Professional Documents
Culture Documents
2
Numerical Line Protection Relay
Operator Manual
Power 7
Blocked 8
1 9
2 10
3 11
4 12
5 13
6 14
Table of Contents
User Guide
Reference Guide
The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of
responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves
the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligation. Should a
conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both,
the latter shall take precedence.
Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes,
the matter should be referred to your local sales office.
The contents of this manual should not become part of or modify any prior or existing agreement, commitment or relationship. The sales
contract contains the entire obligation of Siemens Energy & Automation, Inc. Any statements contained herein do not create new
warranties or modify an existing warranty.
Introduction
Table of Contents
List of Figures
1. Introduction
1.1 Using This Manual
This operator’s manual is intended to provide you with all the information you need to install and
operate the Siemens 7SA511 Numerical Line Protection Relay. In addition to describing the
various tasks of operation, the manual offers general information about the functions and features
of the relay.
Several of the relay’s functions and features are optional, depending on the model ordering
number. This manual identifies all of the relay’s options and frequently refers you to section 1.3,
“Relay Model Number,” so you can determine which options your relay has.
• The User Guide describes how to install, program, operate and maintain the relay, so you
will need to read this part if you are to perform any of these tasks. General information
about the relay’s features and functions is also in this part of the manual.
• The Reference Guide includes the relay specifications, method of operation, relay setting
calculations and worksheets, and information on the relay’s hardware, software, and
communications capabilities. If you are responsible for the application and setting
calculation of the relay, you will need to read this part of the manual.
Refer to Table 1-1 for help in finding the information you need in this manual.
This manual assumes you are using the relay’s operator panel to program, maintain, and operate
the relay. If you are using DIGSI® software or some other application to control the relay, refer
to the appropriate user guide when instructions in this manual are insufficient.
Terms
annunciation 1. Activating the various relay outputs (LCD, LEDs, output relays)
when events occurs.
2. Messages that appear on the operator panel LCD in the event log or
target logs are also called annunciations.
binary input A relay input terminal that responds to the presence or absence of voltage
on the terminal in a digital (on/off) manner.
compensated The neutral system point is inductively grounded to compensate for the
(system) distributed phase-to-ground system capacitance.
dead time Time allowed following fault clearance before attempting an automatic
reclose.
fault loop In phase-selective fault detection systems, this term describes the current
path for phase-to-phase or phase-to-ground faults. For example, if a short
circuit occurs between phase 1 (L1) and phase 2 (L2), the fault loop is
L1-L2. The currents and voltages of the fault loop are decisive when
calculating the distance to fault.
forward Direction—normally downstream towards the line or load (i.e., toward the
protected component).
isolated (system) The neutral system point is purposely not connected to ground
(ungrounded).
Terms
pickup Activation of a protection function either through detection of a fault or as
a result of a binary input. The current and voltage levels or ratios that
cause a protection element to pick up are called pickup values.
reclaim time The no-fault time period following automatic reclose that defines a
successful reclose
reverse Direction—normally upstream towards the bus or source (i.e. away from
the protected object).
This manual frequently refers you to the relay model number so you can determine whether or not
a particular section is applicable to your relay and protected system. When the model number is
used, the character(s) significant to the discussion is bold, and asterisks (*) are used to indicate
that the character is irrelevant to the discussion. For example, model number 7SA511*-**A5*-
**A/E* means the relay does not have the automatic reclose feature, so you can skip the sections
on automatic reclose.
1A 1
5A 5
Rated power supply voltage VDC
24, 48 VDC 2
60, 110, 125 VDC 4
220, 250 VDC 5
Mounting construction
Surface mounting B
Flush mounting C
Fault detection options
For grounded systems, ground current input for protected line only 0
For ungrounded systems, without parallel line compensation 1
For grounded systems, ground current input for parallel line compensation 2
Communications interface (rear port)
None A
Isolated, hard-wired B
Integrated fiber optic C
Automatic reclose (AR)/Parameter changeover (PCO)
without PS without GF 0
with PS without GF 1
without PS with GF 2
with PS with GF 3
* The Power swing (PS) option is only applicable when the fault detection system selected is the polygonal impedance detector (code = 2).
The High-resistance ground fault (GF) protection is only applicable for grounded systems, i.e., the ground fault detection Input code must be
0 or 2.
Product Description
Table of Contents
2. Product Description
2.1 About the Relay
The 7SA511 line protection relay is a microprocessor-based relay designed to provide fast,
reliable, and selective clearance of all kinds of ground and phase faults on overhead lines and
cables being fed from one point or multiple points. The system can be radial, ring, or meshed
topography. The system starpoint can be solidly grounded, compensated (resonant grounded), or
isolated (ungrounded). This relay has 10 binary inputs, 5 trip relays, 11 signal relays, and 16 LED
indicators.
The relay can be flush or surface mounted and is easily programmed and operated using the
controls and keypad on the operator panel. The LEDs on the operator panel continuously display
relay status and target indication. When prompted, the LCD shows the system settings,
configuration settings, protection settings, measured values, calculated values, setting options,
event messages, and other operational information.
The relay can be connected to a PC or to a substation control system, enabling the user to analyze
data stored in the relay’s memory and to monitor the relay’s alarms and status signals.
· Operating settings define the conditions under which the relay will function. These
include the setting of the real-time clock (time and date), choice of display language, and
choice of the data transmission rate for the front port. The operating settings also identify
what information is to be displayed in each of the two lines of the LCD for operational
messages and for fault messages.
The relay’s “Scope of Functions” settings are also considered part of the operating
settings. These settings indicate which functions are activated (EXIST) and deactivated
(NON-EXIST). Operating settings also indicate how the optional functions automatic
reclose and parameter changeover will operate.
· System settings identify the protected power system and switchgear. Information such as
the system starpoint direction and condition, voltage transformer voltages, and current
transformer rated current is required. The relay’s distance protection and ground fault
protection functions use this information to compute the system’s protection requirements.
When the parameter changeover feature is available (see section 2.5.3), system settings
can vary between the parameter sets.
· Protection settings such as for distance protection, pilot protection, and overcurrent
protection, specify the values that are used to identify fault conditions and are the majority
of settings the 7SA511 relay requires. Depending on your relay model (see section 1.3.3),
you may also need to indicate settings for power swing blocking protection or high-
resistance ground fault protection. When the parameter changeover feature is available
(see section 2.5.3), protection settings can vary between the parameter sets.
· Relay configuration settings tell the relay how to process the input information and
logically associate it with the output devices. If desired, you can reassign the binary inputs,
annunciations, and the function of the relay’s output signals, trip relays, and LEDs.
Configuration is also referred to in this manual as programming or marshalling the relay.
· Distance protection
· Emergency overcurrent protection
· Power swing protection (optional)
· Pilot protection
· Ground fault detection for ungrounded systems (optional)
· High-resistance ground fault protection for grounded systems (optional)
· Automatic reclose (optional)
· Distance-to-fault location
You should read the relay’s model number on the front of the operator panel to determine if your
relay has the optional protection functions. section 1.3 in the “Introduction” section of this manual
describes how to read and interpret the relay model number.
Feature Description
Fault detection · Overcurrent fault detection (Iph>>). Use of this fault detection
options scheme depends on high short circuit currents.
Feature Description
Ground fault · Ground faults are detected by ground current ( IE )or displacement
detection voltage ( VE ).
1. Blocking. The distance protection tripping function may be blocked for the duration
of the power swing.
2. Tripping. Tripping may be initiated following the detection of a power swing outside
the defined stability limits.
The pilot protection signal interface is implemented by assigning appropriate logical functions to a
signal relay (transmitter) and a binary input (receiver).
· The relay detects (picks up) the ground fault by monitoring the displacement voltage.
· By measuring the phase-to-ground voltages, the relay determines the faulted phase.
· The direction of the ground fault (residual) current is determined by high accuracy,
real, and apparent component measurement.
When using impedance fault detection, ground fault impedances can occur which appear to lie
outside the pickup characteristic of the relay. The high-resistance ground fault protection function
of the 7SA511 relay also prevents this occurrence.
Working independently from the distance protection elements, distance-to-fault uses its own filter
algorithms and measured values to recognize and locate the fault. The fault location calculation
results in the following outputs:
For accurate impedance measurements in parallel line systems, the optional ground fault detection
function for parallel line compensation is required (relay models 7SA511*-**A5*-2***).
· Real-time clock. A real-time clock with battery backup may be synchronized via a binary
input or through a serial data port (see section 2.5.2). All events are recorded with a date
and time tag.
· Target history log. Operational records for the last three faults are recorded and stored in
the relay’s memory. These records include the fault type, interrupted current, distance-to-
fault, etc.
· Target history for ungrounded systems. Relays with the optional isolated system
ground fault detection function record the details for the last three ground faults in a
separate log.
· Tripping statistics. For each pole of a circuit breaker, it is possible to record the
cumulative total of tripping operations and interrupted current.
Rear Port
The optional port on the rear panel of the relay is intended for remote data retrieval by a
substation control system. It is available as an optical fiber or hard-wired interface (relay models
7SA511*-**A5*-*B/C**). Consult the factory for details on the use of this feature.
Only one parameter set is active at a time. You can change the active parameter set during relay
operation (provided no protection functions are picked up) using the operator panel or through
the binary inputs. If the relay is connected to a PC via the front port, you can use DIGSI®
software to change the active parameter set.
Acceptance Tests
Table of Contents
List of Figures
3. Acceptance Tests
This section provides acceptance test procedures. Follow these procedures carefully to avoid
possible injury and equipment damage. When testing the 7SA511 relay, you should be familiar
with all applicable safety regulations from ANSI, IEC, NEC, and other pertinent standards.
Be sure that you are using the correct tests for your relay configuration. If a test is not applicable
to your relay model number and configuration do not attempt to perform the test.
In the following chapters, the protection functions provided by the relay are referenced with the
IEC designations shown in the list below. This nomenclature is used in the text, the tables and the
LCD. The corresponding ANSI designations are also indicated.
IEC ANSI
I>> 50H/51H High-set emergency overcurrent protection element for
phases
I> 50/51 Definite time emergency overcurrent protection element for
phases
I E> 50G/51G/67G Time overcurrent element for high-resistance ground fault
protection in grounded systems
VE> Displacement voltage threshold for isolated ground fault
detection
AR 79 Automatic reclose
47 Phase sequence check
21 Distance protection with:
Iph>> - Overcurrent fault detection
V</I> - Voltage-controlled overcurrent fault detection
Z< - Impedance fault detection
85 Pilot protection
78 Power swing/out-of-step protection
For information on relay mounting and connection options, refer to the “Installation” section.
The acceptance tests described in the rest of this chapter verify the following are working:
· Power supply
· Metering capabilities
· Fault detection systems
- Overcurrent
- Voltage-controlled overcurrent (7SA511*-*CA52/3-****)
- Polygonal impedance (7SA511*-*CA52-****)
· Distance zone schemes
· Pilot protection signal transmission functions
· Ground fault detection for ungrounded systems (7SA511*-*CA5*-1***)
· High-resistance ground fault protection for grounded systems
(7SA511*-*CA5*-0/2**2/3)
· Automatic reclose (model number 7SA511*-*CA5*-**B/C/F/G*)
· Power swing function (model number 7SA511*-*CA52-***1/3)
· Binary inputs and LED operations
· Output contacts (signal and trip relays)
· DC power supply, 20W nominal minimum with a 1 millisecond peak load capability as
indicated in Table 3-1.
Table 3-1. Power Supply Rated Voltage (VDC) by Relay Model Number
Relay Model Number Rated Voltage Inrush (peak)
7SA511*-2*A5*-**** 24/48 VDC 100 A
7SA511*-4*A5*-**** 60/110/125 VDC 50 A
7SA511*-5*A5*-**** 220/250 VDC 25 A
Note: See section 1.3, “Relay Model Number,” for more information
on how to read and interpret the relay model number.
Note: Commercial test sets that include some or all of the above test tools are
available and can be used in the following tests.
DANGER
Hazardous voltages in the equipment.
This can cause severe personal injury and
equipment damage.
1. Connect the relay to a DC power source that provides the rated relay voltage as described in
Table 3-1.
2. If a protective cover is on the relay, remove the cover to access the operator panel. Refer to
“Installation” section 4.3.1 of this manual for step-by-step instructions on removing the
relay protective cover.
3. Position the On/Off switch on the operator’s panel to the “On” position. After energizing
the relay, the green Power LED should light, and the Blocked LED will light up briefly then
go out, which indicates the relay successfully completed its self-diagnostics tests.
or
(German)
DIREKTE ADRESSE
2. Some tests in this chapter require you to change settings. After acceptance testing is complete,
you will need to change the relay settings back to your settings. Refer to Chapter 5,
“Programming the Relay,” for detailed instructions on how to change relay settings.
3. Using the programming procedures provided in “Programming the Relay” ,ensure that the
frequency parameter at address 7899 is set to 60 Hz.
Note: Inaccurate test results may indicate that the relay settings being used are incorrect.
Always verify the relay settings for each test before beginning the test. If you
repeatedly receive inaccurate test results and the relay settings are correct for the test,
immediately contact the relay manufacturer.
CAUTION
Excessive test currents.
Test currents larger than 4IN may
damage the relay if applied
continuously.
CAUTION
Excessive test voltage.
Test voltages larger than 140 V
may damage the relay if applied
continuously.
Test Procedure
1. Measure the input current while varying the input voltage between the limits indicated in the
table below. The values should be within the “Measured Current” range for the corresponding
entry in Table 3-3.
Test Procedure
1. Connect ohmmeters or other appropriate continuity checking devices to the relay terminals as
indicated in the table below.
2. For the Power On/Off switch settings shown in Table 3-4 (supply or relay), the continuity
reading should be as indicated.
Test Procedure
1. Connect test equipment to the relay as indicated in Table 3-1.
Notes: 1. The frequency of the test current must be the same as the relay’s rated frequency (fN), as
defined at address 7899.
2. The test current must match the relay’s rated current, IN. Refer to the relay model
number to determine the rated current as indicated in the following chart.
Model No. IN
7SA5111-**A5*-**** 1A
7SA5115-**A5*-**** 5A
2. Using the operator panel, display the address corresponding to the terminal pair that has the
current source connected (see Table 3-6).
3. Ensure that the displayed percentage is within the tolerance indicated in Table 3-6
4. Move the current source to the next pair of terminals indicated in the table below. Repeat
steps 2 through 4. Continue testing until all three pairs of current input terminals have been
tested.
5. Display address 5709. Ensure that the displayed value, f[%], is between 99.5% and 100.5%.
Test Procedure
1. Connect test equipment to the relay as indicated in Table 3-7.
Notes: 1. The frequency of the test voltage must be the same as the relay’s rated frequency (fN), as
defined at address 7899.
2. The test voltage must match the relay’s rated secondary voltage (VN SECOND.) setting at
address 1104.
2. Using the operator panel, display the address corresponding to the terminal pair that has the
voltage source connected (see Table 3-8).
3. Ensure that the displayed percentage is within the tolerance indicated in Table 3-8.
4. Move the voltage source to the next pair of terminals indicated in the table below. Repeat
steps 2 through 4. Continue testing until all three pairs of voltage input terminals have been
tested.
Test Procedure
1. Connect test equipment to the relay as indicated in Table 3-9.
Note: The binary input voltage must never exceed the upper relay specification limit defined in
the “Specifications” section.
5. Refer to the “Erasing Stored Data” section in the “Maintenance” chapter to reset the event
log. All other relay settings should be factory presets.
6. Using the operator panel, display address 5100. “OPERATIONAL ANNUNCIATIONS”
appears in the display. Press to display the first entry in the log.
