VOLUME – V

CIVIL, ARCHITECTURAL &


STRUCTURE

SPUR LINES OF CHAINSA – JHAJJAR PIPE LINE

0 10.11.2008

DESIGN BASIS/JOB
SPECIFICATION/ STANDARD
SPECIFICATION/STANDARDS/
DRAWINGS/DATASHEET

REV. DATE
INDEX
--
JOB SPECIFICATIONS

S.NO. DOCUMENT No. NO. OF REV. TITLE


PAGES
Specification for Architectural
1 0001-01-09-02-001 38 0
Finishes.
Standard specification for clean
2 0001-01-09-02-002 22 0
agent system
Specific requirement for
Geotechnical Investigations for
3 0001-01-09-02-003 9 0
pipeline laying and associated
works tender
Job specific requirement for
4 0001-01-09-02-004 4 0 Civil- Strl. Works for pipeline
laying and associated works
Job Specification for packaged
5 0001-01-09-02-005 15 0
equipment inputs

LIST OF ATTACHMENTS DOCUMENT No. REV-0


GAIL (INDIA) LTD
Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STRUCTURAL
STANDARD SPECIFICATIONS
Sl. No. Of
Specification No. Rev Title
No. Sheets
01 S-11-02-001 04 0 Technical Specification civil &
structural works - General
scope.
02 S-11-02-002 16 0 Technical Specification civil &
structural works - Materials.
03 S-11-02-003 11 0 Technical Specification civil &
structural works – Earthwork.

04 S-11-02-004 32 0 Technical Specification civil &


structural works – Plain and
Reinforced cement concrete.
05 S-11-02-005 7 0 Technical specification -civil &
structural works - reinforced
cement concrete in liquid
retaining structures.
06 S-11-02-006 24 0 Technical Specification civil &
structural works – Structural
steel works.

07 S-11-02-007 12 0 Technical Specification civil &


structural works – Miscellaneous
steel works.
08 S-11-02-008 8 0 Technical Specification civil &
structural works – Brick
masonry.
09 S-11-02-009 9 0 Technical Specification civil &
structural works – Stone
masonry
10 S-11-02-010 5 0 Demolition & Dismantling
11 S-11-02-011 8 0 Technical Specification civil &
structural works – Miscellaneous
items.

LIST OF ATTCHMENTS STRUCTURALS DOCUMENT No. REV-0


GAIL (INDIA) LTD
0001-01-11-11-001 Page 1 of 2
NEW DELHI
Copyright GAIL – All rights reserved
STRUCTURAL STANDARDS

No. Of
Standard No. Rev. Title
Sheets
01 S-11-01-001 02 2 Flooring details for buildings
02 S-11-01-002 07 4 Metal insert plates
03 S-11-01-003 05 3 Standard lintels
04 S-11-01-004 07 4 M.S.Anchor bolts
05 S-11-01-005 10 5 Handrail
06 S-11-01-006 6 4 Steel Stair
07 S-11-01-007 6 3 Standard grating details
08 S-11-01-008 3 2 Small operating platforms on
grade/RCC elevated structure
09 S-11-01-009 4 2 Crossover
10 S-11-01-010 17 2 Cable -Trench

LIST OF ATTCHMENTS STRUCTURALS DOCUMENT No. REV-0


GAIL (INDIA) LTD
0001-01-11-11-001 Page 2 of 2
NEW DELHI
Copyright GAIL – All rights reserved
STANDARDS & STANDARD SPECIFICATIONS

STANDARDS DRAWINGS (ARCHITECTURALS)

S.NO. DOCUMENT No. NO. OF REV. TITLE


PAGES
1 S-10-01-001 4 0 Abbreviations and Legends
0 Cable crossing under road (PVC
2 S-10-01-02 1
pipes)
3 S-10-01-003 1 0 Road curves and crossings
0 Standard section of storm water
4 S-10-01-004 1
ditches.
0 Pipe culvert for storm water
5 S-10-01-005 3
drainage
6 S-10-01-006 2 0 Box culvert type I, II, III & IV
0 Details of rungs for manholes,
7 S-10-01-007 1
valve pits, tanks etc.
8 S-10-01-008 1 0 Std. Misc. Details for manholes
0 Concrete bedding and
9 S-10-01-009 1
encasements for pipes.
10 S-10-01-010 1 0 Gully trap chamber
11 S-10-01-011 1 0 Inspection chamber
12 S-10-01-012 1 0 Septic tank (type-I, II & III)
13 S-10-01-013 1 0 Details of soak pit
14 S-10-01-014 1 0 Valve pit type-I for dia.  1.5”
0 Valve pit type-III for dia. 8” to
15 S-10-01-015 1
 16”
0 Chequered plate details (for
16 S-10-01-016 1 masonry valve pit type-I, II III
& IV)
0 Manholes type-I for depth  1m,
17 S-10-01-017 1
(  300mm)
18 S-10-01-018 1 0 Details of neutralization pit
0 Std. detail of chain link fencing
19 S-10-01-019 1
(with conc. post)
20 S-10-01-020 1 0 RCC pavement details.
0 Conc. Sliding sleeper cast-in-situ
21 S-10-01-021 1
Type-II
0 Conc. Sliding sleeper cast-in-situ
22 S-10-01-022 1
Type-III
23 S-10-01-023 1 0 Installation details of fire water

LIST OF ATTCHMENTS ARCHITECTURAL DOCUMENT No. REV-0


GAIL (INDIA) LTD
0001-01-09-11-001 Page 1 of 2
NEW DELHI
Copyright GAIL – All rights reserved
hydrants, water monitor and
foam/water monitor
Installation details of water
24 S-10-01-024 1 0
monitor
25 S-10-01-025 1 0 Upflow Anaerobic filter
26 S-10-01-026 1 0 Steel gate (for entrance)
Repeater Room at SV Station
27 S-10-01-027 1 0
(without DG Rm.), sheet 7/7

LIST OF ATTCHMENTS ARCHITECTURAL DOCUMENT No. REV-0


GAIL (INDIA) LTD
0001-01-09-11-001 Page 2 of 2
NEW DELHI
Copyright GAIL – All rights reserved
ENGINEERING DESIGN BASIS
(GENERAL CIVIL)

SPUR LINES OF CHAINSA JHAJJAR PIPE LINE

ENGINEERING DESIGN BASIS DOCUMENT No. REV-0


GAIL (INDIA) LTD (GENERAL CIVIL)
Page 1 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 CODES AND STANDARDS

3.0 OVERALL PLOT PLAN

4.0 FENCING

5.0 SITE GRADING

6.0 ROADS & PAVEMENTS AND SITE FINISH

7.0 STORM WATER DRAINAGE

8.0 PITCHING

9.0 WATER SUPPLY

10.0 SEWERS & DISPOSAL

11.0 CONTROL ROOM SAFETY

12.0 FIRE PROTECTION SYSTEM

ENGINEERING DESIGN BASIS DOCUMENT No. REV-0


GAIL (INDIA) LTD (GENERAL CIVIL)
Page 2 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
1.0 SCOPE

1.1 This document covers engineering design basis for General Civil works such as site
grading, fencing, roads, pavements, storm water drainage, water supply, waste collection
& disposal system for Despatch terminal (DT), Sectionalising Valve (SV) stations,
Intermediate Pigging stations (IP), Tap-off Points (TOP) etc.

2.0 CODES AND STANDARDS

2.1 Civil works & Roads: Indian Standards (IS) and Indian Road Congress (IRC) Codes

2.2 Water services: Manual on water supply and treatment (Published by Ministry of works
and housing, Delhi)

2.3 Sanitary collection: Manual on sewerage and services sewage treatment. Published by
Ministry of works and housing, Delhi)

2.4 OISD-STD-117 (Fire Protection Facilities for Petroleum Depots and Terminals and Pipeline
installations).
OISD-STD-118 (Layout for Oil and Gas Installation)
OISD - 163 (Process Control Room Safety) For Blast resistant Control room

2.5 IS Codes for Fire Fighting Equipments.

2.6 NFPA Codes for Clean Agent and CO2 system.

2.7 IS codes for various civil works.

3.0 OVERALL PLOT PLAN

3.1 The Overall Plot Plan shall be developed based on good engineering practice & meeting
requirement of statutory bodies.

3.2 Additionally the Overall Plot Plan shall also meet the requirement of OISD norms.

3.3 The various statutory approvals shall be obtained with the Owner’s assistance as and
when required.

4.0 FENCING

4.1 Protection of land acquisition limit.

ENGINEERING DESIGN BASIS DOCUMENT No. REV-0


GAIL (INDIA) LTD (GENERAL CIVIL)
Page 3 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
4.1.1 Intermediate Pipeline installation coming on route i.e. SV, IP, and TOP etc.

- 1.5m high chain link fencing with additional 0.5m high barbed wire fencing over 0.5m
high Brick masonry wall.

4.1.2 Receipt Terminal and Despatch Terminal

- 1.5m high chain link fencing (for installation within existing


- installation) over 0.5m high Brick masonry wall.
- 2m high chain link fencing with additional 0.5m high barbed wire
fencing (for isolated installation) over 0.5m high Brick masonry wall.

5.0 SITE GRADING

5.1 All the tree roots and vegetation shall be grubbed up minimum 150 mm and removed
from site.

5.2 The grading of the area shall be done by cutting and filling with the following:

a. Cutting area : Thoroughly rolled and compacted.

b. Filling area

- Other than Road: Compacted in layers not exceeding 30 cm. to achieve min.

- 90% of max. Dry density (conforming to Indian Standard (IS)-2720, Part-VII ).

- - For Roads: Compacted in layers not exceeding 20 cm. to achieve min. 90% of
max. Dry density (conforming to IS:2720, part-VIII and GAIL standard
specification no. 6-65-0018).

5.3 Plant Finished Grade Level (FGL):

5.3.1 New Site: To be kept 150 to 300mm above the nearby metalled road level and may
vary as per site requirement for new stations/locations.

5.3.2 Existing sites: To be maintained same as FGL for existing stations.

5.4 Slope in graded areas

5.4.1 General site grading : 1 in 500

ENGINEERING DESIGN BASIS DOCUMENT No. REV-0


GAIL (INDIA) LTD (GENERAL CIVIL)
Page 4 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
5.4.2 During micro grading after completion
of major construction (For road corridors) : 1 in 200

6.0 ROADS & PAVEMENTS AND SITE FINISH

6.1 ROADS

6.1.1 Road Width


Location Road width
i. Main Road and Access Road

a) All SV(s), IP(s) and TOP: 4.0 M wide bituminous road consisting of
3.0m wide carriage way and 0.5m wide shoulders on either side.

ii) Road inside Battery limit

a) All SV(s), IP(s) and TOP: 4.0m wide concrete road consisting of 3.0m wide
carriage way and 0.5m wide shoulders on either
side.
b) Receipt Terminal : 6.0 M wide concrete road consisting of 4.0m wide carriage
way and 1.0m wide shoulders on either side.

iii) Foot path : 1.0 M wide of PCC

6.1.2 Camber : 1 in 50 (From road crown to edge of road)

6.1.3 Radius of curve : 8m / 12m / 15m

6.1.4 i) Bituminous Roads : Road shall be designed based on CBR (California Bearing
Ratio) value of sub grade and msa for the proposed road as per IRC 37:2001

ii) Concrete Roads : Shall be designed as per IRC 58

6.1.5 Road finish : Bituminous carpet with seal coat / RCC

6.1.6 Finished road top level above FGL : 0.15 to 0.3 M

6.1.7 Road Gradient : 1 in 30 (in plain terrain)

: 1 in 20 (in hilly terrain)

6.2.0 PAVEMENTS

6.2.1 Material : Reinforced Cement Concrete (RCC)


ENGINEERING DESIGN BASIS DOCUMENT No. REV-0
GAIL (INDIA) LTD (GENERAL CIVIL)
Page 5 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
6.2.2 Pavement slope : 1 in 100

6.2.3 Type : Type-II( 150 mm thick RCC) as per GAIL Standard.

6.3.0 SITE FINISH

6.3.1 Site Finish shall be provided as follows:-

Site Finish Area

Concrete - Operating area & equipment area


Asphalt - Road
Approach to facilities - Footpath

7.0 STORM WATER DRAINAGE

7.1 Run off coefficient

Areas : Run-off coefficient

- Paved (Concrete)area : 1.0


- Bituminous : 0.9
- Compacted area : 0.7
- Open area : 0.4

7.2.0 Storm Water Drains

a. Type: Rectangular/trapezoidal type open drains.

b. Construction: Brick masonry with cement mortar

7.3.0 Culverts and Road Crossings

7.3.1 Pipe culverts: RCC pipes Class Non-pressure Class 3 (NP3) conforming to
IS:458 (if clear cover over pipe is less than 600mm from road top, pipe
shall be encased)

7.3.2 Box culverts : RCC construction

7.3.3 ERC/IRC crossings : Poly Vinyl Chloride (PVC) pipes Class 1 as per
IS:4985 class embedded in concrete. Minimum
pipe size 150 mm. (ERC/IRC - Electrical
ENGINEERING DESIGN BASIS DOCUMENT No. REV-0
GAIL (INDIA) LTD (GENERAL CIVIL)
Page 6 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
Instrumentation Road Crossing)

8.0 PITCHING

In filled up areas where level difference is more than 1.0m and upto 2.0mRR
masonry pitching shall be provided on slopes for protection of earth against erosion
and sliding all around station and approach road. The limit of pitching shall be within
fenced area.

8.1 Side Slope : 1 in 1.5 (1 vertical : 1.5 horizontal)

8.2 Construction : 300 thk. RR masonry pitching 1:6 cement mortars at


joints, flush pointing in 1:4 cement mortar

9.0 WATER SUPPLY

9.1.0 DRINKING WATER SYSTEM

(For Existing Terminal)

Drinking water system shall be extended by hooking up from existing drinking water
system for drinking and toilet needs. Toilet shall be served from 1 Cu.m HDPE
overhead water storage tank placed on top of the Control room / Sub-station
building.

9.1.1 Rate of water supply : 135 lpcd (litres/per capita/day).

9.1.2 Source - To be extended from the existing drinking water network

9.1.3 System- Under ground main ring with Galvanized Iron (G.I.) pipes and fittings
conforming to IS:1239 (Heavy).

9.1.4 Storage- Overhead HDPE water storage tank of Capacity 1.0 cu.m kept on individual
building as per IS:12701

9.2.0 Water System (un-manned stations, i.e. SV and IP and isolated installation)

No Toilet facility and water supply system is considered for these stations.

10.0 SEWERS & DISPOSAL

10.1.0 General

10.1.1 Oily water sewer is not envisaged for any of the pipeline installation.
ENGINEERING DESIGN BASIS DOCUMENT No. REV-0
GAIL (INDIA) LTD (GENERAL CIVIL)
Page 7 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
10.1.2 Acidic waste collected from battery room of control building shall be neutralized
by providing Neutralization Pit and neutralised water to be disposed in the nearest
open storm water drains.

10.1.3 For dry batteries no neutralisation pit is required because there is no acid leakage.

10.2.0 Types of Sewers and Disposal Method

10.2.1 Acidic and Alkali seer : Neutralization Pit (and neutralized water discharge to nearby
open drain).

10.2.2 Sanitary sewer: From individual toilet block disposal by means of providing septic
tank and soak pit combination or septic tank anaerobic upflow filter combination

10.3.0 Cover for sewer line

10.3.1 Minimum cover over sewer line shall be 600 mm

10.3.2 If cushion over sewer pipe is less than 1200mm under roads, sewer shall be
encased in cement concrete.

10.4.0 Manholes

10.4.1 Type and construction of manhole: Brick masonry

10.5.0 Material of Construction for sewers

10.5.1 Acidic and Alkali sewer: High Density Polyethylene (HDPE) as per IS: 4984

10.5.2 Manhole for acid / alkali sewer shall be provided with Acid/Alkali proof lining.

10.5.3 Sanitary sewer

a. Toilet block upto Inspection chamber:


Heavy cast iron (HCI) pipes as per IS: 1729

b. Gravity main & lateral:

RCC Pressure Class 1 (P1) as per IS: 458

11.0 CONTROL ROOM SAFETY

Control room shall be sized and designed meeting requirements of OISD-163


ENGINEERING DESIGN BASIS DOCUMENT No. REV-0
GAIL (INDIA) LTD (GENERAL CIVIL)
Page 8 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
(Process Control Room Safety)

12.0 FIRE PROTECTION SYSTEM

12.1 The Fire Protection facilities shall be provided meeting the minimum the
requirements of TAC for insurance purposes.

12.2 Additionally the requirements of OISD 117 as applicable shall be


provided.

12.3 Adequate number of capacity 4.5kg CO2 type and capacity 10kg dry chemical powder
portable extinguisher of capacity shall be provided at all Despatch Station, Receipt
Station, SV(s) and IP(s) stations as per IS:2190.

Despatch / Receipt Terminal

A) The Firewater network comprising of A93A class piping with hydrants and
monitors shall be provided by extending from the existing Firewater network
(if available).

B) Protection system inside control room shall be clean agent system.

SV & IP Stations and R

A) Carbon dioxide flooding system as per NFPA-12 shall be provided in new


control rooms of unmanned stations

ENGINEERING DESIGN BASIS DOCUMENT No. REV-0


GAIL (INDIA) LTD (GENERAL CIVIL)
Page 9 of 9
NEW DELHI 0001-01-10-03-001
Copyright GAIL – All rights reserved
GAIL (INDIA) LIMITED

SPECIFICATIONS OF
ARCHITECTURAL FINISHES
(ARCHITECTURE)

SPUR LINES OF CHAINSA JHAJJAR PIPELINE

SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0


GAIL (INDIA) LTD FINISHES
Page 1 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
1.0 SPECIFICATION OF ARCHITECTURAL FINISHES

1.1 GENERAL

1.1.1 For any aspect of item not covered in the document, the contractor shall follow
instructions of the engineer-in-charge and execute the work as per relevant I.S
codes/ recommendations of approved manufacturer/ good engineering practice
without any cost or time implication to owner.

1.1.2 All materials shall be of first quality conforming to the specifications & IS or
equivalent with IS marks and shall be obtained from the approved Manufacturer.
The Contractor shall get the materials approved by the Engineer - In - Charge
before ordering & procurement. The Contractor shall furnish necessary certificates
etc. as asked by the Engineer - In - Charge. Further to that he shall get the
materials tested from approved test house if asked by the Engineers - In - Charge &
submit the test certificate at his own cost for which no extra payment shall be made
to him. The Engineer - In - Charge shall have the right to reject all or any of the
materials intended to be used and such materials shall be immediately removed
from the site by the Contractor at his own cost without any claim for compensation
etc. due to such rejection.

1.1.3 Workmanship shall be to the satisfaction of the Engineer - In - Charge. The


contractor shall follow the specifications, relevant Codes & Manufacturer's guidelines
for achieving desired level of workmanship as per specification & good engineering
practice. Any executed work not conforming to the specification or not to the
satisfaction of the Engineer -In-Charge shall be rectified by the Contractor as
directed by the Engineer -In-Charge. No extra payment shall be made to the
Contractor for such rectification. The contractor shall use only first quality approved
material for all items.

1.1.4 All specifications of various finishing items include construction supervision; supply
of all materials, labours, tools, tackles, scaffoldings etc. and are applicable for all
heights, locations etc.

1.1.5 For specifications of construction water, sand, cement, bricks/ stone, aggregates etc.
reference shall be made to the Civil/ Structural specifications attached in the bid
document.

1.1.6 All specialised items of work (e.g. Aluminium Doors and Windows, Waterproofing,
Underdeck and Overdeck Insulation, Precoated roof sheeting/ cladding, False ceiling,
False Flooring, Partitioning and Panelling etc.) shall be got executed by the
Contractor only through authorised applicators/ sub contractors of approved
manufacturer/ vendor. The contractor shall submit list of such authorised
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 2 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
applicators/ sub contractors for approval before execution of such items.

1.2 FLOOR FINISHING

Reference shall be made to the following Indian Standards for any further
information etc. not covered in the specification. In case of any
conflict/contradiction, provision of specification shall override.

IS: 4971 Recommendations for selection of Industrial floor finishes.


IS: 2114 Code of practice for laying in situ terrazzo floor finish.
IS: 1237 Specification for Cement concrete flooring tiles.
IS: 777 Specification for glazed earthenware wall tiles.
IS: 2571 Code of practice for laying in situ cement concrete flooring.
IS: 4631 Code of practice for laying of epoxy resin floor toppings.
IS: 1443 Code of practice for laying and finishing of cement concrete floor tiles
IS: 5491 Code of practice for laying in situ granolithic concrete floor topping.
IS: 4441 Code of practice for use of silicate type Chemical resistant mortars.
IS: 4443 Code of practice for use of resin type chemical resistant mortar.
IS: 1196 Code of practice for laying Bitumen Mastic flooring.

1.2.1 Cement Concrete Flooring


Cement concrete flooring shall be laid in average 25mm thickness over sub base (as
per structural drawings/ specifications) and shall generally conform to IS:2571. The
flooring shall be laid in panels and shall consist of:-

(A) 25 mm thick base course of M-15 grade cement concrete (with 6mm and down size
stone aggregate) laid on the sub-base in panels (each panel not exceeding 1 Sq.
Mtr.in area) in desired shape and pattern. The panels shall be bound by 3x20mm
PVC/ Stainless Steel/5x20mm glass strips’ panel dividers; fixed in position with
their top at proper level maintaining the required levels, slopes, linearity etc. as
required. Base course shall be laid in alternate panels. Before laying the base
course, neat cement slurry @ 2.75Kg. of cement per Sq. Mtr. of area shall be
applied (brushed) over the prepared sub base surface. Cement concrete shall be
placed in position and beaten with trowel, including tamping and finishing smooth.
Finishing of the surface shall follow immediately after completion of laying of base.
The bed for flooring shall be prepared either level or sloped as per drawings and as
instructed by Engineer-in-charge.

(B) Neat cement @ 2.75Kg. per Sq. Mtr. mixed with water to form a thick slurry applied
over the base course (when the concrete is green), spread over the surface, pressed
twice by means of iron floats; once when the slurry is applied and second time when
the cement starts setting. The junction of floor with wall plaster, cladding, skirting
shall be rounded off uniformly upto a radius of 25mm unless otherwise mentioned.
Each finished portion of floor, on completion shall be kept wet with ponding for a
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 3 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
minimum period of 7 days.

1.2.2 Cement Concrete Granolithic Flooring


1.2.3 Cement concrete granolithic flooring shall be laid in overall 40mm/ 50mm
thickness over sub base (as per structural drawings/ specifications) and shall
generally conform to IS:5491 in workmanship. The flooring shall be laid in panels
and shall consist of :-

(A) 25mm/ 35mm thick base Course (Under layer) of M-15 grade Concrete (shall
generally conform to Civil structural specifications) laid over sub base in panels
(each panel not exceeding 1 Sq. Mtr.in area) in desired shape and pattern. The
panels shall be bound by 3x30/40mm PVC/ Stainless Steel/ 4x30/40mm
glass strips’ panel dividers; fixed in position with their top at proper level
maintaining the required levels, slopes, linearity etc. as required. Base course shall
be laid in alternate panels. Before laying the base course, neat cement slurry @
2.75Kg. of cement per Sq. Mtr. of area shall be applied (brushed) over the prepared
sub base surface. The borders of the panels shall have mitred joints at the corners
of the room and intermediate joints shall be in straight line with panel joints.
Cement concrete shall be placed in position and beaten with trowel and finished
smooth. Beating shall cease as soon as surface is found covered with cream of
mortar. Necessary slope shall be provided.

(B) 15mm thick Wearing top layer of cement mortar 1:3 (1 cement: 3 course sand by
volume) which shall be laid within 15 minutes of laying the first layer. The cement
and aggregates for the top layer shall be mixed dry. After mixing, sufficient quantity
of washed sand and water shall be added to make the mix plastic but not flowing.
The top and bottom layer shall firmly grip together. The base course shall be free of
excessive moisture before starting the floor finishing. Use of dry cement, cement
sand mixture sprinkled on the surface to stiffen the concrete or absorb excessive
moisture shall not be permitted.
(C) While the concrete is still green, cement @ 2.75 kg per Sq.M of floor area shall be
mixed with water to form a thick slurry and spread over the surface. It shall be
pressed twice by means of iron floats, once when the slurry is applied and second
time when the cement starts setting. The junction of floor with wall plaster,
cladding, skirting shall be rounded off uniformly upto a radius of 25mm unless
otherwise mentioned.

Each finished portion of floor, on completion shall be kept wet with ponding for a
minimum period of 7 days.

1.2.3 Heavy Duty Flooring


Heavy duty Cement concrete flooring shall be laid in overall 50mm thickness over sub
base (as per structural drawings/ specifications); shall generally conform to IS:5491
in workmanship. The flooring shall be laid in panels and shall consist of :-
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 4 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
(A) Base Course (Under layer) 35mm thick of cement concrete (1 cement : 1.5 coarse sand
: 3.5 stone aggregates of 10mm to 6mm size by volume) laid over sub base in panels
(each panel not exceeding 1 Sq. Mtr.in area) in desired shape and pattern. The panels
shall be bound by 3x40mm PVC/ Stainless Steel/ 4x40mm glass strips’ panel
dividers; fixed in position with their top at proper level maintaining the required levels,
slopes, linearity etc. as required. Base course shall be laid in alternate panels. Before
laying the base course, neat cement slurry @ 2.75Kg. of cement per Sq. Mtr. of area
shall be applied (brushed) over the prepared sub base surface. The borders of the
panels shall have mitred joints at the corners of the room and intermediate joints shall
be in straight line with panel joints. Cement concrete shall be placed in position and
beaten with trowel and finished smooth. Beating shall cease as soon as surface is found
covered with cream of mortar. Necessary slope shall be provided.

(B) Wearing Top layer/ Finishing layer shall be of cement, hardener and stone
aggregate mix of 15mm thickness laid over the base course. Unless otherwise
mentioned, one part of approved quality hardener and four parts of cement by weight
shall be mixed dry. This dry mixture shall be mixed with stone grit of 6mm and down
size in the ratio of 1 hardener and cement mixture : 2 stone grit by volume Just
enough water shall then be added to the mix.

The mixture so obtained shall then be laid on the base course within 2 to 4 hours of
latter's laying. It shall be firmly pressed into bottom concrete so as to have a good bond
with it. After the starting of initial setting, the surface shall be finished smooth and true
with steel floats.

Each finished portion of floor, on completion shall be kept wet with ponding for
minimum period of 7 days.

1.2.4 Cement Plaster Skirting


1.2.5 Cement plaster skirting shall be laid with cement mortar (1 cement:3 coarse sand by
volume) shall be of 6mm/ 12mm/ 18mm thickness. The surface on which the
skirting is to be applied shall be prepared and skirting shall be laid. The junction
between flooring and wall shall be rounded off to a radius of 25mm if not otherwise
mentioned.
While the mortar is still green, cement @ 2.75Kg per square metre shall be mixed with
water to form a thick slurry and applied over the mortar. It shall be pressed twice by
means of iron floats, once when the slurry is applied and second time when the cement
starts setting. The flooring shall be cured for 7 days.

1.2.6 Terrazzo Tiles Flooring

Terrazzo tiles Flooring shall be laid in minimum 40mm overall thickness over sub base
(as per structural drawings/ specifications); shall generally conform in all respects to IS-
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 5 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
1237. The tiles shall be precast hydraulically pressed (factory made) of minimum 22
mm thickness, made with 10mm down size stone aggregates, white & ordinary cement
mix (1 white cement : 6 ordinary cement by volume) and pigments conforming to
IS:2114. Table1. Pigments to be admixed with mortar or for grouting the joints shall
conform to Table -1 of IS: 2114. The tiles shall be laid on a bed of 18mm thick cement
mortar 1:4 (1 cement : 4 course sand by volume) for flooring and 1:3 (1 cement : 3
course sand by volume) for skirting (which shall normally be 125mm high unless
specified otherwise) .The base on which tiles are to be laid shall be cleaned of all dust,
dirt and properly wetted by applying neat cement slurry @ 2.75 kg. of cement per
Sq.M. of area without allowing water pools. The tiles shall be laid on a bed of 18mm
thick cement mortar 1:4 (1 cement : 4 course sand by volume) for flooring and 1:3 (1
cement : 3 course sand by volume) for skirting (which shall normally be 125mm high
unless specified otherwise) .The base on which tiles are to be laid shall be cleaned of all
dust, dirt and properly wetted by applying neat cement slurry @ 2.75 kg. of cement per
Sq.M. of area without allowing water pools. Cut tiles of uniform sizes shall be laid along
periphery, if necessary. Neat cement slurry @ 4.4 kg. of cement per Sq.M. shall be
spread over the mortar bed for laying 20 tiles at a time. The tiles shall then be fixed in
this grout one after the other, each tile being gently tapped and properly bedded in line
and level. The joints shall not exceed 1.5mm in width. After the day's work, the excess
cement slurry on top and the joints shall be cleaned with broom stick and washed
before the slurry sets hard. Next day, the joints shall be filled with the cement grout to
match the shade of the tile. Tiles along the periphery shall be continued by average 12
mm under the wall plaster, skirting or dado.

For skirting/ dado/ risers on the brick masonry wall, the joints shall be raked out to a
depth of at least 15mm while the masonry is being laid. In case of concrete work, the
surface shall be hauled and roughened with wire brushes. The wall surface shall be
uniformly and evenly covered with backing of cement mortar 1:3 (1 cement : 3 coarse
sand by volume) of minimum 12mm thickness. Before hardening of the cushioning
mortar, back of each tile shall be covered with a neat layer of cement slurry @ 4.4 kg of
cement per Sq.M. and edges with white cement with or without pigment to match the
shade of tiles and the tiles then shall be pressed on the backing and tapped.

The tiles shall be corrected to proper planes with joints truly vertical in required pattern
and butt jointed. The fixing shall be done from bottom upward. The top of skirting and
dado shall be truly horizontal.

Grinding shall be commenced after the joints are properly set. Grinding shall be done by
machines except for skirting and small areas. First grinding shall be done with
Carborundum stones of 48 to 60 grade grit fitted in the machine. Water shall be
properly used during grinding. When the chips show up and the floor has been
uniformly rubbed, it shall be cleaned with water baring all pin holes. It shall then be
covered with a thin coat of grey/white cement mixed with pigments to match with
colour of the flooring. This grout shall be kept moist for a week. Thereafter the second
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 6 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
grinding shall be started with Carborundum stone of 120 grit. Grinding and curing shall
follow again. Final grinding shall be with Carborundum of grade 220 to 350 grit using
water in abundance. The floor shall be washed clean with water, oxalic acid powder
shall then be dusted at 35 gms/sq. m. on the surface rubbed with machine fitted
hessian bobs or rubbed hard with woolen rags. The floor shall then be washed clean
and dried with a soft cloth or linen. If any tile is disturbed or damaged, it shall be
refitted or replaced and properly jointed and polished.

1.2.6 Tile Work (Glazed/ Ceramic)

Glazed vitreous tiles shall conform to IS: 777. Ceramic tiles for flooring shall be matt
finished and non slip type. All tiles shall be decorative type of approved shade, pattern,
texture and design and of approved manufacturer. . The sizes of the ceramic tiles shall
generally be 300x300x8mm for flooring and 100x200x6mm or 300x200x6mm for walls
(dado). Pigments to be admixed with mortar for grouting the joints shall conform to
Table -1 of IS: 2114. The tiles shall be laid over a coating of approved neoprene based
adhesive (as per manufacturer’s specification) laid on base floor/ wall plaster. The joints
of the tiles shall be flush pointed with cement paste (white cement and pigment
conforming to IS:2114, Table-l) matching the shade of colours. The tile work shall be
suitably cured.

1.2.7 Acid Resistant Tiles Flooring


The tiles shall be vitrified ceramic tiles of approved size as per approved manufacturer’s
specification and shall be homogeneous having following properties :-
S.No. Property Values Norms
1 Water Absorptions ±0.5% ASTM C 373
2 Scratch Resistance > 6 ASTM C 373
3 Chemical Resistance Unaffected ASTM C 650
4 Abrasion Resistance > 100 ASTM C 501
5 Breaking strength 1400 kg/sq.cm ASTM C 648
6 Density > 2.0 Gm/CC

The base course for flooring shall be Cement Concrete flooring/ Cement Concrete
granolithic flooring and for skirting/ dado it shall be Cement plaster and background
surface shall be prepared as per clause no. 5.2 and IS:4443.
Tiles shall be fixed on the prepared surface over a bitumen priming layer, bitumen
mastic layer and resin type chemical resistant mortar. The bitumen shall conform to
IS:702 and laying of bitumen mastic shall conform to 1S:1196.
Joints shall be allowed to set for 24 hours. The floor shall then be washed as per
manufacturer's specifications to totally remove all marks from tile surface.

1.2.7 Decorative vitrified porcelain flooring

1.2.8 The tiles shall be vitrified porcelain tiles , mirror polished ,of approved size as per
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 7 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
approved manufacturer’s specification and shall be homogeneous having properties
similar to vitrified ceramic acid resistant tiles. The fixing of tiles shall be similar to
ceramic tiles.

1.2.9 Kota Stone Finish

Kota Stone Flooring shall be laid in minimum 40mm overall thickness over sub base (as
per structural drawings/ specifications). The Kota Stone slabs shall be of selected
quality and shade, hard, sound, dense, homogenous in texture, free from cracks, decay,
weathering and flakes. These shall be machine cut to the requisite size and thickness
and chisel dressed. For flooring and skirting/ dado/ riser the thickness of the stone slabs
shall be 25mm and 18mm respectively. Skirting shall normally be 125mm high unless
specified otherwise.

The slabs shall have smooth top (exposed) face before being laid. Before starting the
work, the contractor shall get the samples of slabs approved by Engineer-in-charge.
Each slab shall be machine cut to the required size and shape and fine chisel dressed at
all edges to full depth and machine rubbed to a smooth surface finish. All angles and
edges of the slabs shall be true square and free from chippings giving a plane and
smooth surface.

Preparation of base shall include making it rough, cleaning thoroughly and applying
neat cement slurry @ 2.75 kg of cement per Sq.M. of area to receive the mortar.
Cement mortar shall be 15mm thick !:6 (1 cement: 6 Coarse sand by volume) for
flooring and 12mm thick 1:3 (1 cement: 6 Coarse sand by volume) for skirting. The
mortar shall be laid for fixing one slab at a time. The slab shall be washed clean before
laying. It shall be laid over cement mortar bedding on top, pressed, tapped gently to
bring it in level. It shall be then lifted and laid aside. Top surface of the mortar then
shall be corrected by adding fresh mortar at hollows and depressions. The mortar then
shall be allowed to harden and cement slurry of honey like consistency @ 4.4.kg of
cement per Sq. M shall be spread over the mortar. The edges of the slabs shall be
buttered with white cement (with necessary pigment) grout to match the shade of the
slabs. The slabs shall then be gently placed in position and tapped with wooden mallets
till it is properly bedded in level. The joints shall be as fine as possible. Surplus cement
on the surface of the slab shall be removed. The slabs in flooring shall continue for not
less than 10 mm under the plaster/skirting. The finished surface shall be true to levels
and slopes as instructed by the Engineer-in-Charge. The slabs shall be laid in patterns
as per drawings and size shall not be less than 400 x 275mm, which shall be uniform.
Cut size may be used along periphery as required. Curing, as required shall be done.

Preparation of base shall include making it rough, cleaning thoroughly and applying
neat cement slurry @ 2.75 kg of cement per Sq.M. of area to receive the mortar.
Cement mortar shall be 15mm thick !:6 (1 cement: 6 Coarse sand by volume) for
flooring and 12mm thick 1:3 (1 cement: 6 Coarse sand by volume) for skirting. The
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 8 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
mortar shall be laid for fixing one slab at a time. The slab shall be washed clean before
laying. It shall be laid over cement mortar bedding on top, pressed, tapped gently to
bring it in level. It shall be then lifted and laid aside. Top surface of the mortar then
shall be corrected by adding fresh mortar at hollows and depressions. The mortar then
shall be allowed to harden and cement slurry of honey like consistency @ 4.4.kg of
cement per Sq. M shall be spread over the mortar. The edges of the slabs shall be
buttered with white cement (with necessary pigment) grout to match the shade of the
slabs. The slabs shall then be gently placed in position and tapped with wooden mallets
till it is properly bedded in level. The joints shall be as fine as possible. Surplus cement
on the surface of the slab shall be removed. The slabs in flooring shall continue for not
less than 10 mm under the plaster/skirting. The finished surface shall be true to levels
and slopes as instructed by the Engineer-in-Charge. The slabs shall be laid in patterns
as per drawings and size shall not be less than 400 x 275mm, which shall be uniform.
Cut size may be used along periphery as required. Curing, as required shall be done.
This grout shall be kept moist for a week. Thereafter the second grinding shall be
started with Carborundum stone of 120 grit. Grinding and curing shall follow again.
Final grinding shall be with Carborundum of grade 220 to 350 grit using water in
abundance. The floor shall be washed clean with water, oxalic acid powder shall then
be dusted at 35 gms/sq. m. on the surface rubbed with machine fitted hessian bobs or
rubbed hard with woollen rags. The floor shall then be washed clean and dried with a
soft cloth or linen. If any stone slab is disturbed or damaged, it shall be refitted or
replaced and properly jointed and polished.

1.3 DOORS AND WINDOWS

Reference shall be made to the following Indian Standards for further information etc.
not covered in the specification. In case of any conflict/contradiction the provisions of
the specification shall override.

IS 6248 : Specifications for metal rolling shutters and rolling grill.


IS 1081 : Code of practice for fixing and glazing of metal (steel and Aluminium)
doors, windows and ventilators.
IS 4351 : Specifications for steel door frames.
IS 1948 : Specifications for Aluminum doors, windows & ventilators.
IS 1361 : Specifications for steel windows for Industrial buildings.
IS 1038 : Specifications for steel doors, windows and ventilators.
IS 7452 : Specification for hot rolled steel sections for doors, windows
and ventilators.
IS 2835 : Flat transparent sheet glass.
IS 2553 : Safety glass.

1.3.1 Aluminum Glazed Doors, Windows And Ventilators


Aluminium glazed doors/ windows/ ventilators shall be made of extruded tubular
anodised ( 25 microns )/ electrostatically powder coated (min. 30
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 9 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
microns) Aluminium sections conforming to IS : 733 and IS : 1285 of “INDAL“ or
approved equivalent manufacturer with 5.5mm thick transparent sheet glass
conforming to IS : 2835 ( wt. : 7.2Kg/ Sq.M ) / 6.3 mm laminated safety
glass conforming to I.S.: 2553 fixed with rubber lining or EPDM gasket and
extruded anodised aluminum beading. Extruded aluminium sections used for various
application shall have minimum weights as under.

A. Doors
1. For fixed frames
I) Sides & Top members : 1.975 Kg/RM
ii) Lock rail : 1.594 Kg/RM
iii) Bottom rail : 3.495 Kg/RM
2. For shutter frame : 1.202 Kg/RM
3. Glazing clips ( beading ) : 0.182 Kg/RM

B. Window/Ventilator ]

1. For fixed frames : 0.639 Kg/RM


2. For shutter frame : 0.636 Kg/RM
3. Glazing clips ( beading ) : 0.165 Kg/RM
4. Coupling bars : 0.933 Kg/RM
5. Member for fixing the frame : 0.463 Kg/RM

The frames shall be fixed to masonry by means of Aluminum lugs fixed to the frame
by counter sunk brass machine screws and grouted with M-15 grade concrete in
minimum150 x 150 x 50 mm sized hole in the masonry. In case of RCC, the frames
shall be fixed with 12mm dia dash fasteners in case of concrete. Any steel item
coming in contact with Aluminum shall be galvanized.

Aluminum glazed doors shall be provided with cup pivots ( of aluminum alloy
conforming to IS designation NS-4 of IS 737 and IS designation of A-5-M of IS :
617) riveted to outer and inner frames to permit to swing through an angle of 85
degree.
Following hardware shall be provided for the doors.

1. Heavy duty & hydraulically operated double or single action adjustable door
closer conforming to IS : 6315

2. 250mm and 150mm long, 10mm dia Aluminum tower bolts as per IS : 204
one each for each shutter.

3. Brass body 6 lever mortice lock as per IS : 2209

4. Aluminum door handle for each shutter for each side.


SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 10 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
(Note : All Aluminium fittings/ fixtures shall be of same finish as that of door frame
& shutter)

Side hung window shutters shall be fixed to the frame with Aluminum alloy friction
hinges and shall be complete in all respects including accessories, fittings fixtures of
same finish as that of window frame & shutter, handles of cast aluminum
conforming to IS designation A-5-M of IS : 617 mounted on a handle plate riveted to
opening frames, Aluminum Tower ,bolts, peg stays for ventilators etc. Wherever
specified, decorative aluminium safety grills of approved design shall be provided
which shall be screwed to the main frame.

1.3.2 Steel Doors


Steel doors shall consist of :

(A) Pressed steel door frame of overall 125x 65mm size conforming to IS : 4351 and
made of 16 SWG pressed steel sheet bent to required shape using bending machine
to form solid/ true mitred edges/ corners, stiffened with 50 x 5mm thick MS flat
spacers welded to the frame facing the wall/ column @ 600mm c/c maximum
vertical spacing. The frame shall be fixed to the masonry by means of 300 x 25 x 6
mm thick MS hold fast welded to the spacer and grouted with M-15 concrete in
minimum 350 x 100 x 100 mm sized hole in the masonry. In case of concrete, the
frames shall be fixed by 96mm long, 12 mm dia metallic counter sunk type dash
fasteners through the frame & spacers. Provision for hinges, locking arrangement
and other hardware shall be provided in the frame by machine cutting of required
size cutouts in the frame and welding/ screwing to 3 mm thick MS pad plates
already welded over the cutout from behind. The frame shall be thoroughly cleaned
of rust, mill scale, dirt, oil etc. and then finished with 2 or more coats of
approved quality synthetic enamel paint of approved shade over a priming
coat of approved red oxide zinc chromate primer/ approved shade
electrostatically powder coated (minimum 30 microns). The hollow frame
shall be packed with PCC to fill the cavity without gap.

