Bus_Report

Bus ID Equipment Nom kV Equipment Gap X Factor Grounding Limited App


Bus1 6.3 Other 13.0 2 Ungrounde 3.048

Page 1
Bus_Report

Limited AppRestricted Prohibited Available P Total Bus B Total Bus A Source PD BSource PD A
1.524 0.658368 0.18288 0 1.97 1.965 1.341 1.338

Page 2
Bus_Report

Source Trip Source Trip Source Trip Trip Time ( Open Time Total FCT ( FPB (ft) Incident En
CB2 Relay1 Overcurren 1252.815 3.5 1256.315 15.832 133.739

Page 3
Bus_Report

Working DisHazard /RisPPE DescripInsulated GInsulated Glove Class


18 > Max 7500 1

Page 4
PD_Report

PD ID Equipment Connected PD Type Limited AppLimited AppRestricted Prohibited


CB2 Bus1 HV CB 3.048 1.524 0.658368 0.18288
CB66 Bus1 HV CB 3.048 1.524 0.658368 0.18288
CB65 Bus1 HV CB 3.048 1.524 0.658368 0.18288
CB63 Bus1 HV CB 3.048 1.524 0.658368 0.18288
CB62 Bus1 HV CB 3.048 1.524 0.658368 0.18288

Page 5
PD_Report

PD Bolted ( PD Arcing ( PD FCT (Cy Arcing kA f Upstream SSource PD RSource PD Upstream S


1.341 1.338 1256.315 0
0.025 0.025 1.965 CB2 Relay1 Overcurren 1256.315
0.23 0.229 1.965 CB2 Relay1 Overcurren 1256.315
0.123 0.122 1.965 CB2 Relay1 Overcurren 1256.315
0.277 0.276 1.965 CB2 Relay1 Overcurren 1256.315

Page 6
PD_Report

FPB (ft) Incident En Working DisHazard /RisPPE DescripInsulated GInsulated Glove Class
0 0 18 7500 1
15.832 133.739 18 > Max 7500 1
15.832 133.739 18 > Max 7500 1
15.832 133.739 18 > Max 7500 1
15.832 133.739 18 > Max 7500 1

Page 7