Professional Documents
Culture Documents
Design of Building Foundations
Design of Building Foundations
The main purpose of providing a foundation for a building or another structure is to transfer
its load to the subsoil in a safe manner. The dead load of the roof, floor and the load-bearing
walls, and the imposed load acting on these elements are transferred first to the foundations
and then to the soil strata supporting the building. In order to ensure the stability and safety of
the structure, the safe bearing capacity of the subsoil must be more than the stress in the
Several types of foundations are used for domestic, industrial and commercial buildings, the
Economy
The most common types of foundations for domestic and light commercial buildings are the
strip and the pad foundation respectively. In this section the design of these two foundations
will be discussed.
Figure 4-1 shows a narrow strip foundation which is a long strip of concrete supporting the
walls of a low-rise domestic building. It can also be used for other buildings, if the factors
favour such a choice. From the wall the loading is spread on the foundation at 45º as shown
in Figure App7.1a. The planes through which the loading is distributed are called the shear
planes. The foundation should be designed in such a way that the shear planes pass through
the lower corners of the strip. If the designed foundation width is too wide, as is the case in
weaker soils, plain concrete strip may bend and crack as shown in Figure App7.1b. Concrete
may be made stronger in tension by providing steel reinforcement in the tension zone.
D = P or 150 mm
P P whichever is greater
15 N/mm 2
Shear plane
Shear plane Cracks
(a) (b)
According to the Building Regulations, the design of a strip foundation should satisfy the
following conditions*:
i) The projections of the concrete strip on either side of the wall should be equal.
ii) The thickness of the concrete strip should either be equal to the projection (D = P) or 150
mm, whichever is greater. This means that the minimum thickness of strip foundation is 150
mm.
Example 1:
Design a strip foundation for a domestic building to satisfy the following conditions:
ii) The building load, including the dead load of the foundation, is 40 kN/m.
iii) The safe bearing capacity of the subsoil is 80 kN/m2
Solution:
As the walls and the foundation are very long, the calculations are based on 1 m length of the
wall/foundation. The area of the foundation can be determined from the formula:
Building load
Area of the building foundation =
Safe bearing capacity
40
= = 0.5 m2
80
The normal practice is to provide 600 mm wide foundation. Each projection will be:
The shear planes are drawn at 45º from points c and d, as shown in Figure App7.2, and
vertical lines drawn from points a and b. These lines cross at points e and f, which are joined
The thickness of concrete strip in this case is 162.5 mm which may be increased to 170 mm.
Pad foundation
Pad foundation, also known as isolated foundation, is used for columns of low and medium
rise framed buildings. For light structures, plain or reinforced concrete may be used, but for
e f
Shear plane
Un-reinforced pads are designed on the basis that no tension occurs in the concrete. The
Example 2:
Design a pad foundation for a 300 × 300 mm column, carrying a load of 500 kN. The safe
Solution:
Column load
Area of the pad foundation =
Safe bearing capacity
500
= = 2.5 m2
200
Figure App7.3. In order that the shear planes pass through the lower corners of the pad,
Shear plane
Structure, Department of Communities and Local Government under the Open Government