| Load Flow Calculation Complete System Report:
Substations, Voltage Profiles, Grid Interchange |
-----------------------------------------------------------------------------------
------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model
Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable
Load Flow Error for |
| Consider Reactive Power Limits No | Nodes
1.00 kVA |
| | Model
Equations 0.10 % |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Grid: javier parra System Stage: javier parra | Study Case: Study Case
| Annex: / 1 |
-----------------------------------------------------------------------------------
------------------------------------------------
| rated Active Reactive Power |
|
| Voltage Bus-voltage Power Power Factor Current Loading|
Additional Data |
| [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] |
|
-----------------------------------------------------------------------------------
------------------------------------------------
|BARRA 1 |
|
| 231.00 1.00 231.00 0.00 |
|
| Cub_4 /Sym GENERADOR 365.90 286.57 0.79 1.16 464.76 |
Typ: PQ |
| Cub_8 /Lod L1 60.00 32.00 0.88 0.17 |
Pl0: 60.00 MW Ql0: 32.00 Mvar |
| Cub_6 /Lne LINEA 1-3 173.69 145.41 0.77 0.57 18.87 |
Pv: 6623.48 kW cLod: 0.01 Mvar L: 1.00 km|
| Cub_7 /Lne LINEA 1-2 132.20 109.16 0.77 0.43 14.28 |
Pv: 4225.40 kW cLod: 0.01 Mvar L: 1.00 km|
| |
|
|BARRA 2 |
|
| 231.00 0.89 205.23 -6.71 |
|
| Cub_5 /Lod L2 115.00 67.00 0.86 0.37 |
Pl0: 115.00 MW Ql0: 67.00 Mvar |
| Cub_3 /Lne LINEA 2-3 12.98 15.61 0.64 0.06 1.90 |
Pv: 46.22 kW cLod: 0.01 Mvar L: 1.00 km|
| Cub_4 /Lne LINEA 1-2 -127.98 -82.61 -0.84 0.43 14.28 |
Pv: 4225.40 kW cLod: 0.01 Mvar L: 1.00 km|
| |
|
|BARRA 3 |
|
| 231.00 0.88 202.68 -7.13 |
|
| Cub_5 /Lod L3 180.00 123.00 0.83 0.62 |
Pl0: 180.00 MW Ql0: 123.00 Mvar |
| Cub_3 /Lne LINEA 2-3 -12.93 -15.32 -0.64 0.06 1.90 |
Pv: 46.22 kW cLod: 0.01 Mvar L: 1.00 km|
| Cub_4 /Lne LINEA 1-3 -167.07 -107.68 -0.84 0.57 18.87 |
Pv: 6623.48 kW cLod: 0.01 Mvar L: 1.00 km|
| |
|
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| |
| DIgSILENT | Project: |
| |
| PowerFactory |-------------------------------
| |
| 15.1.7 | Date: 5/9/2018 |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Load Flow Calculation Complete System Report:
Substations, Voltage Profiles, Grid Interchange |
-----------------------------------------------------------------------------------
------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model
Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable
Load Flow Error for |
| Consider Reactive Power Limits No | Nodes
1.00 kVA |
| | Model
Equations 0.10 % |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Grid: javier parra System Stage: javier parra | Study Case: Study Case
| Annex: / 2 |
-----------------------------------------------------------------------------------
------------------------------------------------
| rtd.V Bus - voltage
Voltage - Deviation [%] |
| [kV] [p.u.] [kV] [deg] -10 -5
0 +5 +10 |
-----------------------------------------------------------------------------------
------------------------------------------------
|BARRA 1
|
| 231.00 1.000 231.00 0.00
| |
|BARRA 2
|
| 231.00 0.888 205.23 -6.71
<\\\\\\\\\\\\\\\\\\\\\\\| |
|BARRA 3
|
| 231.00 0.877 202.68 -7.13
<\\\\\\\\\\\\\\\\\\\\\\\| |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| |
| DIgSILENT | Project: |
| |
| PowerFactory |-------------------------------
| |
| 15.1.7 | Date: 5/9/2018 |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Load Flow Calculation Complete System Report:
Substations, Voltage Profiles, Grid Interchange |
-----------------------------------------------------------------------------------
------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model
Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable
Load Flow Error for |
| Consider Reactive Power Limits No | Nodes
1.00 kVA |
| | Model
Equations 0.10 % |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Grid: javier parra System Stage: javier parra | Study Case: Study Case
| Annex: / 3 |
-----------------------------------------------------------------------------------
------------------------------------------------
| Volt. Generation Motor Load Compen- External
Power Total Load Noload |
| Level Load sation Infeed Interchange
Interchange Losses Losses Losses |
| [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ to
[MW]/ [MW]/ [MW]/ [MW]/ |
| [kV] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
[Mvar] [Mvar] [Mvar] [Mvar] |
-----------------------------------------------------------------------------------
------------------------------------------------
| 231.00 365.90 0.00 355.00 0.00 0.00
10.90 10.90 -0.00 |
| 286.57 0.00 222.00 0.00 0.00
64.57 64.59 -0.02 |
-----------------------------------------------------------------------------------
------------------------------------------------
| Total: 365.90 0.00 355.00 0.00 0.00
0.00 10.90 10.90 -0.00 |
| 286.57 0.00 222.00 0.00 0.00
0.00 64.57 64.59 -0.02 |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| |
| DIgSILENT | Project: |
| |
| PowerFactory |-------------------------------
| |
| 15.1.7 | Date: 5/9/2018 |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Load Flow Calculation Complete System Report:
Substations, Voltage Profiles, Grid Interchange |
-----------------------------------------------------------------------------------
------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model
Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable
Load Flow Error for |
| Consider Reactive Power Limits No | Nodes
1.00 kVA |
| | Model
Equations 0.10 % |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Total System Summary | Study Case: Study Case
| Annex: / 4 |
-----------------------------------------------------------------------------------
------------------------------------------------
| Generation Motor Load Compen- External Inter
Area Total Load Noload |
| Load sation Infeed
Flow Losses Losses Losses |
| [MW]/ [MW]/ [MW]/ [MW]/ [MW]/
[MW]/ [MW]/ [MW]/ [MW]/ |
| [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
[Mvar] [Mvar] [Mvar] [Mvar] |
-----------------------------------------------------------------------------------
------------------------------------------------
| \Jenny\ejercicios sepII\SEP 3 BARRAS BASE\Network Model\Network Data\javier parra
|
| 365.90 0.00 355.00 0.00 0.00
0.00 10.90 10.90 -0.00 |
| 286.57 0.00 222.00 0.00 0.00
0.00 64.57 64.59 -0.02 |
-----------------------------------------------------------------------------------
------------------------------------------------
| Total:
|
| 365.90 0.00 355.00 0.00 0.00
10.90 10.90 -0.00 |
| 286.57 0.00 222.00 0.00 0.00
64.57 64.59 -0.02 |
-----------------------------------------------------------------------------------
------------------------------------------------