iandEPA
Test certificate
Document number: (1001202107-1)— Het, 81.01.2008
Sponeor: ‘Sumetborger Gmbit
LobersraBe 108
+110 Wien
Ostereeich
Date of order: 08.11.2007
Ret Conveyor tubes for pneumatic tube systems according to
IN 6860
Test subject: Test procedures forthe acquisition of the building material
class B1 (lame resistant),
Test basis: DIN 4102-1: 1998-05, clause 6.1 and 62
Date of specimen delivery: 08.11.2007
‘Specimen taking: by sponsor
Period of validity upte: 3, Januar 2013
Warning:
the bulding mater, specified above, isnot used as bulding product in accordance with MBO § 2,
clause. 9, fgure 1, 8 general test certicate isnot necessary. Tris tet cetfcate does nat apply i
the tested bulding material's used as a building product n he sense of federal bulding reguations
(BO § 17, Abs. 3). This test certicate is inno case a substiute for any required certification
According to German Buiding roguatons (Landesbavordnung)
In terms of buliing supervision tis test certicate can serve as basis
with regulated building preducts for he prescribed agreement roots.
with not regulated buléing products forthe necessary usefulness proofs
‘The explanations in DIN 4102-1 : 1998-05, appenelx Din particular for extemal supervision are to be
particulary considered,
“This test certification consists of 6 pages inclusive ist page and 11 enclosures.1 Introduction
This test certfcate describes the test procedures and defines the classification assigned tothe
products specified below in accordance with the proceedings given in DIN 4102-1: 1998-05.
2 Test material
‘The product isa conveyor tube forthe use in pneumatic tube systems in accordance with DIN
16660 Its manufactured of unplasticized polyiny chloride (PVCU).
Product description Thickness | Weightper unt | Density
Trem) | area Begine kgm
Conveyor tube PVC-U 160 x32 apps." | 4752018 | app. 1580
(Conveyor tube PVCU 1102.8 app.28 | so=008 | app.t480 |
‘proven by measurement of the testing laboratory
3 Test procedure
‘The test ofthe behaviour in case of fre was accomplished in accordance with DIN 410241
1986-05, ciause 61 and 62
‘The test specimens forthe firepit test were manufactured in accordance with the standard
requirements given in DIN 4102-16, clause 7.17.1. The test specimens were condoned
before the test tun in an alecondltioned compartment at temperature of 23 °C and a relative
humility of 502.
For the tess in the fire box specimens withthe dimensions of 19 cm x 9 em and 23 em x9.em
made of pipes transformed to plates were cut out4 Test results
4.1 Results of the ~Brandachacht
test (DIN 4102+ : 1998-05, clause 6.1
4.1<4 Results ofthe product ,Conveyor tube PVC-U 160 x 3,2"
Tost Middle remaining | Maximum ue gas | Flue gas tubity
length temperature Gémin)
(em) Co)
1 35 194 858
2 29 158 aa
3 18 166 I 855
Mean valve 26 151 851
“Test minut: given in enclosure 1 to 4
PPhoto of te test specimen: given in enclosure @
4.1.2 Results for the product ,Conveyor PVC-U 110x2,3"
Test Midst remaining | Maximum tue gas | Flue gas tubiy
length temperature (Germin)
(om) 0)
1 2 124 ‘08
2 3 126 57
8 a 125 ei
Mean vaue | 2 125 612
Tost minuto: von in enclosure 6108
Photo ofthe test specimen: given in enclosure 94.2 Results ofthe ignitibily test (DIN 4102+
ani
1998-05, clause 6.2)
4.2.1 Results ofthe produet ,Conveyor tube PVC-U 160 x 3,
Time data starting from the beginning ofthe teat un
Edge tlaming/ 1 2 3 4 5
Test No
ignitor: wf 4 1 1 1 1
Reccingot ne gauge |) | — = 5 -
Largest fame height | fom] 5 as 4 5 3
Buming droplet | (8) | no 0 0 0 no
Surface flaming
ignition | 3 2 3 3 2
Reaching ofthe gauge | is) | ~ - S ~ ~
mar
Largestfiame height [tem] 5 a 5 56 5
| Buringaoniets | | 0 no ro ne no
“Test minute: given in enciosure 104.2.2 Test results ofthe product ,Conveyor tube PVC-U 110x2,3"
Time data stating trom the beginning of the test rns
Edge flaming / 1 2 3 4 5
Test No,
Ignition: [4 1 1 1 1
Rescning te omioe [i] |= S ~ ~ -
Largesttame eight [tem | 4-5 5 a8 5 5
Burning droplets | tel | 0 re 0 ro no
Surface flaming
gation: ws 3 3 3 3
Reacting ofthe gauge |) | ~ - ~ ~ =
‘mack
Largest tame height | fom] 56 = 56 5
Burning droplets | ts) | no no 0 0 no
Test minute: gwen in enclosure 11
5 Summary
The results ofthe igitblty tests show thatthe requirements according to DIN 4102-1: 1986-
05, clause 6.2 were met by all samples. During the test runs no buring partcles/dropots
andlor ignition of iter paper were observed
‘The results ofthe “Brandschacht tests show that the requirements according to DIN 4102-1
1996-05, clause 6.1 wore mot by all samples, The tested produets can be designated as flame
resistanty (building material class DIN 4102-81) in accordance with DIN 4102-1: 1986-06.7
7a
72
73
74
and PA
Classification
‘The products Conveyor tube PVO-U 110 x 2.5" and “Conveyor tube PVO-U 160 x3:
classified according to DIN 4102-1: 1996-05 inthe following bulding material class:
‘The test recut is valid only forthe products described in clause 2. Used in connestion with
‘other bulding materials (Le. wth top coatings, intumescent agerts) the fre performance is
canbe
‘Special limitations,
likely to be influenced thus negative, thatthe given classifications are no longer valid. Fire
performance in connection with other materials i to be proven separately according to DIN.
41021: 1990.05,
‘The validly of the test conteate (3100'202/07-1)-Hat ~ from 31. January 2008 ends on
31, January 2018.
The valicty period can only be extended i there willbe no changes in the requirements ofthe
construction supervising authority.
This test centoate cannot be used as building supenising verification of fre behaviour class
according to DIN 4102. This cortieate Is necessary to issue a general bulling code test
cortate.
kes CI. Stu
TA. O61. Host
Soa ree
‘ORR. Oring. A Rohing
Pad ot totngiaboatty
‘Braunschweig, 1 January 2008