7. Ensure that the displayed message is “Table empty.”
8. Exit display of the 5100 block. Increase the binary input voltage to 20 volts. Repeat step 6.
Ensure that the displayed message matches that shown in Table 3-11. Reduce the binary input
voltage to zero.
9. Move the voltage source to the next pair of terminals indicated in Table 3-11. Repeat steps 5
through 8 then exit the test procedure.
Test Procedure
1. Connect test equipment to the relay as indicated in Table 3-12. Binary Input 1 is the only
binary input that should have a connection.
Note: The frequency of the test current must be the same as the relay’s rated frequency, fN, as
defined at address 7899.
5. Increase the input current until it reaches 2.5IN. Wait at least 1 second after completing input
adjustments to ensure that all time delays have expired before examining the results. Verify the
state of the LEDs as indicated in Table 3-14. Reduce the current input to zero. Move the
current source to the next set of terminals in the table and press the Target Reset key.
Repeat this step until all three pairs of current input terminals have been tested.
6. Increase the input current until it reaches 2.5IN. Wait at least 1 second after completing input
adjustments to ensure that all time delays have expired before examining the results. Verify
that one or more of the LEDs are on. Reduce the current input to zero. Except for LED 1, the
LEDs should be unchanged. Increase the voltage source to 20 volts or more. All of the LEDs
should turn off. This completes the test.
Test Procedure
1. Connect test equipment to the relay as indicated in Table 3-15.
Note: The frequency of the test current must be the same as the relay’s rated frequency (fN), as
defined at address 7899.
5. Increase the input current (equally for all three phases) until it reaches 2.5IN. Wait at least 1
second after completing input adjustments to ensure that all time delays have expired before
examining the results. Verify that Signal Relays 6, 7, 8, and 9 are closed. Signal Relay 4
should remain open. Trip Relays 2, 3, 4, and 5 should all be closed.
6. Decrease the input current on phase 1 to zero. Wait at least 1 second after completing input
adjustments to ensure that all time delays have expired before examining the results. Verify
that Signal Relays 6, 8, and 9 and Trip Relays 2, 4, and 5 remain closed. Signal Relay 7 and
Trip Relay 3 should now be open and Signal Relay 4 should be closed.
7. Reduce the input current on all three phases to zero. Wait at least 1 second after completing
input adjustments to ensure that all time delays have expired before examining the results.
Verify that all relay contacts are open.
The overcurrent detection threshold value for phase currents (IPH>> ) is set at address 1601. The
factory presetting is 1.8IN. The threshold value for ground currents (IE>) is set at address 1602
with the factory presetting of 0.50IN.
Prerequisite Settings
Addr. LCD Text Description Setting
7802 DIST.F.DET Select the type of fault detection system OVERCURRENT
7803 EMERG. O/C Emergency overcurrent protection EXIST
function
2601 EMERG. O/C Turn emergency overcurrent protection on ON
or off
Test Procedure
The test current is increased gradually in any phase until the element picks up. The pickup current
value is then verified against the programmed settings. Ensure that the relay picks up at 1.1 times
the setting value and does not pick up at 0.9 times the setting value. The reset value should be
95% of the pickup value.
When testing phase-to-phase current, pickup indication appears for the associated phases. If the
phase overcurrent threshold value is exceeded when testing phase-to-ground current, the pickup
indication for ground current (IE>) appears for the tested phase. The factory preset indicators that
are applicable in these cases are as follows:
Trip delays are normally tested at two times the pickup current value. Depending on the voltage
polarity, directional final time T4 (address 1203) or nondirectional final time T5 (address 1204)
will apply. The set times are pure delay times; operating times of the measurement functions are
not included.
Remove the input voltage. Repeat time measurement for one phase. Now, the trip delay for
emergency backup operation is applicable:
An example of the pickup characteristic is shown in Figure 3-1. With factory settings, the slope of
the voltage-dependent branch is zero since the voltage settings for both the Iph> and Iph>> current
levels are the same (i.e., 48 V for phase-to-ground voltage and 80 V for phase-to-phase voltage).
V
70
60
V(Iph>>)
50
V(Iph>)
40
30
Pickup
20
10
Iph> Iph>>
0
0 I/IN
1 2 3
Prerequisite Setting
Addr. LCD Text Description Setting
7802 DIST.F.DET Select the type of fault detection system U/I
Test Procedure
1. Set test voltage to 0 V.
2. Slowly increase test current of one phase until the fault detector picks up. Pickup should
occur when the test current exceeds the setting value Iph> (address 1611, factory preset is
0.2IN). With factory preset I/O configuration, the following LEDs should light at pickup:
6. Using a phase-to-phase input voltage, set the test voltage of the tested loop to approximately
the rated voltage (VN SECOND at address 1104; factory preset is 100 V). Set the test current of
both the phases to twice the setting value IPH> at address 1611 (factory preset is 0.20 IN) The
phase relationship of the test voltage and test current is irrelevant.
7. Slowly decrease voltage until the fault detector picks up. Pickup occurs for both the tested
phases when the test voltage goes below the set value of addresses 1614 and 1615 (factory
preset is 80 V). With factory preset I/O configuration the following LEDs will light for the
tested phases.
If the voltage dependent branch is inclined, the expected pickup value of the voltage can be
calculated according to the following formula, provided the test current is 2 times the setting
value of Iph>:
I ph >
Pickup value V = V ( I > ) + [V ( I >>) − V ( I >)]
I ph >> - I ph >
Prerequisite Setting
Addr. LCD Text Description Setting
7802 DIST.F.DET Select the type of fault detection system IMPEDANCE ZONE
Test Procedure
Feed a test current of 2IN into the loop under test. If the test voltage will exceed the rated voltage
when the threshold is reached, reduce the test current (minimum current Iph> at address 1621
must still be exceeded). Test current must be kept constant during this test.
Validity X
Validity range KX
range KR
X+A
VP
øp
Ip
R
RA RAE
X-A
Validity range KX Validity
range KR
Determine the threshold point by slowly reducing the voltage. Check indicators and outputs.
Since the fault detection polygon is made up of straight lines (Figure 3-2), different formulas must
be used for the threshold voltages dependent upon the intersections of these lines. The general
formulas are:
VP/V = KRRA(IP/IN)
For phase-to-ground testing, the test current is applied to one phase and the ground current path.
For phase-to-phase testing, the current must flow through the tested phases in opposite directions.
To avoid errors, it is essential the two phase voltages be symmetrical. For the factory set values
and IP/IN = 2, the resultant voltages will be as described in Table 3-17.
If different values have been set for RA1 and RA2, then RA1 is valid for phase angles between
-45° and +45°, and between 135° and 225°. For other phase angles, setting value RA2 is decisive.
Table 3-17. Test Voltages VP With Test Current IP = 2IN and Factory Presets.
Fault Type fp = 0° fp = 90° fp = 180° fp = 270° = 90°
3-phase VP = 12V VP = 24V VP = 12V VP = 5V
2-phase VP = 24V VP = 48V VP = 24V VP = 10V
1-phase VP = 48V VP = 48V VP = 48V VP = 10V
Table 3-18 gives the factors KX and KR for your own settings, for test angles fP = 90° and 0°, and
the generally applicable formulas.
Table 3-18. Test Factors KX and KR for Settings Other Than Factory Presettings.
Fault Type KX KR
fp = 270°/90° General fp = 0°/180° General
3-phase 1 1 1 1
sin φ P cos φ p
2-phase 2 2 2 2
sin φ P cos φ P
1-phase 1+ XE XL 1 + XE XL 1 + RE RL 1 + RE RL
sin φ P cosφ P
Test Procedure
Feed a test current IP = 2IN into the loop under test. If the test voltage will exceed the rated
voltage when the threshold is reached, reduce the test current (the minimum current Iph> at
address 1621 or 1621 and overcurrent Iph>> at address 1601 must still be exceeded). The test
current must be kept constant during a test.
X
Validity range KX
X
Vp
Validity range KR
φp
Ip RE
R
R
45°
Determine the threshold point by slowly decreasing the voltage. Check indicators and outputs.
Since the tripping polygon is made up of straight lines (Figure 3-3), different formulas must be
used for the threshold voltages dependent upon the intersection of these lines. The general
formulas are:
VP/V = KXXZone(IP/IN)
VP/V = KRRZone(IP/IN)
Table 3-19. Test Voltages VP for Zones Z3, Z2, and Z1 at IP = 2 x IN and Factory Presettings.
Zone Test Type f P = 0° fP = 90°
Z3 3-phase VP = 10 V VP = 20 V
2-phase VP = 20 V VP = 40 V
1-phase VP = 40 V VP = 40 V
Z2 3-phase VP = 5 V VP = 10 V
2-phase VP = 10 V VP = 20 V
1-phase VP = 20 V VP = 20 V
Z1 3-phase VP = 2.5 V VP = 5 V
2-phase VP = 5 V VP = 10 V
1-phase VP = 10 V VP = 10 V
Overreach zone Z1L is used only in conjunction with multi-shot auto-reclose. Therefore, this
distance zone can be checked when testing the internal auto-reclose function. This section is
applicable only to relay models 7SA511*-**A5*-**B/C/F/G*.
For the factory set values and IP/IN = 2, the resultant voltages for overreach zones Z1B and Z1L
will be as described in Table 3-20.
Table 3-20. Test Voltages VP for Overreach Zones Z1B and Z1L at IP = 2 x IN and Factory
Presettings.
Zone Test Type f P = 0° fP = 90°
Z1B 3-phase VP = 3 V VP = 6 V
2-phase VP = 6 V VP = 12 V
1-phase VP = 12 V VP = 12 V
Z1L 3-phase VP = 4 V VP = 8 V
2-phase VP = 8 V VP = 16 V
1-phase VP = 16 V VP = 16 V
Table 3-18 gives the factors KX and KR for your own settings, for test angles fP = 0° and 90°, and
the generally applicable formulas.
When measuring the response times, remember that the inherent measurement and trip time of the
relay is additive to the programmed delay time.
Testing of power swing detection requires both three-phase current and three-phase voltage input.
Test Procedure
1. Connect test equipment to the relay as indicated in Table 3-21.
Note: The frequency of the test current must be the same as the relay’s rated frequency (fN), as
defined at address 7899.
5. Increase the input current (equally for all three phases) until it reaches 2IN. Increase the input
voltage (equally for all three phases) until it reaches VN SECONDARY. The phase angle between
the voltage and current should be approximately 0°. Wait at least 1 second after completing
input adjustments to ensure that all time delays have expired. Press the Target Reset key.
6. Decrease the input voltage (equally for all three phases) to zero. Wait at least 1 second after
completing input adjustments to ensure that all time delays have expired before examining the
results. Verify that Trip Relays 3, 4, and 5 (O/S Trip) are all closed.
Once initiated, the transmission signal should be at least as long as the setting at address 2103 (T-
SEND-PRL).
To check the receiver, a short circuit is simulated as indicated in Table 3-26. The binary input
with function >Dis.Recept. (FNo 082) assigned (factory preset is Binary Input 5) must be
activated simultaneously with simulation of the fault.
The overcurrent protection function provides a high-set element and a definite time element. Each
element will be tested separately. In the remaining sections, the required setup for testing each
element is provided and then followed by a common test procedure.
In the common test procedure, a single phase test current is connected sequentially to each of the
four current inputs. The test current is increased until the protection picks up and is then
maintained until the trip time delay expires. The pickup current value and the time delay are then
verified against the programmed settings.
Note: The frequency of the test current must be the same as the relay’s rated frequency, fN, as
defined at address 7899.
*
Signal relays 7-10 should be wired in parallel to the timer start input so that closing of any
one of the four relays will start the timer.
6. Go to the heading that identifies the particular overcurrent element that you wish to test:
· High-set 3.13.2
· Definite time 3.13.3
CAUTION
Excessive test currents.
Test currents larger than 4IN may
damage the relay if applied
continuously.
2. Verify that the pickup current value and the trip delay (timer value) match the values shown in
Table 3-31 for this set of input current connections. Refer only to the set of four values for the
specific overcurrent element that you are testing (e.g. definite time)
3. Reduce the input current until the LED turns off. Verify that the input current level at which
the LED turns off is 95% of the value at which it turned on. Reduce the input current to zero.
4. Move the current source to the next pair of terminals indicated in Table 3-31. Repeat steps 1
through 4 until all four of the current input connections shown in the table have been tested.
5 Reduce the input current to zero and power off the relay. If you wish to test another
overcurrent element, return to section 3.13.1.
Prerequisite Setting:
Addr. LCD Text Description Setting
1201 DIST. PROT. Turn the distance protection function on OFF
or off
Table 3-32. Prerequisite Settings for the Directional Definite Time Test.
Without Directional Comparison
Addr. LCD Text (1st line) Description Setting
7808 EARTH FAULT Type of high-resistance ground fault DIRECTIONAL D.T.
protection
3101 E/F D.T. Turn the directional, definite time ON
ground fault protection on or off
With Directional Comparison
Addr. LCD Text (1st line) Description Setting
7808 EARTH FAULT Type of high-resistance ground fault DIREC. COMPARISON
protection
3201 E/F COMPAR Turn the directional, definite time ON
ground fault protection function with
directional comparison on or off
To perform this test, you will need to assign logical functions to the I/O unit as indicated in Table
3-33. This is necessary since these functions are not preset to any I/O at the factory.
Test Procedure
1. For directional, definite time ground fault protection, the nondirectional backup element is
checked first by slowly increasing the ground current.
Note: For parallel line compensation (relay model 7SA511*-**A5*-2***), increase one
phase current for this test. In this case, address 1111 must be set to “PARALLEL
LINE.”
2. After exceeding 75% of the pickup value setting at address 3103 (IE>), check the event log
under address block 5200 for the message E/F Fault I> (FNo 761), which should appear in
the target log.
3. When the pickup value at address 3103 is exceeded, the message E/F Fault I>> (FNo 762)
should appear in the target log.
4. When the trip delay for the nondirectional backup element (address 3108) has expired, the I/O
unit (LED or signal relay) assigned to, E/F T<> expir (FNo 773), should activate.
Additionally, the E/F Trip -> (FNo 781) message should appear in the event log,.
5. To test the directional element, a residual voltage is necessary. If address 1109 is set as VT
DELTA is “CONNECTED,” the voltage from the residual voltage winding is applied to the
measured value input or, a single-phase voltage will be applied to the phase into which the
current is fed.
Note: The current and voltage applied in the same phase must be in phase opposition so that
the relay trips in the “forwards” direction (function E/F T-> expir, FNo 772).
6. If directional comparison is turned on, the transmission circuit can be checked. Verify that the
function E/F Send (FNo 791) message appears in the target log.
7. To check the receiver circuit, a single-phase fault in the forwards direction is simulated,
simultaneously when the external input of binary input signal >E/F Recept (FNo 090) is
applied. When directional comparison is active, the relay will not trip if the comparison signal
is not received.
Prerequisite Settings:
Addr. LCD Text Description Setting
7808 EARTH FAULT Type of high-resistance ground fault INVERSE TIME
detection
3301 E/F I.T. Turn the nondirectional, inverse time ON
ground fault protection on or off
To perform this test, you will also need to configure, E/F Fault I>> (FNo 762), to a signal relay
or LED. This function indicates that the ground fault protection element has picked up.
Test Procedure
1. Slowly increase the ground current. Pickup indication E/F Fault I>> (FNo 762) should occur
at approximately 1.1 times the pickup value set at address 3303.
2. When the trip delay determined by the setting at address 3304 has expired, the message E/F
Trip <-> (FNo 782) should appear in the target log. This function is factory also preassigned
to Trip Relays 3, 4, and 5.