(B) Pressed steel door shutter shall be made with 18 gauge steel sheets formed by
machine bending in the form of hollow box ( overall 40mm thick ) welded at
meeting of the sheets with pad plate of 3mm thick MS flat all along the perimeter.
The shutter shall be braced with channel shaped 35mm wide horizontal stiffeners by
folding 16 gauge MS sheets @ 500mm c/c fixed by flush riveting. 3mm thick MS pad
plates shall be welded inside at required locations for fixing of hardware. The cavity
inside shall be packed with rigid PU foam/ phenolic foam or glass wool insulation to
fill into the box cavity without gap.

For double shutters, an MS angle ( 25x 45x 3mm thick ) shall be welded to one of
the shutter providing a minimum 25mm wide rebate for the other shutter at the
meeting point.
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 11 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
The shutters shall be fixed to the door frame by means of heavy duty MS butt
hinges of 150mm size conforming to IS : 1341 @ 500mm c/c maximum.
Each door shutter shall have following accessories.

1. Spring loaded pressure die cast zinc alloy door stopper.

2. Heavy duty, MS aldrop 400mm long for double shutter & 300mm long for single
shutter.

3. 12mm dia, 300mm long pressure die cast zinc alloy handles on both sides.

4. 12mm dia, 250mm long MS tower bolt at top and 12 mm dia 150mm long at
bottom.

5. 3- way spring loaded locking & latching system.

6. 150mm x 300mm Vision panel with 16 gauge MS beading bent to “ Z” shape &
4mm thick plain glass conforming to IS : 2853.

The entire shutter including all accessories, fittings & fixtures etc. shall be painted
with 2 or more coats of approved quality synthetic enamel paint of
approved shade over a coat of approved quality red oxide zinc chromate
primer/ approved shade electrostatically powder coated (minimum 30
microns)

1.3.3 Wooden Flush Doors

Flush doors shall consist of:-

(A) Pressed steel door frame of overall 125x 65mm size conforming to IS : 4351 and
made of 16 SWG pressed steel sheet bent to required shape using bending
machine to form solid/ true mitred edges/ corners, stiffened with 50 x 5mm thick
MS flat spacers welded to the frame facing the wall/column @ 600mm c/c
maximum vertical spacing. The frame shall be fixed to the masonry by means of
300 x 25 x 6 mm thick MS hold fast welded to the spacer and grouted with M-15
concrete in minimum 350 x 100 x 100 mm sized hole in the masonry. In case of
concrete, the frames shall be fixed by 96mm long, 12 mm dia metallic counter
sunk type dash fasteners through the frame & spacers. Provision for hinges,
locking arrangement and other hardware shall be provided in the frame by
machine cutting of required size cutouts in the frame and welding/ screwing to 3
mm thick MS pad plates already welded over the cutout from behind. The frame
shall be thoroughly cleaned of rust, mill scale, dirt, oil etc. and then finished with
2 or more coats of approved quality synthetic enamel paint of approved
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 12 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
shade over a priming coat of approved red oxide zinc chromate primer/
approved shade electrostatically powder coated (minimum 30 microns).

The hollow frame shall be packed with PCC to fill the cavity without gap.

(B) Flush door shutters shall be factory made and overall 35mm thick consisting of
solid core block board bonded with phenol formaldehyde synthetic resin
conforming to IS : 848. The shutters shall be faced on both sides with 3 mm thick
commercial plywood or teak veneering conforming to IS : 303, BS : 476 part-7.
35 x 20mm second class Teakwood lipping shall be provided all around the
shutter by means of approved quality neoprene based adhesive and nailing @
300mm (maximum). ). Commercial plywood along with the lipping shall be
painted with 2 or more coats of approved quality & shade synthetic enamel paint
over a coat of approved primer. Teakwood veneering along with lipping shall be
French polished. The shutters shall be fixed to the frame by means of 125mm
long MS butt hinges conforming to IS : 1341 @ 600mm c/c maximum
.
Teakwood used for lipping, beading etc. shall be second class Indian teakwood
(conforming to IS: 4021) of good quality, well seasoned and free from defects such
as cracks, dead knots, sapwood etc. and shall be with no individual hard & sound
knots more than 15 Sq.CM in area and the aggregate area of such knots not
exceeding 2% of area of the piece. The wood shall be fairly closed grains having not
less than 2 growth rings per Cm. Width in cross section.

Following hardware of approved quality and shade shall be provided in each shutter:-

1. Heavy duty, overhead hydraulically operated door closer conforming to IS : 3564.

2 . Anodised aluminum tower bolts as per IS : 204, 10mm dia 250mm long (at top)
and 150mm long (at bottom), one each for each shutter on either side.

3. Brass body 6 lever mortice lock as per IS : 2209 including pair of handles of
pressure die cast zinc alloy (satin finished )
4. 3mm thick plastic kick/push plate (150mm high at bottom for entire width &
200mm x 100mm at handle location).

5. Zinc alloy pressure die cast chromium plated spring loaded door stopper with
heavy duty rubber shoes.

6. 150mm x 300mm Vision panel with of 4mm thick plain glass conforming to IS : 2853
fixed with second class Teakwood beading (not for toilet doors).

1.3.4 Steel Windows

SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0


GAIL (INDIA) LTD FINISHES
Page 13 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
Steel windows, ventilators shall in general conform to IS:1081/ IS:1038 and IS:7452.
Rolled steel sections for the fabrication of steel windows, ventilators shall conform to
IS:7452. Glass panels for glazing purpose shall be 4mm thick (wt. 7.2 kg/ Sq.M)/
5.5mm thick transparent sheet glass conforming to IS: 2835/ 5.5mm thick
wired glass conforming to IS:5437/ 5.5mm thick toughened glass conforming
to IS:5437.The profile and type of windows, ventilators (glazed, partly glazed/
1ouvred, side hung/ top hung/ fixed shutter, composite) shall be as per approved
drawings.

The frames shall be constructed of sections cut to size and mitred. Corners shall be
welded to form a fused welded joint. Process of welding shall be flash butt welding. The
welded joints shall be grinded to square and flat edges. Where larger units are to be
formed by coupling individual units, the mullions, transoms shall be bedded in mastic to
ensure weather tightness.

Mastic shall be applied liberally to the channels of the outside frame sections before
assembly, and the two units being coupled shall be drawn together tight with clamps,
the mastic being squeezed out and cut off neatly when the units shall be screwed
together tight. Where fixed glazing units are placed over openable units a push fit
weather bar shall be provided. Before glazing, all opening parts shall be checked for
their operational smoothness. The frame shall be completely cleaned and bedding putty
shall be placed in the rebate before glazing. Glass then shall be cushioned into the
bedding and shall be fronted with front putty in a manner so as to enable the painting
to be done upto the sight line. The back putty oozing out over the glazing rebate
shall be cut off square and smoothed down. For panels exceeding 600 x 300 mm in
size, glass shall be secured by special glazing clips inserted in holes already
provided in the steel sections, before applying the front putty.

For glazing of very large areas, rust proof steel beading with mitred corners shall be
provided with screws @ 10 cm. from each corner and @ 20 cm. apart from each other.
Putty shall be provided to the face of the bead in contact with glass, in addition to back
putty. Side hung shutters shall be connected to the frame by means of friction hinges.
The handle for side hung shutters shall be of pressed brass mounted on a steel
handle plate welded to the opening shutter frame and shall not be removable easily
after glazing. The handle shall have a two point nose which shall engage with a brass
striking plate on the fixed frame in a slightly open as well as in a fixed position. In case
of fixing with masonry, holes for fixing the lugs/hold fasts shall be cut at required
locations. In case of concrete or stone, the frames shall be fixed by means of dash
fasteners. In case of masonry, the lugs shall be grouted in the holes with cement
concrete, M-15 Grade when fixing to steel work, mastic shall be applied to the sill of the
opening and the unit shall be placed on it with the jambs and head buttered with mastic
and the unit shall be fixed with special fixing dips or with nuts and bolts. All the steel
surfaces shall be thoroughly cleaned free of rust, mill scale, dirt, oil etc. by sand and
shot blasting and then painted with 2 or more coats of approved quality & shade
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 14 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
synthetic enamel paint over a coat of approved quality red oxide zinc chromate
primer.

1.3.5.1 Steel Rolling Shutter

MS rolling shutters shall conform to IS : 6248 and shall be constructed with interlocking
lath sections formed out of cold rolled 0.9mm thick, 80mm wide steel strips for shutter
width upto 3.5 M , or 1.25mm thick, 80mm wide steel strips for shutter width beyond
3.5 M, jointless MS channel section of 3.15mm thickness for guide, MS girders & bottom
rail, shutter suspension stud with pully & cage, top rolling springs, locking arrangement
etc. all complete as per manufacturer’s approved drawings. The entire shutter including
all accessories shall be painted with 2 or more coats of approved quality & shade
synthetic enamel paint over a coat of approved quality red oxide zinc chromate primer.
All the damaged surfaces of wall, columns, plastering etc. shall be made good.

Rolling shutters shall be mechanically operated type, when the size of the shutter
exceeds 9 Sq.M and shall be complete with all accessories for mechanical operation as
per approved manufacturer’s design & drawings. Wherever specified the Rolling
shutters shall be electrically operated; complete with all accessories, electrical motor,
cabling etc. as per approved manufacturer’s design and drawings

Wherever specified the Rolling shutters shall be grill type or partly grill & partly solid
type or fully solid type depending on ventilation requirement.

1.4. PLASTERING

1.4.1 Plain Cement Plaster

Plain Cement plaster shall be provided in following thicknesses :

A. 12mm thick in 1:6 cement mortar for all plumb of the internal masonry walls & RCC
Columns coming in line (flush) with this side of wall.

B. 15mm thick in 1:6 cement mortar for rough side of internal masonry walls RCC Columns
coming in line (flush) with this side of wall.

C. 18mm thick cement plaster in 1:6 cement mortar for all external surfaces as indicated.
Wherever specified, the external plastering shall be with waterproof compound (cement
mortar mixed with approved acrylic waterproof compound @ 1 Kg. per 50 Kg. of
cement).

D. 6mm thick in 1:4 cement mortar for all RCC ceiling, beam etc. However if the undulation
in ceiling is beyond 6mm thick plaster, extra thickness of plaster shall be applied
without any extra cost to give a smooth and fair surface to the satisfaction of Engineer-
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 15 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
In-Charge.

The plastering work shall include preparation of background surface which shall consist
of cleaning of all dust, loose mortar droppings, traces of algae, efflorescence or any
other foreign matter by water or by brushing, roughening up of smooth surfaces by
wire brushing or hacking, trimming of projections whenever necessary. The surface
shall be washed off and well wetted before applying the plaster. The plaster shall be
kept wet for a period of 7 days. During this period the plaster shall be suitably
protected from all damages at the contractor's expense by such means as approved by
the Engineer-in-charge. The date of execution of plastering shall be marked on the
plastering to ensure the proper duration of curing. The plastering shall include all
scaffolding, damage rectification etc. complete.

1.4.2 Sand Face Plaster

1.4.3 Sand face plaster shall consist of 13mm thick 1:4 cement mortar ( 1 cement : 4 coarse
sand by volume ) underlayer and top layer of 7mm thick 1:2 cement mortar ( 1 cement
: 2 coarse sand by volume )
Preparation of background surface, workmanship, curing etc. shall be same as plain
cement plaster.
The first layer shall be started from top floor and carried downwards. Before the first
layer hardens, surface of it shall be roughened up by edges of wooden tapers and close
dents shall be made on the surface. The subsequent layer shall be applied over the first
layer after the first layer has been allowed to set for 3-5 days depending on weather
conditions. The surface shall not be allowed to dry during this period.
All the brick/stone masonry and RCC joints shall be provided with 20 gauge chicken
wire mesh stretched tight and fixed with G.I. “U” type nails before plastering.20mm x
10mm grooves ( horizontal/ vertical ) shall be provided in perfect straight line & plumb
in plastering as per drawings and instructions of Engineer- In - Charge.

Curing shall be started 24 hours after finishing the plaster. The plaster shall be kept
wet for a period of 7 days. During this period the plaster shall be suitably protected
from all damages at the contractor's expense by such means as approved by the
Engineer-in-charge. The date of execution of plastering shall be marked on the
plastering to ensure the proper duration of curing.

The plastering shall include all scaffolding, damage rectification etc. complete.

1.5 ROOF TREATMENT/ WATERPROOF COATING

1.5.1 Polyurethane (PU) Based Waterproofing


The PU based roof treatment/ waterproofing-cum-terracing shall consist of:-

SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0


GAIL (INDIA) LTD FINISHES
Page 16 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
(A) The preparation of the surface shall include thorough cleaning of roof surface with a
wire brush and removal of all foreign matter etc. Well defined cracks on the surface
shall be cut to "V" section, cleaned and filled up with a paste of Polyurethane based
crack filling compound and white cement in a ratio of 1:2.
(B) Application of one component urethane prepolymers based elestomeric membrane
with Iso-cyanurate for rendering flame resistant characteristic.
The coating shall have physical features like high resistance to impact, abrasion and
cracking, superior tensile strength (8 Kg/ Sq.Cm after 4 weeks at ambient
temperature) and perfectly smooth, dust free glossy finish retained at least upto 3
years. It should also be resistant to acid, alkalies and have a very low water
absorption rate (0.5 % maximum at ambient temperature after 7 days).

The one component system shall be in two or more coats of urethane based high solid
content elastomeric membrane (having high viscosity to give a high build film) at
approx. coverage of 0.5 kg per sq.m each coat. Before the membrane coatings a coat
of urethane primer EMP at a coverage of 8 Sq.M per litre by brush shall be applied to
achieve overall thickness of 1.5 mm (+ or -15%) as per ASTM C-836/898. Membrane
coatings shall be applied after the priming coat is cured to a slightly tacky film (in 2-4
hours) but not later than 48 hours. If delay exceeds this, a fresh coat of urethane
primer shall be applied. The second membrane coating shall be applied within 24
hours after the first coating becomes touch dry in 12 to 48 hours (in some conditions
this might be delayed) of its application. Subsequent membrane coating, if required
shall be applied similarly. Both primer and PU coatings shall be continued to be
applied over parapet wall upto 150mm.

The PU coating shall be continued up the parapets/walls for a minimum of 150mm


over the finished roof surface. It shall be continued into rain water pipes by at least
100mm.
The final coat of PU when tacky shall be sprinkled with 300 micron layer of clean
sand.

(C) Plain Cement Concrete screed laid to slope of 1:100 ( Steeper slopes shall be
adopted for high rain fall regions) in 1:3:6 concrete mix. Minimum thickness of
screed shall be

30mm at rain water outlet points. Screed shall be laid only after all the PU
coatings are laid and fully cured and checked for the water tightness.
(D) Finishing protective layer of 25 mm thk. P.C.C.(1:2:4) in panels of maximum
size 1200mm x 1200mm chequered finish with 24 SWG chicken wiremesh
interposed in between finished smooth. The joints between panels shall be
sealed with suitable urethane based elastomeric compound as per
manufacturer’s specifications.
(E) Fillets of 75 mm radius with P.C.C. (1:2:4) at junctions of horizontal and
vertical surfaces shall be provided and finished smooth.
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 17 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
(F) 450mm x 450mm khuras (rain water collecting pits) in 1:2:4 cement concrete
at all outlets, levelled down by min. 25mm, finishing, curing etc. all complete.

(Note: The Contractor shall furnish 10 years performance guarantee for waterproofing.)

1.5.2 Polyurethane (PU) Based Overdeck Insulation with Waterproofing


This shall consist of:-

(A) The preparation of the surface which shall include thorough cleaning of roof
surface with a wire brush and removal of all foreign matter etc. Well defined
cracks on the surface shall be cut to "V" section, cleaned and filled up with a
paste of 2 component Polyurethane based crack filling compound and white
cement in a ratio of 1:2.

(B) Application of a coat of urethane primer EMP at a coverage of 8 Sq.M per


litre by brush.

(C) 50mm thick rigid polyurethane foam of density 40-45 Kg./ Cu. M. and
thermal conductivity of 0.019 K cal/ M/ Hr/ C shall be sprayed over entire
fully prepared R.C.C. slab as per approved manufacturer’s specifications.

(D) One component urethane prepolymers based elastomeric membrane having


physical features like high resistance to impact, abrasion and cracking,
superior tensile strength (8 Kg/ Sq.Cm after 4 weeks at ambient temperature)
and perfectly smooth, dust free glossy finish retained at least upto 3 years. It
should also be resistant to acid, alkalies and have a very low water absorption
rate (0.5 % maximum at ambient temperature after 7 days). The one
component system shall be in two or more coats of urethane based high solid
content elastomeric membrane (having high viscosity to give a high build
film) at approx. coverage of 0.5 kg per Sq.M each coat. coatings to achieve
overall thickness (Primer + Membrane coatings) of 1.5 mm (+ or - 15%) as
per ASTM C-836/898. Membrane coatings shall be applied after the priming
coat is cured to a slightly tacky film (in 2-4 hours) but not later than 48
hours. If delay exceeds this, a fresh coat of urethane primer shall be applied.
The second membrane coating shall be applied within 24 hours after the first
coating becomes touch dry in 12 to 48 hours (in some conditions this might
be delayed) of its application. Subsequent membrane coating, if required
shall be

applied similarly. Both primer and PU coatings shall be continued to be


applied over parapet wall upto 150mm. Each coat shall be allowed to dry
for minimum 12 hours before applying next coat. Care shall be taken for
quick application after mixing the 2 pack primer in view of short pot life of the
mix and shall be fully consumed within the stipulated period as per
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 18 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
Manufacturer's specification (maximum 60 minutes at 30 deg.C) The PU
coating shall be continued up the parapets/walls for a minimum of 150mm
over the finished roof surface. It shall be continued into rain water pipes by
at least 100mm. The final coat of PU when tacky shall be sprinkled with 300
micron layer of clean sand.

(E) Plain Cement Concrete screed laid to slope of 1:100 ( Steeper slopes shall be
adopted for high rain fall regions) in 1:3:6 concrete mix. Minimum thickness
of screed shall be 30mm at rain water outlet points. Screed shall be laid only
after all the PU coatings are laid and fully cured and checked for the water
tightness.
(F) Finishing protective layer of 25 mm thk. P.C.C.(1:2:4) in panels of maximum
size 1200mm x 1200mm chequered finish with 24 SWG chicken wiremesh
interposed in between finished smooth. The joints between panels shall be
sealed with suitable urethane based elastomeric compound as per
manufacturer’s specifications.
(G) Fillets of 75 mm radius with P.C.C. (1:2:4) at junctions of horizontal and
vertical surfaces shall be provided and finished smooth.
(H) 450mm x 450mm khuras (rain water collecting pits) in 1:2:4 cement concrete
at all outlets, levelled down by min. 25mm, finishing, curing etc. all
complete.

(Note: The Contractor shall furnish 10 years performance guarantee for overdeck
Insulation and waterproofing.)

1.5.3 APP Bituminous membrane Water proofing


Material:
The water proofing membrane shall have a non-woven polyester membrane coated
on both side with APP (Atactic polypropylene) modified bitumen. It shall have a Black
finish with a very thin polyethylene foil on both sides It shall be in rolls of 1x10m for
continuous laying on large lengths. When installed, it shall form an impervious,
flexible blanket, which accepts normal structural movement without breaking or
cracking.
Workmanship:
a) Preparation of surface:
The roof surface (or screed) shall be thoroughly cleaned with a wire brush and
all foreign matter etc. shall be removed. Well-defined cracks on the surfaces shall
be cut to a ‘V’ section, cleaned and filled up flush with a paste of filling
compound and cement in the ratio of 1:2. The finished surface shall be perfectly
dry and any dampness should be allowed to evaporate.
b) Laying:

SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0


GAIL (INDIA) LTD FINISHES
Page 19 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
The membrane shall be laid on the perfectly dry prepared surface by torching-on
method with a gas torch. All joints shall have an overlap of 75mm which shall be
torch sealed. The overlap shall be done in a manner, which does not hinder
water flow along the roof slope. The membrane shall be finished with bituminous
base aluminium paint.
The waterproofing shall be continued up to the parapet/wall for a minimum of
600mm over the finished roof surface. It shall be continued into rain water pipes
by at least 100mm.
c) Cement Screed:
Plain cement concrete (1:2:4) of 25mm min. thickness with 24 SWG chicken wire
mesh shall be laid to slope in panels not exceeding 6 m.sq. area per panel over
the roof slab. The joints between panels shall be raked out neatly (after
stipulated curing period) to a min. 6mm x 6mm V-groove and filled up with an
approved quality sealant compound. Drain outlet shall be provided for all spouts/
rain water pipes by suitable rounding, filling and sloping of PCC. At the junction
of the roof and parapet or any other vertical surface, a fillet of 75mm radius shall
be formed in cement mortar (1 cement: 4 coarse sand).
The finished work shall be measured in M.Sq of area for the purpose of payment.
A guarantee of 10 years shall be provided by the manufacturer against the performance
of the finished waterproof coating.
1.6 WHITE/ COLOUR WASHING, PAINTING, POLISHING ETC.
Reference shall be made to the following Indian Standards for further information
etc. not covered in the specification. In case of conflict/ contradictions provisions of
the specification shall override.
IS : 6278: Code of practice for white washing and colour washing.
IS : 2395: Code of practice for painting concrete, masonry and plaster surfaces.
IS : 712: Specification for building limes.
IS : 55: Specification for Ultramarine blue for paints.
IS : 63: Specification for whiting for paint and putty.
IS : 5411: Specification for plastic Emulsion paint for interior use.
IS : 2338: Code of practice for finishing of wood, and wood based materials.
IS : 5410: Cement paint, colour as required.
IS 2524: Code of practice for painting non ferrous metals in buildings.
IS 384: Brushes, paints and varnishes, flat.
IS 486: Brushes, sash, tool, for paints and varnishes.
IS 110: Ready mixed paint, brushing, grey filler enamels for use over primers.
IS 426: Paste filler for colour coats.
IS 345: Wood filler, transparent liquid.
IS 3585: Ready mixed paint, aluminium brushing priming water resistant for wood
work.
IS 426 : Paste filler for colour coats.
IS 106: Ready mixed paint, brushing, priming for enamels, for use on metals.
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 20 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
All materials required for the execution of painting work shall be obtained direct
from approved manufacturers and shall be brought to the site in makers drums,
bags etc. with seals unbroken.
In case of ready mixed paints, thinning if necessary, the brand of thinner shall be as
per recommendations of the manufacturer.
Paint shall be applied by brushing or spraying. Spray machine used may be of high
pressure type or low pressure depending on the nature and location of work. The
paint containers, when not used shall be kept close and free from air.
After the finishing of work, the adjacent surfaces not intended to be washed/
distempered/painted/polished, shall be thoroughly cleaned of all paint patches and
shall be finished in accordance with surface finishing of such surfaces.

1.6.1 White/ Colour Washing

White washing in general shall conform to IS:6278. Scaffolding shall be erected for
white washing in such a way that no part of the scaffolding shall rest against the
surface to be white/ colour washed. The surface shall be thoroughly cleaned of all
dirt, dust, mortar dropping and other foreign matter before white wash is to be
applied. Surfaces already white/colour washed shall be broomed down to remove all
dust, dirt, loose scales of lime wash or other foreign matters.
All damaged portions of the surface plaster shall be removed to full depth of plaster
in rectangular patches and plastered again after raking the joints in masonry
properly. Such portions shall be wetted and allowed to dry before any operation. All
holes, cracks, patches etc. not exceeding 0.1 sq. m. in area shall be made good with
material similar to that of the surface. Surfaces affected by efflorescence, moss,
fungi, algae, lichen etc. shall be treated in accordance with IS: 2395.
The fat lime conforming to IS: 712 shall be slaked at site and shall be mixed and
stirred with about 5 litres of water for 1 kg. of unslaked lime to make thin cream.
This shall be allowed to stand for a period of 24 hours and then shall be screened
through a clean coarse cloth. 4 kg of gum dissolved in hot water shall be added to
each cubic metre of lime cream. Approved quality ultramarine blue (for white wash)
conforming to IS: 55 @ 3 gram per kg. of lime shall be added to the solution. The
whole solution shall be stirred thoroughly before use.
For colour washing sufficient quantity of colour wash enough for the complete job
shall be prepared in one operation to avoid any difference in colour. Mineral colours
of approved shade and quality not affected by lime shall be added to the white wash
solution in proportions as directed by Engineer-in-charge. Solid lumps etc. in the
colour powder shall be ground to fine powder, sieved and mixed evenly and
thoroughly to the white wash solution.
White/ colour wash shall be applied with "MOONJ" brush to the in minimum 3
number of coats. The operation for each coat shall consist of stroke of the brush
from the top to down wards, another from the down to upwards over the first
stroke, similarly one stroke horizontally from right and another stroke from the left.
Each coat shall be allowed to dry before the next coat is applied. The white washing
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 21 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
on ceiling should be done prior to that on walls.
Surfaces of doors, windows, floors etc. shall be protected from being splashed upon.
Such surfaces shall be cleaned of white/ colour wash splashes.

1.6.2 Oil Bound Distempering


The oil bound distempering work shall consist of:-
(A) Preparation of surface:-

The surface shall be thoroughly brushed free from dust, dirt, grease, mortar
droppings, other foreign matter and shall be made smooth by sand papering. In
case of distempering over existing distempered surface, the existing distempering
shall be scrapped by steel scrappers leaving a clean surface. All nails shall be
removed. Pitting in plaster shall be made good with Plaster of Paris mixed with
distemper of colour to be used. The surface then shall be rubbed down again with a
fine grade sand paper and made smooth. A coat of distemper shall be applied over
the patches. The surface shall be allowed to dry thoroughly. The surface affected by
moss, fungus, algae, efflorescence shall be treated in accordance with IS: 2395. Any
uneveness shall be made good by applying putty made of Plaster of Paris mixed with
water including filling up the undulation and then sand papering the same after it is
dry. Scaffolding wherever required shall be erected in such a way that no part of the
scaffolding shall rest against the surface to be painted.

(B) The primer coat:-


The primer coat shall be alkali resistant primer or distemper primer and shall be of
the same manufacture as oil bound distemper.

(C) Base preparation:-


After the Primer coat, the base preparation shall include applying two or more
coatings of oil based putty in paste form made from chalk powder mixed with
linseed oil, white zinc, varnish etc. as per manufacturer’s recommendations. After
each coat of putty, sandpapering of the surfaces shall be done.

(D) Application of Distemper:-


After the base preparation coats have dried, the surface shall be lightly sand
papered and dusted off avoiding rubbing off of the primer coat. The distemper shall
conform to IS: 428 and shall be diluted with water or any other prescribed thinner
recommended by the manufacturer. Minimum two coats of distemper shall be
applied with brushes in horizontal strokes followed by immediate vertical strokes
which together shall constitute one coat. The subsequent coats shall be applied after
at least 24 hours between consecutive coats to permit proper drying of the
preceding coat. The finished surface shall be even and uniform without patches,
brush marks drops etc. Application of a coat in each room shall be finished in one
operation.14 cm double bristled distemper brushes shall be used. After each days
work brushes shall be thoroughly washed in hot water with soap solution and hung
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 22 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
down to dry.

Surfaces of doors, windows, floors etc. shall be protected from being splashed upon.
Such surfaces shall be cleaned of distemper splashes.

1.6.2 Plastic Emulsion Paint

The Plastic Emulsion paint work shall consist of:-


(A) Preparation of surface:-

The surface shall be thoroughly brushed free from dust, dirt, grease, mortar
droppings, other foreign matter and shall be made smooth by sand papering. In
case of plastic emulsion paint work over existing distempered/ emulsioned surface,
the existing distempering/ emulsion shall be scrapped by steel scrappers leaving a
clean surface. All nails shall be removed. Pitting in plaster shall be made good with
‘plaster of Paris’ mixed with plastic emulsion of colour to be used. The surface then
shall be rubbed down again with a fine grade sand paper and made smooth. A coat
of plastic emulsion shall be applied over the patches. The surface shall be allowed to
dry thoroughly. The surface affected by moss, fungus, algae, efflorescence shall be
treated in accordance with IS: 2395. Any unevenness shall be made good by
applying putty made of ‘plaster of Paris’ mixed with water including filling up the
undulation and then sand papering the same after it is dry. Scaffolding wherever
required shall be erected in such a way that no part of the scaffolding shall rest
against the surface to be painted.

(B) The primer coat:-


The primer coat shall be alkali resistant primer or emulsion primer and shall be of
the same manufacture as plastic emulsion paint.

(C) Base preparation:-


After the Primer coat, the base preparation shall include applying two or more
coatings of oil based putty in paste form made from chalk powder mixed with
linseed oil, white zinc, varnish etc. as per manufacturer’s recommendations. After
each coat of putty, sandpapering of the surfaces shall be done.

(D) Application of Plastic Emulsion Paint :-


After the base preparation coats have dried, the surface shall be lightly sand
papered and dusted off avoiding rubbing off of the primer coat. The plastic emulsion
paint shall conform to IS: 5411 (Part- I) and shall be diluted prescribed thinner
recommended by the manufacturer. Minimum two coats of plastic emulsion paint
shall be applied with brushes in horizontal strokes followed by immediate vertical
strokes which together shall constitute one coat. The subsequent coats shall be
applied after at least 24 hours between consecutive coats to permit proper drying of
the preceding coat. The finished surface shall be even and uniform without patches,
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 23 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
brush marks drops etc. Application of a coat in each room shall be finished in one
operation.14 cm double bristled distemper brushes shall be used. After each days
work brushes shall be thoroughly washed in hot water with soap solution and hung
down to dry.
Surfaces of doors, windows, floors etc. shall be protected from being splashed upon.
Such surfaces shall be cleaned of splashes.

1.6.4 Plaster of Paris Punning


Plaster of Paris punning shall be applied over roughened plastered surfaces.
Superior quality Plaster of Paris of approved make shall be mixed with water to
obtain paste like consistency and shall be applied on walls, ceiling etc. in sufficient
thickness to give an absolutely smooth, plumb and straight surfaces.

1.6.5 Waterproof Cement Paint


Scaffolding shall be erected for white washing. The surface shall be thoroughly
cleaned of all dirt, dust, mortar dropping and other foreign matter before white
wash is to be applied. Surfaces already white/colour washed shall be broomed down
to remove all dust, dirt, loose scales of lime wash or other foreign matters.

Scaffolding, Preparation of Surface shall be same as white wash. The surface so


prepared shall be thoroughly wetted with clean water before the paint is applied.
Waterproof cement paint of approved make shall be mixed with water and stirred to
obtain a thick paste which shall then be diluted to brushable consistency. The
proportion of mixture shall be as per manufacturer's recommendation. The paint
shall be mixed in such quantity which can be used up within an hour of mixing to
avoid setting and thickening of the paint.

The surface shall be treated with minimum two coats of waterproof cement paint.
No less than 24 hours shall be allowed between two coats and subsequent coats
shall be applied only after the preceding coat has become hard to resist marking by
subsequent brushing.

The finished surface shall be even and uniform in shade without patches, brush
marks, paint drops etc. Cement paints shall be applied with a brush with relatively
short stiff hog or fibre bristles.

Curing shall be started after the paint has hardened. Curing shall be done by
sprinkling with water two or three times a day. This shall be done between coats
and for at least two days following the final coat.

1.6.6 Water Repellant Finish


It shall be a coating of silicon/ acrylic based Water Repellant finish (as per approved
manufacturer’s specifications) to be applied on walls. All the cracks shall be filled
with white cement and pigment to match. Before that the surface shall be cleaned
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 24 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
of all dust, dirt etc. by rigorous brushing. The coating shall be applied evenly with
brush including curing, drying the coated surfaces for 24 hours etc. all complete as
per approved manufacturer’s specifications and recommendations.

1.6.7 Painting of Wood Surfaces (Synthetic Enamel Paint)


Preparation of wood surface shall conform to IS: 2338 (Part-1) in general. All
woodwork shall be dry and free from any foreign matter. Nails shall be punched well
below the surface. The surface shall be smoothened off with abrasive paper used
across the grain prior to painting, with the grain prior to the staining. Any knots,
resinous, or bluish sap wood, cutting out of which is not justified shall be covered
with red lead conforming to IS: 103. Plywood and block board shall be treated in the
same manner as for wood work. Particle boards surface shall be filled with a thin
brushable filler and finished as for solid wood. Painting of wood surfaces shall
consist of:-

(A) Priming
Priming shall be in accordance with IS :2338 (Part I and II). Dirt or any other
extraneous material on the surface shall be removed and the priming shall be
applied by brushing. Priming shall be done on all exposed and unexposed surfaces.
Unless specified otherwise all joinery work intended to be painted shall receive at
least 2 coats of primer. Type of primer shall be in accordance with Table-1 and
Table-2 of IS: 2338 (Part-II).

(B) Stopping and Filling

Stopping and filling shall be done after priming. Stopping shall be made to the
consistency of stiff paste and shall be used to fill holes and cracks. Filler shall be
used to level up slight irregularities of the surface. Filler shall be applied with a putty
knife and subsequently rubbed down to a level surface with abrasive paper. The
filler coat shall be allowed to fully flatten and harden before subsequent coat is
applied.

(C) Application of Undercoat


Under coat shall be applied after the surface has been primed, stopped and filled,
and rubbed down to a smooth surface. Under coat may be brushed or sprayed. After
drying the coat shall be carefully rubbed down and wiped clean before the next coat
is applied. The type of undercoat shall be depending upon the finishing and in
accordance with Table 1 and Table-2 of IS: 2338 (Part II).

(D) Finishing

The finishing paint shall be two or more coats of synthetic enamel paint and shall be
applied either by the brush or by spraying to give a uniform, smooth and glossy
finish. Reference shall be made to the Table-1 and Table-2 of IS: 2338 (Part-II)
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 25 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
1.6.8 Polishing of Wooden Surfaces (Application of Clear Finishes)
For the application of clear finishes, the following procedures shall generally be
adopted in accordance with IS: 2338 (Part-I)

(A) Filling
Fillers shall be applied to prevent the excessive penetration of the finish to the
surface for obtaining a smooth finish. Fillers shall be conforming to IS: 345.
Fillers shall be heavily applied to the wood surface by hand, using hessian or
juterag across the grain. It shall be rubbed when still wet to get better penetration.
After 5-10 minutes it shall be wiped off by hand across the grain followed by a light
wipe with the grain. The filled surface shall be dried preferably over night and
smoothened with abrasive paper.

(B) Preparation of Wood for Staining


Surface intended for staining shall be kept scrupulously clean and free from greasy
finger marks. It shall be prepared by careful smoothing with fine abrasive paper
used in the direction of the grain. Small cracks/nail holes shall be stopped with
plastic wood/fine plaster of Paris. The stopping shall be rubbed down with fine
abrasive paper when hard and touched with a thinned knotting before staining. In
case of oil staining stopping shall be done after staining using tinted putty or wood
filler.

(C) Staining
Spirit stains are solutions of spirit soluble dyes in Industrial methylated spirit. Oil
stains are solutions of oil soluble dyes in linseed oil, but, usually consist of insoluble,
semi-transparent pigments ground in linseed oil and thinned with turpentine or
other solvent. Stains shall be applied by brushing, and wiping or by spraying. The
stain shall be so thinned that it can be applied fairly, liberally without over staining
and over lapping.

(D) Sealing
A suitable sealer shall be applied on the filled and sanded surface to prevent
absorption by the wood of the succeeding coats of finish and to seal stain and filler
and thus preclude their bleeding into the finish coat. Sealer may be sprayed on
taking care not to flood the surface and it shall be allowed to dry hard. When fully
dry the surface shall be sanded taking care not to cut through at corners and edges.
Dust shall be blown off and surface wiped with a clean rag.

(E) Finishing
The stained surface shall be varnished, wax-polished or French polished as required
after it is dried. Varnishing of wood and wood based material shall be in accordance
with IS: 2338 (Part-I).
Surfaces to be Varnished shall be prepared to produce a smooth, dry and matt

SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0


GAIL (INDIA) LTD FINISHES
Page 26 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
surface and all dust and dirt shall be removed from the surface.

The Varnish shall be applied liberally with a brush and spread evenly over a portion
of the surface with short light strokes to avoid frothing. It shall be allowed to flow
out while the next section is being laid in. Excess Varnish shall be scraped out of the
brush and then the first section be crossed, re- crossed and laid off lightly. The
Varnish, once it has begun to set, shall not be retouched. In case of any mistake,
the Varnish shall be removed and the work shall be started afresh.

Where two coats of varnish are applied, the first coat shall be a hard drying under
coating or flatting varnish which shall be allowed to dry hard and then be flatted
down before applying the finishing coat. Sufficient time shall be allowed in between
two coats.
When flat varnishing is used for finishing, a preparatory coat of hard drying
undercoating of flatting varnish shall first be applied and shall be allowed to harden
thoroughly. It shall then be lightly rubbed down before the flat varnish is applied.
On larger areas, the flat varnish shall be applied rapidly, and the edges of each
patch applied shall not be allowed to set, but shall be followed up whilst in free
working conditions.

French polish shall conform to IS :348. Suitable pigments shall be added to get the
required colour. The surface to be French polished shall be rubbed down to
smoothness with sand paper and shall be well dusted. Pores in the surface shall be
filled up with fillers. A pad of woolen cloth covered by a fine cloth shall be used to
apply the finish. The pad shall be moistened with polish and rubbed hard on the
surface in a series of overlapping circles applying the polish sparingly but uniformly
over the entire area to give an even surface. A trace of linseed oil may be used on
the face of the pad for the purpose. The surface shall be allowed to dry and the
remaining coats applied in the same way. To finish off, the pad shall be covered
with a fresh piece of clean fine cloth, slightly damped with methylated spirit and
rubbed lightly and quickly with circular motions. The finished surface shall have a
uniform texture and high gloss.

1.6.9 Painting of Steel and Other Metal Surface


Reference shall be made to IS :2524 and IS:1447.
The surface, before painting, shall be cleaned of all rust, scale, dirt and other foreign
matter with wire brushes, steel wool, scrappers, sand paper etc. The surface shall
then be wiped finally with mineral turpentine which shall then be removed of grease
etc. The surface then shall be allowed to dry.
In case of GI surface, surface so prepared shall be treated with Mordant solution (5
litre for about 100 sq.m.) by rubbing the solution generously with brush. After about
half an hour, the surface if required shall be retouched and washed down thoroughly
with clean cold water and allowed to dry.
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 27 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
Approved quality primer and paint in specified numbers of coats shall be applied as
per manufacturer's recommendations either by brushing or spraying. Each subsequent
coat shall be applied only after the preceding coat has dried.

1.6.10 Textured Coating


The textured coating shall consist of twin pack fine grade wall coating system;with fine
grade silica granules/ dry flakes made of special grade of china clay / granite type
flakes of ‘Heritage’ or equivalent in approved shade and texture; mixed in-situ
with100% acrylic polymer bonding agent. The textured coating shallbe applied over
plastered surfaces. The granules/ flakes etc., bonding material, mixing, method of
application surface preperation etc. all shall be as per manufacturer’s recommendations
and specifications.

1.7 ROOFING

Reference shall be made to the following Indian Standards for information etc. not
covered in the specification. In case of any conflict/contradiction, provisions of
specification shall override.

IS 277: Galvanized steel sheet (plain & corrugated)


IS 730: Hook bolts for corrugated sheet roofing.
IS 1728: Specification for sheet metal rain water pipes upto 100 mm nom. size gutters,
fittings and accessories.
The roof slope shall be as specified and in general not pitched flatter then 1:5. The
normal pitch if not specified shall be 1:2. Materials shall be supplied by approved
manufacturer. The items supplied shall be free from cracks, chipped edges or corners
or other damages. Storage and safety precautions shall be taken to avoid damage to
the accessories.

1.7.1 Precoated Galvanised Steel Sheet Roofing/ Cladding


The base metal of the roofing shall be Cold rolled in high tensile Galvalume Steel of
550 MPA yield stress conforming to IS:513, IS:14246 and ASTM A446 Grade E. The
substrate shall have hot dip metallic coating of aluminium- zinc alloy (150 grams per sq.
mtr. total on both sides, coating class AZ150 as per per ASTM A792). The bottom
unexposed surface shall then be coated with alkyd backer of minimum 7 microns. Top
exposed surface shall have SMP (Silicon Modified Polyester) paint system Minimum 20
microns top coat applied over 5 microns primer with additional coating of
Fluropolymer (PVF2) paint system (for coastal areas only) over and above the top
coating. The top coat shall be in specified colour. The precoated galvalume steel
sheets shall meet the following performance standards

Pencil Hardness : F minimum


Formability : 2-3 t
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 28 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
Specular Glass (60 deg) : 20- 35%
(ASTM D523)
Impact Resistance : Greater than 10J
Salt spray test : 750 hours
QUV-Wealterometer Test : 1000 light hours
Humidity Test : 1000 hours
Temperature Resistance : 100_C
Fire performance : Class I
The SMP coated steel sheet in standard colour under normal well washed conditions of
exposure shall not show any cracking, flaking or peeling of paint film for at least 10
years. Colour change during service, determined according to ASTM D2244 should not
exceed 5E hunter lab units on light colours.

The profiles shall have a depth of not less than 28mm and pitch of 190mm. Overall
sheet thickness shall be minimum 0.50mm. Minimum weight of the sheet shall be 5.2
kg/ Sq.M

All roofing accessories like ridge, gutters, north light curves etc. shall be fabricated out
of precoated sheet of same thickness (as for roof sheeting) and as per manufacturer’s
specifications. Metallic Fasteners and Fixing accessories shall be corrosion proof
(polyester polymer coated). Self drilling screws/ fasteners with integral washers and
EPDM seals, and nylon colour caps and joint sealants shall be provided for fixing of
sheets as per approved manufacturer’s specifications. Non metallic fasteners shall be of
neoprene. Sealants shall be natural cure type and of cold setting variety. Wind ties
shall be of 40 mm x 6 mm flat iron section and other size as specified. These shall be
fixed at the two eaves end of the sheet. Fixing shall be done with the same loose
bolts which secure sheets to the purlins. Slot holes shall be cut in the wind ties to allow
for temperature variations. The wind ties shall be painted with two or more coats of
synthetic enamel paint of same shade as that of sheeting over a coat of approved
primer.

