NODESCRIPTIONUNITPLN REQUIREDManufacturerto be mentionedTypeto be
mentioned1Standard IEC 62271-100 and IEC 62271-12Service conditionOutdoor; Tropical
area3Type of Circuit breakerLive Tank4Type of arc quenching mediumSF65Number of Phasesphase36Rated voltage (Ur)kV rms3007Rated frequency (Fr)Hz508Rated normal current (Ir)A rms≥ 31509Rated short-time withstand current (I th)kA rms5010Rated peak withstand current (I p)kA peak≥ 2,5 x I th11Rated duration of short circuits≥ 112RATED INSULATION LEVEL : Power frequency withstand voltage, dry for 1 minute- Phase to earth, between the phases kV rms≥ 395Impulse withstand voltage (at 1,2/50 microsecond)- Phase to earth, between the phases kV peak≥ 1050Switching withstand voltage (at 250/2500 microsecond)- Phase to earth and and across the open breaker gapkV peak≥ 850- Between the phaseskV peak≥ 127513Minimum Creepage distancemm/kV25 or 3114OPERATING SEQUENCE AND OPERATING DUTY- Nominal Sequence(rapid auto-reclosing/dead time)O - 0.3s - CO - 180s - CO- Out of phaseO - CO15Rated making and breaking current to Normal/Reclose - Making currentkA peak≥ 2,5 x I th - Breaking current (symmetrical)kA rms50 - % dc component% dc> 2016Breaking current under out of phase conditionkA rms≥ 25 % x I th17Rated