Prerequisite Settings:
Addr. LCD Text Description Setting
7810 AUTO RECL. Indicate whether or not the automatic EXIST
reclose function exists
3401 AR FUNCT Turn the auto-reclose function on or off ON
The settings listed below are required to properly check control of the overreach zone
2101 PUTT MODE Turn the permissive underreach transfer OFF
trip mode on or off
2201 POTT MODE Turn the permissive overreach transfer OFF
trip mode on or off
7904 AR w/o TELE Indicate whether or the auto-reclose YES
function works with or without the pilot
protection schemes (POTT and PUTT)
The logical function >CB ready (FNo 074) must be assigned to a binary input with a simulated
input signal applied at the appropriate time in the test cycle.
Note that each new test can begin only after the reclaim time for the previous test has expired;
otherwise an automatic reclose cannot result. LED 6 with AR not ready (FNo 806) assigned (a
factory preset) must illuminate.
If the circuit breaker is not ready, a reclose attempt must not result; clearance of short circuits
beyond Z1 is delayed by time element T2 or in a later element. However, a normal AR cycle must
occur when the circuit-breaker-ready signal first disappears after the inception of the fault.
Installation
Table of Contents
List of Figures
4. Installation
To install the 7SA511 relay, you must be familiar with all applicable safety regulations from ANSI,
IEC, NEC, and other pertinent standards. You should also have the following illustrations:
The 7SA511 relay is completely tested and preprogrammed at the factory prior to shipment. No
special calibration, or maintenance is required.
Note: There is also a plastic bag attached to the side of the module housing. This bag contains
the backup battery for the relay (see section 4.3).
Keep the original packing material. Should you need to transport the relay again, use the original
packaging to avoid damaging the relay.
Power 7
Blocked 8
7SA511
Numerical Line Distance Protection 1 9
2 10
3 11
4 12
5 13
On
6 14
Pass Direct
Off word Add r 7 8 9
Target Target
Reset Reset
Event 4 5 6
1 2 3
0 +-
F
Back
Space ∞ Enter Data Port
Yes No
If the relay is de-energized and stored for an extended time period, proper voltage should be
applied to the power input for one or two days prior to placing the relay into service again.
CAUTION
Electrostatic Discharge
Possible equipment damage.
The relay module contains CMOS circuits. The
module must never be withdrawn from or
inserted into the housing with power connected.
Electrostatic discharges into or around the
uninstalled relay or any of its components must
be avoided.
Front Cover
ZEA
Board
Releasing Lever
The 7SA511 additional I/O module contains the ZEA board. This board has additional binary
inputs, output relays, and LEDs,.
The location of each board is shown in Figure 4-3. Please refer to this illustration when you are
required to locate components for any of the installation or maintenance procedures.
Increasing the binary input threshold voltage may be accomplished by removing solder bridges on
printed circuit boards inside the module. The location of the solder bridges on the printed circuit
boards is shown in Figure 4-4. Use the following procedure to remove a solder bridge.
· Remove the basic module and the additional I/O module from the housing as described in
section 4.3.2.
· Locate the desired solder bridge(s) as shown in Figure 4-4. The GEA board containing
binary inputs 1 through 4 is in the basic module. The ZEA board containing binary inputs
5 through 10 is in the additional I/O module.
· Carefully cut and bend the solder bridge(s) aside..
· Reinstall the module(s) in the housing as described in section 4.3.2
2 X22
3 X23
4 X24
Binary Solder
Input Bridge
5 X7
6 X8
7 X9
8 X10
9 X11
10 X12
0.6 in 0.6 in
+
1.6 in
Minifuse for
the power supply
Battery location
when installed-
see View A
View A
Jumper X51
1.16 6.77 D
8.7 ± 0.1 D:
0.2 Diameter Screw terminal - 1.75
Wire comp. term. - 1.18
0.29
0.21 Reset and
0.52 7.09 ± 0.02 paging buttons Mounting plate
View A
Washer Cable
Terminal
Screw
Braided
cable
Ground screw M5
See expanded view A The relay must be properly grounded
according to IEC 255-22. A braided
cable must be used to carry high
Rear View frequency currents. Do not attempt
to use stranded wire.
- Normal sensitivity or
- High sensitivity for
ground fault detection
in ungrounded systems
VL1
Line-Neutral VL2
Factory Presets:
Voltage Inputs 1 - Reclose
VL3
2 - General fault detection
VN 3 - Trip command L1
4 - Trip command L2
VL1 5 - Trip command L3
Line-Line
Voltage Inputs VL2
VL3
Neutral
VE Note: All relays
Voltage Inputs
shown in de-
energized position
Factory Presets:
Factory Presets: 1 - Dist. Send
1 - >Reset LED 2 - AR inoperative
2 - >VT mcb Trip 3 - CB Alarm Suppressed
3 - >CB Aux.cont 4 - Measured value supervision
4 - >Manual Close 5 - Relay Failure
5 - >Dist. Recept 6 - Device Trip
6 - >Dist.RecFail 7 - Fault detection L1
7 - >CB ready 8 - Fault detection L2
8 - >AR block 9 - Fault detection L3
9 - >AR on 10 - Fault detection E
10- >AR off 11 - Reverse direction
Wire Port
(3-wire, reduced RS-232-C Subset)
7SA511*-*CA5*-*B**
4A1 4A3
Communication
F-SMA Board F-SMA
RX 4A2 SV 4A4 TX
7SA511*-*CA5*-*C**
8
7
6
5
D C B A
4
3
2
1
1 3 1 3
#8 Ring lugs #10 Ring lugs
8
7
6
5
D C B A
4
3
2
1
1 3
D C B A
Binary Binary Binary Binary
Input 5 Input 6 Input 1 Input 2
8
Signal Relay 1
Signal Relay 2
Signal Relay 3
Signal Relay 4
Binary Binary Binary Binary
Input 7 Input 8 Input 3 Input 4 7
Binary Binary
Input 9 Input 10
Signal Relay 5
6
Trip Relay 5 Trip Relay 1 Trip Relay 2
5
Communications
Trip Relay 3 Trip Relay 4 DC power input
port 4
Line-Neutral
Signal Relay 10
Signal Relay 11
Signal
Signal Relay 7
Signal Relay 9
Signal Relay 8
Relay 6
voltage (phases
1, 2, and 3)
Phase 1 current
3
Line-Line Line-Neutral
voltage voltage (neutral) Phase 2 current
2
Displacement
Neutral current voltage Not Used Phase 3 current
1
4.8.2 Current Transformer (CT) and Voltage Transformer (VT) Connection Diagrams
The CT and VT connection diagrams included in this section are listed below.
Bus Bus
7SA511 7SA511
L1 L2 L3 IL1 3A1
L1 L2 L3 IL1 3A1
3A2 3A2
IL2 2A1
IL2 2A1
2A2 2A2
IL3 1A1
IL3 1A1
1A2 1A2
IE 1D1
1D2
IE 1D1
1D2
Line Line
3 phase CTs with residual connection 3 phase CTs with summation transformer
for ground faults for ground faults
Bus Bus
7SA511 7SA511
L1 L2 L3 IL1 3A1
L1 L2 L3 IL1 3A1
3A2 3A2
IL2 2A1
IL2 2A1
2A2 2A2
IL3 1A1
IL3 1A1
1A2 1A2
IE 1D1
Line
IE 1D1 1D2
IE from
parallel line 1D2
Line
3 phase CTs with parallel line ground current 2 phase CTs with summation transformer
for ground faults in ungrounded systems
Bus
L1 L2 L3 7SA511
CB CB CB
VL1 3B1
VL2 3B2
VL3 3B3
2B3
n e VE 1C1
1C2
Line
Power
Forward 3 V.T. connection with broken-delta for optimum
Flow directional determination
L1
L2
Bus
L3
N
L1 L2 L3
7SA511
CB CB CB
1C1
VE
1C2
VL1 3B1
VL2
3B2
VL3 3B3
Line
Power
Forward 2 V.T. connection with broken-delta
Flow
voltage from bus
· Figure 4-15. Pilot Wire Connections for Overreaching Zone Comparison with
7PA5210.
· Figure 4-16. Pilot Wire Connections for Overreaching Zone Comparison with
7SW90.
4-22
+V1 +V1
-V1 -V1
+V2 +V2
7SA51 7PA5210-XX 7PA5210-XX 7SA51
Transmit K1 K1 Transmit
a c c a
R4 R1 R1 R4
7 3 3 7
Transmission
2 Annunciation 2
7SA511 Line Protection Relay
1 1
5 6 6 5
8 4 4 8
18 Pilot Wire 18
Trip K2 K2 Trip
b d Connection d b
19 R2 R2
19
Receive 17 R5 R5 Receive
17
BI 12 13 13 12 BI
11 11
16 16 16 16
14 Reception 14
Annunciation
-V1 -V1
Power Line
Figure 4-15. Pilot Wire Connections for Overreaching Zone Comparison with 7PA5210.
Rx K2
D
-V1 Rx
6.4k 6.4k
4.7k 4.7k
4.7k 4.7k
Installation
Annunciation 10
1
5 6
Trip 4
8
18 K2 Pilot Wire A
Connection 8
b d
19 R2
Receive R5
17 C
BI 12 13 5 3
11 6 4
16 16 12
14 Reception 11 +V2
Annunciation
10s TD
Figure 4-16. Pilot Wire Connections for Overreaching Zone Comparison with 7SW90.
+V1 Relay K2 C 48, 55, 62.5 VDC
K2 Rx C D Relay K2 D 60, 90, 110 - 125 VDC
-V1 Rx
4.7k 6.4k
4-23
Chapter 4
4.7k
7SA511 Line Protection Relay Installation
Table of Contents
List of Figures
This chapter also identifies the factory presettings for the power system, protection functions, and
relay configuration settings. Setting options and range are included.
Before you begin any procedure in this chapter, either fill out the setting worksheets provided in
Reference F of this manual or get a copy of the worksheets as completed by a relay engineer. To
avoid operating problems due to incorrect parameters, the relay should be configured as soon as
possible after the installation procedures in Chapter 4 are completed.
CAUTION
Possible configuration errors.
May result in incorrect protection
settings.
· Keypad
· Display panel
· On/Off switch
· Relay nameplate
· LEDs
· Reserved area for LED labels
· Serial data port
Operator
panel
Power 7
Areas reserved
for labeling
Blocked 8
the LEDs
7SA511
Numerical Line Distance Protection 1 9
2 10
3 11
4 12
LCD
5 13
On
On/Off switch 6 14
Pass Direct
Off word Addr 7 8 9
Programmable
Target Target LEDs
Reset Reset
Event 4 5 6
(red)
1 2 3
0 +-
F
Back
Space
∞ Enter Data Port
Yes
RS-232C serial
No
interface
Relay
nameplate,
including
model
number
Keypad
The keys on the operator panel keypad have four basic functions: data entry, navigation, control,
and confirmation. The numeric keys are used specifically for data entry or address selection. The
navigation, control, and confirmation keys are used to accept, reject, or modify configuration
option (see Figure 5-1).
Display Panel
This 32-character liquid crystal display (LCD) is made up of two lines of text, 16 characters each.
There are two modes of operation for the LCD.
· The display mode is the normal operating mode. You can read information, but you
cannot change it. The information that is displayed during normal (i.e., no-fault)
system conditions is user-selectable through the configuration process. Stored event
data can be recalled and analyzed in this mode.
· The programming mode is activated by the relay password (see section 5.3.2). Relay
configuration data is displayed in this mode. The relay stays in programming mode
until you change and save at least one setting. The normal protective functions of the
relay continue to be operational while in programming mode. New settings do not take
affect until you exit programming mode.
Note: The LCD is not capable of displaying subscript characters. As a result, lowercase
characters are used for the subscripts in the display (e.g., IPH becomes Iph and IE becomes
Ie). In this manual, specific references to the LCD text show the symbols as they appear in
the display. Otherwise, symbols with correct case and subscripts are used.
On/Off switch
This switch controls the operational state of the relay. When the switch is in the “Off” position,
the microprocessor is reset and processing stops. Secondary (DC) power output from the power
supply module is switched off, so the relay is effectively disabled or blocked in this state. This
switch should stay in the “On” position after the relay has been properly installed, programmed,
and commissioned. The relay is switched off for certain maintenance and testing procedures.
Refer to Chapter 8 for more information on the use of this switch during maintenance.
Nameplate
The nameplate identifies several things about your relay such as rated current and DC supply
voltage. The relay model number is printed at the top of the nameplate, and how to interpret the
model number is described in Chapter 1 section 1.3, “Relay Model Number.”
LEDs
The 7SA511 relay has 16 LEDs, 14 of which can be programmed (see Figure 5-1). The LEDs
that cannot be changed are as follows:
· Power - Lights up GREEN to indicate the relay is working properly. Normally, this
indicator always will be on. It will be off if the On/Off switch is in the “Off” position
or if power to the relay is interrupted. It will also be off if any of the internal failure
monitoring functions detect a device failure.
· Blocked - Lights up RED to indicate that the relay has detected an internal problem
and has blocked itself from operation. This LED also will light briefly during initial
power-up and after the input/output function assignments under address 6000 or the
scope of function parameters under address 7800 are changed and saved.
The remaining LEDs (1 through 14) will light up RED to indicate that the annunciation assigned
to this LED indicator during the configuration process has occurred. These indicators will remain
on until reset, and the relay will retain this data even if power is lost (provided the backup battery
is functional). Whether or not the indications are retained in the nonvolatile memory is a
configuration option. If the indications are not retained, they will be reset when the fault condition
is removed. If they are retained, they can be reset locally by the Target Reset key on the
operator panel, through a serial port, through a binary input, or automatically when a new fault is
detected.
· Select an address
· Place the relay in programming mode
· Select a text-based setting option
· Program a numeric setting
The functions of the keys on the operator panel are described below:
Key Function
Figure 5-2. Description of the Keys on the 7SA511 Relay Operator Panel.
The procedures and tables given throughout this chapter identify the settings that require a
numeric value within a specified range, and the text-based settings that are chosen from a
predefined list of options.
If a protective cover is on the relay, remove the cover to access the operator panel. Be sure that
the On/Off switch is in “On” position and the Power LED is lit. You should also be able to read
the text in the operator panel LCD (see example LCD below).
1000z
PARAMETERS
Note: The direct address method is used in the procedures in this manual.
With the correct address block number displayed, press either of the navigation keys described
below until the LCD displays the address number and setting you want.
· Press the key to go to the NEXT address number. *
· Press the key to go to the PREVIOUS address number.
* This key is accessible with the protective cover installed over the relay.
While the relay is in programming mode, the solid bar following the address number in the LCD
will flash on and off. The relay remains in programming mode until you save the settings as
discussed in section 5.3.4.
1. Press the Direct Addr key, type the address number for the setting to be pro-
grammed, and press Enter. The requested address, description, and presetting appear
on the display.
2. Press the Password key and enter password ‘000000’. Each character (‘0’) you type
appears as the @ symbol on the display.
3. Press Enter.
4. If your entry is correct, the message “CW ACCEPTED” appears on the display. Press
Enter again. You return to the address where you started in step 1, and the relay is in
programming mode. Go to section 5.3.3, “Changing a Setting.”
5. If your entry is not valid, the message “CODEWORD WRONG “ appears on the dis-
play. Begin again with step 2 of this procedure.
1. When the setting displayed is not the one you want, press the No key. The next setting
option appears on the LCD line 2. Continue to press the No key until the setting option
you want to choose is displayed on the LCD.
