INTRODUCTION Withstands 1.2 Gs at 5 to 26 Hz; 0.036" Power for the exciter field and regulator
double amplitude at 27 to 52 Hz; and 5 Gs at circuitry is derived from the generator output
The VR63-4C/UL Voltage Regulators are 53 to 1000 Hz. or auxiliary winding. The operable power
designed for use on 50/60 Hz brushless
Shock: input range is 85 to 139 Vac and is connected
generators. The regulator includes frequency
Withstands up to 20 Gs in each of three to Terminals 3 and 4.
compensation, overexcitation shutdown, a
mutually perpendicular axes. FREQUENCY COMPENSATION
solid-state build-up circuit, and EMI filtering.
WARNING The frequency compensation characteristic is
Weight:
to improve system load pickup performance
To prevent personal injury or equipment 10 oz. (0.28 kg) Net.
by restraining voltage recovery until frequency
damage, only qualified technicians or FUSES has also started to recover.
operators should install, operate, or
service this device. It is recommended that fuses with high For 50 Hz system, the regulator is preset at
interruption capability be installed per the the factory for a 45 Hz “corner frequency”.
ELECTRICAL SPECIFICATIONS interconnection diagram to protect wiring from For 60 Hz systems, a 55 Hz “corner
Dc Output Power: faults before the regulator. Refer to the frequency”. is achieved by cutting the external
4 Adc at 63 Vdc (252W) maximum Interconnection Diagrams. Hz jumper wires on the generator. Be sure to
continuous, insulate the two wires so that they are not
NOTE
7 Adc at 100 Vdc (700W) forcing one minute exposed.
Fuse must be installed per the
(at 120 Vac input). interconnection diagrams to avoid inter-
Exciter Field Dc Resistance: rupting the field current.
15 ohms minimum; 100 ohms maximum.
MOUNTING
Ac Power Input:
Operating range: 85 Vac to 139 Vac, Single The regulator may be mounted in any
phase, 50/60 Hz +5%, Burden 450 VA. position. Refer to the Drilling Diagram.
Sensing Input:
85-139 Vac, Single phase, 50/60 Hz +5%,
common with AC Power Input.
Voltage Adjust Range:
85-139 Vac.
Regulation Accuracy:
Better than ±1.0% no load to full load.
Frequency Compensation Curves
Response Time:
Less than 1.5 cycles for +5% change in OVEREXCITATION SHUTDOWN
sensing voltage. If the exciter field voltage exceeds 95 ±5 Vdc,
EMI Suppression: the regulator automatically removes the field
Internal electromagnetic interference filter current after a time delay. The time delay is
(EMI filter). inversely proportional to the magnitude of the
detected overvoltage condition up to the 140
Overexcitation Shutdown:
Vdc point. Beyond 140 Vdc, the field voltage
Output power is removed under the following
is removed within 0.2 seconds.
conditions: Exciter field voltage exceeds 95+5
Vdc for a time inversely proportional to voltage After shutdown, reset the regulator by
magnitude, or within 2 seconds if the exciter decreasing voltage below 6 Vac either by
field voltage exceeds 140+5 Vdc. stopping the prime mover or interrupting the
Drilling Diagram regulator input with a reset switch for 2
Voltage Build-up:
seconds or more.
Internal provisions for automatic voltage build- EXCITER FIELD POWER CIRCUIT (wires F+
up from generator residual voltages as low as and F-).
6 Vac.
Connect the regulator wire F+ to the brushless
Power Dissipation: exciter field terminal F+, and wire F- to
12 Watts maximum. terminal F-.
PHYSICAL SPECIFICATIONS CAUTION
Operating Temperature: The dc resistance of the exciter field
-40° C (-40° F) to +60° C (+140° F). must be equal to or greater than 15 ohms
Storage Temperature: and less than 100 ohms.
-65° C (-85° F) to +85° C (+185° F). POWER/SENSING INPUT CIRCUIT (wires 3
Vibration: and 4)
Connect as shown by the Interconnection
Diagrams.
Typical Time Delay Characteristic Curves a. Verify that the voltage regulator
VOLTAGE ADJUST specification conforms with the generator
system requirements.
Screwdriver adjustable potentiometer adjusts
b. Ensure that the regulator is correctly
generator output voltage. Adjustment CW
connected to the generator. See
increases voltage.
Interconnection Diagrams.
When using remote voltage adjust rheostat
c. Install fuses per FUSES paragraph.
(VAR), the VAR wire on the regulator should
be cut and the rheostat connected to both d. Set the regulator VAR fully CCW and the
ends. A 1 kohm and 1/2 watt resistance is remote VAR (if used) to centered.
adequate for most applications. See SYSTEM START-UP
Interconnection Diagrams.
a. Start the prime mover and bring up to
STABILITY ADJUST rated speed. Voltage should buildup. If a
An internal screwdriver adjustable minimum residual of 6 Vac is not Operational Test
potentiometer provides adjustment to the present, perform field flashing. FIELD FLASHING
response rate of the generator output voltage b. Slowly adjust VAR CW until voltage When the regulator is operated with the
to a change in load. Clockwise rotation of this reaches nominal value. If used, adjust generator for the first time, the polarity of
adjustment provides an increase in the remote VAR to set generator output to residual magnetism may not be correct or the
response time and therefore decreases the exact value desired. magnitude not enough. If the generator does
amount of voltage overshoot (increased
OPERATIONAL TEST not build-up after startup, shut down the prime
stability). Counterclockwise rotation of this
mover and proceed with the following steps:
adjustment provides a decrease in the a. Connect the test setup as shown in
response time (faster response time) and Operational Test. Do not apply power. a. With the prime mover at rest, apply a dc
therefore increases the amount of voltage source (not grounded) of not more than
b. Adjust regulator VAR and/or remote VAR
overshoot (decreased stability). 12V, to terminals F+(positive) and F-
to maximum CCW.
(negative) in series with a limiting resistor
OPERATION c. Apply 120V, 50/60 Hz power to regulator. of 3-5 ohms.
The following system operation procedures RESULT: Light bulb should flash b. Allow approximately 3 seconds before
provide instructions for adjusting the VR63- momentarily. removing the dc source.
4C/UL Voltage Regulator.
d. Slowly adjust the regulator VAR control c. Start prime mover and measure voltage
CAUTION CW. at regulator leads 3 and 4. If voltage is
Meggers and high potential test RESULT: greater than 6 volts, voltage build-up
equipment must not be used. Incorrect should be successful. Repeat field
1) Before minimum brilliance is reached, the
use of such equipment could damage the flashing procedure if less than 6 V
light bulb should reaches maximum brilliance
semiconductors contained in the residual is measured.
to signify the regulating point.
regulator. d. If repeating steps 1 and 2 does not result
2) At the regulating point, a small change in
in generator voltage build-up, replace the
the VAR should turn the light bulb on or off.
PRELIMINARY SET-UP voltage regulator.
To prevent damage to the regulator, complete ACCESSORY EQUIPMENT
the following steps before proceeding with Voltage Adjust Rheostat for remote mounting -
system start-up. Order Basler P/N 17724 for locking, slotted
shaft rheostat.

Interconnection Diagram, 208/240 V Nominal, 3-Phase, 4-Wire Interconnection Diagram, 240 V Nominal, 3 Phase, 3-Wire
Interconnection Diagram, 120/240 V Nominal, Single-Phase with Neutral

Interconnection Diagram, 120 V Nominal, Single Phase