You are on page 1of 2

To BAT1(-) Breaker on FPRB

Battery Bank #1
(Using NYAF Blue Cable 1*16mm2) 1P, 125 A

To BAT2(-) Breaker on FPRB


Battery Bank 2
(Using NYAF Blue Cable 1*16mm2) 1P, 125 A

To LOAD 1(-) on FPRB


FDD
(Using NYAF Blue Cable 1*16mm2) 1P, 125 A 1P, 63 A

TDD
1P, 63 A

To LOAD 2(-) on FPRB


Speed
(Using NYAF Blue Cable
1*16mm2) 1P, 63 A 1P, 16 A Control

TX #1
1P, 10 A

TEC

TX #2
1P, 10 A

TX #3
1P, 10 A

(Using NYAF Black Cable 1*16mm2)


From FPRB RTN 1(+)
ODC35 V3 Positive BAR
(Using NYAF Black Cable 1*16mm2)
From FPRB RTN 2(+)

Note :
- Brand ABB (S200), Hager(MU), Schneider (C60H).
- Battery Negative Cable NYAF Blue 16 mm2 – 2 x 3 m included scoen, vynil, & label.
- Battery Positive Cable NYAF Black 16 mm2 – 2 x 3 m included scoen, vynil, & label.

Date Scale Rev

Nov 23, 17 000


Page
ODC35 V3 DCPDB Wiring Diagram
1 of 2
On FPRB Rectifier
NYAF Blue Cable 1*16mm2 NYAF Blue Cable 1*16mm2
Battery #1

Battery #2

TX #2
TX #1

TX #3
Main

FAN &
TEC
FDD

TDD
MCB
LLVD1
Main
MCB
LLVD2

BUS BAR

NYAF Blue Cable 1*16mm2 ODC35 V3 DCPDB

NYAF Blue Cable 1*16mm2

NYAF Black Cable 1*16mm2

NYAF Black Cable 1*16mm2

Positive BAR

Date Scale Rev

Nov 23, 17 1 : 2.5 000


Grounding BAR
Page
NYAF Y/GBlack Cable 1*16-25mm2 ODC35 V3 DCPDB Layout Diagram
2 of 2
On FPRB Rectifier