2. Press Enter when the setting option you want is displayed on the LCD. Continue with
section 5.3.4, “Saving New Settings.”
1. With the existing setting displayed, type in the new value, which must be within the
established range.
2. Press Enter. If you entered a value that is outside of the allowable range, the
“VALUE TOO SMALL” or “VALUE TOO BIG” message will appear on the display.
Retype the correct value if you receive one of these messages. Otherwise, the value
you entered is accepted.
3. Continue with section 5.3.4, “Saving New Settings.”
Table 5-1 lists the relay presettings, the optional settings and the setting ranges available for the
rear port. Compare these presettings to the information on the completed worksheets and
determine which settings you need to change to match your operating environment. After all
settings have been verified or changed appropriately, follow the procedure described in section
5.3.4 to save the new settings.
· 19200 BAUD
Reference G of this manual, “Input/Output Functions,” identifies the relay annunciations that can
be transmitted to and accessed from a substation control system.
Table 5-2 lists the preset waveform capture settings and setting options. Compare these preset-
tings to the information on the completed worksheets and determine which settings, if any, you
need to change to match your operating environment.
The following procedure enables the waveform capture function via the front serial port for the
7SA511 relay. It is a good example of how to use the operator panel to change settings, verify
predefined settings, enter new data, and save the new settings.
1. To verify the presettings for the waveform capture function, press the Direct Addr key and
type address number 7806.
2. Press Enter. With the factory presettings, the display should appear as shown below:
7806zFAULT LOCAT
EXIST
3. Press the Direct Addr key, type address number 2801, and press Enter. With the factory
presettings, the display should appear as shown below:
2801zFAULT REC.
ON
4. Press the key to go to address number 2802. With the factory presettings, the display
should appear as shown below:
2802zINITIATION
BY FAULT DETECT.
5.
If you want waveform Then . . .
capture initiated by . . .
fault detection (pickup) Press the key to go to address number 2803.
trip command 1. Change to programming mode (refer to the instructions in
section 5.3.2 above).
2. With “2802 z INITIATION : BY FAULT DETEC.”
displayed on the LCD, press the No key.
“BY TRIP <T-REC” will appear on line 2 of the display.
3. Press Enter to have waveform capture initiated by trip
command.
4. Press the key to go to address number 2803.
6. The factory presetting “2803 z FAULT REC. : TO PC/PD” appears on the display. Since this
example procedure is to set the waveform capture function for the front port, the presetting
is the correct setting. Press the key.
7.
If address 2802 setting Then . . .
is . . .
BY FAULT DETEC. Address 2804 is not available, so address 2801 appears on the
display. Go to the next step of this procedure.
BY TRIP <T-REC 1. Press the key. “2804 z T- REC : 0.30 s” appears on the
display. This setting indicates the time allowed, after a trip
command, before waveform capture recording is started.
2. To accept the T-REC presetting of 30 seconds, press the
key. Go to Step 8.
3. To change the time delay T-REC, place the relay in
programming mode if you have not done so in a previous
step. Type in the new value using the decimal point and
numeric keys, and press Enter. Verify the value you entered
on the display.
8. To change the data rate for communication via the front port, press the Direct Addr key
and type in address number 7002. The display appears as shown below:
7002zOPER. BAUDR.
1200 BAUD
9.
If . . . Then . . .
1200 is the correct data transmission speed for continue with the next step of this procedure.
the front serial port
1200 bps is NOT correct press the No key. The setting options are:
· 2400 BAUD
· 4800 BAUD
· 9600 BAUD
· 19200 BAUD
10. To save the settings, press function key F then press Enter. Press the Yes key in response to
the “SAVE NEW SETTINGS?” message. The “NEW SETTINGS SAVED” confirmation
message will appear on the display. See section 5.3.4 for more detailed instructions on
saving relay settings.
The parameters under this block identify the functions of the relay. Additional On/Off parameters
under addresses within the 1000 to 4000 range are provided so you can manually switch
functions on and off as needed. Section 5.17 discusses the On/Off parameters in more detail.
Table 5-3 identifies all of the relay functions controlled in address block 7800 along with the
presettings and setting options. This table also refers you to the section in this chapter that
describes the function in more detail, including the additional parameters required for the function
to work. Only those functions available in your relay will appear in its display. Refer to your relay
model number and to section 1.3, “Relay Model Number,” to verify which functions you should
be able to control in address block 7800.
Compare these presettings to the information on the completed worksheets and determine which
settings, if any, you need to change to match your operating environment. After all settings have
been verified or changed appropriately, follow the procedure described in section 5.3.4 to save the
new settings.
COMPARISON
· INVERSE TIME
Note: Addresses 7009 and 7010 are required to enable the relay for substation control and
are therefore discussed in section 5.4.
· 9600 BAUD
· 19200 BAUD
7003 DATE FORMAT Date format for the real- DD.MM.YYYY MM/DD/YYYY
time clock
7004 FAULT INDIC When to display stored LED BY FAULT DETEC. BY TRIP COMMAND
indications and fault annun-
ciations
7005 OPER. 1st L Message to appear in first not allocated · IL1 = A
display line during normal · IL2 = A
operation · IL3 = A
· UL12 = kV
· UL23 = kV
· UL31 = kV
· Pa = MW
· Pr = MVA
· f[%] = %
· IL1[%] = %
· IL2[%] = %
· IL3[%] = %
· UL12[%] = %
· UL23[%] = %
· UL31[%] = %
· Pa[%] = %
· Pr[%] = %
7006 OPER. 2nd L Message to appear in second UL12 = (options are same as for
display line during normal 7005)
operation
7007 FAULT 1st L Message to appear in first Fault type · Trip Type
display line after a fault · Prot. Pick-up
event · Prot. Trip
· Time-to-Drop
· Time-to-Trip
· Fault locat.
7008 FAULT 2nd L Message to appear in second Time-to-Trip (options are same as for
display line after a fault 7007)
event
For the real-time clock and calendar to maintain the correct date and time in the event of a power
supply failure, the backup battery must be installed in the relay. See Chapter 4 section 4.3,
“Installing the Relay’s Backup Battery,” for installation instructions.
When the relay is initially installed and energized, the date and time must be set. With address
block 8100 (shown below) displayed, press the key to display the date and time under address
8101.* Continue to press the key to go to address 8102 to change the date, address 8103 to
change the time, etc. Enter the relay password (see section 5.3.2) to change the date or time. The
“T.CLOCK ADJUSTED” message will display after a date or time change.
The message “ENTRY ERROR” will appear if you incorrectly enter the date or time. Press Enter
to clear this message and return to programming mode.
8100zSETTING
REAL TIME CLOCK
Date
A date can be entered at address 8102. When entering the date, the period (.) key is used as the
separator between days, months, and years. Also, the entry must be made using two digits for the
month, two digits for the day, and four digits for the year (i.e., MM.DD.YYYY or
DD.MM.YYYY).
Set Time
The clock can be set by entering a time at address 8103. Enter the time in 24 hour format using
two digits each for hours, minutes, and seconds (i.e., HH.MM.SS). The period (.) key is used as
the separator between hours, minutes, and seconds.
Difference Time
The clock can be adjusted by specifying a difference time at address 8104. In this case, the clock
is adjusted forward or backward by the amount of time entered. To adjust the clock forward,
enter the difference time, then press the Enter key. To adjust the clock backward, enter the
*
Direct access to address 8101 will also display the date and time setting.
difference time, press the +/- key, then press the Enter key. The format for entering the
difference time is the same as for a new time as described above.
To synchronize with a set time entry, use address 8103 and enter a time in advance of the
reference time, then press the Enter key precisely when the reference clock reaches the entered
time. This method can never be extremely precise since it is dependent on operator reaction time.
To synchronize with a difference time entry, use address 8104 and enter a time equal to the time
difference between the relay clock and the reference clock. The difference time method has the
advantage of being independent of the operator reaction time. It does, however, have the
disadvantage of having to know the exact time difference between the relay clock and the
reference clock.
The internal clock accuracy allows a maximum deviation of 8.64 seconds per 24 hour period. It is,
therefore, recommended that elapse time between synchronizing signals not exceed 3 days (72
hours).
System settings and relay protection settings (addresses 1000 to 3999) can be uniquely defined for
each parameter set. You can also copy data from one parameter set to another, including the
original set.
Only one parameter set is active at a time. You can change the active parameter set during relay
operation (provided no protection functions are picked up) using the operator panel or through
the binary inputs. If the relay is connected to a PC via the front port, you can use DIGSI®
software to change the active parameter set.
Prerequisite Setting:
Addr. LCD Text Description Setting
7885 PARAM.C/O Parameter changeover feature EXIST
There are three operations available when parameter changeover is programmed as existing:
Note: The message “COPYING TERMINATED” will appear in the display when the F
key sequences are used. Ignore this message and press Enter to clear it.
When one of these key sequences is used while the relay is in display mode, the parameters for the
selected set can be displayed. The parameter address number in the display will be preceded by the
parameter set ID letter (A - D). For example, the parameter at address 1105 in Set B appears as:
B1105zIn PRIMARY
1000 A
The relay always operates with the active set of parameters (see section 5.8.2) regardless of which
set is being displayed or configured.
All four of the available parameters sets are initialized at the factory the same set of default
parameters identified as the “ORIG.SET.” This set of parameters is permanently stored in the
read-only memory of the relay. If, after making setting changes, it is necessary to restore the relay
to the factory default settings, this can be done by copying the ORIG.SET to any or all of the four
parameter sets.
A selectable set may also be initialized by copying another selectable set. Table 5-5 contains a list
of the available copy options. To perform a copy, access the address corresponding to the desired
copy function. For example:
8512zCopy ?
ORIG.SET->SET C
Press the YES key. The second line of the display will indicate “IN PROGRESS” followed by
“SUCCESSFUL” after a successful copy operation. Press Enter to clear the message. The relay
remains in programming mode. (To exit programming mode see the following Note.)
Note: To properly save the copied parameter set, use the navigation keys to leave the
8500 address block. When you do this you will get the “SAVE NEW SETTINGS”
message.
1. As shown below, the presently active parameter set can be determined by displaying address
8501.
8501zACTIV PARAM
SET A
2. To change the active parameter set, select address 8503. “ACTIVATION z SET A” appears
on the display. Place the relay in programming mode as instructed in section 5.3.2.
8503zACTIVATION
SET A
3. Press the No key until the setting you want is displayed, then press Enter to select the active
parameter set. Table 5-6 identifies the parameter set presetting and options.
4. Save the new active parameter set per the instructions in section 5.3.4. If “SET BY BIN.
INPUT” is selected, see the “Settings Calculation” chapter for further instructions required to
perform parameter changeover via binary inputs.
Important: After a new parameter set has been selected as the active set, the parameter set ID
prefix displayed for addresses 1000 to 3999 will not change until the relay has been
through a reset and restart cycle (see “On/Off Switch” in the “Product Description”
chapter). Therefore, you cannot count on the prefix to indicate the correct active
parameter set at all times. Only the value at address 8501 is always an accurate
indication of the active set.
For detailed information on calculating system settings, refer to Reference A, “Method of Opera-
tion,” and to Reference E, “Setting Calculations.” All equations used to calculate the setting
values are included in one or both of these sections.
Compare these presettings to the information on the completed worksheets and determine which
settings you need to change to match your operating environment. When you have changed all of
the necessary settings, follow the procedure described in section 5.3.4 to save the new settings.
The sensitivity of the measured values monitoring can be changed in address block 2900. Table 5-
8 identifies the factory presettings and available options. Typically, the factory presettings are
sufficient. Compare these presettings to the information on the completed worksheets and
determine which settings you need to change to match your operating environment. When you
have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save
the new settings.
This section identifies the addresses used to configure the relay distance protection functions.
Refer to Reference E, “Setting Calculations,” for information on determining the protection
settings needed for your operating environment. Table 5-9 identifies, by address block, the
distance protection settings in the 7SA511 relay.
Distance protection settings can vary between the parameter sets when the parameter changeover
feature is available (see section 5.8).
The distance protection settings discussed in this section are categorized as follows:
· General settings
· Settings for independent distance zones Z1, Z2, and Z3
· Settings for controlled (overreach) zones Z1B and Z1L
· Fault detection settings as follows:
- Overcurrent fault detection
- Voltage controlled fault detection
- Polygonal impedance fault detection
· Settings for determination of the fault loop in grounded systems
· Settings for determination of the fault loop in ungrounded systems
The direction of the directional zone and the delay times T4 and T5 are set in address block 1200.
You also establish the valid distance measuring range when the circuit breaker is manually closed.
Table 5-10 lists the presettings and setting options. Compare these presettings to the information
on the completed worksheets and determine which settings you need to change to match your
operating environment. When you have changed all of the necessary settings, follow the
procedure described in section 5.3.4 to save the new settings.
Table 5-11 lists the protection presettings and setting options for zones Z1, Z2, and Z3. Compare
these presettings to the information on the completed worksheets and determine which settings
you need to change to match your operating environment. When you have changed all of the
necessary settings, follow the procedure described in section 5.3.4 to save the new settings.
Table 5-11. Distance Protection Settings for Independent Zones Z1, Z2, and Z3
Addr. LCD Text Zone & Description Preset Options/Range
1301 R1 Z1. Resistance for phase-to-phase 1.25 W 0.05 - 65.00 W
faults
1302 X1 Z1. Reactance value (reach) 2.50 W 0.05 - 130.00 W
1303 R1E Z1. Resistance for phase-to- 2.50 W 0.05 - 130.00 W
ground faults
1304 DIREC. Z1 Z1 measurement direction FORWARDS (line) · REVERSE (bus)
· NON-
DIRECTIONAL
1305* T1 1phase Z1. Trip delay for single-phase 0.00 s · 0.00 - 32.00 s
faults · ¥
1306* T1 >1phase Z1. Trip delay for multi-phase 0.00 s · 0.00 - 32.00 s
faults · ¥
1311 R2 Z2. Resistance for phase-to-phase 2.50 W 0.05 - 65.00 W
faults.
1312 X2 Z2. Reactance value (reach). 5.00 W 0.05 - 130.00 W
1313 R2E Z2. Resistance for phase-to- 5.00 W 0.05 - 130.00 W
ground faults.
1314 DIREC. Z2 Z2. Measurement direction. FORWARDS (line · REVERSE (bus)
direction) · NON-
DIRECTIONAL
1315* T2 1phase Z2. Trip delay for single-phase 0.30 s · 0.00 - 32.00 s
faults. · ¥
1316* T2 >1phase Z2. Trip delay for multi-phase 0.30 s · 0.00 - 32.00 s
faults. · ¥
1321 R3 Z3. Resistance for phase-to-phase 5.00 W 0.05 - 65.00 W
faults.
1322 X3 Z3. Reactance value (reach). 10.00 W 0.05 - 130.00 W
1323 R3E Z3. Resistance for phase-to- 10.00 W 0.05 - 130.00 W
ground faults
1324 DIREC. Z3 Z3. Measurement direction. FORWARDS (line · REVERSE (bus)
direction) · NON-
DIRECTIONAL
1325 T3 Z3. Delay time. 0.60 s · 0.00 - 32.00 s
· ¥
*
Normally, addresses 1305 and 1306 are set to the same value, and addresses 1315 and 1316 are set to the same
value.
Table 5-12 lists the protection presettings and setting options for overreach zones Z1B and Z1L.
Compare these presettings to the information on the completed worksheets and determine which
settings you need to change to match your operating environment. When you have changed all of
the necessary settings, follow the procedure described in section 5.3.4 to save the new settings.