1.7.2 C.I. Rain Water Pipes


C.I. rain water pipes shall be 100mm dia or 150mm dia (as specified/ indicated in
drawings); shall bends, Tees, other accessories (as per approved manufacturer’s
specifications) and shall be jointed with spurn yarn and cement mortar 1:2 (1 cement: 2
fine sand by volume). Embedded rain water pipes shall be suitably embedded/ encased
in masonry/ cement concrete (M-15) with nominal reinforcement.

1.7.3 P.V.C. Rain Water Pipes


PVC rain water pipes shall be 110mm dia (O.D.) or 160mm dia (O.D.) as specified/
indicated in drawings; of 6 Kg./ sq. cm. pressure rating. The pipes shall be provided
complete with necessary clamps, connections, bends, Tees, other accessories (as per
approved manufacturer’s specifications) and shall be jointed with approved quality
bonding solution. Embedded rain water pipes shall be suitably embedded/ encased in
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 29 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
masonry/ cement concrete (M-15) with nominal reinforcement.

1.8 SANITARY FITTINGS AND FIXTURES

Reference shall be made to the following Indian Standards for any further information
etc. not covered in the specification. In case of any conflict/contradiction provisions of
specification shall override.

IS-2556 : Specification for Vitreous Sanitary appliances (Vitreous-China, Part 1-15).


1S-774 : Specification for Flushing Cistern for Water Closets and Urinals.
IS-781 : Specification for Cast copper alloy screw down bib taps and stop valves for
water services.
IS-2064 : Code of Practice for Selection, Installation and Maintenance of Sanitary
appliances.

All glazed earthen ware shall be of approved make, colour and of one piece
construction.
All metallic fixtures like taps, stop cocks, soap holders etc. shall be CP brass and
approved make. All wall fittings shall be fixed with nylon sleeve and CP brass screws
and washers.

1.8.1 Indian Type Water Closet


Squatting Pan shall be 550mm x 440mm Orissa Pan conforming to IS: 2556 Part-IIIwith
integrated footrests. The closet shall be fixed in the floor with 150 mm thick sand
cushion and shall be connected with 100 mm dia CI `S' or `P' trap. The closet shall also
be fitted with 10litres valve less syphonic type glazed earthenware flushing cistern,
conforming to IS: 774, and complete with all accessories like 15 mm dia. PVC inlet
connection pipe 450mm long (with 15mm dia CP Brass stop cock and brass union), PVC
ball valves, C.P Brass handle,telescopic 32 mm dia GI telescopic flushing pipe with
union, 15 mm dia GI overflow pipe with mosquito proof net and fixed with glazed
earthenware cover.

The cistern shall be fixed on MS brackets at a minimum height of 2150 mm from top of
pan.

All exposed metallic surface shall be painted with two coats of synthetic enamel paint of
approved quality over a coat of red oxide zinc chromate primer (primer is not required
for GI pipes).
One number heavy grade approved quality CP Brass bib cock conforming to IS: 781
(with necessary connections) shall be provided with each WC.

The work shall include providing and fixing water-closet and flushing cistern with all
accessories, breaking wall and floors and making good the same, all inlet and outlet
connections of cistern and water closet, finishing of solder joints, painting and testing of
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 30 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
all connections etc. complete.

1.8.2 Wash Down (European) Type Water Closet


Wash down water closet shall be of pattern-1 conforming to IS:2556 Part-II. Water
Closet shall be of one piece construction, double trap syphonic type. This shall be fixed
with plastic seat and cover as per IS:2548 of approved make and colour, fixed with CP
brass hinges and rubber buffers and an integral 100 mm dia 'S' or 'P' trap with
antisyphonage vent horn. A low level earthenware cistern conforming to IS:774 of
about 10 litres capacity, with 15mm dia PVC inlet pipe (with 15mm dia CP Brass stop
cock) and brass union with wiped solder joint, internal overflow arrangement, 40 mm
dia CP brass flushing pipe. CI or MS supporting brackets shall be fixed with the water
closet. The closet shall be fixed firmly in the floor with matching cement mortar. All
exposed metallic surfaces shall be painted with two coats of synthetic enamel paint of
approved quality over a coat of red oxide zinc chromate primer.

The clearance between top of pan and bottom of cistern shall not exceed 300 mm.
One number heavy grade approved quality CP Brass bib cock conforming to IS: 781
(with necessary connections); one number approved quality CP Brass Toilet paper
holder (fixed to wall with wooden cleats, CP Brass screws) shall be provided with each
WC. The work shall include providing and fixing of all fittings, breaking floors and wall,
making good the same, making inlet and outlet connection to the cistern and the closet,
testing of joints, painting the exposed metallic surface with two coats of synthetic
enamel paint over a coat of primer etc. complete.

1.8.3 Urinals
Half stall type urinal shall be of size 610mm x 400mm x 380mm and conforming to
IS:2556 Part VI. Urinals shall be of single piece construction with integral flushing box
rim. These shall be mounted on walls. The flushing inlet pipe shall be of CP brass 15
mm dia and wast pipe 32 mm dia GI, 750 mm long shall be embedded in wall.
Necessary unions and CP bottle trap shall be provided in the waste line.
Rawl plugs with CP brass screws shall be used for fixing the urinal. Fixing shall ensure
that no liquid is left over in the pan after flushing. Unless otherwise indicated height
above finished floors shall be 600 mm.

Urinals shall be connected to glazed earthenware automatic flushing glazed


earthenware cisterns either individually, or in groups. Where individually connected to
flushing cistern, the cistern capacity shall be 5 litres. For two urinals, one cistern of 10
litres capacity and for three urinals, one cistern of 15 litres, capacity shall be provided.

Cistern inlet shall be 15 mm dia PVC pipe with brass union. Outlet pipe from cistern
shall be 25mm CP brass main, with 15 mm CP distributor pipe of sufficient lengths to
reach each bowl. Where individual cisterns are provided the outlet shall be of 15 mm CP
brass.
The work shall include urinals inlet and outlet pipes, flushing cistern, breaking and
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 31 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
making good the walls and flooring, making inlet and outlet connections including all
related G.I. piping work (embedded in wall), painting exposed brackets and exposed
metallic parts with two coats of synthetic enamel paint of approved quality over a coat
of red oxide zinc chromate primer etc. all complete.

All The Urinals shall be separated by Marble partitions (of minimum 19mm thick White
Makrana/ White Ambaji/ Abu Green marble slabs; each partition in one piece) of
minimum size 1000mm x 600mm or Granite partitions . These partitions shall be
inserted upto 100mm depth in the wall and fixed with cement mortar 1:3 (1 cement ; 3
coarse sand by volume) and suitable sized M.S. Channel (embedded in wall with
grouting) at bottom. The M.S. Channel at bottom shall be finished with two coats of
synthetic enamel paint of approved quality over a coat of red oxide zinc chromate
primer.

1.8.4 Wash Basins

This shall be flat back wash basin (with require number of tap holes and conforming to
IS: 2556 Part-IV) with anti splash rims on three sides, of size 550mm x 400mm size.
Wash basins shall be of one piece construction including a combined overflow having an
area of not less than 5 Sq. cm. shall be provided in the front or back of the bowl and it
shall be so designed as to facilitate cleaning of the overflow. This shall be fitted on CI
or MS brackets. Brackets shall conform to IS: 775. The brackets shall be given two
coats of synthetic enamel paint or aluminium paint, over a coat of approved primer.
Each wash basin shall be provided with 15mm dia CP brass pillar cock of approved
make, rubber plug with CP brass chain, 32mm CP Waste fitting of standard pattern with
32mm dia G.I. pipe, CP Brass bottle trap, CP Brass 15mm dia stop cock etc. complete
with all related accessories, fittings and fixtures. The wall side shall be fixed well flushed
with the plaster or wall and the joint if any, shall be properly stopped with an
elastomeric sealant. The top of rim of the wash basin shall be fixed at 800 mm above
finished floor level, unless otherwise specified.

The work shall include provision and fixing of wash basin with all accessories, providing
stop cocks and pillar cocks, breaking and making good walls, fixing and making inlet
and outlet connections for stop cock, pillar cock and waste pipe, providing & fixing MS
brackets painted with two coats of synthetic enamel paint of approved quality over a
coat of red oxide zinc chromate primer etc. complete

Following fixtures of approved quality shall be provided for each Wash Basin.

1. Mirror: Round edged Mirror of 5.5mm thick (minimum size of 400mm x 550mm) plain
glass with 6mm thick AC sheet backing, beveled edged.

2. Glass Shelf: 600mm x 120mm x 4mm thick Glass shelf with CP brass bracket & guard
rails; fixed on wall.
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 32 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
3. Towel Rail: Chromium plated brass towel rail of 20mm dia, 600mm length & 1.25mm
thickness.

4. Liquid soap container: Chromium plated Liquid soap container.

All the fixtures shall be fixed to the wall at identified locations with wooden cleats and
CP Brass screws including cutting walls, making good the same etc. complete.

1.9 FALSE CEILING, FALSE FLOORING, PARTITIONING, WALL PANELLING,


UNDERDECK INSULATION ETC.

1.9.1 Aluminium Lineal False Ceiling


Aluminium lineal false ceiling shall consist of:-

(A) Panel Carriers:-


These shall be roll- formed out of coated steel/ 0.95mm thick aluminium alloy; 32mm
wide and 39mm deep with cut-outs to hold panels in a module of 90mm/ 100mm; all
complete as per manufacturer’s standard details and specifications. When two or more
carriers are to be joined, they shall be joined together by means of carrier splices which
will clip on to holes in the sides of the carriers and hold them firmly in place while
maintaining the required module. The carriers shall be suspended from roof by 4mm
dia. galvanised steel wire rod hangers, with height adjustment springs of stainless steel.
Hangers shall be fixed to roof by “J” hooks and nylon inserts. Edge profiles shall be “L”
shaped roll- formed out of 0.6mm aluminium alloy with coating.

(B) Panels:-
Panels shall be 84mm wide, 16mm deep, roll formed out of 0.5mm aluminium alloy
5050 or 3005. The aluminium panels shall be chromatised and stove enamelled (coil
coated) on both sides in approved shade. Panels shall be factory cut in lengths upto 5
metres to suit site dimensions. As per air- conditioning requirements, for return air,
(wherever required) perforated panels shall be used, which shall have 2mm dia holes at
5mm centre to centre staggered in uniform pattern and symmetrically located in the
middle of the panel face.
The ceiling shall be erected in continuous manner as per approved manufacturer’s
recommendations, specifications etc. The false ceiling shall have perfect levels, linearity
etc. as required. Necessary cut outs for Electrical, AC and other fixtures shall be
provided as per drawing and in co- ordination with relevant construction activities.

1.9.2 Aluminium Planks/ Tiles False Ceiling

This false ceiling system shall consist of:-


(A) Panel carriers:-
These shall be rows of 0.5mm thick galvanised steel clip in profiles of size 40mm x
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 33 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
20mm. These shall be suspended from roof structure by means of G.I. suspension
angles, ceiling brackets and hold on clamps @ maximum 1200mm c/c all complete as
per approved manufacturer’s specifications.

(B) Aluminium Tiles:-


Aluminium Ceiling Tiles shall be 600mm x 600mm manufactured out of 0.7mm thick
aluminium alloy AA3105, chromatised and stove enamelled (coil coated) with square
edges produced on advanced equipments. Exposed side of the tile shall have 20 micron
(minimum) coil coated polyester finish and 5 micron back coat of Alklyd primer. The
short sides of each plank shall be raised and pipped and stopped to ensure positive
engagement into the spring clip- in profiles, and shall allow for demounting of individual
planks.
1.9.3 Cavity (False) Flooring (with Particle Board)

This False flooring system shall consist of


(A) Pedestal base plate made of galvanized Mild steel and shall be of 100 mm x
100mm size and 8mm thick.

(B) Pedestal stud 30 mm dia made of galvanized mild steel seamless pipe and
having threads at top and bottom for attaching the top head attachment
and fixing to base plate.

(C) Top head attachments made of pressure die cast aluminium alloy of shape
and thickness as per drawing; and shall be provided with check nuts at
bottom portion for attaching the top head threads in the stud allowing for
adjustment upto 25mm up & down.
(D) Channel stringers made of galvanized, machine cut, cold rolled mild steel
channels of size 40 mm x 40 mm and 3.15 mm thickness.
(E) Floor panels of size 610 mm x 610 mm in general and of 35 mm
thickness; made of unveneered, 3 layer flat pressed, teakwood particle
board (conforming to IS :3087 bonded with BWP type phenol
formaldehyde synthetic resin conforming IS: 848 and categorised as class-
I for `Surfaces of very low flame
spread' as per IS-1642); finished on the underneath side with 0.05mm thick
Aluminium foil turned up and extended by minimum 12mm along the perimeter;
finished on top with 2mm thick antistatic type PVC tiles/ high pressure
laminate and along four sides with hard PVC lipping as per drawing. 12mm x
12mm x 75mm long, 2mm thick Aluminium channel cleats shall be provided on
middle of four sides of the panels for lateral stability.
False flooring pattern shall be as per approved drawing. Pedestal base plates shall
be fixed to the base floor by 6mm dia, 40mm long dash fasteners as per the grid.
The pedestal stud locations shall ensure the grid work as per flooring pattern which
in general shall be of 610 mm x 610 mm dimension. The length of the pedestal
studs shall be such that clear cavity between false flooring and base flooring is of
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 34 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
desired depth.
The top head attachments shall be inserted into the studs and shall be adjusted to
obtain proper level of the finished floor panels by means of the adjustment nuts.
Stringer channels then shall be fitted onto the top heads in position to form the
supporting grid work for the floor panels checking the level once again by adjusting
the nut position if necessary. Now the check nut shall be finally tightened to secure
the final level. Floor panels as specified shall be placed over the stringer channels.
Each floor panel shall be marked with positional numbering on the underneath. The
finished floor panels shall be perfectly levelled, aligned without any gaps in between
the panels.
Each individual panel shall be removable for the purpose of maintenance of the
cavity.
Necessary cut-outs shall be made in the panels for cable routing, control panel
fixation etc. as per drawing.
Necessary ramps, slopes, steps etc. shall be also provided for as per drawing.
Around a control panel/ rack, the residual space left out shall be filled up with cut
panels of uniform size as required to fully close the gap between the adjacent full
panel and the control panel base channel. In this case the part floor panel shall
extend upto the full width of the base channel and the cut size shall be determined
accordingly. An additional row of jack pedestals shall be provided along the cut out
on which the edge of the floor panel shall rest and over which the base channel of
control panel shall be placed. It shall not directly rest on the jack head pedestal or
grid channels.

1.9.4 Phenolic Foam Underdeck Insulation:-


Phenolic Foam Underdeck insulation shall be of rigid slab of 25mm thickness and
approx. 1000mm x 500mm size as specified and shall conform to IS: 13204. It shall
3
have density of 32 kg / M and K Value 0.016 KCal/hr M deg.C as per BS 4370, Part
2. The insulation shall be classified as ` Non Combustible ' as per BS 476, part 5 and
‘Class I’ for surface spread of flame as per BS 476 ,part 7. It shall be prelaminated
on both sides with kraft paper.
The entire soffit of slab and beams shall be thoroughly cleaned. Bituminous primer
or zinc chromate primer shall be applied evenly @ 0.5 kg/m2 over the entire
surface. Hot bitumen or CPRX adhesive shall then be applied on the insulation panel
@ 1.5 kg/Sq.M. The panels shall be pressed in position and further secured by dash
fasteners.

The underdeck insulation shall be fixed only after all fixtures like hooks, clamps,
cleats etc. for light fixtures, ducts etc. have been fixed in the ceiling.

1.9.5 Polyisocyanurate Foam Underdeck Insulation


Polyisocyanurate foam (PIR) shall be rigid slabs of size 1000 x 1500mm and
thickness of 30mm conforming to IS:12436 having density not less than 32 kg./ Cu.
M., thermal conductivity (K- value) not more than 0.023 w/mk measured at 10 deg.
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 35 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
C. The slabs shall be covered on one side with glass fibre tissue/ Aluminium foil
having 50mm overlap. The insulation shall be classified as ‘Non Combustible’ as per
BS 476, part 5 and ‘Class I’ for surface spread of flame as per BS 476, part 7.
First, holes in R.C.C. slab/ beam shall be drilled and nylon rawl plugs of size 8 x
25mm shall be inserted (5 nos. for each slab- One each at 4 corners and one at
center). Entire R.C.C surface shall be thoroughly cleaned of all dust, dirt and loose
particles by wire brushing. Then a coat of bituminous primer @ 0.5 Litres/ Sq.M.
shall be applied to bare R.C.C. surface and allowed it to dry. After the primer has
dried, hot blow grade bitumen of 85/25 grade or cold adhesive CPRX shall be
applied on R.C.C. surface and to the two surface of each PIR panel and shall be
pressed in position while the bitumen is still tacky. The PIR panels shall be secured
in position with the help of G.I. screws (No. 8 x 75mm long) fixed into rawl plugs
and G.I washers 25mm dia. Facing side of the panels shall be the one covered with
fibre tissue/ Aluminium foil. The overlaps shall be covered with approved quality
sealing compound (MAS-94 or equivalent). Chicken wire mesh 24G x 19mm shall
then be fixed to G.I screws and tightened with lacing wire.
The underdeck insulation shall be fixed only after all fixtures like hooks, clamps,
cleats etc. for light fixtures, ducts etc. have been fixed in the ceiling

1.10 MISCELLANEOUS ITEMS


1.10.1 M.S. Pipe Handrail
The M.S. Pipe handrail shall consist of 25mm M.S. square balusters (one on each
step; similar spacing for horizontal portions) with 40mm x 40mm x 6mm M.S flat
shoe welded at bottom of baluster; embedded into floor/ steps and grouted with M-
15 grade concrete in a cut out of 100mm x 100mm x 150mm size block. 32mm dia
N.B. (Medium) M.S. pipe handrail shall be welded to balusters at top. The entire
railing and balusters shall be painted with two or more coats of synthetic enamel
paint over a coat of approved quality red oxide zinc chromate primer. All embedded
metallic portions shall be provided with primer.

1.10.2 Steel Entrance Gate


Steel entrance gate shall be made of MC-75 frame all round, 20mm square M.S bars
welded to frame @ 100mm c/c vertically. A 500mm high (continuous along the
width of the gate) hollow box made of 2mm thick M.S. Sheet welded by means of
12mm square M.S bars to 20mm vertical square M.S bars of the gate shall be
provided. The gate shall be fixed to R.C.C. columns by means of 20mm dia M.S bolt
(with 40mm dia, 3mm thick M.S washer) threaded through 2 nos. 75mm x 75mm x
6mm M.S. angle cleats (one welded to peripheral MC-75 frame of the gate and the
other fixed to R.C.C. column by means of 25mm x 3mm x 200mm long M.S.
holdfast). At bottom towards R.C.C. column the gate shall be mounted on floor by
means of special pivot arrangement comprising of 25mm square bar rounded at
bottom (fixed to gate by means of 2 nos. 6mmx 60mm x 100mm M.S. flats welded
to gate frame from side) to form pivot and moving on 50mm x 50mm x 50mm M.S.
section (with 22mm dia x 20mm deep slot) embedded in floor. The gates shall also
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 36 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
be provided with 75mm dia, 25mm thk. M.S. wheel with ball bearing fixed to bottom
of the gate frame by means of 20mm dia bolt and 50mm wide 6mm thick M.S.
clamp. The gate shall swing on 50mm x 50mm x 6mm M.S. Tee embedded in floor
along its route curve. The gate shall be complete with all fittings and fixtures like
locking arrangement, M.S. heavy duty aldrop etc. Entire gate with all fittings and
fixtures shall be finished with two or more coats of synthetic enamel paint of
approved make and shade over a coat of approved primer. All hidden metallic parts
shall be provided primed.
1.10.3 Transformer Gates/ Fencing
Transformer gates/ fencing shall be made of 50mm x 50mm x 6mm M.S. Angle
frame, 50mm x 50mm x 6mm M.S. Tee stiffeners, 50mm x 50mm x 8mm welded
mesh fixed to the frame by 20mm x 3mm M.S. flat beading. The gate/ fencing shall
be fixed to the masonry/ R.C.C. by M.S. hinge arrangement (consisting of 65mm x
65mm x 6mm M.S. angle, bolt, washers etc.) with M..S. holdfast grouted with M-15
concrete block. The gate shall have M.S. pivot arrangement (ensuring smooth
operation of the gate), one heavy duty 450mm long M.S. aldrop, heavy duty M.S.
tower bolts etc. complete. The entire gate/ fencing with fittings/ fixtures/
accessories shall be finished with two or more coats of synthetic enamel paint of
approved make and shade over a coat of approved red oxide zinc chromate primer.
All embedded metallic parts shall be provided with primer.

1.10.4 Plinth Protection (Without Drain)


The plinth protection (all round the buildings- without drain) shall consist of a layer
(150mm thick) of compacted sand and over that 100mm thick M-15 grade concrete
top layer laid to slope. The top concrete layer shall be trowel finished, cured etc.
complete. The work also includes carrying out the necessary excavation, disposal of
surplus earthwork etc.

1.10.5 Cinder Filling


All the sunken R.C.C slabs of Toilets etc. shall be provided with cinder filling
comprising of:-
(A) Plastering the R.C.C. slab top, sides etc. with 18mm thick cement plaster 1:6 (1
cement : 6 sand by volume) mixed with approved waterproof compound @3% of
cement by weight and finishing with a floating coat of neat cement slurry @ 2.75
kg. per Sq.M, finishing, curing etc. The work includes preparation of base surface
as described in ‘Plastering’ item.
(B) Filling with Cinder concrete 1:10 (1 cement : 10 cinder of 12mm and down
grade) including consolidating, finishing, curing etc. complete.

1.10.6 Sealing of Expansion Joints


All expansion joints (25mm wide) of the building shall be sealed with premium grade
Silicon sealant (‘SILPRUF’ of ‘GE Silicons’ or equivalent) consisting of the following:-

(A) The surfaces over which it is to be applied shall be totally dried and cleaned of
SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0
GAIL (INDIA) LTD FINISHES
Page 37 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
all dirt, oils, mortar droppings, all loose material etc. by vigorous wire brushing
and wherever necessary by grinding and blast cleaning (sand or water).
(B) A backup material or joint filler tapes (as per approved manufacturer’s
specifications) shall be fixed in the expansion joint.
(C) A coat of primer as per approved manufacturer’s specifications (specially
developed for use with Silicon sealant material) shall then be applied over the
surface.
(D) Silicon sealant shall be applied by means of ‘cartridge- type’ caul gun, either
hand or air pressure activated. The sealant shall be applied in a continuous
operation, horizontally in one direction and vertically from bottom to top of joint
opening. The sealant shall be applied in excess so that a positive pressure
adequate to properly fill and seal the joint is created. The sealant shall be struck
with light pressure to spread the material against the back up material and the
joint surfaces properly. The sealant shall be tooled to slightly concave surface. As
the work progresses, the excessive sealant shall be removed. The masking tape
shall be removed immediately after tooling. The sealant shall be cured as per
approved manufacturer’s recommendations.

Entire work shall be carried out as per as per approved manufacturer’s


specifications and recommendations.

1.10.7 Anti Termite Coating


All woodwork (frames, panels etc. including hidden/ embedded portions of
wooden members shall be provided with anti- termite coatings of approved
quality aldrine- chlorinated phenol compound conforming to IS:401. Three or
more coats as required @ 3 Sq. Mtr. per coat per Kg. covering capacity shall be
applied before applying the finishing (painting, polishing, lamination etc. as
specified) coats.

SPECIFICATIONS OF ARCHITECTURAL DOCUMENT NO. REV-0


GAIL (INDIA) LTD FINISHES
Page 38 of
NEW DELHI (ARCHITECTURE) 0001-01-09-02-001 38
Copyright GAIL – All rights reserved
GAIL (INDIA) LIMITED

SPURLINES OF CHAINSA-JHAJJAR PIPELINE PROJECT

DRAWING / DOCUMENT REQUIRED BY OWNER

(ARCHITECTURE)

DRAWING/DOCUMENT REQUIRED DOCUMENT NO. REV-0


GAIL (INDIA) FOR OWNER
Page 1 of 3
LTD (ARCHITECTURE) 0001-01-09-05-001
NEW DELHI
Copyright GAIL – All rights reserved
VENDOR DRAWING AND DOCUMENT REQUIREMENT

The following Data marked “X” shall be furnished by Vendor

S. Description With After Job award


No. Bid
For For Final in
Review Information Book
Form

1 2 3 4 5 6
X
Vendor drawing/ documents
1. X
submission schedule
GA & equipment lay-out of buildings/
2. sheds indicating sizing of internal X
spaces
Preliminary Architectural Drawings of X X
3. the buildings in accordance with bid
indicating Plans, Sections & Elevations
& Architectural treatment. Such
preliminary dwgs shall be prepared
after finalisation of sizes & layout of
the required spaces/ areas/ rooms
and review of the same PMC.
Construction drawings of all the
4. Buildings/ Sheds. Construction
Drawings shall contain the following.
These drawings shall be prepared
incorporating comments etc. on the
preliminary Dwgs.
1. Plan of all levels, Terrace Plan, Key
X X
Plan.
2. Sections as required for complete
understanding of the Design & X X
Construction
3. Elevations of all sides. X X
4. Door/Window details. X X
5. False ceiling/ flooring details &
X X
layouts
6. Schedule of Architectural Finishes X X
7. Architectural details as
X
required.
8. Any other Dwg as required for X X

DRAWING/DOCUMENT REQUIRED DOCUMENT NO. REV-0


GAIL (INDIA) FOR OWNER
Page 2 of 3
LTD (ARCHITECTURE) 0001-01-09-05-001
NEW DELHI
Copyright GAIL – All rights reserved
complete understanding of the
Design & Construction.
5. Specification of materials not
X X
covered under bid document.
6. Documents/ Drawings for Statutory
Approval in accordance with the X X
statutory requirement
7. As-built drawings X X
List of all Sub - vendors / authorized
8. applicators to be engaged for
execution of various specialized
items (like Aluminium Doors and X
Windows, Waterproofing /
Insulation, False ceiling/ Flooring,
Partitioning etc.

DOCUMENT DISTRIBUTION SCHEDULE

1. Documents listed under column 4 are to be submitted in 8 copies (6 copies to


consultant, 2 copies to owner).

2. Documents listed under column 5 are to be submitted in 8 copies (6 copies to


consultant, 2 copies to owner).

3. Documents listed in column 6 are to be submitted as hard bound indexed book for
design calculations and AFC drawings in requisite number of copies as mentioned
elsewhere in tender. (Electronic files of all final drawings & documents shall be
furnished in CD-ROMs (5 sets for GAIL).

DRAWING/DOCUMENT REQUIRED DOCUMENT NO. REV-0


GAIL (INDIA) FOR OWNER
Page 3 of 3
LTD (ARCHITECTURE) 0001-01-09-05-001
NEW DELHI
Copyright GAIL – All rights reserved
GAIL (India) LIMITED

SPURELIENS ON CHAINSA-JHAJJAR PIPELINE PROJECT

SPECIFIC REQUIREMENT PIPELINE LAYING TENDER


(GENERAL CIVIL)
PIPELINE LAYING TENDER

SPECIFIC REQUIREMENT PIPELINE LAYING DOCUMENT No. REV-0


GAIL (INDIA) LTD TENDER
Page 1 of 5
NEW DELHI (GENERAL CIVIL) 0001-01-10-02-001
Copyright GAIL – All rights reserved
1.0 SPECIFIC REQUIREMENTS :

1.1.0 CLEAN AGENT FIRE EXTINGUISHING SYSTEM FOR CONTROL ROOM /


BUILDING/ POTA CABIN AT RECEIPT TERMINALS :

1.1.1 Design, engineering, supply, installation, erection, fabrication, testing & commissioning,
Guaranteeing of auto-operated (with manual override) Clean Agent fire extinguishing
system (fixed installation) along with complete fire detection, alarm and flooding of
Clean Agent system for the fire protection of Telecom room, control Room & UPS Room
of control room building at Despatch & Receipt Termianl as per Specs. No.
(Specification for Clean Agent System), NFPA-2001 (latest edition) and electrical
specifications enclosed in the tender including submitting of design basis, design
calculations, general arrangement, detailed drawings, operation philosophy for review /
approval of GAIL prior to any assembly, installation / construction, revising and
incorporating the comments if any on the above documents/drawings without any extra
cost including supply of all related materials but not limited to main fire alarm panel,
Clean Agent fire protection panel, detectors, response indicators, exit signs, electronic
horn, break glass type manual call point, junction boxes, mandatory spares such as
cylinders, cylinder valve assembly, nozzles etc. all complete as per NFPA-2001, codes,
standards, specifications, drawings, documents and direction of Engineer-in-Charge.
Electrical specs. on fire alarm and detection system shall form part of overall scope.
Main battery of Clean Agent filled cylinders along with 100% standby agent filled
cylinders shall be provided. All Clean Agent cylinders shall be seamless. Additional
quantity of Clean Agent in addition to main shall be provided to compensate for leakage
which will take place from the openings such as doors / windows / exhaust fan
openings / louvers etc. All equipments used for Clean Agent fixed system such as
cylinders / valves/ nozzles/ manifolds/ directional valves etc. shall be FM/UL/VDS/LPC
listed for the intended use. Clean Agent cylinders along with cylinder valves shall be
CCE approved. Approved software shall be used by the contractor for design of Clean
Agent system. The protection shall be provided for Telecom room, control Room & UPS
Room and the system shall be designed as a high pressure Clean Agent system at
21degree centigrade temperature. The system shall be designed for the largest risk
volume of Control Room building. For each risk (room), combined volume of false floor
+ main room + false ceiling shall be considered for calculating the total single largest
risk volume. Full Clean Agent discharge test shall also be performed by the contractor
for the smallest risk volume. The sub vendor, for Clean Agent system executing the job
should have designed and executed at least one such job of similar nature in the past
three years. The contractor shall furnish proper certification of the same from the sub-
vendor along with the bids.

1.2.1 GENERAL

(i) In case of conflict between GAIL spec. & NFPA-2001 (latest edition), NFPA 2001
provisions shall govern.
SPECIFIC REQUIREMENT PIPELINE LAYING DOCUMENT No. REV-0
GAIL (INDIA) LTD TENDER
Page 2 of 5
NEW DELHI (GENERAL CIVIL) 0001-01-10-02-001
Copyright GAIL – All rights reserved
(ii) For acceptance of the system, GAIL or its authorized representative shall be
considered as authority having jurisdiction.

2.0 SPECIFIC REQUIREMENT ON ENGINEERING BY CONTRACTOR

2.1 The construction shall be done as per the drawings prepared by the contractor and
reviewed / approved by GAIIL during the course of execution. The schedule of
submission of various drawings and documents as listed below.

2.2 The drawings / documents submitted by the contractor shall be reviewed by GAIL.
During such review, certain modifications may be suggested in the
drawings/documents. The contractor shall incorporate all such modifications without
any extra cost and time. GAIL may review and offer comments/suggestions on the
layout, schemes, designs and drawings as prepared by the contractor and the bidder
shall adhere to such comments/suggestions and revise/redo these design/drawings
accordingly, and incorporate the same in the construction without any extra cost and
time, maintaining the original time schedule. However, reviewing of design, drawings is
not obligatory on the part of GAIL/and complete correctness/soundness of the
design/drawings and their execution at site shall be the sole responsibility of the
contractor irrespective of the fact whether the same has been reviewed/approved by
GAIL or not. Any defect observed during commissioning and operating the system shall
be rectified by the contractor by carrying out the necessary modification.

2.3 Successful Bidder shall be required to present documentation of all proposed design,
installation and testing procedures for review and approval by GAIL. This shall be done
at least 45 days prior to the commencement of relevant phase of activity. The
fabrication/construction shall commence only after GAIL review/approval has been
obtained. This report shall contain the design assumptions, calculations, materials
specifications and details of construction.

2.4 Minimum six sets of each document/drawings shall be submitted during any
submission. For design calculations three sets are required for submission by the
contractor.

2.5 The contractor shall incorporate the comment (without any cost and time effect) if any,
on documents and resubmit the same for GAIL ’s review.
2.6 Preparation of drawing, scheme and other documents for obtaining statutory approval
as per rules & regulations from central/state government and other statutory
authorities, arranging inspection of work by the authorities at appropriate times,
necessary co-ordination, all liaison work shall be included in the scope of this tender,
within the quoted rates.

SPECIFIC REQUIREMENT PIPELINE LAYING DOCUMENT No. REV-0


GAIL (INDIA) LTD TENDER
Page 3 of 5
NEW DELHI (GENERAL CIVIL) 0001-01-10-02-001
Copyright GAIL – All rights reserved
2.7 The cost of work involved in preparation of document in line with the State/Government
and other statutory authorities for obtaining the approval shall deemed to be included
in the lump sum price including any change modification required at any time either in
design/drawing, field for obtaining the approval.

3.0 DOCUMENTS REQUIRED FROM BIDDER

The deliverables to be submitted in various stages to GAIL for review / approval shall
be as follows:

(⊕ : Means Data required from Vendor)

Description With After Job award


S.N. bids For For After Final
Information review data
1. Clean agent fire ⊕ ⊕ ⊕
extinguishing System
write up with
deviation if any or
modification to
compliance to tender
2. System design ⊕ ⊕
calculation for Clean
agent system for
sizing, storage
capacity, pipes and

3. G.A. Drawings for ⊕ ⊕


Clean agent fire
extinguishing system
4. Complete detailed ⊕ ⊕
drawing for Clean
agent system piping
and storage
arrangement and
manifold

5. Pre commissioning, ⊕ ⊕
commissioning and
performance
guarantee tests
SPECIFIC REQUIREMENT PIPELINE LAYING DOCUMENT No. REV-0
GAIL (INDIA) LTD TENDER
Page 4 of 5
NEW DELHI (GENERAL CIVIL) 0001-01-10-02-001
Copyright GAIL – All rights reserved
procedures

6. Item wise list of ⊕ ⊕ ⊕


recommended spare
parts for two years
trouble free operation
7. Item wise list of ⊕ ⊕ ⊕
commissioning spares

8. Installation, operation ⊕ ⊕
and spare parts
manual
9. As built drawings and ⊕
Information/data
10. Filled up data sheet ⊕ ⊕
for Clean agent
system

SPECIFIC REQUIREMENT PIPELINE LAYING DOCUMENT No. REV-0


GAIL (INDIA) LTD TENDER
Page 5 of 5
NEW DELHI (GENERAL CIVIL) 0001-01-10-02-001
Copyright GAIL – All rights reserved
GAIL (India) LIMITED

SPURELINES ON CHAINSA-JHAJJAR PIPELINE PROJECT

SPECIFICATION FOR CLEAN AGENT SYSTEM


(AS PER NFPA-2001)

FOR PIPELINE LAYING TENDER


(GENERAL CIVIL)

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
CONTENTS

1.0 SCOPE OF WORK

2.0 CODES AND STANDARDS

3.0 DESIGN REQUIREMENTS

3.1 SYSTEM DESIGN

3.2 SYSTEM FLOW CALCULATIONS

3.3 CLEAN AGENT QUANTITY

3.4 CLEAN AGENT STORAGE CYLINDERS

3.5 PIPING, FITTINGS AND DISCHARGE NOZZLES

3.6 DETECTION, ACTUATION AND ALARM SYSTEM

3.7 PAINTING

3.8 OPERATING DEVICES

3.9 LOCAL CONTROL PANEL FOR CLEAN AGENT SYSTEM

4.0 MATERIALS OF CONSTRUCTION

5.0 INSPECTION AND TESTING

6.0 VENDOR DATA REQUIREMENTS

6.1 ALONG WITH TECHNICAL BIDS

6.2 AFTER AWARD OF CONTRACT

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
7.0 MANDATORY SPARES

8.0 BID EVALUATION CRITERIA

ANNEXTURE -I : List of risk and clean agent quantity


ANNEXTURE - II : Technical data sheet

1.0 SCOPE OF WORK

This specification covers the requirements of design, supply of materials,


installation, testing and commissioning of total flooding centralised Clean
Agent System (clean agents to be considered are : IG-541, IG-55, IG-01
and IG-100 as per NFPA-2001) for fire protection of Control Room
building mentioned in this specification.

The work shall include electrically actuated automatic Clean Agent Fire
Extinguishing System complete with clean agent cylinders, manifolds,
pressure reducing devices, cylinder valves, directional valves, pipes,
discharge nozzles, brackets supports, hangers and such other fittings as
necessary for complete installation of the system including chipping of
existing RCC/brick walls of control room buildings, fixing fasteners, etc.
The system shall also comprise of both Automatic and Manual actuation,
cancellation facility etc. with necessary control panel.

Complete Fire Detection and alarm system is in the scope of this


requisition. The clean agent shall be discharged/actuated automatically
after a adjustable time delay based on the detection signal received. The
delay shall be maximum 180 seconds, however it shall be adjustable
from 0 to 180 seconds.

It may be noted that clean agent system to be provided shall meet the
requirements of NFPA-2001 (Latest). Hence any thing specified as
“mandatory” in NFPA-2001, although not specifically mentioned in this
specification, shall form part of this specification and scope of work for
the job to be executed.

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
2.0 CODES AND STANDARDS

- NFPA 2001: Standard on Clean Agent Fire Extinguishing Systems,


2004 Edition.

- BS - 5445, 5446, 5839 : for detectors

- SMPV Rules, 1981, CCE , Nagpur : for Storage Containers.

- Clean Agent manufacturer's recommendations.

- Tariff advisory committee (TAC) rules

3.0 DESIGN REQUIREMENTS

Vendor shall design the system to meet the minimum requirements of


total flooding fire extinguishing clean agent system as per NFPA-2001
˜ ˜
and having design concentration as specified at 70 F(21 C).
The system design shall be centralised and shall protect other risk as
defined in the requirements and scope of work of the project.

3.1 SYSTEM DESIGN

The centralised system of a station shall be designed to protect any of


the risk(volume wise) in a particular room of a building as defined in
Annexure-I to this specification.

The quantity of Clean Agent gas provided shall be sufficient to protect


the single largest risk in each building with 100% standby filled up
cylinders. The system shall have its own storage, distribution piping,
nozzles, alarm, and actuation system, etc.

Both primary and standby supply shall be permanently connected to the


distribution piping through manifold and arranged for easy and auto
changeover.

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
As the system is designed for the largest risk and there are several risks
varying in size in particular building, the system shall permit use of
required no. of cylinders for any individual risk involved so that the
concentration of gas in that risk does not exceed the design
concentration specified in the table below.

TABLE

PROPERTIES OF INERT GAS AGENTS USED AS FIRE EXTINGUISHING


AGENTS

NAME FORMULA NOAEL LOAEL NORMAL MIN. EXTINGUISHING


% % CHARGING DESIGN CONCENENTRATION
PRESSURE PRESSURE
0
AT 130 F

3 3
%AGE M /M OF VOL.

IG- N2 43 52 2175 psi 2575 psi 37.5 0 .470


541 (52%)
Ar 2475 psi
(40%) 43 52 2222 psi 37.5(*) 0.470(*)
IG- CO2(8%)
55 N2-50% 2650 psi
AR-50% 43 52 2371 psi 37.5(*) 0.470(*)
2799 psi
IG-01 AR- 43 52 2404 psi 37.5(*) 0.470(*)
99.9%
IG-
100 N2
(99.9%)

NOAEL : No Observable Adverse Effect Level, the hightest concentration


at which no adverse physiological or toxicological effect has been
observed.

LOAEL : Lowest Observable Adverse Effect Level, the lowest


concentration at which an adverse physiological or toxicological effect
has been observed.

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
(*) Or higher %/quantity of volume as specified by clean agent
manufacturer for clean agent system.
IG-541, 55, 01 and 100 are called as inert gas as per NFPA-2001.

The agent discharge shall be substantially completed in a nominal 60


seconds for IG-541, 55, 01 and 100, or a shorter time .The measured
discharge time is considered to be the time when the measuring device
starts to record reduction of oxygen untill the design oxygen reduction
level is achieved.

The min. Oxygen concentration shall be maintained after release of


clean agent (IG) as 16%.

3.2 SYSTEM FLOW CALCULATIONS

System flow calculations shall be performed using A CALCULATION


METHOD LISTED OR APPROVED BY THE AUTHORITY HAVING
JURISDICTION (e.g. FM/UL/LPC/VDS) and TAC. The system design shall
be within the manufacturers listed limitations. System design including
computerised flow calculations, piping & storage layout of Clean Agent
System shall be submitted along with the technical bids.

3.3 CLEAN AGENT QUANTITY

Minimum design concentration of Clean Agent gas shall be 37.5%(min)


for IG-541,55, 01 and 100 at 70˜F by volume unless otherwise specified
by the agent manufacturer for clean agent fire extinguishing system.

Clean Agent concentration requirement shall be computed considering


the volume of the hazard as specified.
The quantity of Clean Agent shall be worked out by the bidder, as per
NFPA-2001 and in the Performa given in Annexure-I, however vendor
shall quote minimum quantity of agent as given in the Annexure-I.

3.4 CLEAN AGENT STORAGE CYLINDERS

The Clean Agent storage cylinders shall be designed to hold clean agent
GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR
ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
at ambient temperatures. Container shall be of approved type and
freshly imported. Minimum container design level working pressure of
storage container shall be as per clause 2.1.4 and table A-2-1.4.1 of
Appendix-A to NFPA-2001. The containers shall not be charged to a fill
density or superpressurisation (superpressurisation means the addition
of a gas to fire suppression agent container necessary to achieve the
pressure required for proper system operation) level different from
manufacturer’s listing.

The vendor shall select the capacity of cylinder as follows :


IG-01, 55, 541and 100 435 cu.ft

The vendor shall standardised the capacity of cylinder for better


replacement & inter changeability.

