Professional Documents
Culture Documents
Analysis of Distribution System Reliability and Outage Rates PDF
Analysis of Distribution System Reliability and Outage Rates PDF
Analysis of
Distribution System Reliability and Outage Rates
R280-90-7 Reference Data
Utility A
0.715 outages per customer per year (SAIFI),1.056 hours per
outage (CAIDl ), resulting in 0.767 outage hours per customer Figure 1.
per year (SAIDI). Reclosers and fuses provide protection against transient
and permanent faults.
Utility B
0.475 outages per customer per year (SAIFI), 1.4 hours per out-
age (CAIDI), resulting in 0.665 hours per outage per customer The fast trip curve of the recloser is used to clear all transient
per year. faults on the main feeder and taps. For permanent faults on the
taps, the recloser time delay curve allows the tap fuse to clear,
TYPES OF FAULTS—TRANSIENT VS. resulting in an outage on the tap only, as shown in Figure 2.
PERMANENT
Maximum service reliabiIity is achieved when the distribution
system is designed and operated to minimize the effect of any
fault that may occur.
Two types of faults are encountered on an overhead distribu-
tion system: transient and permanent. A transient fault is one
whose cause is transitory in nature. If the arc that results can be
cleared quickly, before it burns into a permanent fault, the cause
of the fault is gone, no equipment damage has occurred, and
the circuit can be re-energized immediately, returning service to
the entire system. Since the “open” time between fault interrup-
tion and re-energization is typically a few seconds in duration,
this operation normally is not classified as an outage.
2
R280-90-7
Investigate outage rates for one fault at F1 and one fault at F2 2. If committed to existing breaker protection adding a recloser
as shown in Figure 3. in line will still provide a dramatic decrease in outage rate:
Each outage = 1 hour in length (time required to locate fault a. 25% decrease due to line sectionalizing as described in
and restore service). earlier systems.
PLUS
b. Reduction in tap outages due to transient fault protection
provided by recloser. 50% of taps x 70% transient fault
rate = 35% reduction in outage rate.
c. Therefore, the total reduction in outage equals 25% +
35% = 60% reduction in outage rate.
Example 3
Figure 3.
Circuit Breaker In Substation With Fast
Calculating reliability.
And Delayed Relay Settings
PROBLEM
Breaker utilizing conventional relay settings of one INST trip
With No Line Recloser:
followed by time delay trip operations, with the INST trip level
Fault at F1: 1000 customers x 1 hr. = 1000 cust. hrs.
set typically at 2-1/2 times the basic phase and ground trip set-
Fault at F2: 1000 customers x 1 hr. = 1000 cust. hrs.
tings. Refer to Figure 5.
Outage Total = 2000 cust. hrs.
Phase trip = 800 amperes, INST at 2000 amperes
Ground trip = 300 amperes, INST at 750 amperes
OPTION TO IMPROVE SERVICE RELIABILITY
The 750 ampere ground trip instantaneous setting generally
1. Refer to Figure 3. Add a recloser at point A as a main line
will not provide “reach” for faults distant from the substation;
sectionalizing device to reduce outage rates caused by faults
thus all transient faults occurring at these locations and all
on the main feeder.
faults below 750 ampere magnitude on any tap, will result in an
With Recloser At A:
outage.
Fault at F1: 1000 customers x 1 hr. = 1000 cust. hrs.
Fault at F2: 500 customers x 1 hr. = 500 cust. hrs.
Outage Total = 1500 cust. hrs.
Example 4
Figure 4. Feeder Protected By Recloser
Substation breaker set on all delay operations to lockout.
OPTION TO IMPROVE RELIABILITY
1. Refer to Figure 6. Add a recloser in the line. This will provide
OPTIONS TO IMPROVE SERVICE RELIABILITY the 25% reduction in the outage rate as described earlier,
1. Replace breaker with recloser. plus some added improvement due to the added “reach” (or
a. Outage rate should decrease by a rate equal to the ratio sensitivity) afforded by the more sensitive trip settings of the
of transient faults to permanent faults on the system. line recloser.
Therefore, if 70% of faults are initially transient by nature,
outage rate will decrease by 70%.
3
NOTE: It is generally very difficult or impossible, for any substation Add a normally open tie recloser between feeders as shown in
device to be set to provide reach for protection to the ends of all taps. Figure 9, set to close upon loss of voltage from either side. The
mid-point reclosers will be sectionalizing type reclosers, set to
automatically open for loss of voltage from their source side.
Fault at F1: 500 customers x 1 hr. = 500 cust. hrs.
Fault at F2: 500 customers x 1 hr. = 500 cust. hrs.
Fault at F3: 500 customers x 1 hr. = 500 cust. hrs.
Fault at F4: 500 customers x 1 hr. = 500 cust. hrs.
Outage Total = 2000 cust. hrs.
Adding the tie recloser as shown in Figure 9 and operating the
Figure 6. mid-point reclosers as sectionalizing reclosers has resulted in a
Feeder recloser with conventional recloser settings. 33-1/3% reduction in customer outage:
(3000-2000)/3000 = 33-1/3%.