Table 5-12. Distance Protection Settings for Controlled (Overreach) Zones Z1B and Z1L
Addr. LCD Text Zone & Description Preset Options/Range
1401 R1B Z1B. Resistance for phase-to- 1.50 W 0.05 - 65.00 W
phase faults.
1402 X1B Z1B. Reactance value (reach). 3.00 W 0.05 - 130.00 W
1403 R1BE Z1B. Resistance for phase-to- 3.00 W 0.05 - 130.00 W
ground faults.
1404 DIREC. Z1B Z1B. Measurement direction. FORWARDS (line · REVERSE (bus)
direction) · NON-
DIRECTIONAL
1405* T1B 1phase Z1B. Trip delay for single-phase 0.00 s · 0.00 - 32.00 s
faults. · ¥
1406* T1B>1phase Z1B. Trip delay for multi-phase 0.00 s · 0.00 - 32.00 s
faults. · ¥
1411 R1L Z1L. Resistance for phase-to- 2.00 W 0.05 - 65.00 W
phase faults.
1412 X1L Z1L. Reactance value (reach). 4.00 W 0.05 - 130.00 W
1413 R1LE Z1L. Resistance for phase-to- 4.00 W 0.05 - 130.00 W
ground faults.
1414 DIREC. Z1L Z1L. Measurement direction. FORWARDS (line) · REVERSE (bus)
· NON-
DIRECTIONAL
1415 T1L Z1L. Trip delay. 0.00 s · 0.00 - 32.00 s
· ¥
Prerequisite Settings:
Addr. LCD Text Description Setting
7801 DIST. PROT. Distance protection function EXIST
7802 DIST. F. DET. Type of fault detection OVERCURRENT
*
Normally, addresses 1405 and 1406 are set to the same value.
Prerequisite Settings:
Addr. LCD Text Description Setting
7801 DIST. PROT. Distance protection function EXIST
7802 DIST. F. DET. Type of fault detection U/I
Important: Address 1501 must not be set to LE:Uphe/LL:Uphe for ungrounded systems.
Conversely, address 1501 must not be set to LE:Uphph/LL:Uphph for grounded
systems.
Table 5-15 lists the presettings, the optional settings and the setting ranges available for polygonal
impedance fault detection. Compare these presettings to the information on the completed
worksheets and determine which settings you need to change to match your operating
environment. When you have changed all the necessary settings, follow the procedure described in
section 5.3.4 to save the new settings.
Prerequisite Settings:
Addr. LCD Text Description Setting
7801 DIST. PROT. Distance protection function EXIST
7802 DIST. F. DET. Type of fault detection IMPEDANCE ZONE
Table 5-16 lists the presettings and setting options for determination of the fault loop for
grounded systems (1700). Compare these presettings to the information on the completed
worksheets and determine which settings you need to change to match your operating
environment. When you have changed all of the necessary settings, follow the procedure
described in section 5.3.4 to save the new settings.
Prerequisite Settings:
Addr. LCD Text Description Setting
1102 SYSTEMSTAR System neutral condition SOLIDLY EARTHED
7801 DIST. PROT. Distance protection function EXIST
Table 5-16. Settings for Determination of the Fault Loop for Grounded Systems
Addr. LCD Text Description Preset Options/Range
1701 Ue> Displacement voltage detection 20 V · 2 - 100 V
for ground fault detection · ¥
1703 2PH-E FLTS Fault loop measurement controls PHASE-PHASE · LEADING PH-E
for double ground faults LOOP · LAGGING PH-E
1704 3PH FAULTS Fault loop measurement controls E/F CONTROL · PH-PH ONLY
1705 1PH FAULTS Select the fault loop measurement PHASE-EARTH PHASE-PHASE
controls to be used for single-
phase faults
5.10.8 Determination of the Fault Loop for Ungrounded Systems (1800) (Optional)
In phase-selective fault detection systems, the currents and voltages of the fault loop are decisive
when calculating the distance to fault. The settings under address block 1800 are applicable for
networks with an isolated or compensated neutral. Skip this section if the system neutral is
grounded.
Table 5-17 lists the presettings and setting options for determination of the fault loop for
ungrounded systems (1800). Compare these presettings to the information on the completed
worksheets and determine which settings you need to change to match your operating
environment. When you have changed all of the necessary settings, follow the procedure
described in section 5.3.4 to save the new settings.
Prerequisite Settings:
Addr. LCD Text Description Setting
1102 SYSTEMSTAR System neutral condition · COMPENSATED
· ISOLATED
7801 DIST. PROT. Distance protection function EXIST
Table 5-17. Settings for Determination of the Fault Loop for Ungrounded Systems
Addr. LCD Text Description Preset Options/Range
1801 TIe 1PHASE Pickup delay for ground 0.04 s · 0.04 - 0.50 s
current detection with single · ¥
phase pickup
1802 Ue> Displacement voltage for 40 V 10 V - 100 V
ground fault detection
1803 PHASE PREF Phase preference for double L3(L1) ACYCLIC · L1(L3) ACYCLIC
ground faults—the preference · L2(L1) ACYCLIC
sequence must be the same · L1(L2) ACYCLIC
throughout the network · L3(L2) ACYCLIC
· L2(L3) ACYCLIC
· L3(L1) CYCLIC
· L1(L3) CYCLIC
Table 5-18 lists the presettings and setting options for power swing protection. Compare these
presettings to the information on the completed worksheets and determine which settings, if any,
you need to change to match your operating environment. When you have changed all the neces-
sary settings, follow the procedure described in section 5.3.4 to save the new settings.
Prerequisite Settings:
Addr. LCD Text Description Setting
7801 DIST. PROT. Distance protection function EXIST
7802 DIST. F. DET. Type of fault detection IMPEDANCE ZONE
7813 POWER Power swing protection func- EXIST
SWING tion
Prerequisite Setting:
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection UNDERREACH
Table 5-20 lists the relay presettings and setting options available for the permissive overreach
transfer schemes. Compare these presettings to the information on the completed worksheets and
determine which settings you need to change to match your operating environment. When you
have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save
the new settings.
Prerequisite Setting:
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection OVERREACH
Table 5-20. Pilot Protection Permissive Overreach Transfer Settings, Address Block 2200.
Addr. LCD Text Description Preset Options/Range
2201 POTT MODE Turn permissive overreach ON OFF
transfer trip on or off
2202 POTT MODE Transfer trip mode Z1B RELEASE · FD DIREC
RELEASE
· Z1B UNBLOCK
· FD UNBLOCK
· Z1B BLOCKING
· PILOT WIRE
COMP.
· REVERS
INTERLOCK
2203 T-TRANSBLO Transient blocking time after 0.05 s 0.01 to 32.00 s
an external fault—this time
must be longer than the
transmission time
2204 T-WAIT TB Waiting time before transient ¥s · 0.01 to 32.00 s
blocking with a missing · ¥
reception signal
2206 T-SEND-PRL Time duration for the 0.05 s 0.01 to 32.00 s
transmission signal
2210 POTT DirFD When the directional FORWARDS · REVERSE
comparison mode (FD DIREC · NON-
RELEASE) is selected at DIRECTIONAL
address 2202, this setting
indicates the effective direction
2212 T-SEND-DEL Transmission signal delay time 0.00 s 0.00 to 32.00 s
2220 ECHO Turn the echo keying function ON OFF
on or off
2221 T-ECHO-DEL Echo time delay 0.20 s · 0.01 - 32.00 s
· ¥
2222 T-ECHO-IMP Duration of echo impulse 0.05 s 0.02 - 32.00 s
2223 T-ECHO-BLO Echo blocking time 0.40 0.01 - 32.00 s
During emergency operation, the pilot protection function is disabled. It is possible, however, to
carry out automatic reclose in the emergency overcurrent protection mode. Refer to section 5.16
for details.
Table 5-21 lists the relay presettings and setting options available for emergency overcurrent
protection. Compare these presettings to the information on the completed worksheets and
determine which settings you need to change to match your operating environment. When you
have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save
the new settings.
Prerequisite Setting:
Addr. LCD Text Description Setting
7803 EMERG. O/C Emergency overcurrent EXIST
protection function
Table 5-22 lists the relay presettings and setting options available for configuring ground fault
protection for ungrounded systems. Compare these presettings to the information on the
completed worksheets and determine which settings you need to change to match your operating
environment. When you have changed all of the necessary settings, follow the procedure
described in section 5.3.4 to save the new settings.
Prerequisite Settings:
Addr. LCD Text Description Preset
7807 ISOL. E/F Ground fault detection for EXIST
ungrounded systems
1102 SYSTEMSTAR System neutral condition · COMPENSATED
· ISOLATED
Table 5-22. Settings for Ground Fault Protection for Ungrounded Systems
Addr. LCD Text Description Preset Options/Range
3001 EARTHFAULT Turn ground fault detection in ON OFF
ungrounded systems on or off
3002 Ue> Threshold value for ground fault 40 V 10 - 100 V
detection
3003 Uph< Phase-to-ground voltage below 40 V 10 - 100 V
which a ground fault is indicated
3004 Uph> Phase-to-ground voltage that 75 V 10 - 100 V
healthy phases will exceed during
a ground fault
3005 Ie> Threshold current value for 0.050 A 0.003 - 1.000 A
directional determination of the
ground fault
3006* CT ERR. I1 Secondary current for maximum 0.050 A 0.003 - 1.600 A
angle error of the CT
3007* CT ERR. F1 Error angle of CT at I1current set 0.0° 0.0 - 5.0°
in address 3006
3008* CT ERR. I2 Secondary current above which 1.000 A 0.003 - 1.600 A
the angle error is constant
3009* CT ERR. F2 Error angle of CT at I2 current 0.0° 0.0 - 5.0°
set in address 3008
3010 T-E/F Amount of time the displacement 1.0 s 1.00 - 320.00 s
voltage must exist before ground
fault pickup
*
This parameter is not necessary for systems with an isolated neutral; however it is typically used for systems with
a compensated grounding.
Each type of high-resistance ground fault protection, listed below, is discussed separately in this
section.
The various high-resistance ground fault protection methods are described in detail in Reference
A, “Method of Operation.”
High-resistance ground fault protection for grounded systems can also work with the automatic
reclose function, when available. Refer to section 5.16 for information on programming the relay
for automatic reclose operations with high-resistance ground fault protection.
Prerequisite Settings:
Addr. LCD Text Description Setting
7808 EARTH FAULT Type of ground fault protection DIRECTIONAL D.T.
1102 SYSTEMSTAR System neutral condition SOLIDLY EARTHED
Table 5-23. Settings for Directional, Definite Time Overcurrent Protection With Nondirectional
Backup Element
Addr. LCD Text Description Preset Options/Range
3101 E/F D.T. Turn the ground fault definite ON OFF
time protection on or off
3103 Ie> Pickup value for ground 0.20 I/In 0.10 - 1.00 I/In
current detection
3104 Ue> Minimum displacement voltage 5.0 V 1.0 - 10.0 V
required for directional
determination
3106 T-DIRECT. Trip delay for directional 0.90 s · 0.00 - 32.00 s
element · ¥
3107 DIRECTION Direction used for directional FORWARDS · REVERSE
determination · NON-
DIRECTIONAL
3108 T-NON-DIR. Trip delay time for 1.20 s · 0.00 - 32.00 s
nondirectional backup element · ¥
3109 T-BLOCK Time duration during which 1.30 s 0.00 - 320.00 s
ground fault protection is
blocked when distance
protection has picked up
Table 5-24 lists the relay presettings and setting options available. Compare these presettings to
the information on the completed worksheets and determine which settings you need to change to
match your operating environment. When you have changed all of the necessary settings, follow
the procedure described in section 5.3.4 to save the new settings.
Prerequisite Settings:
Addr. LCD Text Description Setting
7808 EARTH FAULT Type of earth (ground) fault DIREC.
protection COMPARISON
1102 SYSTEMSTAR System neutral condition SOLIDLY EARTHED
3100 (See Table 5-23 above.)
block
Table 5-24. Settings for Directional, Definite Time Overcurrent Protection with Directional
Comparison and Nondirectional Backup Element
Addr. LCD Text Description Preset Options/Range
3105 T-DELAY Delay time for transmission and trip 0.00 s · 0.00 - 32.00 s
· ¥
3201 E/F COMPAR Turn the ground fault definite time, ON OFF
directional comparison protection on
or off
3203 T-TRANSBLO Transient blocking time, which must 0.05 s 0.01 - 32.00 s
be longer than the transmission time
3204 T-WAIT TB Waiting time before initiating ¥s · 0.00 - 32.00 s
transient blocking with missing · ¥
reception signal
3210 E/F ECHO Turn the echo keying function on or ON OFF
off
3211 T-ECHO-DEL Echo time delay 0.20 s · 0.01 - 32.00 s
· ¥
3212 T-ECHO-IMP Duration of echo impulse 0.05 s 0.02 - 32.00 s
3213 T-ECHO-BLO Echo blocking time 0.40 s 0.01 - 32.00 s
Prerequisite Settings:
Addr. LCD Text Description Preset
7808 EARTH FAULT Type of earth (ground) fault protection INVERSE TIME
1102 SYSTEMSTAR System neutral condition SOLIDLY
EARTHED
· ¥
3305 T-BLOCK Time during which ground fault 1.30 s 0.00 - 320.00 s
protection is blocked when distance
protection has picked up
The relay can be ordered either with three-pole automatic reclose (single- and multi-shot, model
7SA511*-**A5*- **B/F*) or for all modes of automatic reclose (single-pole, three-pole, single-
and three-pole, single- and multi-shot, model 7SA511*-**A5*-**C/G*). If the relay model
configuration is for three-pole automatic reclose only, then only those parameters are available
which relate to this automatic reclose program.
· The device configuration parameters in address block 7900 include settings for how the
automatic reclose function works with other relay protection functions.
· Address block 3400 consists of the specific settings required for automatic reclose in the
7SA511 relay.
Prerequisite Setting:
Addr. LCD Text Description Setting
7810 INTERNAL AR Internal automatic reclose function EXIST
Note: Address number 7910 indicates how the circuit breaker test via binary input is carried out
and is discussed, therefore, in Chapter 7 “Commissioning the Relay.”
Terminology:
RAR Rapid Automatic Reclose, or first AR cycle
DAR Delayed Automatic Reclose, or further cycles (shots), after the first
*
This parameter is only used with single-pole reclose.
Table 5-28 lists the relay presettings and the setting options available for fault location. Compare
these presettings to the information on the completed worksheets and determine which settings
you need to change to match your operating environment. When you have changed all of the
necessary settings, follow the procedure described in section 5.3.4 to save the new settings.
Prerequisite Setting:
Addr. LCD Text Description Setting
7805 FAULT LOCAT. Fault location function EXIST
* Although the LCD will always display the unit of length as kilometers, the per-unit-length values may
be specified as miles as long as both parameters(3803 and 3804) are specified consistently. Reference
E, “Setting Calculations” provides details on calculating secondary values from primary values.
With the relay operating, for example, you may need to turn a function on or off under specific
conditions such as turning off the pilot protection function during maintenance or repair of the
transmission medium, or turning off the automatic reclose system when a transfer bus is being
used.
Table 5-29 identifies all of the On/Off functions available in the 7SA511 relay and shows which
section of this manual discusses the actual function.
On/off control may be accomplished through the operator panel, the front serial port, and the
binary inputs. Refer to Reference E, “Setting Calculations” for detailed information on how on/off
control works and how binary inputs must be configured to turn functions on and off.
If you change any of the configuration settings, the relay microprocessor will automatically reset
and restart after the new settings are saved.
Note: There are two qualifiers on the functions assigned to for binary inputs (NO and
NC) and LED indicators (n and nm). Refer to sections 5.19.3 and 5.19.5,
respectively, for further instructions on selecting the correct mode of operation.