The design pressure for cylinders shall be suitable for the maximum
pressure developed at 130˜ F (55˜C) at the max. controlled temperature
limit.

Each container shall have a permanent name plate specifying the agent,
tare and gross weight in addition to the pressurisation level, and nominal
agent volume.

All clean agent cylinders shall be seamless and bear the mark of
manufacturer, serial number and shall be duly listed by a competent
approval authority of country of origin (FM/UL/VDS/LPC) in addition to
approval by CCE Nagpur (India). Cylinders without the approval will
not be accepted. A reliable means of indication, other than weighing
shall be provided to determine the pressure in refillable containers.

Each container shall have pressure relief valve to protect the cylinders
against excess pressure conditions.

Clean Agent containers shall be arranged in the following manner:

i) In a battery of cylinders manifolded together and leading to common


distribution pipe and discharge nozzles for the risk to be protected
including below floor board and above false ceiling spaces.
ii) A reserve battery of cylinders with manifold, directional valve and
automatic change over to any of the two banks after actuation
shall be provided. The reserve of standby Clean Agent battery
shall be 100% of the quantity required for the single largest risk
as per scope of work.

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
Automatic means such as check valve shall be provided to prevent agent
loss if the system is operated when any containers are removed for
maintenance.

The manifolded containers referred to above shall be securely mounted


on the floor and suitably supported in a rack with provision for
convenient individual servicing and content weighing according to the
manufacturers installation manual. Such servicing or weighing shall be
possible without shutting down the system.

A space marked as cylinder shed on the drawing be made available to


the contractor for placing Clean Agent cylinders. Vendors shall confirm
the adequacy of space provided for storage of Gas cylinders.

3.5 PIPING, FITTINGS AND DISCHARGE NOZZLES

----------------------------------------------------------------------------------------
----------------------------------------------------------------------------------------
CLEAN AGENT PRESSURE U/S OF PRESSURE D/S OF FITTINGS U/S OF
FITTINGS D/S OF
NAME PR / PIPE CLASS PR / PIPE CLASS PR PR
----------------------------------------------------------------------------------------
------------------------------------------------------------------------
IG-541,55, 2650 PSIG/ 1000 PSIG/ AS PER TABLE AS PER TABLE
01 and 100 ASTM A-106,GR C ASTM A-106,GR C A-2.2.3.1 OF NFPA A-
2.2.3.1 OF NFPA
SEAMLESS,WLD SEAMLESS,WLD

----------------------------------------------------------------------------------------
-----------------------------------------------------------------------
PR : STANDS FOR PRESSURE REDUCER ; WLD : STANDS FOR WELDED
CONNECTION
PIPE THICKNESS CALCULATION SHALL BE AS PER ASME B31.1 POWER
PIPING CODE AND FITTINGS SHALL CONFORM TO ANSI B1.20.

The pressure reduction device shall be easily identifiable.

Discharge nozzles shall conform to cl.2.2.5 of NFPA. Discharge nozzles

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
used in this system shall be listed for the use intended for discharge
characteristics. The selection of nozzle orifice shall be such that the
95% of IGs is discharged within 60 seconds through the number of
nozzles of the system. Each nozzle shall be permanently marked to
identify by the part number, orifice code, or other suitable marking as
specified by the authority having jurisdiction.

The vender to note that the clean agent piping to be laid in existing
building, hence the clean agent piping and nozzles etc. shall have to be
planned clearing other facilities coming in the areas where clean agent
protection is being envisaged. The different items that are to be
provided for efficient functioning of the automatic clean agent system
have been indicated but not the quantity of any of them, which has to
be worked out by the contractor.
The clean agent piping shall have to clear:

i) The beams and ribs which criss cross the ceiling.


ii) Path of AC ducts.
iii) Cabling in false flooring.

The vendor shall have to lay the clean agent piping in existing building.
All necessary civil works including breaking the Blast resistant RCC wall
and brick walls and making them good shall be in the scope of work.

3.6 DETECTION, ACTUATION AND ALARM SYSTEM

Fire detection, actuation and alarm system for the system shall be as per
NFPA-2001 latest revision.

There shall alarm in clean agent local control panel at the time of gas
release.

3.7 PAINTING

Painting and colouring of pipelines, nozzles, clean agent storage


containers, supports, etc. shall be done as per Specification O-611.

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
3.8 OPERATING DEVICES

a) Operating devices shall include clean agent releasing devices or


valves, discharge controls, and shut down equipment necessary for
successful performance of the system.

b) Electric Supply: The vendor shall provide 100 V + 6% @ 50 Hz +


3%, 3 phase power supply at a convenient point. Convertor required
to convert 24V shall be in vendor's scope.
c) Electric Supply: The vendor shall provide 100 V + 6% @ 50 Hz +
3%, 3 phase power supply at a convenient point. Convertor required
to convert 24V shall be in vendor's scope.

d) The clean agent cylinders shall be mounted on front and firmly


supported in brackets in a manner that they will not be easily
subjected to mechanical chemical or other damage, which would
render the system in-operative.

e) In addition to Automatic actuation, there shall be a normal manual


control for actuation, which shall be located so as to be conveniently
and easily accessible at all times including the time of fire. This
control shall cause the complete system to operate in its normal
fashion.

f) Manual controls shall not require a pull of more than 40 lb nor a


movement
of more than 14 inches to secure operation. At least one manual
control for activation shall be located not more than 4 feet above the
floor.
g) i) signal shall be provided from the clean agent control panel
to
shut off the air handling unit and air conditioning
dampers/louvers.

ii) Supervision of automatic systems shall be provided and


shall include electrical supervisions of the actuating device
and the wiring connecting the actuation device and the
detection system.

h) Operating instructions shall be displayed on a name plate fitted


permanently on the clean agent skid.
i) Clean agent extinguishing system shall incorporate a
predischarge alarm with a time delay sufficient to allow

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
personnel evacuation prior to discharge.

3.9 LOCAL CONTROL PANEL FOR CLEAN AGENT SYSTEM

The system shall have a main control console and shall consist of:

I) Two alarms and one fault indicator lamp for each zone to be
protected.

II) Combination of alarm silence and alarm off switch.

III) Combination of fault silence and trouble lamp switches.

IV) Alarm test switch

V) Alarm re-set switch.

a. The installation shall have arrangement to indicate by alarm as well


as indication about actuation of the system, hazard to personnel of
failure of any supervised system. The extent and type of alarms or
indicators equipment shall be to the satisfaction of the Engineer-in-
Charge.
b. The system shall have a positive warning device by sounding alarm
to alert personnel of the impending discharging and also a
positive indication to show that the system has actuated.
c. Alarm indicating failure of supervised devices of equipment shall
give prompt and positive indication of any failure and shall be
distinctive from alarm indicating operation of hazardous conditions.
d. Warning and instruction signs at entrance to and inside protection
areas shall be provided.

The following additional provisions shall be made in the main control


panel:

a. Automatic shut off of the Air conditioning dampers/louvers by


solenoid damper closing unit or electrically operated
damper motor. Only signal to be provided from clean agent
system control panel. Rest of the job shall be done by others.

b. Automatic shut off of the air-handling units.

4.0 MA TERIALS OF CONSTRUCTION

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
4.1 The materials of construction used in the system shall be in accordance
with NFPA-2001 or as specified by the equipment manufacturer for the
intended use. (if the same is not specified in NFPA-2001)
.
5.0 INSPECTION AND TESTING

5.1 APPROVAL OF INSTALLATION

The completed system shall be tested to meet the approval of Owner.


The entire clean agent system shall be TAC (Tariff Advisory Committee,
India) approved & vendor to obtain the same. Only listed or approved
equipment and devices shall be used in the systems. All critical
equipments such as cylinders, cylinder valves, directional valves,
pressure reducers, nozzles, actuatation controls, pressure gauges etc.
shall have listings (FM/UL/Vds/LPC) To determine that the system has
been properly installed and will function as specified, the following tests
shall be performed:

a. A thorough visual inspection of the installed system and hazard area.


The piping, operational equipment and discharge nozzles shall be
inspected for proper size and location. The locations of alarms and
manual emergency releases shall be confirmed. The configurations
of the hazard shall be compared, to the original hazard specification.
The hazard shall be inspected closely for un-closable openings and
sources of agent loss, which may have been overlooked in the
original specifications.
b. .A check of labelling of devices for proper designations and
instructions. Nameplate data on the storage containers shall be
compared to specifications.
c. A test for mechanical tightness of the piping and associated
equipment to assure that leakage will not occur and that there will be
no hazardous pipe movements during discharge.
d. Non-destructive operational tests on all devices necessary for proper
functioning of the system.

Vendor shall provide suitable safety measures against increase in


pressure inside the protected area due to release of clean agent.

6.0 VENDOR DATA REQUIREMENTS

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
6.1 Along with the Technical Bids

- List of clause wise deviations, if any, to the specifications. It will be


vendor's responsibility to furnish the deviations. If the same are not
furnished it will be assumed that the offered equipments meet the
specifications of the enquiry document in toto.
- System design including computerised system flow calculations, piping
& storage layout.
- Indian/International standards to which the offered equipments
conform.
- Catalogues/Brochures giving technical particulars and details of
operation/maintenance of the offered elements/system.
- Certificates of agencies who have accorded approval for the elements
offered.
- Numbers & placement / Area coverage for type of nozzles used.
- Quantity of each type of equipment offered along with the calculations.
- Protected room/area layouts.
- Quantity of clean agent offered for various areas as per specifications.
- PFD, P&ID and GA drawing.

6.2 After Award of the Contract

- Calculations for pipe sizes, time of discharge, flow, nozzle rate of


discharge etc.
- GA and dimensional drawings of the areas showing storage, piping and
nozzles for various areas.
- Mounting/fixing details of all the elements.
- Testing and inspection schedule and procedure.
- Cylinders data sheets.
- Other data sheets as per the list attached.

- If the vendor is collaborating with any foreign party for basic


engineering, design etc., he should provide certificate of collaboration
and first submission of design and detailed drawing shall be approved
by the collaborator.

- List of drawings.

7.0 MANDATORY SPARES

The bid must include in the quoted price the following mandatory spares
to be supplied with the clean agent system:

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
1. Clean Agent Cylinders for Centralised : 5% of the total cylinder
(filled).
System

2. Automatic and Manual release system : One of each type/size


used in the
system supplied.

3. Cylinder Valve with safety : One of each type/size used pressure


relief
device in the systems supplied.

4. Clean Agent Nozzles : 10% of total nozzles used in each size/type.

5. Clean Agent Release Push Buttons : 10% of total used of each type
etc.

Recommended Spares:

In addition to above mandatory spares, vendor must recommend list of


spares required for 2 years trouble free operation with unit rates and
quantity along with the offer.

8.0 BID EVALUATION CRITERIA

The bid shall be evaluated based on the following technical criteria,

- Vendor is registered with GAIL


- Vender shall have done one of the following to qualify in last 3 years.

a) Inert gas, fire detection & alarm system

b) CO2 /Halon-1301 system, fire detection and alarm system

c) Fire alarm and detection system with back up consultant for


inert gas

- The bidder shall very clearly mention in his offer that he has
considered total flooding centralised system with directional valves and
also have offered 100% standby Cylinders.
- No deviation from Specification is acceptable.
- System supplied, design calculation is approved by FM/UL/VDS/LPC &
TAC or its accredited agency.
GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR
ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
- Software is approved by FM/UL/VDS
- All equipment shall be approved by FM/UL/VDS/LPC & TAC and
cylinder shall be seamless and CCE approved.
- Vender not having direct experience shall produce along with offer the
collaboration Certificate.

Completion Certificate of jobs completed shall be produced along with


offer.

ANNEXURE-I

LIST OF RISK AND CLEAN AGENT QUANTITY

SL DESCRIPTION ROOM VOLUME DES. MAX GAS


NO (CUM.) VOL. VOL REQ.
(+10%)
3
(M )

IG-01,
55,541
& 100
(0.47
M3/M3
OF
VOL)

FF MR FC TOTAL

1 RECEIVING
TERMINAL, 40.8 204 68 312.8 344.08
DOBHOL
CONTROL ROOM - 144 48 192 211.2 344.08
BUILDING 14.4 72 24 110.4 121.44
161.72
RISK1 :
CONTROL ROOM
(8x8.5)
RISK2 : UPS
ROOM (8X6)
RISK3 :
GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR
ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
TELECOM ROOM
(4X6)

Size of risk mentioned is approximate. Actual Volume of Clean agent


quantity shall be calculated from Final Drg. by bidder / contractor

ABBREVIATIONS:

FF : FALSE FLOOR
FC : FALSE CEILING
MR : MAIN ROOM

ANNEXURE-II

TECHNICAL DATA SHEETS

DETAILS TO BE FURNISHED BY THE BIDDER ALONG WITH THE OFFER


(Clean Agent Data sheets shall be filled in as per NFPA-
2001separately for each stations)

C Means Vendor to furnish data/details

1. Type of system : Total flooding centralised


system (Mention
name of agent &
GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR
ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
manufacturer)
Formula
Normal Charging Pressure : ____C____ psig.

2. Design code/standard to which design/


manufacture/testing conforms. : NFPA-2001-(Latest)

3.0 System designed to protect the largest or


total risk in the building as specified. : Largest risk

3.1 Risk name/volume : C

3.2 Design Concentration : C

3.2.1 Amount of gas required. (Attach separate


sheet, if required).
(List out gas supplied, number of cylinders
etc. for working and standby requirements,
risk wise.) : C

3.3 Clean agent Cylinder Details (Seamless)

a) Manufacturer : C

b) Design Code : NFPA-2001

c) Capacity : (Preferably:- IG-


01,55,541 &100 : 435cuft filled
with 439cuft of gas

d) Gas Holding Capacity (Kg) : C

e) Total Number supplied : C

f) Approving Agency FM/UL/LPC/


VDS & TAC (This must be accep-table to TAC). : FM/UL/LPC/VSD &
TAC

g) Approved by CCE : YES

h) Working pressure (kg/cm²) : C

i) Design Pressure (kg/cm²) : As per NFPA-2001

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
j) Dimension of Cylinder Dia x
length x thickness :C
3.4 Pipes, valves and fittings.

a) Manufacturers

i. Pipes : EIL approved vendor

ii. Fittings : EIL approved vendor

iii. Valves :C

b) Material for Construction

i. Pipes : As per spec

ii. Fittings : As per spec

iii. Valves : As per spec

c) Design Code

i. Pipes : As per NFPA

ii. Fittings : As per NFPA

iii. Valves : As per NFPA

d) Type of Joints : As per NFPA

e) Hydraulic test Pressure of


Manifold/supply lines (kg/cm²) : As per NFPA

f) Directional Valve

i. Make and Type : C

ii. Material of Construction : C

iii. Test Pressure (kg/cm² ) : C

iv. Approved by FM/UL/VDS

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
/LPC & TAC (Yes/No) : C

g) Discharge Nozzles

i. Manufacturer and Type : C

h) Pressure Gauge

i. Make : C

ii. Pressure Range : C

iii. Approved by FM/UL/VDS


/LPC & TAC (Yes/No) : C

i) Pressure Reducer

i. Make : C

ii. Approved by FM/UL/VDS


/LPC & TAC (Yes/No) : C

j) Cylinder valve

i. Make : C

ii. Approved by FM/UL/VDS


/LPC & TAC (Yes/No) : C

k) Cylinder valve actuator

i. Make : C

ii. Approved by FM/UL/VDS


/LPC & TAC (Yes/No) : C

3.5 Painting and colouring of pipeline, : C (As per O-611)

3.6 Operating Devices

3.6.1 Signal from the Clean Agent Control Panel


for shuttering off the air handling unit and
Damper closing. : C

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
3.6.2 Detectors

i. Manufacturer : C

ii. Type :
C

iii. Number : C

iv. Detectors guarded against false


alarm (Yes/No) : C

v. Detectors approved by UL/FM/LPC


/VDS & TAC (Yes/No). : C

3.6.3 Push Button Station

i. Type : C

ii. Manufacturer : C

iii. Model, numbers offered : C

3.6.4 Control Cables

i. Manufacturer : C

ii. Code/Standard : C

iii. Type : C

iv. Size : C

v. Rating : C

3.6.5 Main Control Panel

i. Manufacturer : C

ii. Mounting Detail : C

iii. Number of entries : C

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
iv. Sheet Thickness : C

v. Cable Entry : C

vi. Total heat load predicted for air


conditioning. : C

vii. No. of AC/DC feeders and their


rating. : C

3.7.1 Additional Requirements for Control Panel

a) Whether housing all the necessary


printed card circuits, board cards,
relays indicating lamps, push
buttons, switches, etc. for the
efficient operation of the system,
(Yes/No). : C

b) Input power supply requirement for


operation of panel. (AC/DC Volts) : C

c) Panel Signal Voltage (AC/DC Volts) : C

d) Type/APM Capacity of the


: C

e) Interconnecting cabling between


battery and panel. : C

f) Power supply unit incorporated in


the panel. (Yes/No). :C

g) Audiovisual alarm on panel provided


for battery low conditions(Yes/No). :C
h) Change over from AC Main supply
to standby power supply fully
automatic in either direction
(Yes/No). :C

i) Regulated supply for detectors


provided in the panel (Yes/No). :C

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
j) Dual Red Lamps windows provided
for fire conditions in each zone.
(Yes/No). :C
k) Dual yellow lamps windows
provided for fault conditions in
each zone (Yes/No). :C

l) Following push buttons provided

i) Alarm Accept :C

ii) Reset :C

iii) Test (Yes/No) :C

m) Audio visual indication for AC


supply failure provided (Yes/No). :C

n) Pilot lamp for system ‘ON’ supply


failure provided (Yes/No). :C

o) Dial tone hooter for fire/fault alarm


provided & range of the same. :C

p) Painting (External/Internal) :C

4.0 Material of Construction selected in


accordance with NFPA-2001 (Yes/No) : C

5.0 Inspection and Testing

a) Visual inspection of installed : C


system & hazard area.
b) Check of labelling of devices. :C

c) Check for mechanical tightness


of piping and associated equipments :C

d) Non-destructive operational
tests for all devices included. :C

e) Test with clean agent gas : As per pump test

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
(one no. Cylinder)

GAIL(INDIA)LIMITED STANDARD SPECIFICATION FOR


ENGINEERING CELL - CLEAN AGENT SYSTEM (AS PER NEPA- DOCUMENT No. 0001-01-10-02-002
2001)
GAIL (INDIA) LIMITED

SPECIFIC REQUIREMENTS FOR GEOTECHNICAL


INVESTIGATIONS FOR PIPELINE LAYING AND ASSOCIATED
WORKS TENDER
(STRUCTURAL & ARCHITECH. DEPT.)

SPURELINES OF CHAINSA-JHAJJAR PIPELINE

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 1 of 9
Copyright GAIL – All rights reserved
SPECIFIC REQUIREMENTS FOR GEOTECHNICAL INVESTIGATIONS FOR
PIPELINE LAYING AND ASSOCIATED WORKS

1.0 GENERAL

Geotechnical investigations shall be conducted at Despatch Terminal at Sultanpur,


receiving Terminal at Neemrana and, SV stations, SV Cum CP stations, IP stations as
per Process Flow Diagram . Bidder has to generate required Geotechnical data by
investigations. The report shall be submitted to Owner for review and approval before
adoption in design. Bidder shall acquaint himself with the site condition before quoting
and no claim what so ever on cost and time shall be entertained by the owner on this
account.

2.0 SCOPE

Geotechnical investigations for Pipe laying and associated works tender is as following
table:

Sl. Location Chainage No. Borehole/ Depth Remarks


No.
1 Dispatch Terminal 2 Nos.- (1no.) 10m & 1no.(15m) -Center of
(Sultanpur) (1No.) 15m deep PORTA CABIN
boreholes 1no(10m).- Center of
metering area
2 SV1 1No.-10m deep Near the center of the
borehole plot
3 SV2 1No.-10m deep Near the center of the
borehole plot
4 SV3 1No.-10m deep Near the center of the
borehole plot
5 CGS(DHARUHERA) 1No. - 10m deep Near the center of the
borehole plot
6 CGS(BHIWADI) 1No. - 10m deep Near the center of the
borehole plot
7 CGS(KHUSKHERA) 1No. - 10m deep Near the center of the
borehole plot
8 CGS(NEEMRANA) 1No. - 10m deep Near the center of the
borehole plot
9 CGS(MANESAR) 1No. - 10m deep Near the center of the
borehole plot

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 2 of 9
Copyright GAIL – All rights reserved
10 PRS AT HAYATPUR FOR 1No. - 10m deep Near the center of the
GURGAON. borehole plot
11 RECEIVING TERMINAL 2Nos. - (1no.) 10m & 1no (15m). –Near
AT NEEMRANA (1No.) 15m deep Center of control
boreholes room
1no.(10m) - Center of
scraper Launcher
area

The work shall comprises but not limited to the following:

2.1.1 Equipment

Contractor shall mobilize necessary drilling rigs with adequate capacity for boring in all
kinds of soil of specified depth of borehole.

2.1.2 Boring:

Boreholes of 10m to 15m deep as specified in the above tables the Table
shall be carried out.
Conducting standard penetration tests and collecting disturbed and undisturbed soil
samples from boreholes.

Collection of soil and ground water samples for chemical testing.

Laboratory testing of soil samples collected. Minimum number of laboratory tests to be


conducted per borehole are given in the following table.

SL.No Type of test Number of tests to be conducted

15m deep 10m deep

Borehole Borehole

1 Grain size analysis 4 3

2 Atterberg limits (If clayey strata is found) 4 3

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 3 of 9
Copyright GAIL – All rights reserved
3 Free swell and swelling pressure(If soil is 2 2
expansive in nature)

4 Consolidation tests (If clayey strata is found) 2 1

5 Unconfined compressive strength (If clayey 2 2


strata is found)

6 Triaxial tests UU (If clayey strata is found) 1 1

7 Box shear Test in sandy soil sample 1 1

8 Dry density and moisture content 1 1


relationship

9 Laboratory CBR test on soil samples to be 2 2


used below road /pavement.

10 Chemical tests on soil and ground water 2 2


samples

3.0 REQUIREMENTS

3.1 The contractor shall confirm their schedule of field / laboratory investigations well in
advance for the purpose of witness of tests by GAIL if so desired. The contractor shall
mobilize a qualified Geotechnical engineer for supervision of field works. Also an
experienced Geotechnical Engineer with minimum postgraduate qualification should be
engaged for preparation of the report and he should visit site to familiarize with the site
conditions and to assess various field and laboratory tests to arrive at design
parameters. All test equipments and tools shall conform to relevant IS code of practice.

3.2 BORING

Boring shall be carried out in accordance with the provision of IS: 1892. Minimum
diameter of boring shall be 150mm. Auger boring shall be resorted to above the
water table, whereas below the water table the boreholes shall be advanced by shell
and auger/ rotary drilling with mud circulation through all kinds of soil other than rock.
While boring above water table, no water shall be introduced in the boreholes. Casing
shall be used to support the sides of boreholes in very soft to soft/loose soils.

Use of chisel, percussion and drilling with Nx size may be permitted exclusively in strata
having SPT-N greater than 100 blows per 30cm penetration and as per direction of
Engineer-in-charge.
SPECIFIC REQUIREMENTS FOR
GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 4 of 9
Copyright GAIL – All rights reserved
Termination criteria of boreholes is as follows

i) Maximum depth as specified or

ii) After encountering soft/weathered rock

iii) After observing three consecutive SPT-N values greater than 100 at 1.0m interval
which ever occurs earlier.

3.3 STANDARD PENETRATION TESTS (SPT)

These shall be conducted in boreholes at interval of 1.0m or at change of strata upto


5.0 mt. and at interval of 1.5 mt or change of strata beyond 5.0mt starting first test at
0.5m depths. Last SPT shall be conducted at the termination depth of borehole. The
disturbed representative samples shall be visually classified, labeled for identification
and properly preserved for laboratory testing. SPT shall be terminated at any depth
after three consecutive SPT-N values greater than 100 (number of blows exceeds 100
for a penetration of 30cm or less). All test equipments and tools shall conform to
relevant IS code of practice.

3.4 UNDISTURBED SAMPLES

Undisturbed samples of 100mm dia. shall be taken from all boreholes and from
representative strata at intervals of 2.0m or change of strata whichever occurs earlier
starting first UDS at 1.0 depth. For stiff clays, area ratio of the sampling tubes shall not
exceed 20%. In soft deposits piston sampler shall be used to collect UDS.

Care shall be taken to minimize sample disturbance during collection of samples.


Samples shall be collected by pushing the sampler. Driving by hammer above ground
level (like SPT) is not acceptable. However, for stiff / hard soil a sliding hammer can be
used for driving the sampler at sampler head.
If at any depth SPT and UDS coincide, then UDS shall be taken at that depth. In case
UDS slips then SPT shall be taken immediately below the depth after proper cleaning of
the borehole.

3.5 DISTURBED SAMPLES

Disturbed soil / wash samples shall be collected at every 0.5m intervals and at every
change of strata from boreholes. Identification labels indicating depth, borehole no. and
visual soil classification shall be affixed on the containers.

4.0 LABORATORY TESTS:

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 5 of 9
Copyright GAIL – All rights reserved
4.1 After collecting disturbed and undisturbed samples from different boreholes at different
depths, a laboratory test schedule shall be prepared and submitted to GAIL / Client for
review. Adequate number of the following tests shall be conducted to clearly determine
the mechanical strength and compressibility characteristics of each strata of soil
encountered. All tests on rock and soil samples shall conform to relevant IS codes of
practice. The laboratory tests shall essentially comprise of but not limited to the
followings:

4.2 Grain Size Distribution

Wherever applicable both the sieve & hydrometer analysis shall be conducted to
indicate complete range of grain sizes of soil samples tested.

4.3 Atterberg Limits

Wherever applicable, these tests shall be carried out by the skilled personnel. The test
result should include liquid limit, plastic limit and shrinkage limit of the soil samples
tested. These tests should be conducted as per IS-2720, Part V & VI.

4.4 Free Swell and Swelling Pressure Tests

If the soil is found to be expansive in nature then these tests shall be carried out by the
skilled personnel.

4.5 Consolidation Tests

The following loading stages shall be employed:


2
0.10, 0.25, 0.50, 1.0, 2.0, 4.0, 8.0 kg/cm .

From e Vs log p curves, pre consolidation pressure shall be determined to establish


whether the soil is normally consolidated or over-consolidated. The point (e, p) showing
initial condition of the soil under test must be specifically marked on the consolidation
curves. Settlement predictions based on the field virgin compression curve shall only be
acceptable. The procedure adopted in respect of obtaining compression indices from the
field curve & that for computing settlements for the type of clay under consideration
shall be clearly illustrated in the report.

It is to be noted that deviations from the standard procedure of performing


consolidation tests given in IS-2720 Part XV are permissible in order to enable
computation of settlements based on the above procedure i.e. cycle(s) of loading,
unloading& reloading shall be employed wherever required.

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 6 of 9
Copyright GAIL – All rights reserved
The following curves shall be included in the report:

a) e Vs log P
b) e Vs p
c) Compression Vs log (t) or compression Vs t

The choice of relationship depends upon the shape of the plot, which enables clear
determination of CV, the coefficient of consolidation.
The time period required for 50% & 90% primary consolidation should be given in the
report. Computation of secondary settlements, if significant, shall also be made and
included in the report.

4.6 Unconfined Compressive Strength

These tests shall be done as per IS-2720 (Part- X) on selected soil sample.

4.7 Triaxial Tests

These tests shall be done on specimens saturated by the application of backpressure.


Only if the water table is at sufficient depth so that chances of its rising to the base of
the footing are meager or nil, the triaxial tests shall be performed on specimens at
natural moisture content. The magnitude of the backpressure applied shall be indicated
in the report.

All the stress strain diagrams as well as Mohr circle envelops shall be included in the
report. Density and water content of the sample tested and modulus of elasticity along
with shear strength parameters shall be reported.

In case the soils are predominantly sandy in nature and sampling is not possible for
triaxial shear tests, box shear tests shall be carried out.

4.8 Modulus of Elasticity

E-value shall be determined from the triaxial tests. Relative corrections applied to the
computed 'E' shall be clearly illustrated in the report.

4.9 Dry density and moisture content relationship

This test shall be conducted on soil sample collected within 1.0m from ground surface
below the top soil. The test shall be carried out, as per IS 2720 Part-VIII.

4.10 Chemical tests on soil and Ground water samples.

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 7 of 9
Copyright GAIL – All rights reserved
This test shall be conducted on soil and water samples for pH, Chloride (Cl) and sulphite
and Sulphate content.(SO3 & SO4)

5.0 REPORT:

5.1 Interim reports shall be furnished at various stages of investigation for our comments.

5.2 Detailed report shall be prepared and submitted to us as soon as the field and
laboratory works are completed in a draft form for our review and comments. All the
informations as mentioned below shall be furnished in the draft copy of final report.
After reviewing, contractor shall be informed about our comments / remarks, if any,
the same shall be incorporated. The report shall also include but not limited to
following :

1. A plot plan showing all the test locations with respect to reference chainage.

2. General geological information of the site.

3. Character and genesis of soil.

4. Procedure of investigation and method of various testing adopted.

5. Detailed bore logs indicating co-ordinates, reduced level, ground water table
etc., subsoil section along various profiles indicating boreholes nos. depth wise,
in-situ tests like SPT.

6. All field and laboratory test results shall be plotted against depth and also in
tabular form.

7. Summary of results obtained from various tests and their interpretation to


evaluate various soil parameters.

8. Ultimate and safe bearing capacity from shear as well as from settlement criteria
(i.e. for 25mm & 40mm) for the shallow footings of size ranging from 1m to 4m
and for rafts of size greater 6.0m placed at different depths from 1 to 3 meters.
The capacities shall be worked out based on the various field and laboratory
tests viz. SPT, shear parameters etc.

9. Comments on chemical aggressiveness of soil and ground water on reinforced


concrete, steel and other building materials and firm recommendations on
remedial / preventive measures.

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 8 of 9
Copyright GAIL – All rights reserved
10. Recommendations regarding design and construction of roads and other paved
structures and also suitability of soil for back filling foundations.

11. Recommendation related to site preparation including classification, placement


and compaction of fill materials required to bring the general site level of final
grade level, if so required. Recommendations regarding excavation, stable
slopes for excavation, dewatering and method of dewatering, if warranted.

All recommendations shall be supported by back up calculations.

No extra payment shall be admissible for preparation of report.

SPECIFIC REQUIREMENTS FOR


GAIL (INDIA) LTD GEOTECHNICAL INVESTIGATIONS FOR DOCUMENT No. REV-0
NEW DELHI PIPELINE LAYING AND ASSOCIATED
WORKS TENDER 0001-01-10-02-003 Page 9 of 9
Copyright GAIL – All rights reserved
GAIL(INDIA) LIMITED

JOB SPECIFIC REQUIREMENTS FOR CIVIL-STRL


WORKS FOR
PIPELINE LAYING AND ASSOCIATED WORKS
TENDER

JOB SPECIFIC REQUIREMENTS FOR


DOCUMENT No. REV-0
CIVIL-STRL WORKS FOR PIPELINE
GAIL (INDIA) LTD LAYING AND ASSOCIATED WORKS. Page 1 of 4
NEW DELHI 0001-01-10-02-004
SPECIFIC REQUIREMENTS: CIVIL-STRUCTURAL WORKS

1. Structural concrete shall be of DESIGN MIX.

2. Concrete grade for RCC works shall be M 30, with minimum cement content
3
of 330kg/m and a maximum free-water-cement ratio of 0.5.

3. 75 mm thick lean concrete of proportion 1: 5: 10 shall be provided under all


RCC foundations except under base slab of liquid retaining structures where
100 thick concrete of mix 1:3:6 shall be used. The lean concrete shall extend
50mm beyond the foundation for normal foundations and 75mm under liquid
retaining structures.

4. Concrete grade for PCC works shall be M 15, with minimum cement content
3
of 265kg/m and a maximum free-water-cement ratio of 0.6.

5. Plain cement concrete mud mat of M15 (by weight) of minimum 150mm
thickness shall be provided under all masonry wall foundations.

6. Type of cement and clear cover to reinforcing steel for all foundations and all
structural elements in contact with soil shall be as per Geotechnical data.

7. Anti-termite treatment shall be provided for all buildings as per specifications.

8. Reinforcing steel shall be TMT deformed steel bars of grade Fe415


conforming to IS1786.

9. Structural steel shall be of yield stress of 250 MPa conforming to a minimum of


Grade A of IS 2062. Tubular steel shall conform to Yst 240 of IS1161.

10. Anchor bolts shall be of mild steel confirming to IS: IS2062 grade A.

11. 40mm thick concrete of Grade M20 (using 10mm down aggregates) shall be
provided as Damp Proof Course (DPC) at plinth level under all masonry
walls, overlain with bitumen layers as per specifications.

12. Floor gratings and handrails shall be galvanized. Galvanized Electro forged
MS Gratings shall be of mild steel and minimum 25mm deep. The maximum
size of voids in the grating shall be limited to 30mmx55mm. Galvanizing shall
be 900 g/m of surface area.
13. Shop primer and finish paint shall be applied on all fabricated structural steel
(except handrails and gratings) with paint system as per specification No. 6-
JOB SPECIFIC REQUIREMENTS FOR
DOCUMENT No. REV-0
CIVIL-STRL WORKS FOR PIPELINE
GAIL (INDIA) LTD LAYING AND ASSOCIATED WORKS. Page 2 of 4
NEW DELHI 0001-01-10-02-004
0
44-0004 - Table 8.0 (for a design temperature (-) 14 to 60C). Surface
preparation of structural steel for application of paint shall be as per relevant
clause of 6-44-0004.

14. Grouting shall be done with non-shrink grout as per specifications

15. Fabrication & erection drawings shall be prepared by the contractor as per
clause. no. 3 of Specification .

16. Expansive soils, if encountered, the foundation shall be placed below


the expansive soil or cushion of minimum 500 mm well compacted
morrum/coarse sand laid below foundation. In case rock is
encountered minimum depth of foundation shall be provided as per IS
1904.Expansive soils shall not be used for backfilling purposes.

17. Bricks for masonry work shall be of class 5.0

18. Review of design and approved for construction (AFC) drawings

Complete structural design and AFC drawings for the following structures
shall be got reviewed by owner/owner’s representative in detail before taking
up any construction activity at the work site.

1) Porta Cabin at Dispatch/Receiving Terminals and at SVs


2) Porta Cabins at SV-1, SV-2, SV-3 and SV4
3) Guard Rooms at all SVs and Dispatch and Receiving Terminals
4) Guard Rooms at SV-1, SV-2, SV-3 & SV-4
5) Pipeline facilities
6) Sump Tank
7) Pump Foundation
8) Support for Scraper launcher/receiver
9) Support for basket filters.
10) Compound Wall/ for all PRS , SVs, Despatch / Receipt Terminals

JOB SPECIFIC REQUIREMENTS FOR


DOCUMENT No. REV-0
CIVIL-STRL WORKS FOR PIPELINE
GAIL (INDIA) LTD LAYING AND ASSOCIATED WORKS. Page 3 of 4
NEW DELHI 0001-01-10-02-004
JOB SPECIFIC REQUIREMENTS FOR CIVIL- DOCUMENT No. REV-0
GAIL (INDIA) LTD STRL WORKS FOR PIPELINE LAYING AND
0001-01-10-02-004 Page 4 of 4
NEW DELHI ASSOCIATED WORKS.
Copyright GAIL – All rights reserved
GAIL (India) LIMITED
SPURELIENS ON CHAINSA-JHAJJAR PIPELINE PROJECT

Tender for Pipeline Laying & Terminal Works

JOB SPECIFICATION

(PACKAGED EQUIPMENT INPUTS FOR TENDER FOR PIPELINE


LAYING & TERMINAL WORKS)

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 1 of 15
NEW DELHI
Copyright GAIL – All rights reserved
1.0 TECHNICAL REQUIREMENTS

a) The equipment shall be designed, manufactured, tested and supplied in


accordance with the enclosed data sheets, this job specification, standard
specification for Air conditioning plant, Electrical specifications/data sheets,
Piping specifications, enclosed drawings and all other attachments of the
material requisition.

b) The areas to be air-conditioned are shown in the enclosed architectural


drawings. Accordingly, bidder shall provide all items on lump sum basis and
SHALL NOT INDICATE QUANTITIES OF VARIABLE ITEMS IN THE BID.

c) Relevant constructional details for the areas to be air-conditioned shall be as


per enclosed architectural drawings.

Bidder shall estimate plant capacity considering all internal electrical and
instrumentation heat dissipation. However, minimum capacity of the plant shall
be as indicated in this specification, which shall be complied by the bidder and
bidder shall guarantee the inside conditions throughout the year.

Bidder shall be solely responsible to demonstrate the specified inside conditions.


Bidder shall furnish heat load calculations for summer, monsoon & winter,
psychrometric mixture conditions, and the processes which air undergoes in the
conditioning equipment.

d) Bidder shall include all items required to complete the intent of this specification
not withstanding the fact that such items may have been omitted from the
specification or drawings.

e) Bidder shall furnish all data sheets and drawings for Purchaser's review before
commencement of fabrication/ construction.

f) Bidder shall note that entire data presented by them at bid stage will be
retained for information only. Purchaser shall review the data during detailed
engineering after award of contract, within the framework of this specification.
All comments of Purchaser shall be taken care without any cost and time
implication.

g) Chipping of RCC slab for duct hangers is not allowed. Bidder shall provide
anchor fasteners. Complete supporting structure for duct/ cable /pipe/ tubing
etc. shall be provided by bidder.

h) Air handling section of Packaged Unit shall provide cooling and dehumidification
in summer/monsoon by handling mixture of fresh and return air. Reheating
shall be provided in monsoon to achieve specified inside conditions by means of
finned strip heaters actuated by humidistat, backed up by safety thermostat.
JOB SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 2 of 15
NEW DELHI
Copyright GAIL – All rights reserved
Winter heating shall be achieved by finned strip heaters actuated by heating
thermostat backed-up by safety thermostat.

i) Noise level in AC Plant Room shall not exceed 85 dBA at 1 meter away from
source.

j) Standard Specification for air conditioning plant no. shall be referred for
applicable items by bidder.

k) Bidder shall ensure that fixing arrangement of diffusers is such that there is no
load on false ceiling. Size of diffusers shall match with light fittings. Diffusers shall
be firmly fixed with the ductwork.

l) Insulation material to be used for duct shall have factory laminated aluminium
foil.

m) All foundations including requisite multi layer virgin neoprene pads shall be
provided by the Bidder between foundation blocks & equipments e.g. Package
Unit.

n) All the equipment, electrical and controls shall be suitable for electrical area
classification in which they are installed.

o) All couplings, gears and exposed rotating parts shall be provided with appropriate
guards.

p) Electronically operated spring return type Fire Dampers shall be provided in


supply air and return air paths.

q) Package unit & Fire dampers shall be interlocked by Contractor with gas / smoke
detection and fire fighting system wherever such system exists.

r) The complete supply air ducts shall be insulated. Similarly return air ducts
wherever provided shall be boxed (in exposed areas) and insulated.

s) Safety factor shall be considered as 12.5% in respect of Room Sensible Heat and
10% in respect of Room Latent Heat in heat load calculations. Packaged Units’
actual output capacity shall be worked out based on site conditions.

2.0 DESIGN DATA

2.1 Outside design conditions shall be as indicated.


0
DBT ( C) RH (%)
Summer 38 60
JOB SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 3 of 15
NEW DELHI
Copyright GAIL – All rights reserved
Monsoon 29.4 88
Winter 18.3 65%

2.2 Inside design conditions to be maintained shall be as under:


0
DBT 23 ± 1 C and RH 50 ± 5 %

2.3 Architectural drawing (Areas/ Rooms to be air-conditioned are marked)


Control Building, Drawing No. 0318-00-16-48-1104

2.4 Design information Hours of operation : 24 hours/ day, each day of the
year

3.0 UTILITIES

Electric power shall be provided at single point as specified in Electrical Specification.

4.0 MAKES OF BOUGHT-OUT EQUIPMENT / MATERIAL

ITEM MAKE OF EQUIPMENT

1.Packaged Unit Blue Star/ Voltas/ Batliboi/ Carrier/ KPC/ York 4.Pulleys & Belts Fenner
/ Dunlop 5.Filters Tenacity / Kirloskar / Anfilco / Dyna 7.Fire dampers TSC Instruments
11.Thermal Insulation Lloyds / Metthur Beardsell / U.P.Twiga 12.Pr./Temp. Gauges
H.Guru / Gen.Instruments 13.Solenoid Valves Asco / Rotex / Harion 14.HP/LP/Oil
Pressure Indfoss/Switzer/Honeywell All other Electrical / instrumentation items shall be
of GAIL approved makes as per the approved vendor list. For items not covered in the
above list, bidder shall propose the sub-vendors for the same, with their proven track
record in similar service, which shall be subject to GAIL approval.

5.0 PREPARATION OF SHIPMENT AND PACKING

5.1 Vendor shall prepare equipment with packing appropriate for shipping. Packing shall be
adequate to provide protection against mechanical damage and atmospheric corrosion
in transit and for outdoor storage at job site.

5.2 Open ends of tubes shall be capped for protection.

5.3 One complete set of installation instructions shall be shipped with each
unit.
JOB SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 4 of 15
NEW DELHI
Copyright GAIL – All rights reserved
6.0 IDENTIFICATION

6.1 Each major part of the equipment shall have a permanently attached
stainless steel name plate.

7.0 LAYOUT

7.1 The condenser unit shall be so located that there is enough space at the back (if
required) & sides for free flow of air.

