in the I ' c = aC1 I1
…Equation 4.38
equivalent circuit of the fault. The sequence currents are
As an example of current distribution technique, consider
expressed in per unit terms of the sequence current in
the system in Figure 4.14(a). The equivalent sequence
the fault branch.
networks are given in Figures 4.14(b) and (c), together
In power system calculations, the positive and negative with typical values of impedances. A fault is assumed at
sequence impedances are normally equal. Thus, the A and it is desired to find the currents in branch OB due
division of sequence currents in the two networks will to the fault. In each network, the distribution factors are
also be identical. given for each branch, with the current in the fault
The impedance values and configuration of the zero branch taken as 1.0p.u. From the diagram, the zero
sequence network are usually different from those of the sequence distribution factor Co in branch OB is 0.112 • 4•
positive and negative sequence networks, so the zero and the positive sequence factor C1 is 0.373. For an
sequence current distribution is calculated separately. earth fault at A the phase currents in branch OB from
Equation 4.35 are:
If Co and C1 are described as the zero and positive — —
Ia = (0.746 + 0.112) I0
sequence distribution factors then the actual current in —
a sequence branch is given by multiplying the actual = 0.858 I0
and
current in the sequence fault branch by the appropriate — — —
— — — I ’b = I ’c = -(0.373 + 0.112) I0
distribution factor. For this reason, if I1 , I2 and I0 are
—
sequence currents in an arbitrary branch of a network = -0.261 I0
due to a fault at some point in the network, then the By using network reduction methods and assuming that
phase currents in that branch may be expressed in terms all impedances are reactive, it can be shown that
of the distribution constants and the sequence currents — —
Z1 = Z0 = j0.68 ohms.
in the fault. These are given below for the various
common shunt faults, using Equation 4.1 and the Therefore, from Equation 4.14, the current in fault
appropriate fault equations: V
branch I a =
0.68
j7.5Ω 0.08 n
j0.9Ω j0.4Ω V1' = V − I1 Z1 − ∑ C1 n ∆Z1 n
A
j2.6Ω 0 j1.6Ω
B
1
1.0 0.165 0.112
0.755 0.192 n
V 2 ' = − I 2 Z1 − ∑ C1 n ∆Z1 n
j4.8Ω
0.053
1
(b) Zero sequence network
n
V0 ' = − I 0 Z 0 − ∑ C 0 n ∆Z 0 n
j2.5Ω 0.183 1 …Equation 4.39
j1.6Ω j0.4Ω
A B
j0.75Ω 0 j0.45Ω
1.0 0.395 0.373
Using the above equation, the fault voltages at bus B in
0.422 j18.85Ω 0.556 the previous example can be found.
0.022 From the positive sequence distribution diagram Figure
(c) Positive and negative sequence networks 4.8(c):
[ }]
—
—
I ’a = 26.8∠ -90° A {
V ' 0 = I 0 Z 0 − j (0.165 × 2.6 ) + (0.112 × 1.6 )
I ’b = I ’c =8.15∠ -90° A
The vector diagram for the above fault condition is [
= I 0 Z 0 − j 0.608 ]
shown in Figure 4.15. — — —
For earth faults, at the fault I1 = I2 = I0 = j31.2A, when
—
|V | = 63.5 volts and is taken as the reference vector.
— —
Further, Z1 = Z0 = j0.68 ohms.
Figure 4.15
• 4• V 'c =61.5-116.4° Hence:
—
V’1 = 63.5 - (0.216 x 31.2)
Fa u l t C a l c u l a t i o n s
Under normal system operation there is a capacitance — —
4.6.2 System Z0 / Z1 Ratio
between the phases and between phase and earth; these — —
capacitances may be regarded as being symmetrical and The system Z0 / Z1 ratio is defined as the ratio of zero
distributed uniformly through the system. So even when sequence and positive sequence impedances viewed from
(a) above is satisfied, if the driving voltages are the fault; it is a variable ratio, dependent upon the
symmetrical the vector sum of the currents will equate method of earthing, fault position and system operating
to zero and no current will flow between any two earth arrangement.