1. Select the address number of the I/O unit you want to configure and enter the relay password
(see section 5.3.2). The display will appear similar to this example, which shows address
number 6204.
6204zSIGNAL
RELAY 4
2. Press the F key. An “F” will display over the solid bar following the address number in the
display.
3. Press the key to complete the change to the function selection level. The address number in
the display is replaced with a 3 digit index number 001, which is automatically assigned to the
first function. As shown in the example below, the second line of the display contains an
abbreviated description of the assigned function.
001zRELAY 4
>VT mcb Trip
001zRELAY 4
121
b. Press Enter. The description of the function displays in line 2 as shown in the example
below.
001z RELAY 4
FAILURE 24V
(2) Scrolling through the list of available functions using the No and Back Space keys.
a. Repeatedly press the No key to page forward, or the Back Space key to page
backward, until the description of the function you want is displayed (see example
display in Step 1.b above).
b. Press Enter.
c. Save the new setting(s) as instructed in section 5.3.4.
5. Press the key to go to the index number sequence. The next function assignment will
display with index number 002 as shown below.
002z RELAY 4
FAILURE SI
6. Press the or key to page up and down through the index number sequence. If an index
number is accessed for which no function has been assigned, the second line displays “not
allocated” as shown below.
010z RELAY 4
not allocated
5.19.2 Presettings
Table 5-30 below identifies the configuration presettings for each of the I/O units. Compare these
settings to the data on the completed worksheets to see which settings you need to change.
*
This preset configuration is only true when the relay has the internal automatic reclose function and the function
is programmed as existing under address 7810.
Addr. I/O Unit Index No. LCD Text (2nd line) FNo
6301 LED 1 001 >VT mcb Trip nm 014
002 Failure SI nm 151
003 Failure SUp-e nm 152
004 Failure SUp-p nm 153
005 Failure Isymm nm 154
006 Failure Usymm nm 155
007 Failure Umeas nm 156
008 Fuse-Failure nm 157
009 Fail.PhaseSeq nm 159
6302 LED 2 001 Dist.Fault L1 m 352
002 O/C Fault L1 m 623
6303 LED 3 001 Dist.Fault L2 m 353
002 O/C Fault L2 m 624
6304 LED 4 001 Dist.Fault L3 m 354
002 O/C Fault L3 .m 625
6305 LED 5 001 Dist.EarthFlt m 355
002 O/C Fault E m 626
6306* LED 6 001 AR not ready nm 806
6307 LED 7 001 T1 expired m 361
002 T-I>> expired m 628
6308 LED 8 001 T2 expired m 362
6309 LED 9 001 T3 expired m 363
6310 LED 10 001 T4 expired m 364
6311 LED 11 001 T5 expired m 365
002 T-I> expired m 629
6312 LED 12 001 Dev. Trip L1 m 252
6313 LED 13 001 Dev. Trip L2 m 253
6314 LED 14 001 Dev. Trip L3 m 254
6401* Trip Relay 1 001 Reclose 851
6402 Trip Relay 2 001 Dist.Gen.Flt. 351
002 O/C Gen. Fault 621
003 E/F Fault I> 761
6403 Trip Relay 3 001 O/S Trip 531
002 Dis.Trip L1 481
003 Dis.Trip L123 493
004 O/C Trip L1 652
005 O/C Trip L123 655
006 E/F Trip -> 781
007 E/F Trip <-> 782
008 CB Test L1 881
009 CB Test L123 884
*
This preset configuration is only true when the relay has the internal automatic reclose function and the function
is programmed as existing under address 7810.
Addr. I/O Unit Index No. LCD Text (2nd line) FNo
6404 Trip Relay 4 001 O/S Trip 531
002 Dis.Trip L2 483
003 Dis.Trip L123 493
004 O/C Trip L2 653
005 O/C Trip L123 655
006 E/F Trip -> 781
007 E/F Trip <-> 782
008 CB Test L2 882
009 CB Test L123 884
6405 Trip Relay 5 001 O/S Trip 531
002 Dis.Trip L3 487
003 Dis.Trip L123 493
004 O/C Trip L3 654
005 O/C Trip L123 655
006 E/F Trip -> 781
007 E/F Trip <-> 782
008 CB Test L3 883
009 CB Test L123 884
Note: The presets for Binary Inputs 5 and 6, and Signal Relay 1 implement the pilot
protection interface.
For each input function, you can specify whether the function will operate in the Normally Open
(NO) or Normally Closed (NC) mode. All preset input assignments are set to operate in Normally
Open mode, which means a voltage applied to the input terminals activates the function. Normally
Closed mode means a normally present voltage removed from the terminals activates the function.
When paging through the available functions in the selection level using the No or Back Space
keys, the abbreviated description shown in the LCD is followed by an NO or NC indication, which
changes from one to the other when the No or Back Space key is pressed. In this way, the desired
mode can be selected when the paging method is used.
When entering the function number directly, the function number can be extended by a 0 or 1
where
If the extension is omitted, the function display defaults to NO. This can be changed to NC by
pressing the No or Backspace key then pressing Enter to select.
For each LED function, you can specify whether the function will operate in the latched (m) or
unlatched (nm) mode.
When paging through the available functions in the selection level using the No or Back Space
keys, the abbreviated description shown in the LCD is followed by an m (for memorized) or nm
(for not memorized) indication, which changes from one to the other when the No or Back Space
key is pressed. In this way, the desired mode can be selected when the paging method is used.
When entering the function number directly, the function number can be extended by a 0 or 1
where
If the extension is omitted, the function display defaults to nm. This can be changed to m by
pressing the No or Backspace key then pressing Enter to select.
Table of Contents
List of Figures
· Event log for the relay during normal and fault conditions
· Target log for the last three network faults
· Target log for the last three ground faults in ungrounded systems
· Measured values of the protected system (in grounded and ungrounded systems)
· Circuit breaker operation statistics
The system and relay information is also accessible using analysis software if the relay is
connected to a PC through the front port. In addition, you can also display actual waveforms of
the last fault record when DIGSI® analysis software is used on a PC and the relay is programmed
for waveform capture (see section 5.5).
Table 6-1 lists the address blocks and descriptions that are used to display the system and relay
information. The relay password is not required to display relay data.
Table 6-1. Address Blocks Used to Display System and Relay Information.
Addr. Description
5100 Event log. The relay stores the last 50 messages that displayed.
5200 Target history for the last (most recent) fault.
5300 Target history for the second to last fault.
5400 Target history for the third to last fault.
5500 Ground fault target history for relay models with ground fault detection for
ungrounded systems (model number 7SA511*-**A5*-1***).
5600 Circuit breaker operation statistics.
5700 Measured phase and neutral currents, voltages, and apparent power of the
protected system.
5800 Ground fault measured values for relay models with ground fault detection for
ungrounded systems (model number 7SA511*-**A5*-1***).
The tables in this chapter identify, by address block, all of the messages and values available for
display on the LCD. Whether or not some information can be displayed is dependent on the model
and configuration of the individual relay. The last section in this chapter discusses the waveform
capture feature.
go to address blocks 5100, 5200, etc. You may also use the Direct Addr. key to view any log
address.
5000z
ANNUNCIATIONS
Annunciation refers to the process of activating the various relay outputs when an event occurs.
Messages that appear on the operator panel LCD are also called annunciations in this manual.
The following procedure uses the Event key and the navigation keys to access and display
information. Refer to section 5.3.1, “Selecting an Address,” for information on using the Direct
Addr key to access information.
1. Press the Event key. Address block 5000 appears in the display as shown above.
2. Press the key until the address block of annunciations that you want to review is
displayed as shown in the example below:
5100zOPERATIONAL
ANNUNCIATIONS
3. Press the key to display the first entry in the list you are viewing. The example
below shows how the event log message appears when the relay is operating in
emergency overcurrent mode.
11/02/94 09:03
Emerg. Mode :C
4. Press the or key to move up or down in the list you are viewing.
5. When you are finished reading the information, press the or key to go to
another address block. Information is not updated when the address block is active.
For event log messages, the first line of the display always gives the date and time of the event
(see example below). The time is given to the nearest minute, but the events are sorted (placed in
the order of occurrence) with 1 millisecond resolution. The second line of the display gives the
event description as listed in Table 6-2. Each event description may be followed by a C or G tag.
The C tag (Coming) indicates the message was logged at pickup (see example below). The G tag
(Going) indicates the message was logged at drop-out.
11/02/94 11:15
Param. Set C :C
Only messages consistent with your relay configuration and options will appear in the display. See
Chapter 8, “Maintenance,” for information on how to erase messages in the event log.
6.3 Target Log for All Systems (5200, 5300, and 5400)
Addresses 5200, 5300, and 5400 contain the Target Log for the last three faults. This record is
called a target log because all of these faults can potentially result in a trip command being issued
to a target circuit breaker. Fault information is recorded sequentially from the most recent fault
(5200) to the “oldest” fault (5400)--the oldest fault data is erased when the next fault occurs.
5200zLAST
FAULT
5300z2nd TO LAST
FAULT
5400z3rd TO LAST
FAULT
Up to 80 messages can be stored for each of the three recorded faults. If more than 80
annunciations occur, the messages for those beyond 80 are not stored and the annunciations are
lost.
Each message is identified by a sequence number in the first three character positions of the LCD
(see example below). The first message, 001, displays the date of the fault in the first line of the
LCD. The second line displays the message “System Flt” followed by the consecutive fault
number.
The second message, 002, displays the time the fault event began including milliseconds. The
second line contains the message “Fault.”
If your relay is equipped with the automatic reclose function and an automatic reclose occurs,
then the system fault is finished when the last reset time expires whether or not the automatic
reclose is successful. Thus, the total fault clearance procedure inclusive of automatic reclose
cycles occupies only one fault record.
001z11/02/94
System Flt 65
002z10:23:33.223
Fault :C
003z0 ms
Flt.Dist.L1E :C
At 6 milliseconds after the fault was detected, distance protection issues a three-pole trip
command.
004z6 ms
Dis.Trip L123:C
At 115 milliseconds after the fault was detected, the breaker opened and successfully cleared the
fault.
005z115 ms
Dev. Drop-off:C
The next three messages identify the faulted line loop, and the distance to the fault in units-of-
length and as a percentage of the total line length.
006z115 ms
FL Loop L1E
007z
d =16.0 km
008z
d =63 %
· General faults
· Distance protection faults
· Emergency overcurrent protection faults
· Fault location messages
· High-resistance ground fault protection faults
· Internal automatic reclose issue of the reclose command
Only messages consistent with your relay configuration and options will appear in the display. See
Chapter 8, “Maintenance,” for information on how to erase the target log records.
* Following display of this message, pressing either the or key will cause the first message for the new
fault to be displayed.
6.4 Data Log for Ground Faults in Ungrounded Systems (5500) (Optional)
Address block 5500, shown below, is used to store the data log for the last three ground faults in
ungrounded systems (model number 7SA511*-**A5-*-1***). Skip this section if your relay has a
different model number.
5500zISOLATED
EARTH FLT DATA
Fault information is recorded sequentially from the most recent fault (sequence numbers beginning
with 001) to the “oldest” fault (sequence numbers beginning with 201)--the oldest ground fault
data is erased when the next ground fault occurs.
Each message is identified by a sequence number in the first three character positions of the LCD.
001z10/31/94
E/F Detec 12
· Sequence numbers beginning with digit 0 are assigned to messages for the most recent ground
fault (see above example).
· Sequence numbers beginning with digit 1 are assigned to messages for the second to last
ground fault.
· Sequence numbers beginning with digit 2 are assigned to messages for the third to last ground
fault.
The first message within a sequence--001, 101, or 201--displays the date of the fault in the first
line of the LCD as shown above. The second line displays the message “E/F Detect” followed by
the consecutive ground fault number.
The second message within a sequence--002, 102, or 202--displays the time the ground fault
began.
002z10:43:57
E/F Detection :C
Subsequent display messages provide all the applicable data for the fault. The “End of table”
message will display in the second line of the LCD to indicate there are no more messages for
each of the three reports. Press the key to display the messages for the next report.
For relay models with the optional automatic reclose feature, the number of automatic reclose
attempts are counted separately for single-pole RAR, three-pole RAR, and three-pole DAR.
The counters for circuit breaker operations can be reset at address 8202. See Chapter 8,
“Maintenance,” for information on how to reset the circuit breaker statistics.
Table 6-5 lists, by address number, all of the available messages for circuit breaker operations.
Only messages consistent with your relay configuration and options will be available for display.
All descriptions appear in the first line of the LCD, and all values appear in the second line as
shown below.
5700zOPERATIONAL
MEASURED VALUES
5701zMEAS.VALUE
IL1 = 1060 A
Table 6-6 describes the measured values you can view in address block 5700. The message
“NON-EXISTING” will appear in the second line of the LCD if a value cannot be calculated due
to incorrect parameters.
5800zISOL. E/F
MEASURED VALUES
5801zMEAS.VALUE
Iea = 0.03 A
Table 6-7 describes the four measured values you can view in address block 5800. The message
“NON-EXISTING” will appear in the second line of the LCD if a value cannot be calculated due
to incorrect parameters.
Prerequisite Settings:
Addr. LCD Text Description Setting
7806 FAULT RECRD Indicate if waveform capture exists EXIST
2801 FAULT REC. Turn waveform capture on or off ON
DIGSIÒ software is also required to view the actual waveforms. Reference B of this manual,
“Hardware & Software,” discusses this software package in more detail.
For waveform capture, the sampling rate is 20 samples per power cycle. The starting point,
ending point, and maximum recording time after a pickup is a function of the port being used to
access the data. Table 6-8 provides the specifications.
When the data is accessed and processed by appropriate software it can be displayed in graphical
format. An example of the waveform data and the way it may be displayed using DIGSIÒ
software is shown in Figure 6-1. The display shows the actual current and voltage waveforms on
each phase and ground with markers for pickup (FD), trip (Trip), and drop-out (Reset). The
points at which the fault occurred and the circuit breaker opened are also visible. The horizontal
time line is in milliseconds. In this example, the results of an unsuccessful automatic reclose can be
seen at approximately +390 milliseconds.
Uphe
Scale 83 ms
-33..100
ms t [ms]
Table of Contents
List of Figures
The measured values recorded for the relay are also useful for commissioning. Address block
5700 displays the measured phase and neutral currents, voltages, and apparent power of the
protected system.
For ungrounded systems, the ground fault data log is under address block 5500 and the measured
values are under address block 5800.
Chapter 6, “Displaying System and Relay Information,” describes in more detail the type of data
available for display in the operator panel LCD.
WARNING
Hazardous conditions.
Can cause death, serious injury, or
property damage.
· Do not exceed the limit values given in the specifications in Reference D of this
manual.
· It is recommended that the actual settings for the relay be used for commissioning
tests.
· Always press the Target Reset key to reset the relay after tests that cause LED
indications.
Symmetry Error
If a symmetry error, Failure Isymm or Failure Usymm, is indicated in the event log (address
block 5100), the transformers and their connections should be checked for interruptions or short
circuits. If there are no problems in these areas, then it is likely that the currents or voltages are
asymmetrical. If this is a normal operating condition for the system, the symmetry parameters
(addresses 2901 - 2904) should be adjusted appropriately. Reference E, “Setting Calculations,”
provides information on how to correctly set these parameters.
Summation Error
If a summation error Failure SUp-e, Failure SUp-p, or Failure SI is indicated in the event log
(address block 5100), the transformer ratio matching factors (Vph/Vdelta or IE/Iph) at addresses
1110 and 1112 should be checked. Reference E, “Setting Calculations,” provides information on
how to correctly set these parameters. The residual current must be fed to the ground current
input of the relay for the current summation check to function properly.