MANUFACTURER SPECIFICATION

8.0 DATA SHEET OF PACAKGE UNIT

OPERATING CONDITIONS

Area Classification Safe

Refrigerant R-22

Type Air cooled

Capacity TR

Quantity

Working

Stand By

Ambient temperature for 400C


selection of air cooled
condensers

MANUFACTURER SPECIFICATION

COMPRESSOR

Make

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 5 of 15
NEW DELHI
Copyright GAIL – All rights reserved
Model

Quantity of compressors per No


package units

Saturated suction temperature Deg c

Saturated suction pressure Kg/Cm2

Saturated discharge temperature Deg c

Saturated discharge pressure Kg/Cm2

Nominal capacity TR

Capacity at design conditions TR

Capacity control arrangement

Type Seal/Open/Semi hermetic

Method of lubrication Oil pump/splash

Shaft power BKW

Shaft speed RPM

Motor KW RPM

Guaranteed power at motor KW


terminals

Grade of lubrication oil

Detail of unloaded starting


arrangement

AIR COOLED CONDENSER


Make
Model
Quantity of condensers per
package unit

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 6 of 15
NEW DELHI
Copyright GAIL – All rights reserved
Type
Total heat rejection TR
Face area of each coil Mm x mm

Face velocity across coil m/sec

Tube O.D. mm

Tube thickness mm

Bends thickness mm

Fin spacing FPI

Quantity of fans per condenser Nos

Air flow rate per fan M3/hr

Type of fan for air circulation

Motor (KW / RPM) per fan KW / RPM

Diameter of fan impeller mm

Make

Model

Total air flow rate - m3 / hr.

Size of filter element- mm x mm


x mm

Air flow rate per element - m3 /


hr.

Quantity of filter elements - Nos.

Face velocity- m /sec

Filtration efficiency-% down to

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 7 of 15
NEW DELHI
Copyright GAIL – All rights reserved
micron

Pressure drop in clean condition -


mm WC

Maximum
allowable pressure drop - mm
WC

Fixing - Flange / Channel

Type of filter - HDPE mesh –


reusable

COOLING COIL

Make

Model

Air entering condition 0C DB / 0C WB

Air leaving condition 0C DB / 0C WB

ADP 0C

Capacity TR

Total air flow rate CFM

Face size mm x mm

Number of rows Nos.

Type DX

Bypass factor

Pressure drop, air side mm WC

Tube O.D. mm

Tube wall thickness mm

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 8 of 15
NEW DELHI
Copyright GAIL – All rights reserved
Bends thickness mm

Fin spacing FPI

Bonding of fins Hydraulically / with mandrel

Velocity of air across coil m/sec.

BLOWER

Make

Model

Type Centrifugal

Blade profile Forward / Backward / Radial

Air Flow CFM

No of impellers Nos.

Impeller diameter
mm
Impeller speed RPM

Static pressure 50 mm WC

Power consumption at shaft kW

Guaranteed power at motor kW


terminals

Drive arrangement V-belt drive

Air outlet velocity m /sec.

Motor
kW / RPM

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
0001-01-10-02-005 Page 9 of 15
NEW DELHI
Copyright GAIL – All rights reserved
Bearing lubrication Oil / grease

Noise level db

No. of belts Nos.

ACCESSORIES

Purchaser’s Bidder’s
Requirement Confirmation

Guard for moving parts Required

Belt tensioner Required

Insulated drain pan with drain Required


connection

First charge of refrigerant, oil, Required


lubricants

Grease nipple for bearings Required

Painting Required

Drain piping Required

V-belt drive package with V-belts Required

Anti vibration mounting Required

Lifting lugs Required

Base frame Required

On-Off damper at the outlet of Required


each package unit

HP / LP cutout Required

Low oil pressure cutout Required

Audio/visual annunciator Required


JOB SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
Page 10 of
NEW DELHI 0001-01-10-02-005
15
Copyright GAIL – All rights reserved
Refrigerant controls

AIR COOLED CONDENSER

Make
Model
Quantity of condensers per package Nos.
unit
Type
Total heat rejection TR
Face area of each coil mm x mm
Face velocity across coil m /sec.
Tube O.D. mm
Tube thickness mm
Bends thickness mm
Fin spacing FPI
Fin thickness mm
Quantity of fans per condenser Nos.
Air flow rate per fan m3 / hr.
Type of fan for air circulation
Motor (KW / RPM) per fan KW / RPM
Diameter of fan impeller mm

FILTER AT PACKAGE UNIT INLET & FINE FILTERS(95% at 5


microns)
Make INLET FILTERS FINE FILTERS
Model
Total air flow rate - m3 / hr.
Size of filter element- mm x mm x
mm
Air flow rate per element - m3 / hr.
Quantity of filter elements - Nos.

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
Page 11 of
NEW DELHI 0001-01-10-02-005
15
Copyright GAIL – All rights reserved
Face velocity- m /sec .
Filtration efficiency-% down to
micron
Pressure drop in clean condition -mm
WC-
Maximum allowable pressure drop -
mm WC
Fixing - Flange / Channel
Type of filter - HDPE mesh – reusable

COOLING COIL
Make
Model
Air entering condition 0C DB / 0C WB
Air leaving condition 0C DB / 0C WB
ADP 0C

Capacity TR
Total air flow rate CFM
Face size mm x mm
Number of rows Nos.
Type DX
Bypass factor
Pressure drop, air side mm WC
Tube O.D. mm
Tube wall thickness mm
Bends thickness mm
Fin spacing FPI
Bonding of fins Hydraulically / with
mandrel
Velocity of air across coil m/sec.

BLOWER
Make

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
Page 12 of
NEW DELHI 0001-01-10-02-005
15
Copyright GAIL – All rights reserved
Model
Type Centrifugal
Blade profile Forward / Backward /
Radial
Air Flow CFM
No of impellers Nos.
Impeller diameter mm
Impeller speed RPM
Static pressure 50 mm WC
Power consumption at shaft kW
Guaranteed power at motor terminals kW
Air outlet velocity m /sec.
Drive arrangement V-belt drive

Motor kW / RPM
Bearing lubrication Oil / grease
Noise level
No. of belts Nos.
ACCESSORIES
Purchaser’s Bidder’s
Requirement Confirmation
Guard for moving parts Required
Belt tensioner Required
Insulated drain pan with drain Required
connection
First charge of refrigerant, oil, Required
lubricants
Grease nipple for bearings Required
Painting Required
Drain piping Required
V-belt drive package with V-belts Required
Anti vibration mounting Required
Lifting lugs Required
Base frame Required
JOB SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
Page 13 of
NEW DELHI 0001-01-10-02-005
15
Copyright GAIL – All rights reserved
On-Off damper at the outlet of each Required
package unit
HP / LP cutout Required

Filter media HDPE mesh - reusable


Blower

Low oil pressure cutout Required


Audio/visual annunciator Required
Refrigerant controls Required

MATERIAL OF CONSTRUCTION
Air Cooled Condenser

Tubes Seamless copper tubes


Fins Aluminium
Frame/casing Carbon steel / Galvanised sheet
Cooling coil
Tubes Seamless copper tubes
Fins Aluminium
Frame/casing Carbon steel / Galvanised sheet
Filter

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
Page 14 of
NEW DELHI 0001-01-10-02-005
15
Copyright GAIL – All rights reserved
Impeller Carbon steel / aluminium /
stainless steel
Shaft EN-8
V-pulleys C.I. multi grooves
DIMENSIONS / WEIGHT
Overall size mm x mm x mm
Overall Kgs.
weight

INSPECTION AND TEST


As per Standard Specification attached.

List of Attachments
1. Scope of Work/ Scope of Supply, Document No. .
2. Drawing Data Requirements, Document No..
3. Standard Specification for Air-conditioning Plant
4. Architectural Drawing of Control Building,

JOB SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR PACKAGED EQUIPMENT INPUTS
Page 15 of
NEW DELHI 0001-01-10-02-005
15
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
SURVEY WORKS

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 1 of 7
NEW DELHI
Copyright GAIL – All rights reserved
CONTENTS

1.0 GENERAL

2.0 SCOPE

3.0 PERFORMANCE REQUIREMENTS

4.0 LOCATION SURVEY OF EXISTING CONTROL POINTS

5.0 TOPOGRAPHICAL SURVEYS

6.0 SPOT LEVELS & CONTROL PLANS

7.0 SURVEY OF EXISTING STRUCTURES

8.0 GRID-STATIONS , BOUNDARY PILLARS AND PERMANENT PILLARS (BUOYS)

9.0 MAPS & DRAWINGS

10.0 DOCUMENTS TO BE HANDED OVER BY THE


CONTRACTOR TO CLIENT.

11.0 PAYMENT

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 2 of 7
NEW DELHI
Copyright GAIL – All rights reserved
1.0 GENERAL

The intent of this specification is to cover the basic requirements for conducting the land
surveys to generate requisite information for the design and field engineering activities.

2.0 SCOPE

This specification covers the land surveys consisting of the following works.

a) Preparation of contour survey maps, with spot levels.

b) Establishment of base line and grid system for defining the co-ordinates of the various
areas.

C) Preparation of surveys maps. One set of survey maps shall be prepared as below :

d) Overall layout of the area to a scale of 1 :2000 with spot levels @ 50 m C/C
and a contour interval of 0.5 meters unless specified otherwise.

e) Electronic file for spot levels.

2.1 The grid system shall be established by constructing cement concrete pillars brick
pillars. stone masonry pillars @ 400 m C/C along the base line and a 200 m C/C at
right angles to the baseline.

2.2 The survey maps shall show all cross drainage works, U/G cables, pipes etc. irrigation
structures, building, trees, electric, Telegraphic poles, transmission towers or any other
prominent physical feature.

2.3 Establish reliably High flood level and its source and indicate the source of information.

2.4 For sea shore locations, indicate tidal data such as low tide, high tide and mean tide

2.5 Identify storm water disposal point as naturally existing as per site conditions.

2.6 The contractors shall identify Bench mark of the area and shall carry over level from
Bench Mark to the site bench mark. This reference of BM shall be recorded on survey
drawings.

3.0 PERFORMANCE REQUIREMENTS

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 3 of 7
NEW DELHI
Copyright GAIL – All rights reserved
3.1.1 The work shall be carried out as per the well established, sound survey practices and
standards and by qualified and competent surveyors under the direct supervision of
qualified engineers and surveyors.

3.2 The Contour survey shall be carried out with reference to the existing permanent bench
marks.

3.3 All measurements shall be in metric units.

3.4 The corrections arising from the standard errors, variations in temperatures, pulls etc.
shall be incorporated to the linear ground measurements.

3.5 The observations for the measurement of vertical distances on bench marks and turning
points shall be read nearest to 5 mrn and for other nearest to 10mrn.

3.6 The error for linear measurement shall not exceed 1: 10,000 and for angular
measurements, six seconds per station.

4.0 LOCATION SURVEY OF EXISTING CONTROL POINTS

4.1 A preliminary survey to identify exising control points shall be carried out and their
correctness ensured.

4.2 All such control points shall be demarcated in the area plan.

4.3 The nearest available permanent bench mark shall be transferred to the area either on
a permanent feature or on a concrete pillar specially erected for the purpose.

5.0 TOPOGRAPHICAL SURVEY

The topographical surveys shall be carried out in the following way.

5.1 Horizontal Control

The horizontal control shall be fixed by one or a combination of the following:

a) Triangulation.

b) Closed Traverse.

5.1.1 Triangulation

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 4 of 7
NEW DELHI
Copyright GAIL – All rights reserved
The triangulation work shall start from a baseline, having a minimum length of 100
meters in relation to a point whose co-ordinates have been established. The accuracies
of linear and angular measurement shall meet the requirements defined in Para 3.0.

5.1.2 Before starting the triangulation work, grid pillars shall be constructed on the base line.

5.1.3 Closed Traverse


The closed traverse shall be set by the measurement of angles between two successive
lines.

The angles shall be measured with theodolite only. The distance between two traverse
stations shall not be more than 100 meters.

The cumulative angular error of the closed traverse shall not be more than 30lN
seconds where N is the number of traverse station. All the traverse shall have an
accuracy of not less than 1:5000.

5.2 Vertical Control

5.2.1 Vertical control points shall be fixed by dumpy level on all the traiangulationltraverse
Station, and shall be closed by coming back to the starting point. The accuracy of the
main control shall be + 5 4 K mrn where K is the distance in Kilometers,

5.2.2 After setting horizontal and vertical control, inter-filling can be done either by the
theodolite or by any other means:

6.0 SPOT LEVELS & CONTOUR PLANS

6.1 For taking the spot levels, the area shall be divided into main grids of 50M x 50 M and
levels observed at every inter section. These grids shall be further sub-divided into
smaller grids of 25 M x 25 M to locate prominent physical features of the terrain. The
field levels shall be so obtained as to get a countour interval of 0.5 meters.

7.0 SURVEY OF EXISTING STRUCTURES

The survey of the existing structures shall include road with centre line co-ordinates,
width of roads, berms, details of curves, location of storm water drains, culverts etc.

8.0 GRID STATIONS, BOUNDARY PILLARS AND PERMANENT


PILLARS (BUOYS) :
These shall be constructed of cement concrete brick stone masonry work of sizes as
below:

- Grid stations - 300 x 300 x 1200 mm deep (500 mm below G.L. and 700

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 5 of 7
NEW DELHI
Copyright GAIL – All rights reserved
mm above G.L.).

- Boundary pillars along land acquisition limits at all corners and at 400 mm
C/C in straight reaches shall be constructed. Size shall be 300 x 300 x 1000
mm deep. ( 500 mm below GL and 500 mm above GL).
Permanent Pillars(Buoys) shall be of size 1500 x 1500 x 2000 mm with co-ordinates
on RI for future reference as per locations marked in the reference drawings.

Grid stations and Permanent Pillars shall be provided with steel plates 150 x 150 x 10
mm embedded in concrete with 12 mm dia x 150 mm long anchor bolts. These shall
be provided with punch lines & painted with anticorrosive paint. All Grid station and
pillars shall be numbered for easy identification.

9.0 MAPS & DRAWINGS


The survey maps shall be based on the survey work executed and shall show all
relevant information regarding existing features, physical terrain, grid system;
permanent bench mark etc. These maps shall be the sole property of the owner.

10.0 DOCUMENTS TO BE HANDED OVER BY THE


CONTRACTOR TO CLIENT

10.1. The contractor shall hand over all field books neatly maintained as specified elsewhere.
Any clarification required on the field book shall be promptly furnished by the contractor
to Client/Engineer-in-charge.

10.2 Five copies of check prints of the plotted maps shall be supplied by the contractor to
Client/Engineer-in-Charge for their approval along with original which shall be
prepared on the tracing cloth.

10.3 On approval of check prints by Engineer-in-Charge, ten copies of blue prints along with
original tracings on polyster non-tear transparent tracing film in ink for the map shall be
handed over to Engineer-in-Charge.

10.4 In addition to the requirements given above the contractor shall furnish the field in
Electronic file using NORTON EDITOR software in the following formats

STORE bnl,bx, by, bz, b*

STORE bn2, bx, by, bz, b*

nl 1,2,3,4 , n(node no. of spot level

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 6 of 7
NEW DELHI
Copyright GAIL – All rights reserved
b blank space

x x-coordinate

Y y-coordinate

Z z-coordinate
** from key board

Property of Maps

Maps prepared by the contractor based on survey work carried out under this
agreement shall be the sole property of Client. The contractor shall have no right to use
reproduce or pass on to the third party without prior written permission of Client.

11.0 PAYMENT

Payment for survey work shall be made on Area basis as per schedule of items Payment
for grid stations, boundary pillars, permanent pillars (Buoys) shall be made on unit basis
as per schedule of items. No other payment shall be made. All connected works
including supply of drgs. and Electronic files shall be considered as part of the total
work.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SURVEY WORKS
S-10-02-001 Page 7 of 7
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
EARTHWORK FOR UNDERGROUND
PIPING
(GENERAL CIVIL)

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-002 Page 1 of 5
NEW DELHI UNDERGROUND PIPING
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. MATERIALS

3. EARTHWORK IN EXCAVATION FOR TRENCHES FOR PIPELINES

4. BACK FILLING AROUND VALVE PITS AND TRENCHES

5. TRANSPORTATION OF SURPLUS EARTH

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-002 Page 2 of 5
NEW DELHI UNDERGROUND PIPING
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
1. SCOPE

This specification deals with Earthwork for underground piping in all locations covered
under this tender.

2. MATERIAL
All workmanship and material shall conform to the provisions of the following codes and
Standards Specifications IS : 1200 (Part-1) and IS : 3764.

3. EARTHWORK IN EXCAVATION FOR TRENCHES FOR PIPELINES

3.1 Trenching work shall be carried out in all classes of soil including soft rock and
excluding hard rock.

3.2 The trench shall be cut true to the line and level as per drawings.

3.2.1 If the trench is excavated below the required level indicated in the drawing, the extra
depth shall be filled with concrete or approved equivalent materials as directed by the
Engineer-in-Charge at no extra cost to the owner.

3.3 In case of pressure piping, the trench shall be excavated generally as to provide a
cover of 1000 mrn or dia of pipe whichever is more. In case of gravity sewer pipes, the
trench shall be excavated to conform to invert levels as per drawings. However in
certain cases the pipes may run shallower levels. or at deeper levels depending upon
drawing, site condition etc. No rebate for lesser excavations nor extra payment due to
deeper excavations shall be admissible in those cases where pipeline laying rates are
inclusive of earthwork items. The rates quoted shall be deemed to cover all work
connected with trenching, whether trenches with single pipeline or pipelines in common
trenches including road cutting.

3.4 The width of the trench shall be sufficient to give free working space on each side of
the pipe. The free working space shall confirm to IS : 783. Generally it shall not be less
than 150 mm on either side or 1/3 dia of the pipe whichever is greater.

3.5 When pipelines are running parallel whether the trenching shall be individual or
common shall be decided by the Engineer- in-Charge and such decision shall be final
and binding on the contractor. No extra shall be payable for common excavations.

3.6 All earthwork involved in excavations of all types of manholes, catch pits, valve
chamber, inspection chambers, chambers for instrumentation tapping etc. which
are coming on the alignment of U/G piping or defined by drawing as a point of
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-002 Page 3 of 5
NEW DELHI UNDERGROUND PIPING
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
the U/G piping work is deemed to have been covered in the rate for pipe laying.

3.7 All types of shoring and strutting wherever necessary shall be adopted to with hold the
face of earth or cutting in slope as per site requirements, and as directed by the
Engineer- in-Charge . Earthwork in excavation includes dewatering if required, for
which no extra payment will be made.

3.8 Excavated materials shall not be deposited within 1.5M from the top edge of the
excavation, or within a distance equal to the depth of excavation whichever is
higher.

3.9 Any obstacle encountered during excavation shall be reported immediately to the
Engineer-in-Charge and shall be dealt with as-instructed.

3.11 The contractor shall maintain excavated pit in a dry and trim condition

3.12 Necessary barricading and protection of slopes against slips due to traffic shall be
provided to the satisfaction of Engineer-in-Charge. Also necessary warning flags
and lights shall be provided to caution traffic.

3.13 In case of road cutting, all material i.e. metal, soling stone etc., shall be taken out
carefully and kept separately for reuse and road work shall be redone up to the original
level prior to cutting the road with the excavated road materials after lying and testing
of the pipeline within 10 days from the date of starting this work at the cost of the
contractor. The contractor shall provide suitable warning signs and barricades to prevent
accidents
He shall also provide reasonable bye pass at his own cost when a road is cut for laying
pipeline. Tankage dykes cut due to laying of the pipes, shall1 be redone conforming to
the original specifications by the Contractor at his own cost.

3.14 Dewatering shall be done in advance of the installation of the pipe to allow adequate
inspection of padding of the bottom if required and dewatering shall be continued
throughout during installation and backfilling. In muddy or slushy ground, the bed shall
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-002 Page 4 of 5
NEW DELHI UNDERGROUND PIPING
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
be provided with a layer of sand or concrete as directed by the Engineer-in-Charge at no
extra cost. The trench shall follow the gradient of pipeline as specified in the drawing
contractor shall keep the trench in good condition until the pipe is laid and tested . The
and no extra claim shall be entertained due to its caving or setting down either before
or after the pipe is laid. In case pipe is lowered in caved trench and backfilled before
being inspected by the Engineer-in-Charge, the Contractor shall re-excavate the trench
for inspection and backfill it at his own cost.

4.0 BACKFILLING AROUND VALVE PITS AND TRENCHES

4.1 The soil used should be selected and approved by Engineer-in-Charge. Suitable material
can be extracted from available excavated material. The soil should be free from
rubbish, grass, organic matter, stones, building waste etc. It should be free from clods
and hard lumps.

4.2 The filling should commence only after approval of Engineer-in-Charge is obtained and
after the structures or pipes getting buried are tested and approved. Otherwise, if
required contractor shall uncover buried portion and refill at his own cost.

Filling should be done in layers. Each layer should be not more than 20 cm thick when loose
and should be well rammed. With necessary watering, to obtain at least 90% of maximum
laboratory dry density

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-002 Page 5 of 5
NEW DELHI UNDERGROUND PIPING
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION
FOR
BARBED WIRE

STANDARD SPECIFICATION FOR BARBED DOCUMENT No. REV-0


GAIL (INDIA) LTD WIRE
S-10-02-003 Page 1 of 5
NEW DELHI
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 MATERIALS

3.0 EARTHWORK

4.0 PLAIN CEMENT CONCRETE

5.0 BARBED WIRE FENCING WITH R.C.C. POSTS

6.0 BARBED WIRE FENCING WITH M.S. ANGLE POSTS

STANDARD SPECIFICATION FOR BARBED DOCUMENT No. REV-0


GAIL (INDIA) LTD WIRE
S-10-02-003 Page 2 of 5
NEW DELHI
Copyright GAIL – All rights reserved
1.0 SCOPE
This specification establishes and defines the material and construction requirements
for barbed Wire Fencing.

2.0 MATERIALS

2.1 Materials for Civil Works Refer Technical Specification Civil & Structural works
- Materials - Spec. No.S-11-02-002.

2.2 Miscellaneous

All other materials not specified, but required to complete the work shall be of approved
type, make as per relevant Indian Standard Specification (if applicable) and shall be
approved by the Engineer-in-Charge before Procurement.

3.0 EARTHWORK

3.1 Refer Technical spec. Civil & Strl works - Earth work Specification No. S-11-02-003.

4.0 PLAIN CEMENT CONCRETE


Refer Technical spec. Civil & Structural works - Plan and Reinforced Cement concrete -
Spec. No. S-11-02-004.

5.0 BARBED WIRE FENCING WITH R.C.C. POSTS

5.1 Cement Concrete in Precast Post Struts

5.1.1 Cement concrete shall be of M-15 grade with 20 mm and down size crushed stone
aggregates conforming to IS : 383.

5.1.2 The work shall be carried out as per IS:456 in all respects.

5.1.3 Necessary moulds shall be provided for casting the concrete posts and the same sRall
be smooth finished with 1:3 cement sand mortar as directed by the Engineer-in-Charge.

5.1.4 The concrete shall be cured for a minimum period of 14 days.

5.1.5 Payment for this item shall be made on cubic meter basis and the rate shall include
labour, materials, mixing, placing, leaving pockets, fixing barbed wires, inserts in
concrete posts while casting as shown in the drawing or as per the directions of
Engineer-in-Charge. keeping the concrete posts in proper position while concreting,
scaffolding, shuttering, all moulds, curing etc. complete

5.1.6 including handling & transportation from precasting yards to place of fixing, preparation
of precasting yard etc. but excluding cost of reinforcement.

5.2 Barbed Wire for Fencing


STANDARD SPECIFICATION FOR BARBED DOCUMENT No. REV-0
GAIL (INDIA) LTD WIRE
S-10-02-003 Page 3 of 5
NEW DELHI
Copyright GAIL – All rights reserved
5.2.1 Barbed wire shall conform to IS : 278. The coating on the wire shall be smooth and
relatively free of lumps, globes or points. Wires with excessive roughness, blisters,
salarnmoniac spots shall be rejected. Barbed wire shall be made from two strands of
galvanised, twisted 2.5 rnm (12 gauge) steel wire with 4 points of barbs. Each barb shall
have two turns, tightening around one or both line wires making altogether four
complete turns. The barb shall be so finished that four points are set and locked at right
angles to each other. The barbs shall be of gauge 12.

5.2.2 Bracing of the rows of barbed wire shall be as shown in drawing.

5.2.3 All miscellaneous material like staples, straining bolt etc. shall be galvanised. Minimum
length of staples shall be 50 mrn.

5.2.4 The fencing shall be plumb, taut, true to line and complete in all respects.

5.2.5 The barbs shall have a length of not less than 13 mm and not more than 18 mm.

5.2.6 Payment for barbed wire shall be made on running metre basis of two ply, four points
barbed wire fixed in position. The rate shall include supplying and fixing necessary G. 1.
staple, clips, straining bolts painting, tensioning the barbed wire and all materials, labour
etc. required to complete the job.

6.0 BARBED WIRE FENCING WITH M.S. ANGLE POSTS

6.1 M.S. Angle Posts & Struts

6.1.1 Structural steel work shall conform to latest edition of IS : 2062 or equivalent. Barbed
wire fencing shall be as per 5.2 above.

6.1.2 Structural steel work shall be fabricated and erected as shown in the drawings.
Fabrication and erection shall conform to IS : 800.

6.1.3 All materials used for fabrication shall be of new and unused stock and shall be free
from twist, kinks, buckles, or any other defects. Maker's test certificate shall be made
available to the Engineer-in-Charge when called for.

6.1.4 All materials, tools and plants required for fabrication shall be provided by the contractor
and the rates quoted shall make the allowance for the same.

6.1.5 Changes in direction where the angle of deflection exceeds 20" shall be considered
corner post.

6.1.6 Painting shall not commence till it has been inspected by Engineer-in- Charge.

6.1.7 All the paints used shall be synthetic enamel conforming to IS :293 and of approved
manufacturer.
STANDARD SPECIFICATION FOR BARBED DOCUMENT No. REV-0
GAIL (INDIA) LTD WIRE
S-10-02-003 Page 4 of 5
NEW DELHI
Copyright GAIL – All rights reserved
6.1.8 All loose scales, dirt, rust etc. shall be removed with steel wire brushes before applying
a coat of red oxide primer conforming to IS : 2074.

6.1.9 The surface after applying primer shall be made absolutely dry before applying paint.

6.1.10 Two coats of approved synthetic enamel paint over a coat of red oxide primer shall be
applied unless otherwise specified.

6.1.11 Each coat shall be allowed to dry for sufficient time as per manufacturer's directions.

6.1.12 The payment shall be made on weight of the installed structural steel work. The weight
shall be calculated on the basis of IS hand book. The rate shall include supply of all
necessary materials and labour for fabrication, cutting, drilling holes, aligning, fixing
barbed wires, keeping the post in proper position while concreting, including painting
etc. complete as per drawings and directions of Engineer-in-Charge.

STANDARD SPECIFICATION FOR BARBED DOCUMENT No. REV-0


GAIL (INDIA) LTD WIRE
S-10-02-003 Page 5 of 5
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
CHAIN LINK FENCING
(GENERAL CIVIL)

DOCUMENT No. REV-0


GAIL (INDIA) LTD STANDARD SPECIFICATION FOR
Page 1 of 5
NEW DELHI CHAIN LINK FENCING S-10-02-004.
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
1.0 SCOPE

This specification specifies the requirements of chain link fence for security purposes.
The height of the fence shall be approximately 2.00 m to the top of the chain link
fencing at the posts and approximately 2.5 m in vertical height at the top line of barbed
wire attached to the cranked tops of the posts.

2.0 EARTHWORK FOR CIVIL WORKS


Refer specification No S-11-02-003

3.0 CEMENT CONCRETE FOR FOUNDATION & SILL

Refer specification NO S-11-02-004 .

4.0 CEMENT CONCRETE IN PRECAST POSTSISTRUTS


(Straining posts, intermediate posts and struts)

4.1 Post RCC shall be M25 , size 200 sq. Cover R/f 45 stirrups dia 8 ,

Continuous 500mm high & 230 m wide Brick masonry wall (in 1:4 CM with 16 thk. 1:3
CM with 16 thk. 1:3 CM) plaster with proper Fdn. And leveling PCC (M125) shall be
provided . Top of the wall shall be finished with 50 thk. M20 coping Post Fdn. PCC M15
ht. of Overhang 500. Ht. of Chain link fencing 1650 (500 depth high adjusted with Brick
wall beneath chain link fencing) and down size crushed stone aggregates conforming to
IS : 383.

4.2 The work shall be carried out as per IS : 456 in all respects.

4.3 Necessary moulds shall be provided for casting the concrete posts and the same shall
be smooth finished with 1:3 cement sand mortar as directed by the Engineer-in-Charge.

4.4 The concrete shall be cured for a minimum period of 14 days.

4.5 Payment for this item shall be made on cubic metre basis and the rate shall include
labour, materials, mixing placing, leaving pockets, fixing chain link fencing, line wires,
barbed wires inserts in concrete post while casting as shown in the drawing or as per
the directions of Engineer-in-Charge, keeping the concrete post in the proper position
while concreting, scaffolding, all moulds, curing etc. complete including handling &
transportation from precasting yards to place of fixing, preparation of precasting yards
etc. but excluding cost of reinforcement.

5.0 REINFORCEMENT

Refer specification NOS S-11-02-004. & 11-02-005.


DOCUMENT No. REV-0
GAIL (INDIA) LTD STANDARD SPECIFICATION FOR
Page 2 of 5
NEW DELHI CHAIN LINK FENCING S-10-02-004.
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
6.0 CHAIN LINK FENCING

6.1 Materials

6.1.1 Chain Link Fencing

The material requirement shall conform to IS:2721 latest edition. The chain link fencing
shall be woven from 3.55 mm dia wire with mesh size of 50 mm. The mesh wire shall
not vary from the specified dia by more than + 0.05mm.

6.1.2 Galvanised Wires

6.1.2.1 All steel wires shall be hot dipped galvanised wire and dia of the wire shall be
3.55MM. over the galvanised coating.

6.1.2.2 The line wire shall be 4 mm dia mild steel.

6.1.2.3 The stirrup wire for securing the line wires to the concrete intermediate posts &dl
be 2.5 mm diameter mild steel.

6.1.2.4 The tying wire for securing the chain link fencing to the line wire shall be 1.6mm
diameter mild steel.

6.1.2.5 Hair pin staples for fastening down the bottom of galvanised chain link fencing to the
concrete sill shall be of 3.55 mm wire. The ends shall be bent outwards to secure
anchorage.

6.1.3 Cleats for eye bolts shall be of uniform size and shall consists of mild steel angle of
75x50X6 mm.

6.1.4 Eye Bolt Strainers

6.1.4.1 The eye bolt strainer shall consist of bolts with welded eye sufficiently threaded and
fitted with a nut and waster.

6.1.4.2 Two-way eye bolt strainer shall have suitable ring nuts, fitted after wires have been
strained on one side.

6.1.5 Stretcher bar shall consist of mild steel flats 25 mm x 4.75 mm. They shall be secured
to the cleats by steel bolts.

6.1.6 Droppers for barbed wire shall be of M.S not less than 25mm x 4.75 mm thick with
38mm x 4.85 mm half round staples for fastening the barbed wire to them.
DOCUMENT No. REV-0
GAIL (INDIA) LTD STANDARD SPECIFICATION FOR
Page 3 of 5
NEW DELHI CHAIN LINK FENCING S-10-02-004.
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
6.1.7 Barbed Wire

6.1.7.1 Barbed wire shall conform to IS : 278. The coating on the wire shall be smooth and
relatively free of lumps, globes or points, wire with excessive roughness, blisters,
salarnmoniac spots shall be rejected. Barbed wire shall be made from two strands of
galvanised, twisted 2.5 mm (12 gauge) steel wire with 4 points of barbs. Each barb
shall have two turns, tightening around one or both line wires making altogether four
complete turns. The barb shall be so finished that four points are set and looked at
right angles to each other.

6.1.7.2 Bracing of the rows of barbed wire shall be as shown in drawing.

7.1.6.3 The barbs shall have a length of not less than 13 mm and not more than 18 rnrn.

6.2 Erection

6.2.1 Straining posts shall be provided at all ends and corners of fences, at changes in
direction or acute variations in level and at intervals not exceeding 66 mm on
straight lengths of fence. Intermediate posts shall be spaced at regular intervals not
exceeding 3m.

6.2.2 Struts shall be fitted to all straining posts behind the chain link fabric in the direction
of the line of fence.

6.2.3 Fixing chain link fencing

6.2.3.1 There shall be four evenly spaced rows of line wire. the top wire shall be doubled,
making five line wires in all. The bottom wire shall be close to the ground.

6.2.3.2 Each line wire shall be strained tightly by means of eyebolt strainers or winders at each
straining point.

6.2.3.3.1 Each line wire shall be secured to each intermediate post by a wire stirrup passed
through a hole in the posts and secured to the line wire by three complete turns on
each side of the post.

6.2.3.4 The chain link fencing shall be strained between each pair of straining posts and
secured to each straining post by means of a Stretcher bar. One of the top linewires
hall be threaded through the appropriate adjacent rows of mesh, care being taken
that no meshes in the rows are bypassed by the line wire except wheredeviation is
necessary at the straining posts. The second top line wire shall be strained in front of
the fencing. The fencing shall be attached to the top and bottom line wire by wire
ties spaced 150mm apart and to the other line wires by wire ties spaced 450 mm
DOCUMENT No. REV-0
GAIL (INDIA) LTD STANDARD SPECIFICATION FOR
Page 4 of 5
NEW DELHI CHAIN LINK FENCING S-10-02-004.
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
apart.

6.2.3.5 The bottom of the fencing shall be treated as follows:

Continuous concrete sill 125 mtr wide x 225 high for full length between post shall
be cast with the top 25 mm above G.L. and 25 mm below the chain link fencing. Hair
pin staples shall be threaded through the bottom row of mesh at 0.75 m clc and
set in the sill to a depth of 150 mm.

6.2.3.6 Payment

Payment for chain link fencing shall be made on running meter basis for bottom 2.0
meter height of the total fence height including supply of chain link fencing in 1.9
meter width roll, fixing in position true to line and as per drawing. The rate shall also
include supplying and fixing necessary galvanised line wires, stirrup wires, tying wires,
hair pin staples for fixing the fence in conc. sill, etc. tensioning the line wire and
fencing, all materials and labour etc. required to complete the job as per drawings and
direction of Engineer-in Charge.

6.2.4 Fixing barbed wires for Anticlimbing device

6.2.4.1 Three lines of barbed wire shall be provided as shown in drg. The wires shall be
attached by eye bolts to the cranked tops of the straining posts. On concrete
intermediate posts they shall be secured to cranked tops with stirrup wires. The barbed
wire shall be fitted with one dropper at the centre of each bay, secured to the wires so
that they cannot be bunched together.

6.2.4.2 Payment

Payment for barbed wire shall be made on running meter basis of two ply, four points
barbed wire fixed in position. The rate shall included supply and fixing necessary
droppers, straining bolts tensioning the barbed wire etc. and all materials and labour
etc. required to complete the job.

DOCUMENT No. REV-0


GAIL (INDIA) LTD STANDARD SPECIFICATION FOR
Page 5 of 5
NEW DELHI CHAIN LINK FENCING S-10-02-004.
(GENERAL CIVIL)
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
CLASSIFICATION OF SOIL FOR
EARTHWORK IN SITE GRADING

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD CLASSIFICATION OF SOIL FOR
Page 1 of 5
NEW DELHI EARTHWORK IN SITE GRADING S-10-02-005
Copyright GAIL – All rights reserved
CONTENTS
1 .0 SCOPE

2.0 ORDINARY SOIL

3.0 SOFT ROCK

4.0 HARD ROCK

5.0 FILLING SOIL

6 .0 METHOD OF FILLINGIFIELD DENSITY FOR SOIL COMPACTION

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD CLASSIFICATION OF SOIL FOR
Page 2 of 5
NEW DELHI EARTHWORK IN SITE GRADING S-10-02-005
Copyright GAIL – All rights reserved
1 .0 SCOPE

This Specification covers classification of soil for earth work in excavation and filling for
site grading work. Method of field density for soil compaction using soft rock and hard
rock is also explained.

2.0 ORDINARY SOIL

2.1 Soft Soil/loose Soil

Generally any soil which yields to the ordinary application of pick and showl, or to
phawra, rake or other ordinary digging implements such as :

i) Sand, gravel, loam, clay, mud, black cotton soil.

ii) Vegetables or organic soil, turf, peats, soft shale or loose moorum.

iii) Mud concrete below ground level.

iv) Any mixture of soil mentioned above.

2.2 Hard/ Dense Soil

Generally any soil which requires the close application of picks or jumpers or scarifier
and rippers to loosen the same, such as :

i) Stiff heavy clay, hard shale or compact moorum requiring grafting tool and / or pick
and shovel.

ii) Shingle and river or nallah bed boulders.

iv) Soling or roads, paths, etc. and hard core.

v) Macadam surface of any description (water bound, grouted tarmac etc.).

vi) Lime concrete, stone masonry in lime or cement mortar below ground level.

vii) Soft conglomerate when the stone can be detached from the matrix with picks and
shovels.

3.0 SOFT ROCK

This is fissured/disintegrated rocky strata, boulders (volume less than 0.4M3 and more
than 0.028 SqM ) and also which cannot be quarried excavated by using above manual
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD CLASSIFICATION OF SOIL FOR
Page 3 of 5
NEW DELHI EARTHWORK IN SITE GRADING S-10-02-005
Copyright GAIL – All rights reserved
tools but can be quarried I excavated manually by using crow bars is classified as soft
rock. Soft rock shall include all kinds of stiff and stratified rock as shales, thinly bedded
philites, laterite hard conglomerate, lime stone, sand stone, unreinforced cement
concrete below ground level. Soft rock may be queried or split with crow bar or picks
and can also be excavated by rippers, dozers and other mechanical equipment but
without the aid of blasting. If required, light blasting may be resorted to for loosening
the materials, but this will not any way entitle the material to be classified as "Hard
Rock".

4.0 HARD ROCK

4.1 Hard Rock (Not Requiring Blasting)

This shall include all types of hard and compact rock having closely spaced fissures or
joints on account of which blasting is not considered necessary.

4.2 Hard Rock (Requiring General Blasting)

This shall include all types of hard and compact rock occurring in unfissured masses or
similar foundations, boulders (volume more than 0.4m3) for excavation of which
blasting is considered necessary such as quartzite, granite, basalt stones, reinforced
cement concrete (reinforcement to be cut through but not separated from concrete)
below ground level and the like.

4.3 Hard Rock (Requiring Controlled Blasting)

This type of excavation becomes necessary when excavation is done in formations


mentioned in clause 4.2 in the vicinity of existing foundations I structures. Mode of
blasting shall be decided by Engineer-in-charge keeping in view the sensitivity of
structures.

4.4 Hard Rock (Blasting Prohibited)

Hard rock requiring blasting as described in clause 4.2 above but when blasting is
prohibited for any reasons and excavations has to be carried out by chiseling, splitter or
any other agreed method.

The use of excavation shall not be considered as a reason for classification under hard
rock requiring blasting unless clearly found necessary in the opinion of Engineer-in-
Charge.

5.0 FILLING SOIL

5.1 Ordinary soil used for filling shall meet requirements of clause 3 of Spec.No S-10-02-
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD CLASSIFICATION OF SOIL FOR
Page 4 of 5
NEW DELHI EARTHWORK IN SITE GRADING S-10-02-005
Copyright GAIL – All rights reserved
005 for site grading.

5.2 Use of soft rock for filling shall be determined based on compaction test of filling
material. Well graded soft rock with sufficient fines should make a good filling material.
This shall be tested in field for compaction and then density of compacted soils shall be
determined. Test patches shall be made in field using this material and number of
passes of rollers determined for each patch. A minimum of 3 test patches of 10M x 10M
shall be made. Density of compaction shall be determined in each patch. A density of
1.90gmlcc or more shall be acceptable.

5.3 Use of hard rock with soft rock and soil for filling shall be determined based on
compaction test of rock material to be used for filling. Test patches shall be made as in
case of soft rocks and number of rolls shall be determined for each test patch. Density
of material in all test patches shall be found which should not be less than 2.0gmIcc.

5.4 Engineer-in-charge decision with regard to suitability of such materials shall be final.

6 .0 METHOD OF FILLINGIFIELD DENSITY FOR SOIL COMPACTION

6.1 Filling With Soft Rock/hard Rock Soil

The earth for filling shall be rock soil mass available from cutting areas. Filling shall be
done in loose thickness of 400mm. Voids shall be filled with smaller size material to
ensure well graded and compacted fill, watering, ramming, and compacting with rollers
or other suitable means as approved by Engineer-in-Charge shall be done to achieve
atleast 90% maximum dry density. Stones used in fill material shall not exceed 150mm
in size.

6.2 Field Testing For Density

Each layer shall be tested in field for density and accepted by the Engineer-in-Charge
subject to achieving the required density before laying the next layer. In the event if it
is not possible to conduct compaction test due to presence of stones, the compaction
shall be determined at site by excavating a pit of size O.5m x 0.5m x0.3m (depth) in
compacted area. The excavated soil shall be weighed. The pit shall be filled with water
after laying a thin polythene sheet and weight of water so filled shall be determined.
Alternatively sand can also be used for filling the pit for determine the density. Density
of Filled Material shall be = Weight of Soil/Weight of water This shall not be less than
1.90gm/Cubic Centimetre for soft rock and 2.0 gm/Cubic Centimetre for hard rock fill
area. One test/ 4 0 0 0 SqM compacted area shall be done for every layer of filling. No.
of tests can be increased due to variation in quality of fill material and/or at the
discretion of Engineer-in-Charge.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD CLASSIFICATION OF SOIL FOR
Page 5 of 5
NEW DELHI EARTHWORK IN SITE GRADING S-10-02-005
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
SITE GRADING & ROCK CUTTING
FOR SITE GRADING

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 1 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 GENERAL

3.0 MATERIAL FOR EARTHWORK

4.0 CUTTING TREES

5.0 CLEARING AND STRIPPING

6.0 EARTHWORK IN EXCAVATIONICUTTING

7.0 EARTHWORK IN FILLING

8.0 REMOVAL OF SURPLUS EARTH

9.0 EXCAVATION IN ROCK

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 2 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
1.0 SCOPE

This specification and the method of measurements described thereon are applicable
for Earthwork involved in Site Grading & Rock Cutting.

