Identification
Device
Order number
Short code
‘System
Manufacturer
PNO profile
Device family
Device subfamily
Device class
Function group
Field bus in
m interfa
Devic
1D
HW
FW version
interface
Inspection counter
TuM version
TuM data
Service number
Time stamp
Device details
Ie setting range from
Te setting range to
Rated voltage
Upper current limiting value
Performance class
Max. motor heating
‘Max. trace memory size
Short-circuit tripping factor
Control function
Switchgear technology
Contact block type
Contaet block name
Contact block cooling time
Corre
Heatsink temp.
3RW44**-*BC**
DSSte 4DV4D0
SIRIUS soft starter HF
SIEMENS AG
Load feeder
Motor starter
Direct soft starter
70
A
A
VAC
Measured values
Current detection
‘ansformer ratio
Byte arrangement
Daca. TSG ESSE! — DoS a
FE aT THE SN
PRET ESProcess data format 1
Process data format 2
Supported baud rate:
Motor protection deactivation rule
FW version ul
FW version pC2
FW version wC3
Marking
Plant code
Location code Not supported!
Date of installation (YYYY-MM-DD)
Description ‘Not supported!
Author
(Comment
a THiS TSS | DoT Doane
ra TE ae Te
ETT RTEDevice configuration
Basic Unit Sofftstarter 3RW44
Version vil
Motor control
Control function reversing starter no
Control function soft starter yes
Control function speed regulating
theostat
Control function slow speed yes
Electrical braking procedure yes
Braking output no
Emergency start yes
Quick Stop no
Cold start no
Safety technology no
Motor protection
‘Thermal motor model yes
‘Temperature sensor yes
Substation monitoring
Current limits yes
Asymmetry yes
Ground fault yes
Inputs yes
Outputs yes
Connector monitoring, no.
Main power
Main energy monitoring yes
Voltage measurement yes
(Current measurement yes
Mechanical switching no
Solid-state switching yes
Self-protection
Line protection no
Short-circuit protection no
‘Thermal contact block model yes
Bypass function yes
a THiS TSS | DoT Doane
ra TE ae Te
PRET
ESModule
HMI module yes
Memory module no
Communication
Field bus interface yes
Device interface yes
Cyclic Send Data no.
Diagnosis
Trace yes
Logbook yes
Maintenance
Maintenance no
Self-test no
FW update no.
PROFlenergy
Energy saving mode no
Measurement function no
Da Tea RS. — [DOSE Doane
oa CTE roa Te
STITT
aEDevice parameters
Basic parameters
Protection against voltage failure
Response to contact block supply
voltage cut-off
Parameter set 1
yes
Group error
Rated operating current Ie 62.004
Rated voltage Reserved VAC
Rated power reserved kW
Rated frequency eserved Hz
Rated speed 1645 RPM
Rated operating torque 22Nm
Load type 3-phase
Parameter set 2
Rated operating current Ie
Rated voltage
Rated power
Rated frequency
Rated speed 1500 RPM
Rated operating torque ONm
Parameter set 3
Rated operating current Ie 313.00 A
Rated volta Reserved VAC
Rated power eserved kW
Rated frequ reserved Hz
Rated speed 1500 RPM
Rated operating torque ONm
Field bus interface
‘Type of interface PROFIBUS
MLFB communication unit 3RW49 00-0KCO0
Station address 80
Baud rate 12,000 kBd
Waiting for start-up datasets no
Parameter set 1
Group diagnostics Block
Response to CPU/master STOP _—_Switch substitute value
ECTS TERT ESE — DES aT
ra TE ae TEE
EROSTE oSSubstitute value
Motor RIGHT no
Motor LEF1 no
Brake 20
Trip reset no
Emergency start no
Self-test 00
Slow speed no
Reserved no
Output 1 no
Output 2 no
Active parameter set Bit0 no
Active parameter set Bit no
Reduction factor BitO no
Reduction factor Bit] 20
Reduction factor Bit2 10
Disable quickstop no
Motor control
Control function soft starter
Parameter set 1
Startup mode Voltage ramp
Starting voltage 30%
Starting torque 10%
Limiting torque 150%
Current limiting value 450
Starting time 20.08
Max. starting time 00s
Breakaway voltage 40%
Breakaway time 0.00
Motor thermal capacity 20%