Adding the three reclosers as shown in Figure 9 to the two
Example 5 feeders has reduced the outage rate to 50% of the original:
Loop Schemes (4000-2000)/4000 = 50%.
For the highest level of service reliability, some utilities have uti-
lized loop schemes. The following example shows the improve-
ment in service reliability that can be accomplished by mid-point
sectionalizing, and addition of a “tie” recloser between feeders.
Refer to Figure 7 and assume one fault at each section, for
one hour duration each.
Fault at F1: 1000 customers x 1 hr. = 1000 cust. hrs.
Fault at F2: 1000 customers x 1 hr. = 1000 cust hrs.
Fault at F3: 1000 customers x 1 hr. = 1000 cust hrs.
Fault at F4: 1000 customers x 1 hr. = 1000 cust. hrs.
Figure 9.
Normally open tie recloser between feeders.
Example 6
Application Of Recloser At Feeder Tap
Refer to Figure 10 and assume “reach” of recloser A extends to
point D on tap.
If a fuse is used at location C:
1. Any transient fault on the main tap line beyond location D will
cause fuse “C” to operate, resulting in an outage on the entire
tap, for a fault that was initially transient.
2. Service restoration can be delayed since crew may spend
Figure 7.
considerable time looking for a fault that no longer exists.
Typical recloser-protected feeders without mid-point 3. For a transient fault beyond any of the downline fuses, the
sectionalizing. downline fuse will operate, again resulting in an unnecessary
outage for a fault that was initially transient.
Refer to Figure 8 and assume one fault at each section for Use of a recloser at location C can normally be sized to pro-
one hour duration to show the effects of mid-point sectionaliz- vide reach for the entire tap. The “fast” trip of the recloser (as
ing. shown in Figure 2) will then clear transient faults, the reclosing
Fault at F1: 1000 customers x 1 hr. = 1000 cust. hrs. operation then restoring service to all customers on the tap.
Fault at F2: 500 customers x 1 hr. = 500 cust. hrs.
Fault at F3: 1000 customers x 1 hr. = 1000 cust. hrs.
Fault at F4: 500 customers x 1 hr. = 500 cust. hrs.
Outage Total = 3000 cust. hrs.
(25% reduction)
Figure 10.
Feeder tap without recloser protection.
Figure 8.
Reclosers at midpoint of feeders.
4
R280-90-7
UNDERGROUND DlSTRIBUTlON For this automated operation, switches have been developed
For an underground distribution feeder or system, comparison to that have a stored energy operator (allows remote switching
an overhead distribution system for purpose of operating reliabil- without power at the switch location) and fault indicators to pro-
ity presents some differences. An underground feeder has no vide remote indication of fault location. Use of switches allows
transient faults, fewer outages and outages of longer duration. more sectionalizing points on the feeder without adding any
steps of coordination. Reclosers are used to provide immediate
Since an underground system has no transient faults, there local fault clearing capabilities that are independent of the com-
generally is no need for fast tripping or reclosing operations. munication system or remote computer control.
Typically, protection at the substation consists of a single time
delay trip operation and lock open. SUMMARY
An underground system will have fewer faults than an over- Increased usage of electricity has led to the need to increase
head system, since there is no exposure to wind, trees, ice, distribution system voltages. Utilization of these higher distribu-
sleet, etc., and limited exposure to wildlife, lightning surges, etc. tion voltages has resulted in decreased system reliability and
When a fault does occur, the outage duration can be quite higher customer outage rates. Efficient application of reclosers
long. The time to patrol the line and locate the fault can be quite can provide dramatic improvements in distribution system relia-
lengthy, equipment or cable repair can also require considerably bility.
more time than equivalent overhead equipment repair. Even Using reclosers to provide transient fault protection on the
though the number of outages on an underground feeder may entire distribution system can improve outage rates by 50-90%.
be limited, the long outage times required for fault location and Reclosers or sectionalizers used as main line sectionalizing
repair can result in unacceptable outage ratio. Addition of a mid- devices can improve outage rates an additional 25%.
point fault sensing and interrupting device can be used to Even greater service continuity can be achieved by using
reduce the number of customers affected and reduce the time nearby feeders as backup supplies. By using reclosers or sec-
required for fault location. tionalizers as normally open feeder ties with local supervisory
controls, outage rates can be improved by an additional 50%
SYSTEM AUTOMATION over unsectionalized systems.
After protective devices are properly applied on a distribution Additional improvements in distribution system reliability can
system, the next higher level of system reliability can be be obtained through the application of supervisory control or
achieved by automating the entire system for remote identifica- distribution automation.
tion of faulted sections and rapid isolation of these sections by
means of remote switching operations.
Remote identification of the faulted section eliminates the time
required for line patrol. The remote switching function allows the
faulted line to be isolated, and service restored to all other line
sections (assuming availability of an alternate feed to the remote
sections) in less than 2 minutes. Thus, the outage is limited to
only the faulted portion of the line.
Figure 11 illustrates a distribution system using both remotely
operated switches and line reclosers that can also be operated
remotely.
Figure 11.
Automated distribution system.
5
P.O. Box 1640
© 1996 Cooper Industries, Inc. Waukesha, WI 53187
Kyle® is a registered trademark of Cooper Industries, Inc. www.cooperps.com