1.1 Reference Standards


Classification of soil for earth work in site grading 6-65-0016.

2.0 GENERAL

2.1 CONTRACTOR shall maintain adequate drainage facilities at SITE at all times during the
execution of work. Additional ditches, drains & such other temporary means to achieve
this, over and above what is shown in the drawings, will be provided and maintained by
CONTRACTOR at his own cost.

2.2.1 Adequate dewatering facilities like dewatering pumps, piping etc. will also be provided
by the CONTRACTOR for this work and also for dewatering during excavation etc. at his
own cost.

3.0 MATERIAL FOR EARTHWORK

3.1 Only Material considered suitable for the Engineer-in-charge shall be employed for the
construction and that considered unsuitable shall be disposed off, as directed by
Engineer-in- charge, at his own cost and no claim for compensation will be entertained.

3.2 The CONTRACTOR shall give the samples of earth he proposed to use for filling along
with the following characteristics of the samples to Engineer-in-charge, prior to
collection and use, for approval. The tests for these characteristics shall be done in a
laboratory 1 test house as approved by Engineer-in-charge.
I. Mechanical analysis or grain size distribution as per IS:2720 part IV.
ii. Liquid limit as per IS:2720 part v.
iii. Plastic limit as per IS-2720 part v.
iv. Moisture density relationship as per IS-2720 part VII.
3.3 The material ( soil) used for filling shall be free from boulders, lumps, tree roots,
rubbish or any organic deleterious matter.

3.4 Material (Soil) having plasticity index less than 20 shall be used for filling purpose.

3.5 Soil having laboratory maximum dry density of less than 1.5 gms/cc shall not be used.

3.6 Care shall be taken to see that unsuitable waste material is disposed off in such a
manner that there is no likelihood of its getting mixed with the material proposed to be
used for filling.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 3 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
3.7 The work shall be so planned and executed that the best available material (soil) are
reserved for the top portion of Embankments.

4.0 CUTTING TREES

4.1 All trees having girth between 30 cms and 120 cms and which are not marked for
preservation, shall be cut down and their roots dug up to a depth of 1 meter from the
existing ground level.

4.2 All holes or hollows produced by digging up roots shall be carefully filled with approved
material (soil) including all leads and lifts, rammed and compacted to obtain 90%
of maximum laboratory dry density of soil and levelled as directed.

4.3 All uprooted trees shall be stacked or disposed off as directed by Engineer-in-
charge.

4.4 Payment
Cutting of trees above 30 cms girth shall be paid per number. The rate quoted shall
include cutting, uprooting removing the trees within plant boundary as directed,
including filling holes or hollows produced by removal of roots etc. as per specifications.

5.0 CLEARING AND STRIPPING

5.1 The areas including depressions, where filling or cutting is to be carried out shall be
cleared and stripped completely of bushes, roots, vegetation, plantation trees, shrubs,
trees upto 30 cms girth, organic and other objectionable materials. All these shall be
completely uprooted and virgin soil exposed and not merely scrapped at the surface.
The roots of trees of girth upto 30cmsshall be removed to a minimum depth of 1M
below existing ground level and holes, hollows filled up with selected approved available
earth within all leads and lifts and compacted to obtain 90% of laboratory dry density of
soil and leveled as directed by Engineer-in-charge. All soft patches must be worked out
to remove soft soil and selected approved earth must be filled back and the areas
areas coming under filling) compacted to obtain 90% of maximum laboratory dry
density of soil, as per IS:2720 part VII. The depth of stripping shall be generally 50 to
150 mm as decided by Engineer-in-charge.

5.2 Material obtained from clearing shall be stacked or disposed off as directed by
Engineer-in-charge within a lead of 2000M.

5.3 Payment
No separate payment shall be made for clearing, stripping and disposal of materials
obtained from clearing. This shall be considered as part of cutting work in areas of

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 4 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
cutting and filling work in areas of filling and the rates quoted under the respective
items of

i. Earthwork in Excavation/Cutting

ii Earthwork in filling (Both with available earth & earth obtained from approved
borrow areas), shall be inclusive of clearing and stripping with all operations
described above in clause no.5 in respective areas of cutting and filling.

No separate payment shall be made for cleaning, stripping and disposal of materials
obtained from clearing of borrow areas for earth as directed by Engineer-in-charge. This
shall be considered a part of filling work in area of filling and the rate quoted under the
respective items.

6.0 EARTHWORK IN EXCAVATION I CUTTING

6.1 After clearing, stripping of areas as specified above in clause No.5, spot levels at
intervals, and pattern as decided by the Engineer-in-charge shall be taken jointly with
the CONTRACTOR AND Engineer-in-charge, and Excavation 1 cutting shall commence
only after the levels are signed by the contractor as a token of his acceptance.

6.2 Excavation I cutting for this work shall be carried out strictly as per the instruction of
Engineer-in-charge.

6.3 If the contractor excavates 1 cuts beyond the required level, additional quantity of
earthwork shall not be paid for. The excavation taken below the specified level shall be
made good by filling with approved material to the required compaction at Contractor's
cost.

6.4 The final bed and sides of excavation must be leveled, dressed and compacted. In case
of areas under excavation for Site Grading, the final surface shall be leveled, dressed
and consolidated by means of sheep footlpower driven rollers to obtain maximum
compaction. However, no test control is required in such areas.

6.5 Shoring and strutting shall be adopted only with the permission of Engineer-in-charge in
writing. Such shoring and strutting shall be follow the necessary specification and shall
be paid for under the relevant item of Schedule of Rates.

6.6 Provisions for dewatering shall be governed by the relevant clauses.

6.7 Payment

Payment for Excavation shall be on the basis of volume of excavation calculated on the
basis of joint level taken as per clause 6.1, and the final finished grade levels, the
volume being calculated by the Trapezoidal rule. Intermediate payment will be on the
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 5 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
basis of volume calculated based on spot levels taken during the time of the billing,
reference is also invited to clause 6.3.

7.0 EARTHWORK IN FILLING

7.1 After clearing, stripping and consolidation of areas as specified in clause 5, spot levels
at intervals and pattern as decided by Engineer-in-charge shall be taken jointly with the
CONTRACTOR and Engineer -in-Charge and filling shall commence only after the levels
are signed by the CONTRACTOR as a token of his acceptance. Approved fill Material
shall be spread in uniform layers not exceeding 30 cms in loose depth.

The contractor has to make his own approach and access roads from the borrow area
to the demarcated filling areas. While the CONTRACTOR may make use of such short
cuts as may be available to him for earth movement from borrow areas to the filling
areas, the OWNER does not guarantee any passage way or right of way for the
CONTRACTOR work other than available at site. No claim shall also be admissible to the
CONTRACTOR on account of his having to take longer leads or routes for earth
movement, than envisaged by him, either due to any road cuttings, non-availability of
routes, or any other grounds whatsoever.
In case total filling required in any area consists of earth both from borrow areas and
available approved excavated material from within plant area, then joint levels, shall be
taken before commencing filling with earth from borrow area.

However earth from borrow areas required for filling can be used only after the
available earth from excavation within demarcated area has been utilised and clearance
to this effect obtained from the Engineer-in-charge.

7.2 All clods, lumps etc, shall be broken before compaction.

7.3 Successive layers of filling shall not be placed until the layer below has been thoroughly
compacted to satisfy the requirements laid down in this specification.

7.4 Prior to rolling, the moisture content of material shall be brought to within plus or minus
2 % of the Optimum Moisture Content as described in IS:2720 part VII. The moisture
content shall preferably be on the wet side for potentially expansive soil.

7.5 After adjusting the Moisture Content as described in clause 7.4, the layers shall
Be thoroughly compacted by either sheep foot roller or power driven roller or vibratory
roller as approved by Engineer-in-charge till the specified maximum laboratory dry
density is obtained..

7.6 Each layer shall be tested in field for density and accepted by Engineer-in-charge
subject to achieving the required density before laying the next layer. A minimum of
one test per 5001112 for each layer shall be conducted.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 6 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
7.7 If the layer fails to meet the required density, it shall be reworked or the material shall
be replaced and method of construction altered as directed by Engineer-in-charge to
obtain the required density.

7.8 The filling shall be finished in conformity with the alignment, levels, cross-section and
dimensions as shown in the drawing.

Earthen embankment shall be filled 300mm more on both sides, where height is more
than 1 M, and this extra filling shall be dressed, after compaction, in conformity with
alignment, level, cross-section and dimension as shown in the drawing to achieve
proper compaction in the slope. No extra payment shall be made in this regard.

7.9 Extra material shall be removed and disposed off as directed by the Engineer-in-charge.

7.10 Tolerances
General site grading including cutting and filling in depressions shall be carried out to
within up down tolerance o +5 cms of final lines grades and slopes.

7.11 Payment
Payment for filling shall be made on cubic meter of volume calculated on the basis of
cross section plotted from the levels of ground, where filling is to be carried out and the
levels reached after filling is duly consolidated, volume being calculated by Trapezoidal
method. In case of simultaneous cut and fill operation, wherever specified, payment
shall be made on the basis of one composite rate for cutting and filling, all other details
about measurement etc. remaining same as above. No extra payment shall be made
towards testing charges.

8.0 REMOVAL OF SURPLUS EARTH

8.1 Surplus earth and soil excavation and general site grading shall be removed from the
construction areas to the area demarcated by the Engineer-in-charge.

8.2 Payment
Payment shall be made only for lead beyond initial lead from construction area. Rate
shall include loading, transportation, dumping, stacking the surplus earth and soil in the
area demarcated by the Engineer-in-charge.

Payment shall be made on cubic meter basis of the difference of measurements of


The volumes of the excavation and the measurement of the filling with the excavated
earth. However, the contractor's entitlement to payment shall be restricted to the actual
quantity of earth removed. Quantity generated due to void
in back filled volume of earth shall also be removed by the contractor at no extra

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 7 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
cost and this disposal of earth shall not be measured and paid under any item.

9.0 EXCAVATION IN ROCK

9.1 Blasting operations shall be carried out with the prior permission and in the presence of
the Engineer-in-charge or his authorised representative and during fixed time hours of
the day.

Blasting operations shall be carried out as per Indian Explosive Rules 1983, amended up
to date. The contractor shall obtain license from controller of explosives to carry out
blasting operations as well as for obtaining and storing the explosives as per Indian
Explosive Rules (latest). All safety precautions such as providing safety nylon netting
etc. shall be carried out as per instructions of the Engineer-in-charge.

9.1.1 The contractor shall ensure that all workmen and the personnel at site except those
who have actually to light the fuse are evacuated from the unsafe area to be
determined by the Engineer warned by loud speaker in local language to safe distance,
not less than 200 meters at least 15 minutes before firing time by sounding warning
siren. The area shall be encircled by red flags. The contractor shall be responsible for
any accident to workmen, public or property due to blasting operation.

9.1.2 Gun powder, gelatin and other safe explosives only shall be used wherever possible.
Explosives with nitroglycerine shall be used only under exceptional circumstances with
prior approval of the Engineer.

9.1.3 All fuses shall be cut to the length required before being inserted into the holes.

9.1.4 The no. of charges to be fired and the actual no. of shots heard shall be compared and
the person responsible must satisfy himself by examination that all the charges have
exploded before work people are permitted to approach the scene. The withdrawal of a
charge which has not exploded shall under no circumstances be permitted, but the
charges shall be flooded with water and the hole marked into a distinguishing manner.
The next hole to be fired shall be at a distance of about 500 mm from the old hole and
fired in the usual way.

9.1.5 The contractor or any of his competent authroised person shall be in charge of the
blasting operations and shall be held responsible for strictly observing the safety rules,
particularly applicable to blasting operations, in addition to other safety rules.

9.1.6 In blasting rocks with dynamite , the following general principles shall be observed.

In genera1, the following diameter of drills shall be used for different depth of bore-
holes.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 8 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
From 1-2 meters 25mm diameter

From 2-3 -25 meters 37-50mm diameter

From 3.25-4.75metres 50-65mm diameter

The boreholes should generally be not more than 1.5m deep and the distance apart
should be from one and a half to twice their depth.
Cracks and fissures in the rock to be blasted shall be carefully studied to ascertain the
best position for the boreholes. The charge shall always be placed in a sound piece of
rock, if possible not nearer than 300mm from the crack.

9.2 Rules for Blasting with Dynamite and other High Explosives

9.2.1 The Person-in-charge must show that he is thoroughly acquinted with the blasting
operations and that he understands the rules herewith laid down. We will be held
responsible for any accident that may occur. He must be a licenced blaster with a valid
license from DGMS.

9.2.2 Boreholes must be of such a size and uniform that the cartridges can easily pass down
them.

9.2.3 The position of all holes to be drilled must be marked out with white paint thus and the
person-in-charge must take particular note of these positions.

9.2.4 The drilling operation being finished, the person-in-charge must make a second
inspection and satisfy himself that the boreholes marked out by him have been drilled
and cleaned properly.

9.2.5 The person-in-charge must prepare all charges necessary for boreholes.

9.2.6 Number of holes to be loaded and fired at one time shall be as per explosive rules.
Boreholes must be thoroughly cleared before a cartridge is inserted. The loading is to
be done by the person-in-charge himself and the position of the charge holes carefully
noted by him. Wooden tamping rods only to be used in charging holes (not pointed out
cylindrical thought, one cartridge at a time must be inserted) and gently pressed with
the tamping rod.

9.2.7 Immediately before firing a blast, due warning must be given and the person-in-charge
must see that all the labour have retired to safety.

9.2.8 The safety fuse of the charged holes are to be lighted in the presence of the person-in-
charge who must see that the fuses of the holes charged have properly ignited .After

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 9 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
the blast, the person-in-charge must carefully inspect the work and satisfy himself that
all the charges have exploded.

9.3 Misfires

9.3.1 Misfires are a source of great danger, if it is suspected that part of the blast failed to
fire is delayed, allow sufficient time to elapse before entering the danger zone. When
fuse and blasting caps are used, a safe time, atleast an hour should be allowed.

9.3.2 None of the drillers are to work near these holes until the three following operations
have been done by the person-in-charge.

a. The Person-in-charge should very carefully extract the tamping with a wooden scrapper
and withdraw the fuse with the primer and detonator attached, after which a fresh
primer and detonator with fuse should be placed in this hole and fired; or

b. The hole may be cleared of 300mm of tamping and the direction then ascertained by
placing a stick in the hole. Another hole may then he drilled 150mm away and parallel
to it: this hole to be then charged and fired when the other charge should explode.

c. Drilling in holes not completely exploded by blasting shall not be permitted.

9.4 Precautions Against Misfire

9.4.1 The safety fuse should be cut in an oblique direction with a knife.

9.4.2 All saw dust must be cleared from the inside of the detonator; this can be done by
blowing down the detonation and tapping the open end. No instrument shall be
inserted into the detonator for this purpose.

9.4.3 After inserting the fuse in the detonator, it shall be fixed by means of nippers.

9.4.4 If there is water present, or if the boreholes be damp, the junction of the fuse and
detonator must be made water tight by means of grease, white lead or tar.

9.4.5 The detonator should be inserted into the cartridge, so that about one third of the
copper tube is left exposed outside the explosives. The safety fuse outside the
detonator, should be necessarily tied in position in the cartridge. Water proof fuse only
to be used in the damp boreholes, or when water is present in the bore-hole.

9.4.6 If a misfire has been found to be due to defective fuse, detonator or dynamite, the
whole quantity or box from which the detective article was used shall be rejected.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 10 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
9.4.7 Storage of materials for blasting shall be as per statutory regulations / stipulations of
the concerned authorities.

It shall be the Contractor's responsibility to arrange for proper storage of


Explosives obtain required permissions from concerned authorities. No separate
payment shall be payable for the above.

9.4.8 Cleaning of Excavation

Excavation shall be cleaned, trimmed to exact shape and all disturbed material and
other debris shall be removed. When the excavation have been taken out to the lines
specified as shown on the drawings and the surface cleaned as specified, the contractor
shall notify the Engineer that the excavation is ready for inspection and no further work
shall be done with concrete or backfill until it has been inspected and approved by the
Engineer. Cost of this work is deemed to have been included in the until rates for
excavation.

9.4.9 Use of Excavation on Material

Where any material obtained from the excavation is in the opinion of the Engineer
suitable for use in a particular section of the work as fill or backfill such material shall
be selected if necessary, loaded, hauled, placed, spread and used to construct the fill of
backfill the lines and grades specified for the work. As far as possible the most suitable
of the materials excavated for the work shall be used to construct the fill and backfill
embankments, roads and storage areas where required. The useful rock available shall
be stacked at the locations as decided by the Engineer and the rate is inclusive of the
same also. Materials containing brush roots or other perishable materials will not be
considered suitable.

The suitability of the materials and their disposition in the work shall be subject to
The approval of the Engineer.

9.4.10 Disposal of Surplus

All surplus materials shall be carried away from the site and disposed at dumping sites
selected by the Engineer, upto a lead as indicated in the relevant items of the schedule
of rates. The Engineer may ask the contractor to dump the excavated materials in
regular heaps, bunds, blankets, riprap with regular slopes as directed by the Engineer
and leveled so as to provide natural drainage. As a rule, all softer material shall be laid
along the centre of heaps, the harder and more weather resisting materials forming the
casing on the sides and the top. Excavated rocks which can be used in soling, as road
metals or for making concrete aggregates shall be stacked separately as directed by the
Engineer. All such works as mentioned above is deemed to have been taken into
account while quoting for the excavation and no extras shall be claimed by the

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 11 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
contractor for the above works.

All rock excavated from the pits shall be the property of the Owner.

9.4.11 Stock Piles

When the removal of material from excavations progresses at a faster rate or at


different times then placement in backfill is being accomplished, such excavated
materials shall be stock piled at approved locations adjacent to the work until their use
is authorised.

9.4.12 Spoil Areas

Material excavated for the works which is rejected as unsuitable or not required by the
Engineer shall be disposed of in spoil areas as specified by the Engineer.

The spoil areas shall be left in a neat and sightly condition and sloped to drain properly
as may be directed by the Engineer.

9.5 Control Blasting

9.5.1 General

These specifications lay down the requirements for control blasting for rock excavations
wherever required.

Wherever required by the Engineer, the rock blasting shall be controlled so that
vibration generated during the blasting do not cause damage to the buildings and
installation around built up areas. Similarly the rock pieces should not fly off the pits
and thus damage the buildings and installation around. Apart from the general
precautions mentioned in the preceding paragraphs following protective measures are
suggested as guidelines. Tenderers are requested to carefully check the site conditions
and submit the details of the scheme they propose to adopt for controlling the blast.

9.5.2 Protective Measures

a). Short delay blasting with light charges shall be used.

b). The blast hole shall be covered with 0.6 to 1.0 sqm. mild steel plate of
minimum 6mm thickness.

c. Reinforcement rod mesh not less than 20mm dia at 150mm centers in both
directions shall be over the steel plates.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 12 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
d. Steel plate and reinforcements shall be inspected after every blasting operation
and all twists shall be removed before reuse to the satisfaction of the Engineer.

e. The thickness of the covering plate and the kind of dead weight is to be duly
approved by the Engineer.

When blasting is necessary adjacent to partially or completely built structures the


contractor shall take all precautions necessary to prevent flying rock from
causing damage to the structures. In no case shall blasting be allowed closer
than 15m to any structure after concrete placing has started.

The contractor shall be responsible for all damage caused by blasting whether to
permanent or temporary structure and shall replace or repair the structures at
his own cost.

9.6 Payment
If soil of any classifications other than that specified in the Schedule of Rates is met
during Excavation, the decision of the Engineer-in-charge as to the classification of soil,
levels of the strata of different classifications and their locations shall be binding. In
above case, the total quantity of Excavation shall be computed from the measurement
of the pit trench excavated. The hard rock and soft rock shall be measured separately
from the relevant stacks and each shall be reduced by fifty percent for voids, and paid
under the relevant items. The balance, that is the total quantity of excavation minus the
reduced ( for voids) quantity of excavation for rocks shall be paid as soil as per the
discretion of the Engineer-in-Charge. However, the maximum payment shall be limited
to the volume of the excavated pit trench as approved by Engineer-in-charge.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD SITE GRADING & ROCK CUTTING
S-10-02-006 Page 13 of 13
NEW DELHI FOR SITE GRADING
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION
FOR
CONCRETE PAVEMENT

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 1 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


Abbreviations:
IS INDIAN STANDARD

WBM WATER BOUND MACADAM

RCC REINFORCED CEMENT CONCRETE

PCC PLAIN CEMENT CONCRETE


mm MILL1 METER

Kg/cm2/cm KILOGRAM/SQUARE CENTIMETEWCENTIMETER

M.S. MILD STEEL

"C DEGREE CELCIUS

BS BRITISH STANDARD

C1. CLAUSE

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 2 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


CONTENTS

0.0 SCOPE

0.0 REFERENCE CODES AND SPECIFICATIONS

0.0 MATERIALS

0.0 GRADES AND PROPORTIONING

0.0 EQUIPMENTS

0.0 PREPARATION OF SUB GRADE

0.0 BASE COURSE

0.0 FORMS

0.0 LAYING OF REINFORCEMENT, MIXING, PLACING, COMPACTION &


FINISHING AND CURING

10.0 JOINTS

11.0 OPENING TO TRAFFIC

12.0 METHOD AND BASIS FOR PAYMENT

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 3 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


1.0 SCOPE
This specification establishes the requirements of material, laying and finishing of
concrete pavements.

2.0 REFERENCE CODES AND SPECIFICATIONS


IS: 456- Plain and Reinforced Concrete-Code of Practice.

IS: 1834- Specification for Hot Applied Sealing Compounds for Joints
in Concrete.

IS: 1838, Part-l- Specification for Preformed Fillers for Expansion Joints in
Pavements and Structures (Non Extruding and Resilient
Type): Part 1 Bitumen Impregnated Fiber.

IS: 2720, Part-8- Method of Test for Soils-Part 8: Determination of Water


Content-Dry Density Relation Using Heavy Compaction.

IS: 9214- Method of Determination of Modulus of Sub-grade Reaction


(k value) of Soils in the Field.

Standards for RCC pavement Details.

Standards for Standard Specification for Roads and Flexible Pavement


(Upto WBM Layer)

Standards for Technical Specification - Civil & Structural Works -


Materials.

Standards for Technical Specification - Civil & Structural Works -Plain and
Reinforced Cement Concrete.

In case of conflict between the Clauses mentioned in this Specification and those in
above Codes And Specifications, this Specification shall govern.

3.0 MATERIALS

3.1 Material for Cement Concrete viz. Cement, Sand, Coarse and Fine aggregate and water,
Reinforcements Bars, Embedment, Inserts and Admixture etc.

3.2 Material for WBM shall be as described in GAIL Specification no. 6-65-001 8.

0) GRADES, TYPE OF CONCRETE MIX, PROPORTIONING AND BATCHING

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 4 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


4.1 The grades of concrete shall be as follows:
Type-I Pavement - M30
Type-I1 Pavement - M25
Type-I11 Pavement - M25

4.2 Specification for Concrete mix, Mix Proportioning and Batching shall be as described in
Standard Specification S-11-02-004 and IS: 456.

5.0 EQUIPMENTS
All equipments like sub grade templates, hand tempers, vibrating screens, internal
vibrators, longitudinal floats, bridges, push brooms, straight edges, edging tools etc.
shall be on the worksite in first class working condition and shall have been inspected
by the Engineer-in-Charge before paving operations are permitted to start. Throughout
the construction period, the contractor shall maintain adequate equipment in first class
working conditions to ensure the proper execution of the work.

5.0 PREPARATION OF SUB GRADE

5.0 The area where concrete is to be placed must be cleared of all loose material and
virgin soil must be exposed. Such exposed surface must be consolidated properly to
obtain 95% of Maximum Laboratory Dry Density of the soil. All soft patches must be
worked out to remove the soft soil and selected approved earth must be filled back
and compacted.

5.0 For areas, where pavement is to be laid on cutting / natural grade level, Sub grade
shall be thoroughly compacted to 95% of laboratory dry density as per IS: 2720
Part VIII. For filled up areas, top 450 mm of the soil shall be compacted to 95% of
laboratory dry density below pavement in layers of 150 mm.

5.0 The difference between the sub grade levels of Type-I, Type-I1 and Type-I11
Concrete pavements (due to difference in thickness of Type-I, Type-I1 and Type-I11
pavements) shall be achieved by stripping the grade level and not by filling. Hence,
site-grading level below pavement shall be kept up to sub grade level of Type-I1 or
Type-I11 as the case may be, to avoid filling of smaller thickness at later stage.

5.0 The sub grade or sub base for laying of the concrete pavement shall comply with the
following requirements:

5.0.0 No soft spots shall be present in the sub grade


5.0.0 The uniformly compacted sub grade or base course shall extend at least 300mm on
either side of the area to be concreted.

6.4.3 The sub grade shall be properly drained.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 5 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


6.4.4 The minimum modules of sub grade in wet condition, reaction obtained with a Plate
Bearing Test as per IS: 92 14, shall be 6.0 Kg/cm2/cm.

6.4.5 Sub grade shall be prepared to the lines and grades to match with the slope of
pavement as shown on the drawings.

7.0 PREPARATION OF SUB BASE

7.1 WBM under Type-1 Pavement (Ref. GAIL Standard Drawing No. )
WBM Base Coarse shall consist of 2 layers of WBM Gr.-11, each of 75mm compacted
thickness, as per IRC-19 and described in GAIL Specification no.
7.2 PCC 1 :5: 10 under Type-I1 and Type-I11 Pavement (Ref. GAIL Standard Drawing
No.

6.2 PCC 1 :5:10 in sub base layer shall be as described in GAIL Specification no.

6.2 Sub Base layer shall be prepared to the lines and grades to match with the slope of
pavement as shown on the drawings.

7.5 No concrete shall be placed around manholes or other structures until they have been
brought to required grade and alignment. All sides of manholes / pits etc. shall have
same elevation.

7.6 The sub base layer shall be in moist condition at the time of concrete placement.

8.0 FORMS

8.1 All side Forms shall be of mild steel unless use of wooden sections is specially
permitted. The steel forms shall be of MS channel sections and their depth shall be
equal to thickness of the pavement. The sections shall have a length of at least 3.0m
except on curves, where shorter sections may be used. These forms should be
provided with ample bracing and supports to prevent the springing of the forms
under the concrete pressure or thrust of machinery operating nearby.

8.2 The forms should be in a sufficient number and they should not be removed until
concrete has hardened sufficiently.

8.3 In case wooden forms are permitted, these shall have minimum base width of 100
mm for 15Omm or lesser thick slabs and 15Omm for 200mm thick slabs.

9.0 LAYING OF REINFORCEMENT, MIXING, PLACING, COMPACTION &


FINISHING AND CURING

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 6 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


9.1 Laying Of Reinforcement
All reinforcement work shall confirm to IS: 456 and as described in GAIL Specification
no

9.2 Mixing
Mixing shall be as described in GAIL Specification no. 6-68-0004.

9.3 Placing

8.2.0 The place where concrete is to be poured should be clean and free from all loose dirt,
wooden pieces, dust, standing water etc.

8.2.0 Walking on reinforcement layers is not permissible. Walkways of wooden planks or


similar material can be placed with removable supports and should be independent of
the reinforcement. The reinforcement position should not be disturbed nor should it sag
during carriage and placement of concrete.

8.2.0 Placing and vibration should not take totally more than 20 minutes from time of mixing.
Method of placing should be got approved by Engineer-in-Charge. Segregation during
carriage and placement should be avoided. If during carriage concrete segregates, it
should be remixed before placement.

8.2.0 Concrete should not be dropped from a height of over 1.5m.

8.2.0 To ensure bond and water tightness between old concrete surface and fresh concrete
to be placed, the surface should be cleaned and roughened by "initial green cut" by
wire brushing or chipping. The initial green may be done by wire brush after 6 hours of
placing concrete in order to facilitate the work. Chipping can be done only after 48
hours. A layer of cement slurry with 1:l mix (1 cement: 1 sand) should be poured to
obtain a uniform coating on old concrete. Immediately thereafter, the fresh concrete
should be poured.

8.2.0 Concrete shall be mixed in quantities required for immediate use and shall be deposited
on the sub-grade in a single operation to the required depth and width of the
pavement. Spreading shall be as uniform as possible to avoid re-handling of concrete.
Where however, a certain amount of redistribution is necessary, it shall be done with
shovels and not with rakes. Concrete shall be vibrated with internal vibrators. Concrete
shall be placed continuously until completion of the part of the work between
construction joints or as directed by Engineer-in-Charge continuously until completion of
the part of the work between construction joints or as directed by Engineer-in-Charge.

8.2.0 Placing in inclement weather

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 7 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


All precautions shall be taken for concreting in extreme weather in accordance with
the relevant clauses of IS: 456. Due protection shall be provided to prevent cement
being blown away while proportioning and mixing during windy weather. No
concreting shall be carried out in continuous heavy rains. Necessary arrangements to
cover the freshly poured concrete shall be provided, to protect it from the direct rays
of the sun and from drying winds.

8.2.0 All concreting placement should be co-coordinated with placement of conduits,


inserts, embedded parts etc. executed either by same agency or separately.
8.2.0 Concrete shall be laid in panels as shown in the standard drawing or as directed to;
Engineerin-Charge.

8.2 Compaction & Finishing

8.2.0 Compaction
The surface of the pavement shall be compacted either by means of power driven
finish machine or a vibrating hand screed. For areas where width of the pavement is
very small, hand consolidation and finishing shall be done as follows:

9.4.1.1 Concrete as soon as placed, shall be struck off uniformly and screened to the crown
and cross-section shown on the plans and to such level above the base that when
compacted and finished, the pavement shall conform to the grade and cross-section
indicated by the plans. The entire surface shall then be tamped until a close-knit dense
surface is obtained.

9.4.1.2 The Tamper shall rest on the side forms and shall be drawn ahead with a swing
motion in combination with a series of lifts and drops alternating with lateral shifts.
The aim of this operation is compaction and screeding to the approximate level
required. Subsequent tamping should advance 75 mm at a time in the direction in
which the work is proceeding and in final stages, the tamping should be closer, about
12 mm at a time, until a level and dense surface is obtained.

9.4.1.3 If so directed by Engineer-in-charge, hand operated vibrating tamper consisting


of normal type of hand tamper attached to a pneumatic or electric vibrating unit shall be
used for compaction.

9.4.1.4 Segregated particles of coarse aggregate, which collect in front of the tamper,
shall be thrown outside the forms or thoroughly mixed by hand with a mass of concrete
already on the base.

9.4.1.5 Compaction by tamping shall be carried on till the mortar in the mix just works
up to the surface. The surface shall be examined after compaction correction. If needed
correction shall be made by adding or removing concrete, followed by further
compaction and finishing.
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-007 Page 8 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


9.4.2 Floating
As soon as practicable, after concrete has been struck off and compacted, it shall be
further smoothened and compacted by means of a longitudinal float, 1200 mm long
and 75 mm wide, operated from a foot bridge.

9.4.3 Straight Edging


After floating is completed and excess water removed but while concrete is still
plastic, the slab surface shall be tested for trueness with a straight edge and rectified,
if necessary.

9.4.4 Brooming
After belting and as soon as surplus water has risen to the surface, the pavement shall
be given a broom finish to produce corrugations of uniform appearance of not more
than 1/16 inch in depth.
9.4.5 Edging
Before the concrete has its initial set, the edges shall be carefully finished with an
edger of the radius required and pavement edge shall be left smooth and true to line.
t

9.5 Curing
Curing of concrete shall be as described in EIL Specification no. 6-68-0004.

10.0 JOINTS

10.1 Wherever called for on the drawings, expansion joints, construction joints and sealing
joints shall be provided as per details indicated in the drawing and as directed by
Engineer-in-Charge.

10.2 Sealing of Joints

10.2.1 After the curing, the temporary seal or other intruded materials of all expansion and
contraction joints shall be removed completely and the slots filled with approved joint
sealing compound as conforming to IS: 1834, Type B. The filler material for Expansion
and Sealing joints shall be preformed fillers of Bitumen Impregnated Fiber, conforming to
IS: 1838, Part-I.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 9 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


10.2.2 The edges of the joints shall be thoroughly cleaned and primed with a thin
bituminous paint, which shall be allowed to dry before the sealing compound is
applied.

10.2.3 The primer shall be applied with a brush. The composition of primer shall be as
follows:

Name of Material Percent by weight


1. 200-Penetration Bitumen 66
Blended
2. Light creosote oil 14
Hot/ Cold

3. Solvent Naphtha 20

The bitumen shall be melted and fluxed with oil. When cold, solvent Naphtha shall
be added. BITUMINOUS emulsion shall not be used as primers. Care shall be taken
to ensure that the sealing compound is not heated above 200•‹C and the temperature
does not exceed 180•‹C for long periods.

9.1.3 Sealing compound shall be poured into the joint opening in such a manner that the
material will not be spilled on the exposed surface of the concrete. When required to
prevent pick up under traffic, the exposed surface of the sealing compound shall be
dusted with hydrated lime.

1 1.0 OPENING TO TRAFFIC


1 1.1 Traffic shall not be allowed for a period of 28 days after laying of concrete in
pavement.

1 1.2 Before opening the pavement to traffic, all joints shall be filled and trimmed or
topped out as required.
1 1.3 Sampling, testing and acceptance of concrete work shall be according to IS: 456-2000

12.0 METHOD AND BASIS FOR PAYMENT

12.1 Plain and Reinforced Concrete

12.1.1 Payment for plane and reinforced concrete in pavements shall be made on cubic metre
basis of the volume of the actual finished work done and shall be inclusive of cost of
providing Forms, Pockets, Chamfers, Fillets, Grooves, Cement wash, Curing by
normal moist curing or using curing compound etc. as directed by Engineer-in-
Charge. The rates shall be deemed to include complete cost of getting the respective
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-007 Page 10 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


mix designs approved, making and testing concrete cubes and carrying out other tests
including tests of various ingredients, as per specifications and as directed by
Engineer-in-Charge.

12.1.2 No separate payment shall be made for any admixture used by the contractor for
accelerating or retarding the strength of concrete or for achieving specified
workability / water tightness The rate quoted shall be deemed to be inclusive of all
costs related to any such additive /admixture.

12.1.3 The rate shall however be exclusive of reinforcement, metal inserts, pipe sleeves and
any filler material in expansion / sealing joints.
12.1.4 Where the strength of concrete mix (nominal or design mix) as indicated by tests, lies
in between the strengths of two grades given in Table-1 of GAIL Specification No. it
is accepted by owner/Engineer-in-charge, such concrete shall be classified as a grade
belonging to the lower of the two grades between which it lies. In case the cube
strength shows higher results than those specified for the particular grade of the
concrete, it shall not be placed in the higher grade nor shall the Contractor be entitled
for any extra payment on such account. The concrete giving lower strength than
specified may be accepted at reduced rates after satisfying the safety of the
structure by checking it with tests as specified or rejected entirely at the discretion of
the Engineer-in Charge. The rejected concrete shall be dismantled at no extra cost to
the owner and no payment or extension of time shall be granted for the concrete
so rejected and the formwork and reinforcement used for the same. Cost of any
material supplied by the Owner free of cost shall be recovered from the contractor at
double the prevailing market rate. In case the concrete of lower strength can be
improved by carrying out some strengthening measures entirely at the discretion of the
Engineer-in-Charge, then Contractor shall carry out the said measures including all
related tests at his own cost. If the Contractor is able to make up the strength to the
required grade by such improvement measures to the entire satisfaction of Engineer-in-
Charge, payment shall be made for the grade achieved. However, if the strength of
concrete is not made up to the strength of required grade, payment shall be made only
for the lower strength if such concrete is accepted by the Engineer-in-Charge.

12.1.5 Deductions for openings, pockets etc. shall be as specified in relevant Indian Standard
Codes.

12.2 Reinforcement

12.2.1 Payment for plain round mild steel reinforcement bars and high strength
deformed steel bars shall be on the basis of weight of bare steel, irrespective of any
coating applied, in metric tons.The weight of the bar shall be derived from the sizes and
corresponding unit weights given in hand book of Bureau of Indian Standards.
Standard hook length, chairs, spacer bars and authorised laps only shall be included
in the weight calculated. Binding wire shall not be weighed nor otherwise measured.
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-007 Page 11 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


Measurement for weight shall not include cutting allowance etc.

12.2.1 Rate quoted for reinforcement shall include cost of supplying, decoiling,
straightening, cleaning, cutting, bending, placing, binding, welding if required, and
providing necessary cover blocks of concrete.

12.3 Joints
Payment for expansion joints, construction joints and sealing joints shall be made on
running meter basis. The rate shall include cleaning of joints, filler material and
sealing with approved compound, all material, labour etc. complete, as per
drawing.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-007 Page 12 of
NEW DELHI CONCRETE PAVEMENT
12

Copyright GAIL – All rights reserved


STANDARD SPECIFICATION FOR
FLEXIBLE PAVEMENTS WITH
BITUMEN PREMIX CARPET

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 1 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
CONTENTS
1. SCOPE

2. BITUMEN PREMIX CARPET

3. QUANTITIES OF MATERIALS(PREM1X CARPET)

4. LAYING

5. PAYMENT

6. REMOVEL OF SURPLUS EARTH

7. JOB SPECIFICATION FOR BRICK PITCHING

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 2 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
1.0 SCOPE

This specification establishes the material and construction requirements for the flexible
pavement with Bitumen-Premix Carpet.

2.0 BITUMEN PREMIX CARPET

2.1 Material

2.1.1 Coarse aggregate

The aggregate shall consist of crushed stone of Clean,hard,tough,durable rock of


uniform quality and shall be clean, free from excess of dust, flat or elongated pieces
,soft or disintegrated stone, clay or other deleterious matter. The size of aggregate shall
be as mentioned in the schedule of quantities.

2.1.2 Sand

The sand shall consist of clean hard, durable, uncoated, coarse dry particles and shall
be free from injurious amounts of dust, soft or flaky particles, organic matter or other
deleterious substances.

2.1.3 Binder

The binder shall be bitumen of penetration 80/100 conforming to IS:73. The bitumen
shall be collected on road side drums. Any drum leaking or damaged shall not be
accepted.

3.0 QUANTITIES OF MATERIAL( PREMIX CARPET)

3.1 For Premix Carpet 20mm thick

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 3 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
Material For Premix Carpet For seal coat
Per 100 m2 per 100m2
1) Coarse Aggregate 2.75m3 --
12mm and down size.

2) Bitumen 801 100 150 Kg 68.3 Kg

3) Coarse sand as -- 0.6 M3


sealing aggregate

3.2 For Premix Carpet 25mm thick

1) Coarse Aggregate 3.5m3 --


12mm and down size.

2) Bitumen 801 100 185 Kg 68.3 Kg

3) Coarse sand as - 0.6 M3


sealing aggregate

3.3 For Permix Carpet 50mm thick

1) Coarse aggregate 25mm 5.5M3 --


and down size 5.5m3
(For 35mm thick Carpet 1 Layar).

2) Coarse Aggregate 12mm 2.0 m3 --


and down size (For 15mm
thick Carpet layer).

3) Bitumen 801 100 269 Kg 68.3m3


a). For 35mm thick Carpet
( 1 layer)

b) For 15mm thick Carpet 110 Kg


( I1 layer)

4) Coarse sand as sealing -- 68.3 kg.


aggregate
.
3.4 For Permix Carpet 75mm thick

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 4 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
i) Coarse Aggregate 25mm
and down size ( For 50mm
thick 1 layer)

ii) Coarse Aggregate 25n1m


and down thick I1 layer

iii) Bitumen 801 100


a) For 50 thick I layer 375 kg 68.3 kg.

b) For 25 thick I1 layer 185 kg. --

iv) Coarse sand as sealing -- 0.6m'


aggregate

4.0 LAYING

4.1 Preparation of Road Surface

The existing surface shall be thoroughly cleaned of dust, loose materials caked mud and
other foreign matter with the help of wire brush, chisel, picks etc. before laying the tack
course. The cleaning shall be carried out in such a manner as to expose the stone metal
to a depth of 1 to 2mm without dislodging the interlocking of the metal. All dust and
other material thus removed shall be carried away and dumped at suitable places as
directed by the Engineer-in-charge.

4.2 If pot holes or ruts are found on the existing road surface, these irregularities must be
filled in with premix chippings and well rammed about a week before the carpet is laid.

4.3 Tack Coat

4.3.1 The bitumen shall be heated in asphalt boilers to 1770 - 1880 C and shall be spread
uniformly at the rate of 1 kg/m2 - by means of sprayers. The applied binder shall be
evenly burshed. 4.3.2 The tack coat shall be applied just ahead, keeping pace with
laying of premix carpet.

4.4 Preparation of Premix

4.4.1 Mechanical mixers shall be generally used for preparation of premix Improvised hand
mixing drums may be used if permitted by the Engineer-in-charge. 4.4.2 Stone
chippings of specified size shall be thoroughly mixed dry in the mixer at the rate
indicated above. Binder heated at temperature suitable for the grade of bitumen is
added to the mixer drum at the specified rate per loom3 of surface and thoroughly
mixed till the stone chips are completely coated with the binder.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 5 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
4.4.3 The premix shall be emptied on to wheel barrows or stretchers and carried to work site.

4.5 Spreading of Premix


Immediately after applying the tack coat, the premix shall be spread with rakes to the
required thickness land distributed evenly by means of a drag spreader. The camber
shall he checked by means of camber board and the uneveness shall be rectified.

4.6 Rolling

When the premix has been laid for a length of 15-20 meters. rolling shall be
commenced
with tandem rollers ( 8 to 10 tonnes). Rolling should commence from edges and
proceed
towards centre longitudinally. The wheels of roller shall be continuously moistened to
prevent the permix adhering to the wheels and being picked up.

After the preliminary rolling and honey combing, high spot or depressions shall be
rectified by adding or removing the premix as per requirements and the surface shall be
rolled again to compaction. Camber shall be checked at every stage and any defects
found shall be rectified. Excessive rolling shall be avoided.