If the CT ratio matching factors and the ground current connections are correct, it may be
necessary to adjust the current summation parameters (addresses 2905 and 2906). Reference E
“Setting Calculations” provides information on how to correctly set these parameters.
If your system normally has counterclockwise rotation, connections for two of the phases must be
interchanged. This exchange of phase connections must be taken into account for the following
circumstances:
The line to which the relay is connected must be energized and carrying at least 10% of the rated
current. The load should be either purely resistive or resistive-inductive and in a known direction.
Where there is any doubt about the direction, interconnected or ring networks must be isolated.
Test Procedure
Follow this procedure to run the directional test:
4200zDIRECTIONAL
TEST
4201zDIREC. TEST
L1E ?
3. Press the Yes key to start the test. The selected measurement loop (e.g., L1E) carries out a
directional check and indicates the result on the display. There are three possible results:
4. Press the key to continue to the next address, 4202 in the example shown below.
4202zIMPEDANCES
L1E ?
5. Press the Yes key to confirm checking the active and reactive component of the load
impedance for the indicated loop. The message “IN PROGRESS” will appear in the second
line of the display until the test is complete. When complete, the calculated values will appear
in the display as shown below (refer also to Figure 7-1).
The n’s in this example display represent the
actual numeric values that should appear in the
Rr = nnn W relay’s display.
Xr = nnn W
6. Repeat steps 2 through 5 of this procedure for each of the six measurement loops.
Provided that the direction is indicated, all six measurement loops should indicate the same,
known direction of the load flow. If all directions are wrong, then the polarity of the measuring
transformers and the programmed setting at address 1101 (polarity) do not agree. Check the
polarity and program correctly. If the indicated directions for the individual phases differ (e.g.
phase 1 is forward and phase 2 is reverse), either the individual phase connections in the
transformers are interchanged or the polarity connections are not correct. Check the connections.
Capacitive loads caused by under-excited generators or charging currents can frequently result in
undefined or inconsistent directional information. By means of the load impedance calculation, the
position of the load impedance vector can be determined. The load impedances allow
determination of the position of the load impedance vector as shown in the R/X diagram in Figure
7-1.
Positive reactive
power
ZLoad
Direction
characteristic Forwards
Active power
R
~45°
Reverse
Negative reactive
power
Pactive Preactive
ZLoad = +
I2 I2
The line protection devices at both line ends must be in operation. At first the auxiliary voltage for
the fail-safe current loop around the pilot wires should not be switched on.
Prerequisite Settings:
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection scheme OVERREACH
2201 POTT MODE Turn the POTT protection ON
scheme on and off
2202 POTT MODE Mode of operation for permis- PILOT WIRE COMP.
sive overreach transfer scheme
Test Procedure
1. Simulate a short circuit beyond Z1 but within overreach zone Z1B. Because of the absence of
the receive signal, the relay first trips in one of the upper zones (normally T2). Perform this
test from both line ends.
2. Turn on the DC voltage for the fail-safe loop. The additional relays for pilot protection must
be in operation. The loop now carries monitoring current, and the additional relays at both line
ends are energized.
3. Simulate a short circuit at one line end beyond the first zone but within the overreach zone
Z1B. Tripping occurs instantaneously or after T1B (when a delay is set). Perform this test also
at both line ends.
Since the DC monitor is an essential part of the pilot wire system, this test has simultaneously
proved that the pilot wires are functioning correctly; therefore, all other tests described in section
7.3.3 can be skipped.
Reverse Interlocking
The test procedure in this section checks the reverse interlocking pilot protection method. Skip
this section if a different pilot protection method other than reverse interlocking is used.
The protection relay on the incoming feeder and those on all outgoing circuits must be in
operation. At first the auxiliary voltage for reverse interlocking should not be switched on.
Prerequisite Settings
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection scheme OVERREACH
2201 POTT MODE Turn the permissive overreach ON
transfer scheme on and off
2202 POTT MODE Mode of operation for permis- REVERS INTERLOCK
sive overreach transfer scheme
Test Procedure
1. Simulate a short circuit within zone Z1 and within the overreach zone Z1B. Because of the
absence of the receive signal, the relay trips in the (delayed) time T1B.
2. Turn on the DC voltage for the reverse interlocking. The test as described above is repeated,
with the same result.
3. Simulate a trip on each protective device on all outgoing feeders. Simultaneously, a short
circuit is simulated on the incoming feeder (as described before). Tripping now occurs after
delay T1.
4. These tests have simultaneously proved that the pilot wires are functioning correctly;
therefore, all other tests described in section 7.3.3 can be skipped.
Prerequisite Settings
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection scheme OVERREACH
2201 POTT MODE Turn the permissive overreach ON
transfer scheme on and off
2202 POTT MODE Mode of operation for permis- · Z1B RELEASE or
sive overreach transfer scheme · FD DIREC RELEASE or
· Z1B UNBLOCK or
· FD UNBLOCK
2220 ECHO Turn the echo function on and ON (at both line ends)
off
Test Procedure
1. Simulate a short circuit in Z1B beyond Z1. Since the relay at the other line end has not picked
up on fault, the echo function will be effective at that end and a trip signal results.
2. The effect of the echo delay time and the input of the circuit breaker position can be checked
at this time. With the following tests, the echo function of the relay at the opposite line end is
checked.
a) The circuit breakers at both line ends must be open. A short circuit is simulated as above.
Because of the echo function of the relay at the opposite line end, the signal is received
and a trip signal occurs at once.
b) Close the circuit breaker at the opposite line end. Repeat above test once more. Received
signal and trip command occur again but now with an additional delay caused by the echo
delay time at the opposite line end (0.2 seconds as delivered, see address 2221).
c) If delayed and undelayed echo are interchanged, the function mode (NO/NC operation) of
the binary input for the circuit breaker position could be wrong. Check and correct it at
the opposite line end per the relay programming instructions given in Chapter 5,
“Programming the Relay.” When delivered from the factory, the input for the circuit
breaker auxiliary contact is INPUT 3, assigned to the function CB Aux Cont NO. Change
the function mode from NO to NC if necessary (i.e., CB Aux. Cont NC). If the circuit
breaker position input is asigned differently, change the mode accordingly.
d) Open the circuit breaker. Repeat these tests for the other line end.
Prerequisite Settings
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection scheme OVERREACH
2201 POTT MODE Turn the permissive overreach ON
transfer scheme on and off
2202 POTT MODE Mode of operation for permis- Z1B BLOCKING
sive overreach transfer scheme
Test Procedure
1. At the line end to be tested as sender, simulate a fault in reverse direction; at the other end,
simulate a forward fault within zone Z1B but beyond the limit of Z1. Since the transmitter
sends a blocking signal, the receiving protection must not trip, unless in a delayed zone, as
long as blocking signal is transmitted. After switching off the reverse fault on the sending side,
the receiving side remains blocked for the send prolongation T-SEND-PRL (address 2206)
plus the transient blocking time T-TRANSBLO (address 2203) of the receiving side.
Prerequisite Settings
Addr. LCD Text Description Setting
7804 TELEPROTEC. Type of pilot protection scheme UNDERREACH
2101 PUTT MODE Turn the permissive underreach ON
transfer scheme on and off
Test Procedure
1. At the line end to be tested as sender, simulate a fault within zone Z1.
2.
If address 2102 Then . . . Result
setting is . . .
Z1B ACCELERATION At the receiving end, simulate a The protection trips at once (or T1B), without
fault within zone Z1B but beyond reception a delayed time element can only be
Z1. effective.
FD ACCELERATION At the receiving end, simulate any The protection trips instantaneously, without
pickup. reception in a delayed time element.
This test is to be performed from both line ends. The carrier system can be checked from one end
of the line with the echo function.
Prerequisite Settings
Addr. LCD Text Description Setting
7808 EARTH FAULT Type of high-resistance ground fault DIREC.COMPARISON
detection
3201 E/F COMPAR Turn on and off the directional ON
comparison protection function
3210 E/F ECHO Turn on and off the echo function for ON
directional comparison ground fault
protection
1201 DIST. PROT. Turn on and off the distance protection OFF
function
Test Procedure
1. Simulate a ground fault in the line direction. Since the relay at the other line end has not
picked up on fault, the echo function will be effective at that end and a trip signal results.
2. The effect of the echo delay time and the input of the circuit breaker position can be checked
unless it has already been done as part of the test in section 0. The opposite line end is
checked.
a) The circuit breakers at both line ends must be open. A ground fault is simulated as above.
Because of the echo function of the relay at the opposite line end, the signal is received
and a trip signal occurs at once.
b) Close the circuit breaker at the opposite line end. Repeat above test once more. The
received signal and trip command occur again but now with an additional delay caused by
the echo delay time of the relay at the opposite line end (0.2 seconds as delivered, see
address 3211).
c) Open the circuit breaker. Repeat these tests for the other line end.
In the 7SA511 relay, confirmation of a closed circuit breaker is always required from the operator
panel. It will also be required from a binary input if CB AUX.CNT at address 1113 is set to
CONNECTED.
Test Procedure
1. Place the relay in programming mode by entering the password, then access address 4404.
4400zCB TEST
LIVE TRIP
2. Press the key to go to the next address as shown in the example display below.
4401zTRIP
CB POLE L1 ?
3. Press the Yes key to confirm starting the test. The message “CB CLOSED?” appears in the
second line of the display as shown below.
4401zTRIP
CB CLOSED ?
DANGER
A successfully started test cycle will cause
the circuit breaker to close if this relay is
connected to an external auto-reclose
device.
This can cause death or serious injury.
4. If the circuit breaker is closed, press the Yes key. Otherwise, abort the test by pressing the
key. If you press the Yes key, verify that the circuit breaker opens.
5. Repeat steps 2 through 4 of this procedure as applicable to your relay. Table 7-2 identifies, by
address number, all tests within the 4400 block. Only those tests options applicable to your
relay will appear in its display. Each test option is followed by the “CB CLOSED?” message
as explained in step 3 above.
Table 7-2. Circuit Breaker Trip Test Options, Address Block 4400.
Addr. LCD Text Description
4401 TRIP CB POLE L1? Single-pole test cycle for circuit breaker pole L1
4402 TRIP CB POLE L2? Single-pole test cycle for circuit breaker pole L2
4403 TRIP CB POLE L3? Single-pole test cycle for circuit breaker pole L3
4404 TRIP CB THREE-POLE? 3-pole circuit breaker test cycle
Note: As a safety precaution, delete the assignment of FNo 880 to the output relay controlling
the circuit breaker before returning the relay to service.
If the model contains only 3-pole auto-reclose, then only those test options are available which
relate to the 3-pole auto-reclose program. Single-pole tests will only be carried out by the relay
when single-pole auto-reclose is also permitted. Check the setting at address 3412 to determine
which test options should be available when testing your relay:
As described in section 7.3.4 above, the programming of the CB auxiliary contact control at
address 1113 must be correct before the relay will allow the test. Additional prerequisites to
starting the internal automatic reclose test are:
Prerequisite Settings:
Addr. LCD Text Description Setting
7810 INTERNAL AR Indicates whether or not the relay has EXIST
the internal auto-reclose function
3401 AUTO-RECL. Turns the auto-reclose function on or ON
FUNCTIONS off
TestProcedure
4300zCB-TEST
TRIP-CLOSE CYCLE
2. Press the key to go to the next address as shown in the example display below.
4301zCB TEST
L1 WITH AR ?
3. Press the Yes key to confirm starting the test. The message “CB CLOSED?” appears in the
second line of the display as shown below.
4301zCB TEST
CB CLOSED ?
DANGER
A successfully started test cycle will
cause the circuit breaker to close.
This can cause death or serious injury.
4. If the circuit breaker is closed, press the Yes key. Otherwise, abort the test by pressing the
key.
5. Repeat steps 2 through 4 of this procedure to display or perform the circuit breaker test
options available for your relay. Table 7-3 identifies, by address number, all tests within the
4300 block. Only those tests options applicable to your relay will appear in its display. Each
test option is followed by the “CB CLOSED?” message as explained in step 3 above.
Table 7-3. Circuit Breaker Trip-Close Test Options, Address Block 4300.
Addr. LCD Text Description
4301 CB TEST L1 WITH AR? Single-pole test cycle for circuit breaker pole 1
4302 CB TEST L2 WITH AR? Single-pole test cycle for circuit breaker pole 2
4303 CB TEST L3 WITH AR? Single-pole test cycle for circuit breaker pole 3
4304 CB TEST L123 WITH AR? Three-pole circuit breaker test cycle
4305 CB TEST SEQU. L1-L2- Sequence of single-pole test cycles for circuit
L3? breaker poles 1, 2, and 3
· Verify that the relay protection and configuration settings are correct.
· Press the Target Reset key to clear any indications.
· Verify that the green Power LED is lit.
· Verify that the red Blocked LED is not lit.
· If a test switch is installed, return the switch to the normal position.
Maintenance
Table of Contents
8. Maintenance.........................................................................................................................8-3
8.1 Tracing Hardware and Software Faults...........................................................................8-4
8.2 Troubleshooting Tips .....................................................................................................8-4
8.3 Inspecting the Power Supply Fuse..................................................................................8-4
8.4 Replacing the Backup Battery.........................................................................................8-5
8.5 Erasing Stored Data (8200) ............................................................................................8-6
8.6 What To Do With Defective Relays................................................................................8-7
8.7 Storing Relays That are Taken Out of Service ................................................................8-7
List of Figures
Figure 8-1. Power Supply Minifuse and Backup Battery on the Basic GEA module.................8-5
8. Maintenance
The 7SA511 relay is designed so that no special testing, calibration, or maintenance is required.
All measurement and signal processing circuits are fully solid state and, with the exception of the
internal backup battery, require no periodic maintenance. The following basic maintenance
procedures are provided in this section
To inspect the power supply fuse or replace the backup battery, the relay’s front cover must be
removed and the relay removed from its housing. If required, see Chapter 4 “Installation” for
procedures on removing the front cover and removing or replacing relay modules.
DANGER
Hazardous voltages in the equipment.
This can cause severe personal injury and
equipment damage.
CAUTION
Electrostatic Discharge
Possible equipment damage.
The relay module contains CMOS circuits. The
module must never be withdrawn from or
inserted into the housing with power connected.
Electrostatic discharges into or around the
uninstalled relay or any of its components must
be avoided.
The relay’s event log and target log data may be useful for maintenance. The event log is under
address block 5100, and the target logs for the last three faults are under address blocks 5200,
5300, and 5400, respectively. Refer to Chapter 6, “Displaying System and Relay Information,” for
more information on the type of data included in the event log and target logs.
If the red Blocked LED is lit and the green Power LED is not lit, the device has recognized an
internal fault. To reinitialize the unit, turn the DC auxiliary voltage off then back on using the
operator panel On/Off switch. When the DC auxiliary voltage is off, the relay will lose any event
log data, target log data, and configuration settings that have not been saved.
The fuse holder is located at the rear of the basic relay module as shown in Figure 8-1. If the fuse
is blown, there is very likely a problem in the internal power supply, and the relay should be
returned to the factory for repair.
Minifuse for
the power supply
Battery location
when installed-
see View A
View A
Jumper X51
Figure 8-1. Power Supply Minifuse and Backup Battery on the Basic GEA module.
occurs. This battery should be replaced at least every five years to avoid unexpected loss of fault
data. A lithium battery 3 V/I Ah, type CR 1/2 AA, is the recommended type of replacement
battery.