points in the system. When a fault to earth occurs in a When assessing the distribution of residual quantities
system an unbalance results in condition (b) being through a system, it is convenient to use the fault point
satisfied. From the definitions given above it follows as the reference as it is the point of injection of
that residual currents and voltages are the vector sum of unbalanced quantities into the system. The residual
phase currents and phase voltages respectively. voltage is measured in relation to the normal phase-
Hence: neutral system voltage and the residual current is • 4•
compared with the three-phase fault current at the fault
I R = Ia + Ib + Ic point. It can be shown [4.4/4.5] that the character of
these quantities can be expressed in terms of the system
and — —
Z0 / Z1 ratio.
V R = V ae + V be + V ce …Equation 4.40
The positive sequence impedance of a system is mainly
Also, from Equations 4.2: reactive, whereas the zero sequence impedance being
affected by the method of earthing may contain both
I R = 3 I 0 resistive and reactive components of comparable
— —
V R = 3 V0 …Equation 4.41 magnitude. Thus the express of the Z0 / Z1 ratio
approximates to:
It should be further noted that:
Z0 X R
V ae = V an + V ne = 0 − j 0
Z1 X1 X1
V be = V bn + V ne …Equation 4.44
V
I3φ =
Z1 1.5
Thus:
1.0 Residual voltage for
Double-Phase-Earth fault
IR 3
=
(2 + K )
…Equation 4.45
I3φ 0.5
0 1 2 3 4 5 •
3 Z1
I R = 3I0 = − I1 Z0
Z1 + Z 0 K =
Z1
I1 =
(
V Z1 + Z 0 ) Figure 4.17: Variation of residual quantities
at fault point
2 Z1 Z 0 + Z12
Hence: 4.6.3 Variation of Residual Quantities
The variation of residual quantities in a system due to
3 V Z1 3V
IR = − = − different earth arrangements can be most readily
2 Z1 Z 0 + Z12 (
2 K + 1 Z1 ) understood by using vector diagrams. Three examples
have been chosen, namely solid fault-isolated neutral,
Fa u l t C a l c u l a t i o n s
n a(F)
The curves in Figure 4.17 illustrate the variation of the VbF VcF
— —
above residual quantities with the Z0 / Z1 ratio. The Iab
-VbF=Eab VR
residual current in any part of the system can be b
obtained by multiplying the current from the curve by (b) Vector diagram (c) Residual voltage diagram
the appropriate zero sequence distribution factor.
Similarly, the residual voltage is calculated by Figure 4.18: Solid fault-isolated neutral
subtracting from the voltage curve three times the zero
sequence voltage drop between the measuring point in
the system and the fault.
Fa u l t C a l c u l a t i o n s
Ia X ZL F
A At relaying point X:
Iab — — — —
B VR = VXn + Vbn + Vcn
Iac
C
Ian
Iab Iab
Ia X
ZS IF ZL F
A
B
C
(a) Circuit diagram
IF
Iac IF
c
-Vcf
(a) Circuit diagram • 4•
c
VR VFn VR VXn
VcX VcF
Figure 4.19: Solid fault-resistance neutral Figure 4.20: Resistance fault-solid neutral
4.7 REFERENCES
4.1 Circuit Analysis of A.C. Power Systems, Volume I.
Edith Clarke. John Wiley & Sons.
4.2 Method of Symmetrical Co-ordinates Applied to
the Solution of Polyphase Networks. C.L.
Fortescue. Trans. A.I.E.E.,Vol. 37, Part II, 1918, pp
1027-40.
4.3 Power System Analysis. J.R. Mortlock and M.W.
Humphrey Davies. Chapman and Hall.
4.4 Neutral Groundings. R Willheim and M. Waters,
Elsevier.
4.5 Fault Calculations. F.H.W. Lackey, Oliver & Boyd.
Fa u l t C a l c u l a t i o n s
• 4•