4.7 Seal Coat ( For low rainfall areas - under 150 cm/yr )

4.7.1 A premix seal coat, mix preferably in a mechanical mixer after heating the sand should
he
applied immediately after laying the carpet and rolled. Materials required for this seal
coat are as per clause 3.

4.7.2 Seal Coat ( For high rainfall areas- over 150cmlyr)


The material requirement for seal coat in high rainfall areas is as under :-

Binder 80/ 100 = 98 kg / 100m2 of road surface

Coarse aggregates
6.3mm passing IS l0mm
Square mesh retained on
IS sive 2.36mm = 0.9m31 100m2 of road surface.

A liquid seal coat, preferably with chippings as above ( through coarse sand can
also be used) should be applied after laying the carpet. The binder, heated to permitted
temperature, should be applied to the cleaned surface, blinded with chippings and
rolled.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 6 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
Traffic may be allowed on the road preferably 24 hours after providing the seal coat.

5.0 Payment

Payment shall be made on sq.m. basis of finished surface including all labour &
materials as per above specifications.

6.0 REMOVAL OF SURPLUS EARTH

6.1 11 be removed from construction area to the area Surplus earth and soil from
excavation shall demarcated by the Engineer-in-charge.

6.2 payment shall be made only for lead beyond initial 50M from construction areas Rate
shall include loading, transportation, dumping, stacking the surplus earth and soil in the
area demarcated. Payment shall be made on cubic meter basis of the difference of
measurements of the volumes of the excavated pits and the measurements of the
backfilling.

7.0 JOB SPECIFICATION FOR BRICK PITCHING

7.1 Excavation
Trench shall be excavated /dressed true to line, section and grade as per drawings prior
to starting the pitching work.

7.2 Material

7.2.1 Bricks shall be locally available best bricks.


7.2.2 Cement, sand and water used shall be as per IS:269,2 1 16.

7.3 The concrete mix used for bedding shall be as per drawings and schedule of rates.
7.4 The work of pitching shall be done after the bottom concrete has been laid and sides
properly trimmed to the required grade and thoroughly compacted.

7.5 Brick pitching shall be done in 1 :4 cement mortar using best quality locally available
bricks.

7.6 Bricks shall be laid in herring bone pattern with their length at 450 to the length of the
ditch as shown in drawings.

7.7 Mortar joints shall never exceed 6mm in thickness and all bricks shall be laid with
vertical joints quite full of mortar.

7.8 Bricks shall be soaked for a period of at least 12 hours immediately before use and no
broken and damaged bricks shall be used in any part of the work except such as will he

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 7 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
required to close any line of bricks.

7.9 The face of pitching shall be made even and smooth.

7.10 The brick work shall be raked and flush pointed with cement mortar 1 : 3 as specified.

7.10 Payment

Payment for brick pitching shall be made on the basis of area paved. It shall include all
operations described above except the excavation item.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD FLEXIBLE PAVEMENTS WITH
S-10-02-008 Page 8 of 8
NEW DELHI BITUMEN PREMIX CARPET
Copyright GAIL – All rights reserved
GAIL(INDIA) LIMITED

STANDARD SPECIFICATION
FOR RCC PIPE CULVERS
&
ERC CROSSING ETC.

STANDARD SPECIFICATION FOR RCC PIPE DOCUMENT No. REV-0


GAIL (INDIA) LTD CULVERTS & ERC CROSSING ETC.
S-10-02-009 Page 1 of 5
NEW DELHI
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. MATERIALS

3. TRANSPORTATION AND STACKING

4. LOWERING AND LAYING OF PIPES

STANDARD SPECIFICATION FOR RCC PIPE DOCUMENT No. REV-0


GAIL (INDIA) LTD CULVERTS & ERC CROSSING ETC.
S-10-02-009 Page 2 of 5
NEW DELHI
Copyright GAIL – All rights reserved
1. SCOPE

The scope of this specification covers R.C.C pipes culverts and ERC crossings etc.

2. MATERIALS

2.1 the pipe materials , the following codes shall apply:

Specification for precast Concrete Pipes


(With and without reinceforcement ) IS : 458

Code of practice laying of concrete Pipes IS 783

2.2 All pipes must be new and perfectly sound free from cracks cylindrically straight and of
standard nominal diameter and length with even texture. Each pipe shall have collar.

2.3 The contractor shall submit a Manufacture’s test certificate wherever demanded by
Engineer-In- charge or his authorized Representative.

2.4 Spun yarn for pipe joints shall be best quality. It shall be from dust etc.

3.0 TRANSPORTATION AND STACKING

3.1 The transportation of materials to the worksite and stacking shall be done in manner to
cause minimum inconvenience to the traffic and other construction work.

3.2 The pipe shall be protected during handling against impact, shock and free fall to avoid
cracks and damage.

3.3 The contractor shall be fully responsible for the safety and security for materials
transported and stacked in the field.

3.4 Earthwork

Refer STD Specification No S-10-02-005

4. LOWERING AND LAYING OF PIPES

4.1 GENERAL

Laying and jointing of pipes shall confirm to IS : 783 Pipe shall jointly by collar Joints.
STANDARD SPECIFICATION FOR RCC PIPE DOCUMENT No. REV-0
GAIL (INDIA) LTD CULVERTS & ERC CROSSING ETC.
S-10-02-009 Page 3 of 5
NEW DELHI
Copyright GAIL – All rights reserved
The trench shall be checked for proper level, grade and alignment before lowering the
pipes.

4.2 Lowering

The pipe shall be lower cautiously to prevent disturbance of the bed and sides of
the trench. The heavy pipes shall be lowered by means of proper tripodes.
Chain pulley blocks or as directed by Engineer-In-Charge. Maximum care should be
taken to prevent sand etc.

4.3 Laying

4.3.1 Laying of pipes shall proceed up grade of slopes.

4.3.2 The error of grade shall not be rectified by packing up earth under neath the pipe. If
required . Concrete shall be used for packing.

4.3.3 The ends of the pipes shall be kept closed to keep dirt, mud and foreign materials out .
Adequate provision shall be made to prevent floating of pipes in the event of flooding of
trenches.

4.3.4 The body of the pipe for its entire length shall rest on an even bed in the trench and
places shall be excavated to receive the collar for the purpose of joining.

4.4 Jointing of Pipes

4.4.1 A few skeins of spun yarn, soaked in neat cement wash shall be inserted in the groove
at the end of the pipes and the two adjoining pipes butted against each other . The
collar shall than be slipped over the joint covering equally both the pipes. Spun yarn
soaked in neat cement wash shall be passed round the pipes and inserted in the joint
means of caulking tools from both end of the collar. More skein of yarn shall be added
and well rammed home. The object of the yarn is to center the two end of the pipes
within the collar and to prevent the cement mortar of the joint penetrating in to the
pipes.

4.4.2 Cement Mortar 1:2 ( 1 Cement : 2 Sand ) shall be slightly moistened and must on no
amount be soft or sloppy and shall be carefully inserted by hand into the joint. The
mortar shall than be punched and caulked into the joint and more cement mortar added
until the space of the joint has been filled completely with tightly caulked mortar. The
joint shall be finished off neatly outside the collar on both side at an angle of 45
degree.

4.4.3 Any surplus mortar projecting inside the joint is to be removed and the guard against
STANDARD SPECIFICATION FOR RCC PIPE DOCUMENT No. REV-0
GAIL (INDIA) LTD CULVERTS & ERC CROSSING ETC.
S-10-02-009 Page 4 of 5
NEW DELHI
Copyright GAIL – All rights reserved
any damage sack or gunny bags be drawn past each joint after completion.

4.5 Curing

The cement mortar joints shall be cured at least for seven days.

4.6 Testing

All joints in culverts pipe lines shall be tested to a head of 1.5 meters of water above
the top of the highest pipe.

4.7 Payment

Payment shall be made on running Meter basis which includes supplying, lowering,
alying, jointing, curing , all complete.

STANDARD SPECIFICATION FOR RCC PIPE DOCUMENT No. REV-0


GAIL (INDIA) LTD CULVERTS & ERC CROSSING ETC.
S-10-02-009 Page 5 of 5
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
UNDERGROUND AND BOVE GROUND G.I.
PIPELINE SYSTEM (WATER SERVICES)

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD UNDERGROUND AND BOVE GROUND G.I.
S-10-02-010 Page 1 of 4
NEW DELHI PIPELINE SYSTEM (WATER SERVICES
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. MATERIAL

3. EARTHWORK IN EXCAVATION AND BACK FILLING

4. FABRICATION AND ERECTION OF G.I. PIPING


SYSTEM

5. TESTING

6. PAYMENTS

1. SCOPE
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD UNDERGROUND AND BOVE GROUND G.I.
S-10-02-010 Page 2 of 4
NEW DELHI PIPELINE SYSTEM (WATER SERVICES
Copyright GAIL – All rights reserved
This specification covers the fabrication, and erection of G. I. pipeline system both
underground and above ground including excavation, backfilling for the pipeline and testing of
completed system. Rates shall include all incidental work such as transportation of all materials
from owners stores, custody , and fabrication and laying of G.I. piping system.

2. MATERIALS

a) All G.I. piping shall conform to IS: 1239 part I .


b) All gun metal valves shall conform to IS : 778 Class 11.
c) All G.I. fittings shall conform to IS : 1239 Part I1 .

The schedule of pipes & fittings shall be as per schedule of items under respective works.

3. EARTHWORK IN EXCAVATION AND BACKFILLING ETC.

All earthwork for G.I. lines shall be governed by the provisions of GAIL specification s-
10-02-002 "Earthwork for underground piping " to the extent applicable. All earthwork
in excavation, backfilling and transportation are included in the quoted rates.

4. JOINTING AND ERECTION OF G.I. PIPING SYSTEM

4.1 Screw socket Joints.

The screwed end of all GI pipes shall be thoroughly cleaned and painted with a mixture
of red and white lead or teflon before jointing. The joint shall be made by winding a
few threads of hamp round the ends of tubes and then screwing them into sockets to
the full depth of threads. Exposed threads shall be coated with approved anticorrosive
paint. No pipe shall be bentloffset to save fittings. The offset in GI pipes shall be made
only after the permission of the Engineer-in-charge . If threaded end of pipe is
damaged, the contractor shall cut the end with hacksaw and shall prepare new threads
conforming to IS :554 to required length .

All fittings shall be malleable galvanised iron approved by the Engineer-in-charge.


Fitting in GI line shall include all couplings, elbows,
tees,bends,unions,nipples,reducers,flanges with nuts and rubber insertion and all other
fittings to make a complete job.
4.2 Flanged Joints

Flanged joints shall be made by painting the faces of the flanges with red lead and
bolting up evenly on all sides with compressed asbestos gasket as per piping material
specification.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD UNDERGROUND AND BOVE GROUND G.I.
S-10-02-010 Page 3 of 4
NEW DELHI PIPELINE SYSTEM (WATER SERVICES
Copyright GAIL – All rights reserved
4.3 Valves

Flanged or screwed valves shall be installed in locations shown on the drawings as per
specification for screwed or flanged joints.

5. TESTING
All completed G.I. lines shall be hydrostatically tested to a test pressure of 5 Kg/cm2.

6. PAYMENT

Payment shall be made on running meter basis of finished pipeline with fitting after
testing etc, complete. No separate payment shall be made for earthwork in trenching
and backfill, road cutting etc. Payment for valves and flanges etc. shall be made as per
schedule of items on unit rate basis The unions shall be provided at every 50 meter
unless otherwise stated in schedule of items/contraction drawing.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD UNDERGROUND AND BOVE GROUND G.I.
S-10-02-010 Page 4 of 4
NEW DELHI PIPELINE SYSTEM (WATER SERVICES
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
COATING AND WRAPPING OF
UNDERGROUND PIPES

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 1 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. REGULATIONS

3. LIMIT OF UTILIZATION

4. MATERIAL AND PROCEDURE OF WORK

5. REPAIR OF PIPE

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 2 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
1. SCOPE

The scope of this specification is to describe the method of protecting the underground
pipelines by the process of coating and wrapping. The job shall be generally performed in
the following operations:

i) Cleaning the external pipe surface by blasting

ii) Priming with synthetic primer

iii) First coat of coal tar enamel

iv) First layer of inner wrapping with glass fibre

v) Final Coat (2nd. coat) of coal tar enamel

vi) Outer wrap of coal tar impregnated glass fibre

vii) Kraft paper

viii) White wash

In addition, this specification also covers and defines the material specification. method
of cleaning, priming, procedure of coating & wrapping, testing, repairing, handling and
storing etc., required for the satisfactory completion of the job.

2. REGULATIONS

2.1 All materials used shall conform to the quality and testing requirement indicated in
ANSI\AWWA C-203-91 - Coal-Tar Protective Coatings and Linings for steel water pipelines
- Enamel and Tape-hot applied or BS 4164-1987 Coal-Tar - based hot applied coating
materials for protecting iron and steel, including a suitable primer. or ASTM Standards
and or as directed by Engineer-in-charge.

2.2 ISO-850 1 - 1988 Pictorial surface preparation standard for painting steel surfaces.

2.3 SSPC-SP steel structure painting council surface preparation specifications.

SSPC-SP- 1 Solvent cleaning


SSPC-SP-3 Power tool cleaning
SSPC-SP-10 Near white metal blast cleaning

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 3 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
2.4 All appurtenances and equipment to be used for cleaning, priming, coating and wrapping
and testing shall be approved by the Engineer-in-charge.

2.5 If any procedure/specification is seen not covered by this specification then ANSI/AWWA
C-203, BS 4164 clause shall apply.

3. LIMIT OF UTILISATION

The underground pipe line protected by coating and wrapping as described in this
specification should be able to carry a liquid at a temperature up to 600C.

4. MATERIAL AND PROCEDURE OF WORK

4.1 Preparation and Cleaning of Piping

4.1.1 The exterior surafaces of pipes shall be thoroughly cleaned of all rust, mill scale, oil,
grease, dirt, weld scales, weld burrs or other foreign matter etc. mechanically as per
SSPC-SP3. All oil, grease or other contaminants shall be removed by solvent cleaning in
accordance with SSPC-SPI prior to shot or grit blast cleaning. All exterior surfaces of
pipes shall be blasted to SSPC-SP10 or IS0 grade 2%). The surface profile after blasting
shall be 15-25 microns. The procedure for cleaning shall be approved by Engineer-in-
charge. The primer application after cleaning should be within 4 hours of completion of
blasting.

4.1.2 The abrasive blast material shall be free of impurities and inclusion of water and oil. All
abrasives shall be removed by brush off, blast or vacuum type cleaner prior to applying
coatings.

4.1.3 The compressed air for blasting shall be free of impurities and inclusion of water and oil.
Separators and traps shall be provided at the compressor and blasting station. Separators
and traps shall be checked daily for effective moisture and oil removal during coating
operations.

4.1.4 Blast cleaning operation shall not be conducted on surfaces that are less than 15oCor
when the relative humidity is greater than 85% unless preheating of the pipe is
performed. Blast cleaning under these conditions may be performed, provided the pipe
can be warmed to a temperature (not to exceed 400 C) sufficient to perform the blasting
operations.

4.1.5 Prior to primer application, the pipe shall be cleaned to remove any wetness or other
contaminations.

4.1.6 The pipe can be rejected if any laminations or other irregularities at the steel surface
become visible after blast cleaning unless in the opinion of Engineer-in-charge, it can be
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 4 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
accepted by grinding and re-blasting.

4.1.7 The cleaning, priming, coating and wrapping should be carried out by suitable machine
either in contractor's workshop or in well organised site (yard). The entire pipe length
shall be cleaned, primed and coated and wrapped but the ends of the pipes shall be left
without coating and wrapping for a distance of 200mm on each end of pipes for joints,
which shall be coated and wrapped manually at site with two wraps of coal tar tape
coating 2mm thick each as per ANSI IAWWA -C-203-91SEC-8.0 after welding and testing
the pipes. At the end of coated section of the pipe, coating and wrapping should be
tapered for length of 50mm for producing better bond with tape to be done for field weld
joints. The weld end bevels shall be protected at all times during surface preparation.
handling, coating and wrapping of large diameter pipes shall be done individually before
jointing of pipes whereas coating and wrapping of smaller diameter pipes shall be done
after jointing of two or three or more pipe lengths together depends on facilities
available.

4.1.8 Alternatively, if permitted by the Engineer-in-charge. the pipelines shall be adequately


scrubbed manually with stiff wire brushes and scrapped where necessary. The primer
coating should immediately follow the cleaning of pipes. The primer coating may also be
done manually if permitted by the Engineer-in-charge.

4.2. Priming

4.2.1. Material

The primer shall be a type B (fast drying, synthetic) certified to meet ANSIIAWWA C-203-
91 or British Standard BS-4164, Section 3. The primer shall consist of chlorinated rubber,
synthetic plasticiser and solvents suitably blended to produce a liquid coating which can
be readily applied cold by brushing or spraying and which will produce effective bond
between the metal and subsequent coating of coal tar enamel. The main characteristics
of the primer shall be as follow:

-Drying time to touch at normal humidity @ 30•‹C (70%) Approx 5- 15 minutes.


-Flash point, BS 2000: part 170 230 C (minimum)
-Flow time (4mm flow cup) at 230 C,
BS 3900: part A6 35-60 Sec.
-Volatile matter (105-1100C), max.
BS 4164 Appendix A 75% loss by mass
-Coverage @ 25 microns/coat 8-12 m2/lit.

4.2.2. Priming Operation (Cold Application)

- The primer shall be applied on the pipes in uniform thin film (Single coat)@ 25
microns DFT/Coat leaving no drips or runs. The entire surface of the pipe should
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 5 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
be primed without any patch left out by spray I hand brushing. Any holidays or
unprimed places shall be reprimed immediately. Any flooded areas or primer
applied on improperly cleaned pipe shall be cut down to surfaces of pipe and
reprimed at Contractor's cost. The primer shall be cold applied to a clean dry
surface, immediately after cleaning operation.

- The surface shall be dry at the time of applying primer coat. Primer shall not be
applied during rain or fog or on wet surface.

- Primer which becomes foul with foreign substances or thickened through


evaporation of solvent shall not be used.

- Freshly primed pipe shall be placed on clean square cut skids and shall not be
allowed to come in contact with the ground or with any other foreign matter. It
shall remain on skids until lifted or cradled for the coating & wrapping operation.

- During the periods of cold weather, when the temperature of the steel is below
7Oc (45oF) or at any time where moisture collects on the steel, the steel shall be
warmed to a temperature of approximately 30o C which shall be maintained long
enough to dry the pipe surface prior to priming.

- All primed pipes which have excessive coat of dust or primer accumulated over
them before the primer is dry or where primer has become dead shall be
reprimed. The application of coal tar coating shall be taken up after the primer
coat has dried up completely and normally within 24 hours after priming with
maximum limit of 5 days. Otherwise a fresh coat of primer shall be applied at
contractor's cost. The Engineer-in-charge shall approve the primer coat before the
next coat is applied.

- The primer shall be kept in tightly sealed containers when not in use to prevent
evaporation.

- The primer shall be applied as received from the manufacturer and should not be
thinned under any circumstances.

4.3 Coating And Wrapping

4.3.1. Coal Tar Enamel

Enamel shall be composed of a specially processed hard coal tar pitch combined with an
inert mineral filler. Coal tar shall be produced from coal that has a minimum heating
value of 13,000 Btu/lb (7.233x106 Cal/kg) on a moisture and mineral free basis (ASTM D
388), and that has been carbonised in a slot type coke even at a temperature of not less
than 900o.C No Asphalt of either petroleum or natural base shall be acceptable as part of
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 6 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
the ingredients. The enamel (Type -I) shall have the following physical characteristics
conforming to ANSIIAWWA C 203-911BS-4164-1987.

Min. Max.
- Softening point (Ring and ball)
ASTMD – 36 1040C 1160C

- Filler (Ash) ASTM D-2415 by wt. 25% 35%

- Fineness of filler, through 200 mesh


ASTM D-546 by wt. 90% -

- Specific gravity at 25 "C ASTM D 71 1.4 1.6

- Penetration, ANSI/AWWA C 203-91,


Sec.7.2, 0.1 mm
@77 " F(2S " C)- 100 gm . weight for 5 sec. 5 10
@ 1 15 "F(46 "C) 50 g. weight for 5 secs. 12 30

- High Temperature Sag Test


@ 160•‹F(71 "C) ANSI/AWWA C-203-91
sec.7.4 - 1/16” (1.6mm)

- Low Temperature cracking test @-10•‹F,


(-23.3 "C) ANSI/AWWA C 203-91,
sec.7.5 - None

- Impact test @77"F (2S•‹C)650 gm ball,


8ft drop ANSI/AWWA C-203, Sec. 7.7
Direct impact disbonded area - 16in2 (10.323 mm2)
Indirect impact disbonded area

- Peel test, ANSI/AWWA C-203-91, Sec.7.6 - 6 in2 (3871 mm2)

- Spark test 15 KV low amperage - None

- Water absorption, 35 weeks - 0.3%

- Application temperatures(max) - 2250 C2450 C

- Cathodic disbondment test BS 4164 5mm (max)

4.3.2. Glass Fibre Mat for Inner Wrapping

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 7 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
The fibre glass mat for inner wrapping shall be thin, flexible, uniform mat composed of
chemically resistant borosilicate glass fibre tissue or hydrolitic class 3-m conforming to
DIN-12-111 mono - filaments distributed in a random open porous structure, bonded
together with a thermosetting phenolic type resin which shall be compatible with the coal
tar enamel. The inner wrap glass fibre tissue shall be longitudinally reinforced by
continuous filament glass yarn embedded in mat & shall have nominal thickness of 0.5
mm (0.02") and shall conform to ANSIIAWWA C 203-91, Sec. 10.3.1 .excepting the
paramters defined above.

- No disbonding of individual glass fibre shall occur during or following the


embedding process.

- The glass fibre mat shall not cause bubbling under the condition of application.

- The glass fibre mat shall be sufficiently porous so that it can be embedded in the
hot coal tar enamel as it is applied to the exterior of the pipe.

- The glass fibre mat shall be free from thin spots, pimples, lamination, uncured
binder flows, wrinkles, torn edges, dust oil and grease etc.

- The glass fibre mat (reinforced glass wrap) shall also conform to ANSI/AWWA C
203-9 1 section 10.3.1 and the following characteristics

- Weight (minimum) 41 gms/m2

- Nominal thickness 0.5 mm + 0.1 mm

- Tensile Average, Breaking Strength

- Longitudinal direction 2280 N/M of width (min)

- Transverse direction 700 N/M of width

- Porosity The Glass Fibre mat shall have a


prosperity of not more than 1.90mm of water
gauge measured at pressure difference across
the sample at an air velocity of 61 M/Minutes,

- Temp. Resistance The glass fibre tissue shall be


unaffected under load in hot enamel at 5300F
(2880C) for one minute
- Moisture absorption
by wt. at relative humidity
of 95 " at 120•‹F (50•‹C) for 24 hrs.
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 8 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
4.3.3. Outer Wrap Coal Tar Impregnated Glass Fibre

The outer wrap shall be non-woven, thick, reinforced glass fibre mat uniformly
impregnated with coal tar enamel and shall conform to ANSI\AWWA C-203-91, Section
2.4.2 with following characteristics:

- Glass Tissue Base 0.77kg per 100 ft2(9.3 m2)

- Weight (Finished Material) 5.4kg to 6.8 kg per 100 ft2(9.3 m2)

- Thickness 0.76 mm (30 mills)

- Tensile strength
(Average Breaking Strength)

- Longitudinal Direction 6130 N/m of width (min)

- Transverse Direction 4730 N/m of width (min)

- Pliability(1" dia Mandrel 25"C, 2 sec) No cracking

- Weight loss on heating at 2 % (max)


820 C for 2 hours.

- Moisture absorption 5% (max)


percentage of weight at
a relative humidity of
95% & 1200F (500C)
for 24 hours.

The finished reinforced glass fibre mat outer wrap shall have a smooth, uniform surface
free of visible defects. When unrolled at a temperature from 0•‹C to 50•‹C, the outer
wrap shall not crack or stick to such an extent as to cause breaking or tearing. The outer
wrap shall he purchased in tightly wound tied rolls with a 3" diameter core in widths and
lengths as specified at the time of purchase. The rolls shall he packed to exclude dust
and dirt during shipping and handling and shall have card board separators and end
shields adequate to prevent roll damaged when stacked. The sides of the rolls shall be
clean, smooth and squared cut and shall have no telescoping.

4.3.4 Polyethylene craft paper shall be as per sec. 2.4.3 and 2.5 of ANSI\AWWA-203.

4.3.5 The white wash used as a final coat shall be manufactured in accordance with white
wash formulas as specified in ANSI\AWWA C-203-9 1, Section 2.7.
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 9 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
4.3.6 Preparation Of Coating Materials

The coal tar enamel shall be furnished in expandable sheet metal or drums that shall be cropped
or cut out on a suitable platform to prevent the enamel from coming in contact with
weeds, cinders, grass and other form of contamination. The cropped or cut pieces of
enamel may not weigh more than 10 kgs. The pieces of enamel shall be covered when
they are in danger of contamination because of atmospheric conditions. The broken
enamel shall be placed in a clean melting kettle and slowly heated at a uniform rate of
2250C to 2450C (application temperature) or manufacturer's recommended temperature.
Any coating material heated to more than the above mentioned temp. shall be rejected.
Spilled material which has become contaminated shall not he returned to the melting
kettle.

The coating being prepared for use by coating machine shall be agitated in melting
kettles having continuous mechanical agitators. The melted enamel in these kettles shall
be stirred at an interval of not more than 15 minutes during heating with metal agitators.
Wooden paddles or sticks shall not be used for stirring. Accurate thermometers shall be
used on heating kettles in such a way as to be read clearly. The thermometer bulb shall
be within 100 mm from the bottom of the kettle, and shall have temperature range from
1000C - 3000C. Thermocouple can also be used for monitoring the temperature.

Any coating material that has been heated in the kettles to a temperature in excess or
what is specified herein or by manufacturer's recommendation shall be condemned and
shall not be used.

4.4 Application Of Hot Coal Tar Enamel And Inner Glass Fibre

4.4.1. First coat of hot coal tar enamel shall be applied over the adequately cured primed
surface to a minimum thickness of 2.0 mm. The Engineer-in-charge shall cut samples and
test the thickness of coating and further work of outer coating shall be taken up only
after the inner coating has been approved by the Engineer-in-charge.

Simultaneously with first coat of coal tar the glass fibre mat shall be mechanically applied
in machine. It is preferable to pass the fibre glass mat through a bath of hot coal tar
enamel before being applied over the pipe. Sufficient tension shall be applied to the rolls
of fibrous mat to embed it in the coal tar enamel before it cools to furnish a proper bond
with the next layer of coal tar enamel. The glass fibre mat shall be of suitable uniform
width for smooth spiral application. The over lap of the mat shall not be less than 112
inch (12mm). A second coat of hot coal tar enamel shall then be applied of such a
thickness that finished thickness of two layers of enamel, inner and outer wraps shall be
a minimum of 4.0 mm.

4.5 Application Of Second (Outer) Layer Of Coal Tar Enamel Coating & Glass Fibre
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 10 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
Wrapping

Immediately after application of the 2nd layer of coal tar enamel, outer wrap of coal tar
impregnated glass fibre mat shall be applied in a tight uniform spiral and shall be spirally
wound round the pipe with a minimum of 15 mm of overlap on each spiral. The thickness
of final coat of enamel shall he so adjusted that the total finished thickness of double
coating & wrapping in dividing outer wrap is maintained minimum 4.0mm. The coating
and wrapping must be free of pin holes, bubbles or holidays. The Engineer-in-Charge
shall cut samples from the coating from time to time to determine the thickness and bond
of coating.

4.6 Primer, Coating and Wrapping Application for Field Joints of Pipes after Laying
at Site.

4.6.1. Primer shall be applied with brushes after cleaning the pipe throughly (joints portion etc)
as per specification.

4.6.2. Two wraps of coal tar tape 2mm thick each shall be applied as per ANSIIAWWA C-203-91
Sec.8.0.

4.7 Inspection

The word 'Inspector' means a person designated by the Engineer-in-Charge for inspection
and approval of the work under this specification. The entire procedure of applying the
protective coating material as herein specified will be rigidly inspected from the time the
bare pipe is received until the coated pipe is laid in the trench and back-filled and/or
installation of coated pipe is complete. Such inspection shall not relieve the contractor of
his responsibility to furnish material and perform work in accordance with these
specifications and shall not relieve him of the guarantees under this contract. All coating
and wrapping work to be acceptable must be applied in the presence of the inspector.
and all such work done in his absence will be subject to rejection unless the continuance
of the work during his absence in specifically allowed by the inspector. If at any time it is
found that the procedure of applying the protective coating and wrapping material in not
in accordance with these specifications, all such coating work may be rejected. The
coating and wrapping work will be inspected in stages namely after cleaning of the pipes,
application of primer coat, application of coal tar enamels, fibre glass inner wrap and
outerwrap, coal tar impregnated glass fibre.

Prior to approval of the contractor's material, samples of materials submitted by the


contractor will be tested by the contractor for various tests as per the relevant standards
and if any sample is found not conform to these specifications, material represented by
such samples will be rejected. If samples of contractor's approved materials are found
not to conform to the specifications all such materials will also be rejected.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 11 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
Samples submitted to the Engineer-in-charge will be tested in an approved responsible
commercial laboratory, designated by the Engineer-in-charge.

The expenses of testing of all samples of materials offered by the contractor and the
expenses of all subsequent tests due to failure of samples of material originally offered to
comply with these specifications will be borne the contractor.

In addition to above, the contractor shall submit manufacturer's certificates. in original for
each batch of materials used on the job.

The contractor shall furnish the inspector reasonable facilities and space without charge
for the inspection testing and obtaining of such information as he desires regarding the
characteristics of materials used and the manner in which the work is progressing.

Inspection shall be carried out for coating thickness adhesion and holidays along with
visual inspection.

The Field Peel Test Procedure, as per ANSI\AWWA C-203-91 section 7.8 or BS 4164
Appendix -L shall be applied to each pipe initially till the Engineer-in-charge relaxes it
later to a random of one in ten pipes.

The pipe shall be thoroughly inspected for any holidays, pinholes, torn, abraided or
mutilated spots.

The contractor shall furnish and operate at his own cost, a high voltage electronic holiday
detector of type acceptable to Engineer-in-charge. The detector will have to be calibrated
by the contractor at his own cost before use and the calibration shall be witnessed and
approved by the Engineer-in-charge.

4.8 Testing and Repairs

4.8.1. Repair of Pinpoint Or Bubble Type Damage

Dirt, foroeign matter, kraft paper and outerwrap shall be removed using a sharp kinfe,
taking care not to damage the surrounding enamel. Correctly heated enamel shall be
poured over the prepared area to the specified thickness and covered with a patch of
outer wrap.

4.8.2 Repair of Exposed Metal Type Or Extensive Damage

Remove dirt, foreign matter and all surrounding disbonded enamel with a shart knife.
Make a square repair area of 4sq.inch(min) by cutting with a kinfe or higher size if
required. Remove the primer by emery paper. Feather out the edges of coating wrapping
over 112 inch width with a file. Clean the entire area with compressed air. Apply one coat
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 12 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
of synthetic primer.

Use hot-applied coal tar tape (4rnm thick) as per AWWA C-203(91) section 8 for repair.
Take a square cut of the tape with 1 inch higher dimension than the size of the damaged
area. Feather out around 1 inch width on all four sides with a file. Hot apply the tape
patch as per manufacturer instructions. Allow to cure.

4.8.3 Both the repaired area in 4.8.1. and 4.8.2 shall be electrically inspected using a holiday
detector after curing.

4.9 Handling & Supporting Coated Pipes

4.9.1. Contractor shall develop the method of stock piling and loading out coated pipes and
shall receive approval from Engineer-in-charge prior to handling of coated pipes.

4.9.2 The coated pipes shall be carefully handled so as not to damage them in any way. No
wire ropes or chains shall be used to lift the coated pipe. Canvas or rubber belts of
minimum 300mm width and sufficient strength shall be used. The use of tongs, Bare
pinch bars, , chain slings, protruding rivets, pipe hooks without proper padding or any
other handling equipment that may injure the coating shall not be permitted.

4.9.3. If the pipes are coated in a shop, one pipe should not be placed above another during
transit in the wagon or truck. The pipe shall be carried on suitable paddle skids mounted
on the wagon or a truck to ensure that the coating will not be damaged in any way.

4.9.4. Pipes shall be stored in the field under covered protection during rains. Pipe shall he kept
on clean square cut padded wooden skids protected with fibre glass mat felt or straw
until ready to be lowered in the trench.

4.9.5. The contractor handling and transporting the pipe shall conform to standards as set out
in ANSI\AWWA C 203-91 section 9.1 "Handling and Transporting Enameled Pipe".

4.10 Adjacent pipe-lines, Structures etc.

If any damage is caused to the coating and wrapping of adjacent pipes or any other
existing structure during excavation of subsequent work or during coating and wrapping
of field joints the contractor shall carry out necessary repairs at his own cost in an a
manner as directed by the Engineer-in-charge.

5.0 REPAlR OF PIPE

Any damage to the pipe, Such as dents, gauges, flattening or damage caused by
contractor to bevels shall be cut out, the pipe beveled and if necessary, re-welded with
prior approval of Engineer-in-Charge. All such re-welding shall conform to the applicable
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 13 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
provisions of codes. The cost of work, plus the cost of pipe lost due to repair will be to
the account of contractor.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD COATING AND WRAPPING OF
Page 14 of 14
NEW DELHI UNDERGROUND PIPES S-10-02-011
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
MISC. CIVIL & STRUCTURAL

WORKS FOR U/G PIPING & OTHER


(CIVIL WORKS)

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-012 Page 1 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


CONTENTS

1. SCOPE

2. EARTHWORK AND BACK FILLING

3. PLAIN AND REINFORCED CEMENT CONCRETE

4. BRICK WORK

5. CEMENT PLASTERING

6. M.S. RUNGSIC. I. STEPS

7. CHEQUERED PLATES AND STRUCTURAL STEEL


WORKS

8. C. I. MANHOLE FRAME AND COVER

9. VENT PIPES

10. FUNNELS, CLEAN OUTS, PLUGS

11. BRICK BAT FILL

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-012 Page 2 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


1. SCOPE

This specification covers the material and construction details for various civil works as
given below:

a. All Earthwork except for Site Grading and UIG Piping.

b. Plain and reinforced cement concrete work in catch pits clean outs manholes,
pipe

supports, water monitors, hydrant pedestals, Thrust block etc.

c. Brick work for various structures such as Manholes, Catch basins, Valve
Chambers,

instrument tapping chambers, Flushing chambers, etc

d. Plastering for the above structures as applicable.

e. Manhole frames, manhole covers, ladder rungs etc. for the above
structures as applicable.

f. Miscellaneous structure steel work such as ladders, platforms, chequered plate


covers, gratings etc.

The work shall include supply of various materials as per relevant standards, required for
the execution of work except for those items designated as Owner's scope of supply in the
special conditions of contract or elsewhere in the contract documents. Contractor shall
transport from Owner's stores those materials which are a part of owner's supply.

All materials not fully specified herein and which may be used in the WORK shall be of
quality approved by the Engineer-in-charge and he shall have the right to determine
whether all or any of the materials offered or delivered for use in the WORK are suitable
for the purpose. CONTRACTOR shall give the samples of material to the Engineer-in-charge
and shall get it approved before procurement and use.

2.0 EARTHWORK & BACKFILLING

2.1 Refer the specification covered elsewhere in the tender


document.

3. PLAIN AND REINFORCED CEMENT CONCRETE

3.1 Refer the specification No S-11-02-004 covered elsewhere in the tender document. Plain

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-012 Page 3 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


and Reinforced Cement Concrete work shall confirm to Indian Standard for Plain and
Reinforced Cement Concrete- Code of Practice ( Fourth Revision) IS 456:2000.

4.0 BRICK WORK

4.1 Refer the specification covered elsewhere in the tender


document

5.0 CEMENT PLASTERING

5.1 Materials

The specifications for cement, sand and water shall be as given in specification of
the materials.

5.2 Cement mortar shall be of grade and thickness specified in drawing or as directed by the
Engineer-in-Charge, if not specified. The surface on which plastering is to be done shall
be thoroughly cleaned from dust, dirt, oil, etc. It should be washed properly and watered
for 4 hours before plastering. The joints of brick work shall be raked out to a depth of at
least 12mm when plastering has to be done. On cement concrete surface, the surface
shall be scarified by lines with trowel when it is still green or hacked if concrete is hard a
as directed by Engineer-in-Charge.

5.3 Plaster shall not in any case, be thinner than specified. It shall have uniform specified
thickness. Any extra thickness of plaster done by contractor will not be paid for. When
smooth finishing is required the cement plaster shall be floated over with neat cement
within 15 minutes of the application of the final coat. During the process of plastering
all corners shall be rounded to a radius of 25mm unless otherwise specified.

5.4 The plaster shall be protected from sun and rain by such means as the Engineer-in-
Charge may approved. The plaster shall be cured for 7 days.

5.5 Construction joint shall be kept in plastering work at places approved by Engineer-in-
Charge.

5.6 Payment

5.6.1 Payment for plastering shall be made on basis of the area of surface plastered,
measured before plastering. All Measurements shall be separately made for each face
of walls.

5.6.2 The rate of plastering shall include cost of scaffolding, swings, cleaning the surface,
raking out joints, hacking concrete surfaces, etc. needed for carrying the work and
shall cover the extra labour for plastering the jambs, sills, and soffits or opening except
for plastering bands, cornices and skirting upto 30 cm width.
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-012 Page 4 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


6.0 M.S. RUNGSIC. I. STEPS

The rungs for valve pits and manholes shall be of M.S. conforming to Indian Standard
and to the shape and size as shown Drgs. C.I. steps for manholes if used shall be as
per IS : 5455. M.S. Rungs or CI steps shall be coated with 2 coats approved bituminous
paint.

Payment for steps/ rungs shall be made per number and the rate shall include supply
and fixing, finishing the wall etc. complete.

7.0 CHEQUERED PLATES & STRUCTURAL STEEL WORKS

Chequered plates shall be 6mrn (7mm moreover chequers and shall conform to IS :
3502). Steel for chequered plate shall conform to IS32062 and shall be clearly rolled
and free from harmfull surface defects such as crack surface flaws etc. The plate shall
be cut to shape and fixed to the bearing members as shown in relevent drgs and as
directed by Engineer-in- Charge. The edges shall be made smooth, no burrs or gagged
ends shall be left. The plates may be spliced with prior consent of the Engineer-in-
Charge. But in that case care should be taken so that there is continuity in the pattern
of the plates between the portions. Lifting arrangements shall be provided including
lifting rods.

Grating shall be fabricated out of M.S flats, angles and rounds etc., as per drawings and
as approved by Engineer-in-Charge. Steel for grating plates shall conform to IS : 2062
of general Weldable quality and shall be clearly rolled and shall be free from harmful1
surface defects.

Payment shall be made on the basis of weight of M.S Gratings/ chequered plate and
supporting frame actually laid. The rate shall include supply of all necessary, steel
materials cutting to size, fabricating, smoothening edge if necessary, transporting and
fixing at all positions and providing lifting arrangements. Full deductions shall be made
for all opening above 30mm square and the rate shall include making of opening of all
sizes and supplying and painting 2 coats of anticorrosive paint over a coat of red oxide
zinc chromate primer. The expose surface of grating and frame shall be painted with
two thick coats of coal tar. The rate shall include providing and laying M.S grating and
frame, breaking and making good existing concrete/brick masonry surface if necessary
finishing, painting etc. complete with all labour and materials. Payment shall be on
number basis.

8. C.I. MANHOLE FRAME AND COVER

C I manhole frame and covers shall conform to IS : 1726 with size and grade as shown
in Drgs .

9.0 VENT PIPES


STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-012 Page 5 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


These shall be M .S. Black Steel Tube conforming to IS : 1239 Medium grade or as
specified in drgs. The pipe bends shall be embedded in M-20 grade plain cement
concrete suitable for sever exposure condition confirming to IS 456:2000. All pipes
shall be 25mm clear of wall or column with M.S. holder bat clamp as per instructions of
the Engineer-in-Charge. All holes in walls and column shall be made good by M-30
grade plain cement concrete suitable for sever exposure condition confirming to IS
456:2000.

All pipes and clamps shall be painted with two coats of paints of approved make.
Payment shall be made on running meter basis and the rate shall include supply of all
materials, cutting, edge preparation, jointing by welding, fixing in concrete block,
cutting of walls or concrete and making good the same, painting with 2 coats of
anticorrosive paint necessary scaffolding etc. complete. The rate shall also include
excavation and backfilling if any.

10. FUNNELS, CLEAN OUTS., PLUGS

These shall be fabricated from M.S Plates, pipes chequered Plates, rounds, angles etc., to
be supplied the by contractor. The fabric action shall be in accordance with the approved
drgs.

Payment for these items shall be made on weight basis and rate shall include fabrication,
erection, welding jointing and painting etc. all complete.

11.0 BRICK BAT FILL

11.1 The brick bat used as filling in valves pit shall be from common burnt clay building bricks.
A sample of brick bats used shall be got approved from Engineer-in-charge.

11.2 The compaction of the layer of brick bats shall be proper so that brickbats are not
disturbed and do not sink in the soil.

11.3 The payment for brick-bat fill shall be made on MP basis as shown in drawing and the
rate shall include supply, laying, compacting etc. complete with all materials & labour.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-012 Page 6 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
S-10-02-012 Page 7 of 7
NEW DELHI Misc. CIVIL & STRUCTUR

Copyright GAIL – All rights reserved


STANDARD SPECIFICATION
FOR
UNDERGROUND SEWER
SYSTEM -PRE CAST R.C.C. PIPES

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 1 of 6
NEW DELHI UNDERGROUND SEWER SYSTEM-PRE CAST S-10-02-013
RCC PIPES
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. MATERIAL

3. EARTHWORK IN EXCAVATION, BACK FILLING, TRANSPORTATION

4. LOWERING AND LAYING

5. JOINTING

6. TESTING

7. RESTORATION OF DAMAGED SURFACES AND CLEARING THE SITE.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 2 of 6
NEW DELHI UNDERGROUND SEWER SYSTEM-PRE CAST S-10-02-013
RCC PIPES
Copyright GAIL – All rights reserved
1.0 SCOPE

This specification covers the supply, laying, cutting, jointing and testing of Precast
RCC pipes and related works.