The battery is located at the rear edge of the processor board of the basic module as shown in
Figure 8-1.
The relay must be removed from its housing (see “Installation” section 4.3.2) to replace the
backup battery. Removing the relay from the housing will disconnect the external power, so if the
currently stored fault data is to be retrieved, it must be done before removing the relay from the
housing.
Following all recommended safety procedures, replace the backup battery as follows:
1. If desired, retrieve the currently stored fault data through either of the serial ports or by
readout through the LCD on the operator panel (address block 5000). (Note: Configuration
data is stored in a different memory and is not affected by this process.)
2. Remove the relay from the housing as described in “Installation” section 4.3.2.
3. Remove the used battery from the terminals according to Figure 8-1. Caution: Do not place
battery on conductive surfaces.
4. Replace the used battery with the same or equivalent type. If required, see “Installation”
section 4.6, Figure 4-5, for instructions on preparing the battery for installation.
5. Insert the battery into the terminals as shown in Figure 8-1 and tighten the screws.
6. Reinstall the relay module in the housing as described in “Installation” section 4.3.2.
7. Set the clock to the correct date and time either through the operator panel or the front
serial port.
In each case, a question asking whether or not to reset a particular data group is displayed. If
clearing of that group is desired, press the Yes key. During the clearing operation, the message
“TASK IN PROGRESS” is displayed. When the clearing operation is complete, the address of the
group (8201 - 8205) that was reset is displayed along with the message “RESET EXECUTED.”
If the relay is de-energized and stored for an extended time period, proper voltage should be
applied to the power input for one or two days prior to placing the relay into service.
Method of Operation
Table of Contents
List of Figures
A. Method of Operation
A.1 Overview of Hardware and Protection Functions
The 7SA511 relay is a microprocessor-based, high speed, numerical distance relay designed to
provide fast, reliable, and selective clearance of all kinds of ground and phase faults on overhead
lines and cables being fed from one point or multiple points. It can also be used as local backup
and/or bus protection through reverse interlocking or to provide backup protection for
generators, and it can be installed on grounded or ungrounded systems. Figure A-1 shows the
basic structure of the unit.
The relay provides full digital processing of all functions, from data acquisition of measured
values to the trip commands for the circuit breaker. Protection functions provide by the 7SA511
relay are:
The analog input module (see Figure A-1) contains input amplifiers, sample and hold elements for
each input, multiplexers, and analog/digital converters. Analog current input signals enter into the
relay isolating transformers and then pass through anti-aliasing filters to the analog input module.
The anti-aliasing filters’ bandwidth and processing speed are optimized to match the protection
algorithms. The input signals are sampled 20 times per power cycle (one sample every 0.83
milliseconds at 60 Hz) and converted to digital signals.
The 7SA511 relay has seven voltage transformers and four current transformers. The first three
voltage transformers are wired in a wye to measure the phase-to-ground voltages. The second
three voltage transformers are wired in a delta to measure the phase-to-phase voltages. The three
delta terminals are internally connected in parallel with the three wye terminals. This connection
scheme results in a total of 4 inputs - one for each of the three phases and the neutral. The
remaining voltage transformer input VE is used for measurement of the displacement voltage VE
from the broken-delta windings of the VTs. Three of the five current inputs are for input of the
phase currents of the protected line. The remaining current input is used for one of the following:
The relay also has 10 optically isolated binary inputs, 16 LEDs, 5 trip relays, and 11 signal relays.
Power System
Bus MUX
L1 A/D Converter
L2 Microprocessor
Isolating
L3 Transformers MUX
LCD
IL1
Blocked
IL2
Ready
IL3
IE
11 Signal Relays
(programmable)
P-G
VL1
P-G
VL2
P-G
14 LEDs
VL3
(programmable)
P-P
P-P
P-P
5 Trip Relays
(programmable)
VE
Line Membrane
Keypad
Reverse
Power Rear Port
Substation
Serial Interface
Flow with isolation Control System
10 Binary
Forward Inputs
(Programmable) Front Port Personal
Serial Interface Computer
DC
Power Supply
DC
The microprocessor performs all impedance and overcurrent calculations and makes all protection
logic decisions. The microprocessor also provides the following functions:
Binary inputs are isolated through optical couplers. Outputs include trip contacts, signal contacts,
LEDs, and an alphanumeric LCD on the operator panel. You can program the binary inputs,
output contacts, and LEDs as discussed in Chapter 5, “Programming the Relay.”
Using the operator panel keypad and LCD, you can read or change the system, protection, and
relay configuration settings, access and read the relay’s measured values, and review the target
history logs for the last three faults. This interaction with the relay can also be accomplished using
DIGSIÒ software on a personal computer connected to the serial interface port on the operator
panel (refer to Figure 2-1 in Chapter 2, “Product Description”).
An integrated DC-to-DC converter supplies multiple voltages to the relay subsystems as follows:
Voltage Subsystem
+24 V Output relays
±15 V A/D converters
+12 V EEPROMs
+ 5V CPU and associated logic
The relay can withstand a loss of input supply voltage for 50 milliseconds (VH ³ 110 V) without
going out of service (refer to Reference D, “Specifications”).
· Overcurrent (7SA511*-**A51-****)
· Overcurrent, Voltage-controlled overcurrent, and Polygonal impedance (7SA511*-
**A52-****)
· Overcurrent and Voltage-controlled overcurrent (7SA511*-**A53-****)
· Trip delays
· Determination of the faulted line loop(s)
· Release of trip commands
· Auxiliary functions
· Identification of the faulty phase(s)
The overcurrent fault detection unit is used for high fault current detection. If there is no
significant difference between normal current (including overload) and short circuit current, then
the voltage controlled overcurrent or polygonal impedance fault detection unit must be used.
Power systems with highly fluctuating system impedance or systems using short circuit current
limiting devices also require voltage controlled overcurrent or polygonal impedance fault
detection units.
The ground current detector monitors the fundamental wave of the total of the phase currents (IE
= 3I0) in comparison with the threshold value. It is restrained against faulty pickup caused by
asymmetric operating currents or distorted currents in the secondary circuit of the current
transformers (CTs) resulting from different CT saturation with ground-free short circuits. The
actual pickup value is automatically increased as the phase currents increase. In Figure A-2, with
an example for setting IE>/IN = 0.2, the horizontal branch is shifted according to different settings.
The reset value is 95% of the pickup value.
IE>
IN
1.0
IE pick-up
0.8
0.6
0.4 Pickup
0.2
IE reset
10%
0
0 1 2 3 4 5 6 7
Iph max
IN
The displacement voltage detector monitors the fundamental wave of the displacement voltage
(VE = 3 V0) in comparison with the set threshold value. The reset value is 95% of the pickup
value.
In grounded systems (solidly or resistance grounded), the pickup of the ground current monitor
or the displacement voltage monitor lead to pickup of the ground fault detector. Detection of a
ground fault on its own is not announced, and it does not lead to a general fault detection signal of
the distance protection. It does, however, control the other fault detection elements.
To enable measured value selection, the phase-dedicated fault detection signals are converted into
phase-loop information (see section A.3). In grounded systems, this process is carried out accord-
ing to the ground fault detection function and the parameter, 1PH FAULTS, selected for single-
phase pickup without ground fault detection. In ungrounded system, the multi-phase loop is
always selected in the case of a single-phase pickup without ground fault detection.
The faulty phases are indicated (see Table A-1). The overcurrent fault detector is reset when the
pickup value is below 95%.
The impedances are calculated separately for resistance, R, and reactance, X, in cyclic time
intervals and compared with the set values of any of the six line loops for which the current
conditions are met. A measured value step change monitor is used to synchronize the
measurement window on occurrence of a fault. The calculation procedure is the same as that
described for distance measurement.
The polygonal impedance fault detector utilizes a special “dog bone” characteristic (Figure A-3)
to provide secure pickup for faults without pickup on load. The X-intersections X+A and X-A are
decisive for the fault reach in the forward and reverse directions respectively. The R-intersections
can be set differently for multi-phase loops (RA1) and phase-to-ground loops (RA1E). It is therefore
possible, for example, to permit a larger fault resistance tolerance for ground faults (bold dotted
lines in Figure A-3). Extension of the polygon in the R-direction is only valid when a ground fault
has been detected as described in the previous section.
In order to guarantee the criteria for distinction between load operation and a short-circuit,
especially in the case of long, heavily loaded lines, the characteristics can be set dependent on the
phase angle with the RA2 intersection applicable for phase angles above 45°, and the RA1
intersection applicable for phase angles below 45°.
X
X+A
Forward
direction
45° RAE
RA1
R
RA2
Reverse
direction
X-A
To avoid intermittent pickup signals near the perimeter of the characteristic, a hysteresis of 6% is
provided.
Pickup results for the measurement loop in which the impedance vector lies within the fault
detection polygon (shaded area in Figure A-3). If detection occurs in more than one loop, the
relay regards as valid all loops whose impedance is not greater than 150% of that smallest
impedance. This avoids incorrect pickup signals which could be caused by the influence of the
fault currents and voltages on the unfaulted line loops, especially in cases of small source
impedances.
The impedance fault detection for phase-to-ground loops is supplemented by the overcurrent
element (I>>) where pickup of only the overcurrent element leads to detection if the associated
impedance loop has been eliminated as described above. In this manner, double faults with a high
current are also detected even though the fault loop has been eliminated. Since the overcurrent
element can only re-establish eliminated loops for pickup, erroneous fault detection due to an
overcurrent is prevented if the short-circuit currents in the fault-free phases can exceed the set
overcurrent value on ungrounded feeding transformers or grounded consumer transformers.
Impedance fault detection can be used only for ground faults where the phase-to-ground
measurement is enabled by ground fault detection. Phase-phase faults in this case are detected
with high-set overcurrent (I>>) element. This detection program is only of advantage in systems
with limiters for ground currents (grounded with low impedance—resistance grounding) where a
short-circuit current, sufficient for pickup by the overcurrent element, flows for phase-to-phase
faults but not for phase-to-ground faults. Ground-free faults are thus detected by the high-set
overcurrent element (I>>).
Pickup caused by single-phase ground faults in ungrounded systems is suppressed by the measures
described in section A.2.1.
Fault detection of a phase is reset when the respective current is less than 95%, or the respective
voltage is greater than 105%. The shaded area in Figure A-4 identifies the fault detection area.
V
70
60
V(Iph>>)
50
V(Iph>)
40
30
Pickup
20
10
Iph> Iph>>
0
0 I/IN
1 2 3
Each of the three fault detection modules is controlled by the phase-to-ground voltages (VPh-E) or
the phase-to-phase voltages (VPh-Ph). You must program the relay to indicate whether the phase-
to-ground voltages (VPh-E) or the phase-to-phase voltages (VPh-Ph) are decisive, or whether this
depends on the ground fault detection as described in section A.2.1. Optimum control largely
depends on whether the system neutral is grounded with a low impedance (resistance grounded),
is solidly grounded, or is not grounded (isolated or compensated).
Table A-2. Voltage Controlled Overcurrent Fault Detection - With Phase-to-Ground Voltages
Fault Detection Measured Measured Ground Parameter (1705) Resultant Annunciation
Module Current Voltage Fault 1PH FAULTS Loop
Detection
L1 L1 L1-E no PHASE-PHASE L3-L1 L1
L2 L2 L2-E no (Uph - Uph) L1-L2 L2
L3 L3 L3-E no L2-L3 L3
L1 L1 L1-E no PHASE-EARTH* L1-E L1
L2 L2 L2-E no (Uph - E) L2-E L2
L3 L3 L3-E no L3-E L3
L1 L1 L1-E yes irrelevant L1-E L1, E
L2 L2 L2-E yes L2-E L2, E
L3 L3 L3-E yes L3-E L3, E
In grounded systems, the measured line loop depends on the ground fault detection function
(section A.2.1) and the parameter, 1PH FAULTS (address 1705), selected according to Table A-
2. In ungrounded system, the phase-to-phase loop is always selected in the case of a single-phase
pickup without ground fault detection. The faulty phases are identified.
Table A-3. Voltage Controlled Overcurrent Fault Detection - With Phase-to Phase Voltages
Fault Measured Measured Ground Fault Parameter Resultant Annunciation
Detection Current Voltage Detection (1705) Loop
Module 1PH FAULTS
L1 L1 L1-L2 irrelevant irrelevant L1-L2 L1
L2 L2 L2-L3 L2-L3 L2
L3 L3 L3-L1 L3-L1 L3
If the voltage loops are set to be dependent on the ground fault detection, the high sensitivity for
phase-to-ground faults then also applies to phase-to-phase faults. This possibility is, in principle,
independent of the treatment of the system neutral; it assumes, however, that the ground fault
criteria according to section A.2.1 have been satisfied safely for all ground faults. Table A-4
applies to the fault detection program for phase-to-ground or phase-to-phase voltages with single-
phase pickup.
Table A-4. Voltage Controlled Overcurrent Fault Detection - Phase-to Ground Voltages With
Ground Fault and Phase-to-Phase Voltages Without Ground Fault
Fault Measured Measured Ground Fault Parameter Resultant Annunciation
Detection Current Voltage Detection (1705) Loop
Module 1PH FAULTS
L1 L1 L1-L2 no irrelevant L1-L2 L1
L2 L2 L2-L3 no L2-L3 L2
L3 L3 L3-L1 no L3-L1 L3
L1 L1 L1-E yes irrelevant L1-E L1, E
L2 L2 L2-E yes L2-E L2, E
L3 L3 L3-E yes L3-E L3, E
It is also possible to control with phase-to-ground voltage loops (VPh-E) when a ground fault has
been detected. Detection for phase-to-phase faults then takes place only with high-set overcurrent
(I>>). This option is advantageous in systems with a low-impedance ground (resistance
grounding) when only ground faults are to be detected by the voltage controlled overcurrent fault
detection. The measured loop is independent of the parameter 1PH FAULTS. Table A-5 shows
the assignment of the phase currents, loop voltages and output results for single-phase pickup
with ground fault detection only.
For example, when calculating the impedance of a phase-to-phase loop for a two phase short
circuit in L1-L2 (Figure A-5), the following identity applies:
I L1 ZL − I L2 ZL = VL1 − VL1
VL1 − VL 2
ZL = .
I L1 − I L 2
IL1 ZL
L1
VL1
IL2 ZL
L2
VL2
L3
For calculation of a phase-to-ground loop for a short circuit in L3-E (Figure A-6), observe that
the impedance of the ground return path is not normally equal to the impedance of the phase. In
the loop equation
I L 3 ZL − I E ZE = VL 3− E ,
ZE
ZE is replaced by ZL , which gives us
ZL
Z
I L 3 ZL − I E ZL E = VL 3− E ,
ZL
L1
L2
IL3 ZL
L3
VL3-E
IE ZE
E
With double faults, pickup normally occurs in two phases and ground (overcurrent detection) or
for two phase-to-ground loops (impedance detection). In this case, it is possible to set the relay so
that preference is given to one of the fault loops. Only the phase-to-phase loop, the loop of the
leading phase-to-ground, or the loop of the lagging phase-to-ground will be selected.
Note: In grounded power systems, the relay must be connected to three wye-connected
VTs with grounded primary common and to three CTs. The common connection
for the CTs should be connected to the ground current input of the relay. If the
current input of the relay is fed from other current sources, such as from the
common connection of the CT set of a parallel line for parallel line compensation,
the relay calculates the ground fault from the sum of the three phase currents. If
the VTs have residual voltage windings, these should be connected in broken-
delta to the voltage input to enable the relay to monitor the VTs’ secondary
circuits.
Table A-6 and Table A-7 show the measurement quantities used for distance measurement in
grounded systems.