Coasting method Pump stop
Coast-down time 15.05
Stopping voltage oe
Stopping torque 20%
Parameter set 2
Startup mode Voltage ramp
Starting voltage 30%
Starting torque 10%
Limiting torque 150%
Current limit value 450
aa TERT IESE — Daa aT
ra ST ae TEE
EROSTE SE SEStarting time 100s
Max. starting time 00s
Breakaway voltage 40%
Breakaway time 0.00s
Motor thermal capacity 20%
Coasting method Pump stop
Coasting down time 15.08
Stopping voltage 0%
Stopping torque 20%
Parameter set 3
Startup mode Voltage ramp
Starting voltage 30%
Starting torque 10%
Limiting torque 150%
(Current limit value 450
Starting time 100s
Max. starting time 0.08
Breakaway voltage 40%
Breakaway time 0.00s
Motor thermal capacity 20%
Coasting method Pump stop
Coasting down time 15.08
Stopping voltage 0%
Stopping torque 20%
Control function slow speed
Parameter set 1
Clockwise rotation (right)
Slow speed factor 7
Slow speed torque 50%
CCW rotation (left)
Slow speed factor 7
Slow speed torque 50%
Parameter set 2
Clockwise rotation (right)
Slow speed factor (PS2) 7
Slow speed torque (PS2) 50%
a THiS TSS | DoT Doane
ra TE ae Te
PRET
Ta
EECCW rotation (left)
Slow speed factor (PS2) 7
Slow speed torque (PS2) 50%
Parameter set 3
Clockwise rotation (right)
Slow speed factor (PS3) 7
Slow speed torque (PS3) 50%
CCW rotation (left)
Slow speed factor (PS3) 7
Slow speed torque (PS3) 50%
Electrical braking procedure
Parameter set 1
Dyn. braking torque 50%
DC Braking torque 50%
Braking time 00s
Parameter set 2
Dyn. braking torque (PS2) 50%
Braking torque (PS2) 50%
Braking time 00s
Parameter set 3
Dyn. braking torque (PS3) 50%
Braking torque (PS3) 50%
Braking time 00s
Motor protection
‘Thermal motor model
Parameter set 1
‘Tripping class CLASS 10
Idle time Os
‘Motor heating 80%
Remaining time for tripping Os
Response to overload ‘Tripping without restart
Recovery time 1.0 min
Daa. TSG SSS — DoS a
FE Tae by SN
PRET Sa‘Temperature sensor
Parameter set 1
‘Temperature sensor Disabled
‘Temperature sensor monitoring yes.
Response to overload Tripping without restart
Substation monitoring
Current limits
Parameter set 1
Rated operating current Ie 62.00,
Response to residual current detection Warning
Blocking curren 0%xI
Blocking time 00s
Response to current limit violation Warming
Limit deactivated no
Lower current limit 18.75 % (11.63 A)
Limit deactivated no
Upper current limit 112.50 % (69.75 A)
Parameter set 2
Rated operating current Ie 313.00 A
Response to residual current detection Waming
Blocking curren O%xIe
Blocking time 0.08
Limit deactivated no
Lower current limit 18.75 % (58.69 A)
Limit deactivated no
Upper current limit 112.50 % (352.13 A)
Parameter set 3
Rated operating current Ie 313.00 A
Response to residual current detection Warning
Blocking current 0%xlIe
Blocking time 00s
Limit deactivated no
Lower current limit 18.75 % (58.69 A)
Limit deactivated no
Upper current limit 112.50 % (352.13 A)
a THiS TSS | DoT Doane
ra TE ae Te
PRET SaAsymmetry
Parameter set 1
Response to asymmetry
Limit deactivated
Asymmetry limit
Ground fault
Parameter set 1
Response to ground fault
Inputs
Parameter set 1
Input 1 - Action
Input 2 - Action
Input 3 - Action
Input 4 - Action
Outputs
Parameter set 1
Output 1 - Action
Output 2 - Action
Output 3 - Action
Self-protection
Thermal contact block model
Parameter set 1
Response to overload - contact block
HMI module
Parameter set 1
‘Tripping
40%
‘Warming
Motor right with PS1
Manual operation local
Quick stop
Trip reset
Control command motor ON
Ready for motor ON
‘No action
‘Tripping without restart
Language Spanish
Response to warning Blinking
Response to fault Flickering
Contrast 50%
HMI keys activity monitoring time 0.5 min
aT
PRET
THE
ESReaction time keys 60%
Auto repeat speed 80%
Auto repeat time 80 ms
barra TBS aT
oa CTE Ta TEE
STD 3S] SE