2.0 MATERIALS

2.1 The pipes shall be centrifugal cast concrete pipes with reinforcement conforming to IS : 458.
The class of pipes shall be as specified on drawings.

2.2 The surfaces and edges of the pipes shall be well defined and their ends shall be perpendicular
to longitudinal axis.

3.0 EARTHWORK IN EXCAVATION, BACKFILLING AND TRANSPORTATION

3.1 All earthwork involved in laying of RCC pipes and related works is deemed to have
been included in the quoted rates for the laying of RCC pipes.

3.2 All earthwork shall be carried out as per specification No.6-65-0006 "Earthwork for
underground piping system".

3.3 The bed of trench if in soft 'or' made up earth shall be well watered and rammed before laying the
pipes and the depressions, if any shall be properly filled with earth and consolidated in 20 cm layers.

3.4 If the trench bottom is extremly hard 'or' rockey or loose stoney soil, the trench shall be
excavated at least 150 mm below the trench grade. Rocks, stone 'or' other hard
substances from the bottom of the trench shall be removed and the trench brought
back to the required grade, by filling with selected fine earth 'or' sand (in fine murrum if
fine sand 'or' soil is not available ) and compacted so as to provide a smooth bedding
for the pipe.

Where excavation requires blasting operations, it shall be ensured that no pipes are stacked in
vicinity and complete pipe lines in the vicinity have already been covered before starting of
blasting operation.

3.5 The trench shall be kept free from water. Shoring and strutting / timbering shall be done
wherever required. Excavation below water table shall be done after dewatering the
trenches.

3.6 After excavation of the trench is completed, hollows shall be cut at the required position to
receive the socket of the pipes and these hollows shall be of sufficient depth to ensure that
the barrels of the pipes shall rest throughout their entire length on the solid ground and that
sufficient spaces left for jointing the underside of the pipe joint. These hollows shall be refilled
with sand after jointing the pipe.

4.0 LOWERING & LAYING

4.1 The pipes shall be lowered when the trench is ready and the bottom has been properly
graded as per drawings.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 3 of 6
NEW DELHI UNDERGROUND SEWER SYSTEM-PRE CAST S-10-02-013
RCC PIPES
Copyright GAIL – All rights reserved
4.2 Before lowering, the pipes shall be inspected carefully. Broken or cracked pipe shall
be rejected. The inside of the pipe shall be cleaned off from sand, earth or any other
matter.

4.3 The pipe shall be lowered carefully so as not to disturb the bed and sides of the
trench. Heavy pipes shall be lowered with chain pulley blocks or crane.

4.4 Pipes shall be set according to line and grade. Prior to making joints all surface shall be
thoroughly cleaned and prepared as required for the type of joint to be made. Pipe
shall be carefully centered so that the completed sewer will have a smooth uniform
invert.
4.5 In socket & spigot pipes the socket end shall face the upstream direction.

4.6 In case of RCC pipes with collar joints, the collar shall be slipped on before the next
pipe is laid.

4.7 Railway authorities or other appropriate authorities shall be consulted wherever the
pipeline crosses a railway line, canal, etc.

4.8 Connection to existing sewer shall be done through a manhole generally.

4.9 The ends of the pipe line shall be kept sealed to prevent entry of any foreign materials.
The seals will be broken before/after the testing is done.

4.10 Wherever the joining material is cement, six or more lengths of pipe shall be laid in
advance of each joint before it is finished.

4.11 In cases where the natural foundation is inadequate the pipes shall be laid either in
concrete craddle supported an proper foundations 'or' any other suitably designed
structure. If a concrete cradle bedding is used the depth of concrete below the bottom of
pipe shall be atleast 1/4th of the internal dia of the pipe subject to the min. of l0cm
and a maximum of 30 cm, the concrete shall extend upto the sides of the pipe atleast to
a distance of 114 of the outside diameter of pipes 300mm and above in dia. The pipes
shall be laid in this concrete bedding before the concrete has set. Pipeslaid in trenches in
earth shall be bedded evenly and firmly and as far as up the haunches of the pipes so
as to safety transmit the load expected from the backfill through the pipe to the bed.

This shall be done either by excavating the bottom of the trench to fit the curve of the
pipe or by compacting the earth under and around the curve of the pipe from an even bed.
Necessary provision shall be made for joints wherever required.

5.0 JOINTING

5.1 Joint in the pipe line shall be of the socket and spigot type and conforming to relevant
Indian standards.

5.2 As per IS 458-1988 joints in pressure pipes shall be flexible rubber ring joints only.
Contractor shall provides Pipes of socket and spigot type meeting the above
requirements.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 4 of 6
NEW DELHI UNDERGROUND SEWER SYSTEM-PRE CAST S-10-02-013
RCC PIPES
Copyright GAIL – All rights reserved
5.3 Concrete pipes where permitted by site -in-charge with collar shall be water tight.

5.3.1 The groove in between the pipe ends is to be filled with jute impregnated with bitumen
rolled in the form of gasket ring centrally around the pipe to ensure uniform annular
space between the collar and the pipe.

5.3.2 Cement mortar of proportion 1:2 shall be used for caulking the annular space. Care
shall be taken to see that the bottom of the collar joint is also caulked properly.

5.3.3 The joint shall be finished at an angle of 45 Deg and shall be kept wet for 10 days
for curing.

6.0 TESTING

6.1 The pipeline shall be tested for water tightness of joints. The test shall be carried out from
manhole. Pipe ends shall be closed and filled with water so that water level is up to the top of
the manholes.

6.2 The line shall be kept full for 24 hours. Observations shall be taken after one hour interval and if
leakage is within 2.5 liters/km/hrs/cm of dia of pipeline, it shall be deemed to have passed the
test..

6.3 Engineer-in-Charge may at his own discretion ask the subcontractor to test the laid pipe line in
sections, in which case the subcontractor will do the same as per the procedure to be
decided by the Engineer-in-Charge without any extra cost to Owner. The procedure adopted in
such cases, however, will be to test the pipeline according to the criteria mentioned in 6.2
above.

6.4 In case joints are found to leak, they shall be repaired or redone and test shall be repeated
until the joints are approved by Engineer-in-Charge.

6.5 After completion of the test all temporary seals will be removed, the test water shall be
drained out/pumped out and the line cleaned properly.

6.6 Before commissioning the cleanliness of the pipeline will be checked by :-

6.6.1 Torch & Mirror Test

In this method of testing, a torch will be held at one end of the pipeline inside a manhole and its
image through the pipeline will be reflected and seen on a mirror held at the opposite end of the
pipeline, inside the next manhole. Any obstruction/debris/major misalignment will not give a
clear image in which case the pipeline will again be cleaned/rectified and the test redone.

6.6.2 Ring Test

In this method of testing, two steel wooden rings of suitable thickness and design shall be
fixed facing each other at a distance of 2 feet or more. The block of rings shall be inserted
from one end of the pipeline, inside manhole and pulled by a rope fixed to the block from
the other end of the pipeline inside the next manhole. The rings shall be of dia. 2" less than
the inside dia of pipe under testing. The rope used for pulling the ring block may be
inserted in the pipeline by the subcontractor either during construction or afterwards by
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
Page 5 of 6
NEW DELHI UNDERGROUND SEWER SYSTEM-PRE CAST S-10-02-013
RCC PIPES
Copyright GAIL – All rights reserved
suitable means. Any obstruction/debris/major misalignment will prevent the ring to pass
through the pipeline in which case the pipeline will again be cleaned/rectified and the test
redone.

The ring test shall be performed for the complete network of the sewer system before the
same is put in commission.

7.0 RESTORATION OF DAMAGED SURFACES AND CLEARING THE SITE

7.1 All pavements, structures, pipelines, cables, etc. removed, damaged or disturbed during the
pipe laying work shall be restored to original conditions.

7.2 Surplus excavated soil or rubbish material shall be removed to a place as directed by
Engineer-in-Charge.

8. PAYMENT

8.1 Measurement of pipeline work for the purpose of payment shall be taken in running meters
of the laid pipe measured along centre line, inclusive of joints . No extra payment shall be
made for providing, laying etc., of fittings like bends, tees, etc. (except valves) that may he
necessary in work. The rate quoted shall be inclusive of excavation, lowering. laying,
jointing, testing, cleaning of pipe lines, backfilling and any other operation involved in the

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 6 of 6
NEW DELHI UNDERGROUND SEWER SYSTEM-PRE CAST S-10-02-013
RCC PIPES
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION
FOR
PLUMBING & BUILDING
DRAINAGE

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 1 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 STOP COCKS

3.0 H .C.I. NAHNI TRAP (FLOOR TRAP)

4.0 STONEWARE GULLY TRAP CHAMBER

5.0 BRICK MASONRY (MANHOLESIINSPECTION CHAMBER &


VALVE CHAMBERS)

6.0 C.I. SOILIWASTE PIPES

7.0 C.1. SOILIVENT PIPES

8.0 G.I. PIPES AND FITTINGS

9.0 GUNMETAL VALVE

10.0 HALF ROUND CHANNEL

11.0 PRECAST RCC PIPES

12.0 M.S. RUNGS/CI STEPS

13.0 SOAK PITS

14.0 SEPTIC TANKS

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 2 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
1.0 SCOPE
1.1 The specification is intended to establish and define the materials and
constructional requirements for plumbing &building drainage works.
1.2 All materials. fixtures and workmanship shall be in accordance with the relevant
Indian Standards Specifications, Codes of practices and good Engineering practices.
2.0 STOP COCKS
2.1 Stop cocks of screw-down type shall conforms to IS:781. All taps shall be of heavy
grade. The taps shall be chromium plated brass or ordinary easy cleaning
type as specified.
2.2 The payment shall be made on units basis. The rate quoted shall include supplying
and fixing bib or stop cocks with white zinc and yarn etc. complete.
3.0 H.C.I. NAHNI TRAP (FLOOR TRAP)
3.1 Nahni trap shall be of heavy cast iron as per IS:3989 with l00mm inlet and
80/100mm outlet with CP pressed steel grating. It shall be of self-cleaning design.
Grating shall be of either hinged or screwed down type. It shall be fixed in cement
mortar 1:2 and as directed by Engineer-in-Charge.
3.2 The payment shall be made per number basis. The rate shall include supplying and
tixing Nahni trap, including cement mortar, cutting walls and floors and making
good the same, providing and fixing chromium plated pressed steel grating all
complete.
4.0 STONEWARE GULLY TRAP CHAMBER
4.1 The square mouth guilly trap shall be of l00mm dia, conforming to IS:651 of
specified and/or approved quality stoneware, complete with cast iron grating. and
shall be got approved by the Engineer-in-Charge. The size of CI frame and cover
shall be of 3000mm x 300mm. It shall be properly fixed as directed by the
Engineer- in-Charge. The size of the chamber shall be 300 x 300 x 675mm
(internal) it shall be constructed of brick masonry walls 125mm thick in 1.4
cement mortar and M-15 concrete foundations. Inside &outside faces of the
masonry walls shall be plastered with 1:3 cement mortar. The top of the chamber
shall be provided with CI cover and frame.
4.2 The payment shall be made on per number basis. The rate shall include supplying
and fixing of stoneware gully trap, CI grating, construction of masonry
chamber. providing and fixing CI frame and cover, earthwork in excavation,
foundation concrete and backfilling removal of surplus earth upto a lead of 30m.
etc and labour and material complete.
5.0 BRICK MASONRY (MANHOLESIINSPECTION CHAMBER & VALVE CHAMBER)
5.1 The size of the manholes and valve chambers shall be as specified in the drawings or

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 3 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
items. It shall be constructed of brick masonry walls 230mm thick in CM 1 :4 (1
cement. 4 sand) resting on M-20 concrete foundations. The inside and outside face
of the masonry wall shall be plastered with 13mm thick plaster of cement motar 1:3
(1 cement : 3 sand) The top of chamber shall be provided with reinforced concrete M-
20 grade slab as per drawing and direction of the Engineer-in- Charge. M.S. rungs
made out of 16mm dia M.S. bars shall be fixed inside the manhole as shown in the
drawing after applying two coats of anticorrosive paint.
Valve chambers shall be provided and fixed with a light duty CI cover and frame. The
top of chamber shall be provided with reinforced cement concrete M-30 grade as per
drawings and direction of Engineer-in-Charge.

The C. I. manhole covers and frames shall conform to IS: 1726. The type size and
grade shall be as per drawing. schedule of items and the directions of the Engineer-
in-Charge. The frame shall be fixed in position during concreting of top slab, inside
faces of frame and cover shall be given two coats of approved anti-corrosive paint.
The specification for brick masonry, plastering, concreting, excavation, and back-fill
ing ,etc . as given under relevant clauses shall be applicable for this work also.
5.2 Payment shall be made as per number basis including excavation, backfilling,
removal of earth, construction of the chamber/manhole, making connections of
pipes through the walls, cost of M.S. rungs, cover slab, cost of CI cover and frame,
etc. as per the directions of the Engineer-in-Charge.
The rate shall include breaking concrete or brick masonry work and making good
the same with 1 :4 cement mortar if necessary, finishing. painting, etc. as per
directions of Engineer- in-charge.
6.0 C.I. SOILIWASTE PIPES
6.1 Cast iron pipe, socket and spigot shall be of standard quality conforming to IS :
1729 including encasing the pipe in 50mm thick PCC M10.(heavy duty).
The spigot of the pipe shall be placed fully resting inside the socket and hemp
caulked home to leave space for lead depth as specified. Lead conforming to IS :
782 in molten state shall then be poured into the joint filling the same in one
pouring. The lead shall be caulked by proper tools to make it even all round.
Depths of lead in the joints from the top of the socket shall be 37mm for 150mm
dia pipes, 25mm for l00mm and 5Omm dia pipes. All pipes shall be fixed 25mm
clear of the wall with MS holder bat clamps or as approved by the Engineer-in-
Charge. All holes in walls and floors shall be made good by cement concrete M- 15
grade and should be leak proof. All soil and waste pipes shall he tested for
leakage by hydraulic test.
All pipes shall be painted with two coats of paint of approved make and shade over
a coat of prime. Earthwork in excavation backfilling and removal of surplus earth
shall be considered as a part of the work. No separate payment will be made for
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
Page 4 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
the same.
6.2 The payment shall be made per running metre of pipe laid with fitting as required
on site. The rate quoted shall include supplying and fixing of pipes and necessary
specials including cowl with hemp and lead, jointing & testing, bat clamps, fixtures
painting, cutting of walls, flloors and making good the same and necessary
scaffolding, earthwork in excavation, back fllling & removal of surplus earth etc.
complete.
7.0 CI/SOIL/VENT PIPES

7.1 C1 pipes shall be standard quality conforming to IS : 1729. The supply shall include
all necessary accessories e.g . bends, tees etc. complete. Jute yarn gasket of
suitable diameter shall be used as required to support the spigot of the pipe at
the proper grade and make truly concentric joints. Single piece of sufficient length
shall be used to pass around the pipe and lap at the top and shall be
throughly saturated in bitumen. This gasket shall be laid in the socket for lower
third of the circumference of the joint and covered with cement mortar. The
spigot of the pipe throughly cleaned with wet brush, inserted and carefully driven
home after which a small amount of cement mortar ( 1 :2) shall be inserted in
the annular space around the entire circumference of pipe and solidly rammed
into the joint with caulking tool. The joint shall then be completely filled with
mortar and bevelled off at angle of 45" with outside of the pipe: Cement used to
joint shall conform to IS : 269

All holes in walls and floors shall be made good by cement concrete M-15 grade. All
CI pipes shall be painted with two coats of anticorrosive bituminous paint
externally. The payments shall be on running metre basis of pipes laid. The rate
shall include supplying and fixing pipes jute gaskets dipped into bitumen and
cement mortar and necessary specials including jointing with clamps, painting,
cutting of walls, floor and making good the same, necessary scaffolding etc.
complete.

8.0 GI PIPES AND FITTINGS 8.1 All G.I. pipes and fittings shall conform to IS :
1239 and shall be of medium grade for water supply system.

All screwed tubes and sockets shall have pipe threads in accordance with the
requirements specified in IS : 554. Unless specified otherwise, pipes shall be
supplied screwed with taper threads and sockets parallel thread.
All fittings shall be malleable galvanlsed iron approved by the Engineer-in-Charge.
Fittings in G.I. line shall include all couplings, elbows tees, bends, unions, nipples,
reducers, flanges with nuts bolts and rubber insertions, bushes and all other fittings
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
Page 5 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
to make a complete job.
Screwed G.I. pipes shall be jointed with screwed socket joints using screwed
tittings. Care shall be taken to remove any burr from the end of the pipes after
threading. While lead with a few strands of fine hemp shall be applied while
tighting. Compounds containing red lead shall not be used.
All pipes above ground shall be fixed with G.I. holders bat clamps clear off the wall
at 1.2 M centres. If the pipes are fixed in encased or embedded in wall, they shall
be secured in position by iron hoops at 1.2 M centres. All visible pipes and
clamps ithin and outside building shall be painted with two coats of white paint or
aluminium paint as directed by the Engineer-in-Charge. No extra payment shall
be made for clamps, hooks, cutting holes in walls, chasing and making good the
same.
All underground pipes shall have a minimum earth cover of 600mm or as directed
by the Engineer-in-Charge. No extra payment shall be made for excavation in
trenches, refilling the same and removal of surplus earth. Before any pipes are
painted or covered up they shall be tested to a hydro-static pressure of 6 kg/sq.cm.
8.2 Payment shall be on running meter basis of actual pipeline laid. In addition to the
Sectional testing of water supply piping, the contractor shall test entire installation
on completion of the job to satisfaction of the Engineer-in-Charge. No extra
payment shall be made for testing. The contractor shall make his own arrangement
for supply of water for testing at his own cost. The rate for this item shall include
supply and laying of G.I. pipes with necessary fittings, cutting of pipes to required
lengths, threading; making holes in walls and floors and making good the same,
jointing, painting, excavation and refilling including the testing and directed by the
Engineer-in-Charge.
9.0 GUN METAL VALVE
9.1 All full way and globe valves shall be of heavy gunmetal and tested at 300 psi and
shall he approved by the Engineer-in-Charge. Valves shall conform to IS : 778. Size
of valve chamber shall be as per item description, construction of valve chamber
shall be carried out as detailed in clause 13.0 above. Valve chamber shall be
provided & fixed with heavy duty C.I. surface box conforming to IS : 3950. The
surface box shall be hinged pin open type & shall be fixed in the chamber slab. It
shall have a hole for opening.
9.2 The payment shall be made per number basis including valve chamber & surface
box. The rate shall include construction of valve chamber supplying and fixing
valves & surface box in position as per drawings and directions of Engineer-in-
Charge.
10.0 HALF ROUND CHANNEL
10.1 Half round channel shall be plain or with stop end and shall have internal dia of
I00 mm approved by the Engineer-in-Charge. The jointing work shall be done with
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
Page 6 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
white cement slurry. The drains shall be provided with proper slopes as indicated
in drawings or as specified by the Engineer-in-Charge. Channel shall be covered
with matching tiles leaving provision for cleaning the same.
10.2 The payment shall be made per meter basis and shall include all labour, material
etc. complete including laying, jointing etc.

11.0 PRECAST R. C. C. PIPE


11.1 Materials
For pipe materials, the following specifications shall apply :
Spec. for Pre cast concrete pipes IS : 458
(With and without reinforcement)
Code of practice for laying of concrete pipes IS : 783
For cement sand, mortar, water etc. the specifications laid down for concrete works
shall apply
All pipes must be new and perfectly sound, free from cracks, cylindrical, straight,
and of standard nominal diameter and length with even texture. Each pipe shall
have one collar with it.
The contractor shall submit manufacturer's test certificate whenever demanded by
Engineer- in-Charge or his authorised representative. Spun yarn for pipe joints shall
be of best quality. It shall be free from dust etc.

1 1.2 Transportation and Stacking


The transportation of materials to the work site and stacking shall be done in a
manner to cause minimum inconvenience to the traffic and other construction
works. The pipe shall be protected during handling against impact; shocks add free
fall to avoid cracks and damage.
The contractor shall be fully responsible for the safety and security of materials
transported and stacked in the field.

1 1.3 Lowering and Laying of Pipes


General
The laying and jointing of pipes shall conform to IS : 783. The trench shall be
checked for proper level, gradient and alignment before lowering the pipes.

Lowering
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
Page 7 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
The pipes shall be lowered cautiously to prevent disturbance of the bed add sides
of the trench. The heavy pipes shall be lowered by means of proper shear legs,
chain pulley blocks or as directed by Engineer-in-Charge. Great care should be
taken to prevent sand etc. from entering the pipes.
Laying
Laying of pipes shall proceed up grade of slopes. The error of grade shall not be
rectified by packing up earth underneath the pipes. If required, concrete shall be
used for packing. The ends of the pipes shall be kept closed to keep dirt, mud and
foreign materials, out. Adequate provision shall be made to prevent floating of pipe
in the event of flooding of trenches.
The body of the pipe for its entire length shall rest on an even bad in the trench
and places shall be excavated to receive the collar for the purpose of jointing.
1 1.4 Jointing of Pipes
Joint in the pipe line shall be of the socket and spigot type and conforming to
relevant Indian Standards.
As per IS 458-1988joint in pressure pipes shall be flexible rubber ring joint only.
Contractor shall provide pipes of socket and spigot type meeting the above
requirement. Concrete pipe where permitted by site incharge with collar shall be
water tight.
A few skeins of spun yarn soaked in neat cement wash shall be inserted in the
groove at the end of the pipe and the two adjoining pipes butted against each
other. Collar shall the he slipped over the joint covering equally both the pipes.
Spunyarm soacked in neat cement wash shall be passed round the pipes and
inserted in the joint by means of caulking tools from both ends of the collar. More
skeins of yarn shall be added and well rammed home. The object of the yarn is to
centre the two ends of the pipes within the collar.
Cement mortar 1:2 (1 cement 2 sand) shall be slightly moistened and must on no
account be soft or sloppy and shall be carefully inserted by hard into the joint. The
mortar shall then be punched and caulked into the joint and more cement mortar added
until the space of the joint has been filled completely with tightly caulked mortar. The
joint shall be finished off neatly outside the collar on both side at an angle of 45".
Any surplus mortar projecting inside the joint is to be removed and to guard against
any such projections. Sack or gunny bags shall be drawn past each joint after
completion.
11.5 Curing
The cement mortar joints shall be cured at least for seven days.

11.6 Testing
STANDARD SPECIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD FOR
Page 8 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
All joints in the pipes shall be tested to a head of 1.5 meters of water above the top
of the highest pipe.
Payment for supplying, lowering, laying, jointing and testing shall be made on
running meter basis. The length of pipes laid include collars and the rate shall
include all supplies and works mentioned in proceeding paras, including excavation
backfilling, concrete, removal surplus earth etc . complete.
12.0 M.S. RUNGS1C.I. STEPS
12.1 The rungs for pits manholes and septic tanks shall be of M.S. conforming to Indian
Standard and to the shape and size as shown in drawings. C1 steps for manholes if
needed shall he as per IS-5455.
M.S. rungs shall be coated with 2 coats of approved bituminous paint.
Payment for rungs steps shall be made as per number and the rate shall include
supply, fixing, finishing the walls. painting etc. complete

13.0 SOAK PITS


All earthwork in excavation, brick work etc. shall conform to relevant I. S .
standard. The brickbats should preferably be slightly over burnt or throughly
well burnt, deep red in colour with some proportion of deep blue of black veins.
Spongy or vitrified material as a result of excessive over burning is useless and shall
be rejected. Brick bats bigger than specified size shall be reduced to required size
(40 to 50mm) before filling in soak pit and no extra payment shall be made for this.
It shall be stacked at site as directed by Engineer- in-Charge. Soak pit & septic tank
shall be connected with required piping.
Payment of soak pit shall be made per number basis. Rate quoted shall include brick
masonry work, providing & filling brick bats, earthwork in excavation backfilling making
inlet connection with pipe and connecting same to septic tank etc. complete as shown
in drawing.
14.0 SEPTIC TANK
14.1 Ready made septic tank shall be as per drawing , consisting of sewage chamber
inspection door, vent pipe, inlet / outlet connections, manhole cover, MS rungs
etc. shall be used. Supply, installation, testing and commissioning of septic tank shall
conform to IS : 2470 Part-I. Access opening shall be provided for desludging &
inspection.
The ventilating pipe shall be provided with pipe of atleast 50mm dia extended 2 meters
above the nearest working platforms.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 9 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
14.2 Payment of septic tank shall be made per number basis & Rate shall include all
accessories like, inlet, outlet, vent pipe, manhole cover & C.I. steps, earthwork in
excavation &

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 10 of 10
NEW DELHI PLUMBING AND BUILDING DRAINAGE S-10-02-014
Copyright GAIL – All rights reserved
STANDARD SPECIFICATIONS FOR CO2
TYPE FIRE EXTINGUISHERS

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-015 Page 1 of 3
NEW DELHI CO2 TYPE ESTINGUISHER
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 MATERIAL, SHAPE, CONSTRUCTION, METHOD OF OPERATION,


PERFORMANCE, CONTENTS AND TESTS

3.0 APPROVALS

4.0 MARKING

5.0 ACCESSORIES

6.0 INSPECTION

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-015 Page 2 of 3
NEW DELHI CO2 TYPE ESTINGUISHER
Copyright GAIL – All rights reserved
1.0 SCOPE
This standard lays down requirements regarding material, shape,
construction, method of operation performance and tests of portable fire
extinguisher of carbon dioxide type The extinguisher shall be supplied along
with C02gas duly charged.
2.0 MATERIAL, SHAPE, CONSTRUCTION, METHOD OF OPERATION,
PERFORMANCE, CONTENTS AND TESTS
2.1 The material, shape, construction, method of operation, performance and
test shall comply with IS. 2878.
2.2 Nominal sizes,
2.2.1 The extinguisher shall be of following nominal sizes in Kg : 2,3 and 5.0 for
portable type and 7,9 and 22.5 for trolley mounted.
2.3 Contents
2.3.1 Carbon dioxide gas used shall conform to I.S. 307 and extinguisher shall be
filled as per CI. 4.0 of I.S. 2878.
3.0 APPROVALS
3.1 A clearance/approval certificate for filling the extinguisher from "Chief'
Controller Explosive" Govt. of India, Nagpur shall be submitted for each
cylinder.
4.0 MARKING
4.1 Each extinguisher shall be clearly and permanently marked as per I.S. 2878
along with I.S. certification mark and purchaser's name.
5.0 ACCESSORIES
5.1 Each extinguisher shall be supplied with M .S. bracket, wood screws and
spanner as may be necessary. The details of the bracket shall be submitted
with the offer.
6.0 INSPECTION
GAIL or its authorised representative shall have access at all reasonable
time to the manufacturer's works where extinguishers ordered are being
manufactured and or tested.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
S-10-02-015 Page 3 of 3
NEW DELHI CO2 TYPE ESTINGUISHER
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION
FOR
PORTABLE DRY POWER TYPE
EXTINGUISHER

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD PORTABLE DRY POWER TYPE Page 1 of 4
NEW DELHI S-10-02-016
EXTINGUISHER
Copyright GAIL – All rights reserved
CONTENTS

1 .0 SCOPE

2 .0 MATERIAL, SHAPE, TYPES. CONSTRUCTION,


ANTICORROSIVE TREATMENT. PAINTING AND TEST

3 .O PRINCIPLE

4.0 CAPACITY

5 .O ACCESSORIES

6.0 MARKING

7.0 INSPECTION

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD PORTABLE DRY POWER TYPE Page 2 of 4
NEW DELHI S-10-02-016
EXTINGUISHER
Copyright GAIL – All rights reserved
1.0 SCOPE

1.1 This specification lays down die requirements regarding material, shape, type.
construction, anticorrosive treatment and test for ordinary dry powder type fire
extinguisher. The extinguisher shall be supplied along with the dry powder duly
charged.

2.0 MATERIAL, SHAPE, TYPES, CONSTRUCTION, ANTICORROSIVE


TREATMENT, PAINTING AND TEST.

2.1 The material, shape, construction, anticorrosive treatment, painting and test shall be as
per I.S. 2171.

2.2 The extinguisher shall be gas cartridge or pressure type.

3.0 PRINCIPLE

The method of expulsion of type powder shall be as per I.S.2171 with either of the
method of operation specified therein. The vendor shall indicate clearly the method
adopted for operation.

4.0 CAPACITY

4.1 Nominal capacity of the extinguisher and the dry powder contents of the assembled
hody or dry powder container shall be as follows when charged with dry powder
conforming to I.S. 4308.

Nom. capacity of Dry powder contents when


Extinguisher (kg) charged Min. (kg)

1 1

2 2

5 5
10 10

4.2 Only dry powder conforming to I.S. 4308 shall be used for charging the extinguisher.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD PORTABLE DRY POWER TYPE Page 3 of 4
NEW DELHI S-10-02-016
EXTINGUISHER
Copyright GAIL – All rights reserved
5.0 ACCESSORIES

Each extinguisher shall be supplied with a suitable wall bracket or holder onto which it
may be mounted and from which it may be removed for use in an emergency and
screws and spanner as may be necessary.

6.0 MARKING

Each extinguisher shall he clearly and permanently marked with the information
specified in I.S. 2171 along with I.S. certification mark and purchaser's name.

7.0 INSPECTION

7.1 GAIL or its authorized representative shall have access at all reasonable times to the
manufacturer’s works where the extinguishers are being manufactured and or being
tested Samples from lots under a quality control system shall be done as per Appendix
B of I.S.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD PORTABLE DRY POWER TYPE Page 4 of 4
NEW DELHI S-10-02-016
EXTINGUISHER
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD PORTABLE DRY POWER TYPE Page 5 of 4
NEW DELHI S-10-02-016
EXTINGUISHER
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
STAND POST TYPE FIRE HYDRANT
(WITH OR WITHOUT PUMPER
CONNECTION)

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD STAND POST TYPE FIRE HYDRANT
Page 1 of 4
NEW DELHI (WITH OR WITHOUT PUMPER S-10-02-017
CONNECTION)
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. CODES AND STANDARDS

3. MATERIAL

4. DESCRIPTION

5. WORKMANSHIP AND FINISH

6. TESTING

7. PAINTING

8. MARKING

9. INSPECTION

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD STAND POST TYPE FIRE HYDRANT
Page 2 of 4
NEW DELHI (WITH OR WITHOUT PUMPER S-10-02-017
CONNECTION)
Copyright GAIL – All rights reserved
1.0 SCOPE

This standard lays down the requirements of codes and standards, type. shape,
dimensions, material and test for vertical stand post type fire hydrant (with or without
pumper connection) to be installed on fire water main. The Hydrant shall be supplied
normally without pumper connection unless specifically mentioned in the Material
Requisitions.

2.0 CODES AND STANDARDS

IS : 3 1 8 Leaded tin bronze ingots and castings


IS:902 Suction hose couplings for fire fighting purposes
IS : 903 Fire hose delivery couplings. branch pipe
IS: 1239 Mild steel tubes, tabulars and other
IS: 1367 Wrought iron fittings
IS : 2062 Steel for general structural purposes
IS :27 12 Compressed asbestos fiber jointings
IS:2932 Enamels, synthetic, exterior
(a) undercoating
(b) finishing

3.0 MATERIAL

3.1 Hydrant vertical post and hydrant arms shall be fabricated from pipe conforming to I.S.
1239 heavy grade and shall be with welded construction.
3.2 Flanges shall be of M.S. plate to 1.S. 2062 FIF slip on type.
3.3 Hydrant valves 75 mm size shall comply to I.S. 5290 type A.
3.4 63 mm. coupling shall comply to I.S. 903, while bllind cap (for pumper connection) with
its lugs shall be of gun metal complying to IS: 3 18 Gr.11. Chain shall be of mild steel.
3.5 Bolts and nuts for flanges shall comply to IS: 1367 class 10.9 and 12 respectively while
gasket 2mm thick full face shall be made of CAF 40 to IS:2712.

4.0 DESCRIPTION

4.1 The hydrant shall be stand post type. The vertical post shall be of 100 mm diameter
with two horizontal hydrant arms each 80mm diameter on which independent hydrant
valve shall be fixed. Hydrant valve shall comply to I.S. 5290 type A.
4.2 63mm coupling shall comply to IS:903, and that the lug shall be twist release type.
4.3 For hydrant assembly with pumper connection, the vertical post shall have 100 min
outlet as pumper connection and provided with a blind cap as shown in the enclosed
sketch. The 100 mm outlet shall have round male threads conforming to IS:902 and
blind cap. Shall be provided with four fixing lugs and 500 mm long M.S. chain.

4.4 All flanges for hydrant valve and base shall have drilling dimensions conforming to
STANDARD SPECIFICATION FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD STAND POST TYPE FIRE HYDRANT
Page 3 of 4
NEW DELHI (WITH OR WITHOUT PUMPER S-10-02-017
CONNECTION)
Copyright GAIL – All rights reserved
ANS1.B. 16.5 lbs rating flat face, slip on type.

5.0 WORKMANSHIP AND FINISH

5.1 All parts shall be good workmanship and finish. All parts and sharp edges shall be
removed. The waterways shall have smooth finish.
5.2 Wherever B.1.S has been specified the latest edition of the same shall be followed.

6.0 TESTING

Hydrant assembly with hydrant valves closed shall be satisfactorily tested and proved
water tight under a hydraulic pressure of 18.0 kg/cm2. The pump connection shall he
kept closed during testing in case the same is provided on hydrant assembly.

7.0 PAINTING

7.1 The stand post and its arms shall be painted with three coats of anti-corrosive fire red
paint conforming to I.S. 2932 from outside while internal surface shall be painted with
three coats of chlorinated rubber based rasin paint or zinc chromate paint.

8.0 MARKING

8.1 Each hydrant shall be clearly and permanently marked with the
a) Manufacturers name or trade mark
b) I.S. 5290 on hydrant valve
c) Year o f Manufacture
d) Purchaser name.

9.0 INSPECTION

GAIL's authorized representative shall have access at all reasonable times to the
manufacturer's work where hydrant are being ordered and or tested.

STANDARD SPECIFICATION FOR DOCUMENT No. REV-0


GAIL (INDIA) LTD STAND POST TYPE FIRE HYDRANT
Page 4 of 4
NEW DELHI (WITH OR WITHOUT PUMPER S-10-02-017
CONNECTION)
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
STAND POST TYPE
WATER MONITOR

STANDARD SPECIFICATION FORSTAND DOCUMENT No. REV-0


GAIL (INDIA) LTD POST TYPEWATER MONITOR
S-10-02-018 Page 1 of 4
NEW DELHI
Copyright GAIL – All rights reserved
CONTENT

1.0 SCOPE

2.0 MATERIAL

3.0 CONSTRUCTION

4.0 WORKMANSHIP AND FINISH

5.0 ANTICORROSIVE TREATMENT AND PAINTING

6.0 TEST

7.0 ACCESSORIES

8.0 MARKING

STANDARD SPECIFICATION FORSTAND DOCUMENT No. REV-0


GAIL (INDIA) LTD POST TYPEWATER MONITOR
S-10-02-018 Page 2 of 4
NEW DELHI
Copyright GAIL – All rights reserved
1.0 SCOPE
This specification lays dawn the requirement of material, design, method of
construction and test for stand post type water monitor.

2.0 MATERIAL

2.1 Body, elbows, bends (45", 90•‹, 180") shall be either M.S. seamless or carbon steel
conforming to I.S. 4310.
2.2 Swivel joints shall be made of copper alloy as specified in CL. 3.3.1 of l.S 8442 and
locks of horizontal and vertical rotation shall be made of brass to I.S. 291. Ball
bearings shall be of stainless steel S.S. 304.

2.3 Base flange shall conform to I.S. 2004 class 2 and 3. Bolts and nuts shall conform
to 1.S 1367 class 10.9 and class 12 respectively while gasket CAF 40 to I.S. 27 12.

2.4 Water barrel and pipe for drain connection shall be of M. S. seamless pipe to I. S.
1239 med- grade (pt -I).

2.5 Nozzle shall be of copper or aluminium alloy. Copper alloy shall be as per I.S. 8442
clause 3.8 while aluminium alloy used for casting shall conform to 1.S. 617
designation 4450 (A-8- WP) or 4225 (A-16-WP).

2.6 Handle shall be of M.S. bar to I.S. 1732.


2.7 Drain valve shall conform to I.S. 778.

3.0 CONSTRUCTION
3.1 In general water monitor shall conform to type I of I.S. 8442 with a discharge
capacity of 2.58 m3/mnt at a pressure of 7 kgf/cm2. The minimum water jet throws
shall be 60 m horizontally at 45" trajectory and 28 M vertically up in still air at 7
kgf/cm2 pressure.

3.2 Monitor shall have traversing mechanism to give 360" rotation in either direction
in the orizontal plane and 125 " in the vertical plane (+80" ,-45 ") with separate
swivels through a quick acting handle bar. For unattended operation of the monitor
at the desired angles, suitable locks or swivel joints shall be provided. One handle
for traversing both the horizontal and vertical rotation of the monitor shall be
STANDARD SPECIFICATION FORSTAND DOCUMENT No. REV-0
GAIL (INDIA) LTD POST TYPEWATER MONITOR
S-10-02-018 Page 3 of 4
NEW DELHI
Copyright GAIL – All rights reserved
provided on the monitor body.

3.3 The monitor shall be mounted on a 100 mm (4") NB. M.S. FIF slip on type flange
whose drilling dimensions shall conform to ANSI. B-16.5 lbs rating. Bolts and nuts
for base flange shall have dimensions conform to ANSI B 16.5. Gasket shall be full
face 3 mm thick drilled to suit the hole on the flange.

3.4 Near the base flange a drain connection shall be provided with a drain valve 15 mm
(112") NB to drain the water out of the vertical post of monitor. The drain pipe
shall be long enough to discharge water away from the base flange.
3.5 At the end of water barrel the nozzle shall be fixed. The outlet of barrel shall have
external threads conforming to 1.S. 2643 (Pt-1) with class A tolerance. The nozzle
shall conform to fig. 5 of I.S. 8442 with orifice dia of 38 mm and its performance
requirements given in clause 8.0, the internal threads on the inlet connection of the
nozzle shall suit the external threads on the barrel pipe. The threaded end of the
nozzle shall be hexagonal to facilitate screwing of the nozzle on the outlet
connection of the barrel with nozzle spanner.
3.6 External threads near the nozzle outlet shall be provided to enable a fog nozzle or a
blank cap to be connected when desired. Threads shall suit both the requirements.
Blank cap shall be supplied by the Vendor alongwith monitor.

4.0 WORKMANSHIP AND FINISH


4.1 The complete assembly shall be of good workmanship and finish free from burrs
and sharp edges, particularly water way and nozzle shall have smooth finish.
5.0 ANTICORROSIVE TREATMENT AND PAINTING
5.1 All steel components subject to direct water contact shall be hot dip galvanised to a
thickness of not less than 0.012 mm. the thickness of coating shall be measured as
per 1.S. 3203.
External surfaces and non-ferrous components may be coated with lead tin alloy by
electrical deposition process.
5.2 Monitor shall be painted with fire red colour conforming to I.S. 5 shade No. 536
and the paint shall conform to I.S. 2932.
6.0 TEST
6.1 For performance the monitor shall be tested at operating pressure of 7 kgtlcm2 to
give a discharge of 2.58 M3/minute with a minimum horizontal and vertical throws
of 60m and 28m respectively in calm air.
6.2 The entire assembly shall be hydraulically tested to a pressure of 23 kgf/cm2 for 5
minutes without any leakage.
STANDARD SPECIFICATION FORSTAND DOCUMENT No. REV-0
GAIL (INDIA) LTD POST TYPEWATER MONITOR
S-10-02-018 Page 4 of 4
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD SPECIFICATION FOR
FIXED CO2 FIRE EXTINGUISHING
SYSTEM

STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0


GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 1 of
NEW DELHI
10

Copyright GAIL – All rights reserved


CONTENTS

1.0 SCOPE

2.0 REFERENCE CODE

3.0 GENERAL DESCRIPTION OF SYSTEM

4.0 THERMO SWITCHES

5.0 CHARACTERISTICS OF FIXED INSTALLATION

6.0 CHARGING

7.0 DISCHARGE HEADS

8.0 MANIFOLD WITH CONNECTION TO DISCHARGE HEADS

9.0 DISCHARGE NOZZLES

10.0 CO, SYSTEM CONTROL PANEL

11.0 MATERIAL SPECIFICATION

12.0 STATUTORY APPROVAL

13.0 TESTING AND MARKING

14.0 PAINTING

15.0 SPARES

TECHNICAL DATA SHEET - PAGE 6-9 OF 9

STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0


GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 2 of
NEW DELHI
10

Copyright GAIL – All rights reserved


1.0 SCOPE

This specification covers the general description, material of construction and test for
the fixed type carbon dioxide fire extinguishing system designed to be actuated by
electronic control/thermo electric process.

2.0 REFERENCE CODE

(i) NFPA- 12 - Carbon Dioxide Extinguishing system.


(ii) SMPV (unfired) Rules 1981 by CCOE).

3.0 GENERAL DESCRIPTION OF SYSTEM

3.1 The CO, system shall be designed and supplied strictly as per the requirements of
NFPA-12 and the criteria given herein below:

3.2 The system shall be a high pressure (850 psi) and shall be such that it is -

a) Extremely quick in action


b) Non poisonous
c) Safe and
d) Clean

3.3 Fire shall be extinguished by the total flooding of the space with CO, gas to render the
atmosphere inert and non supporting to combustion.

3.4 CO, gas cylinder's capacity provided shall be sufficient to discharge CO, gas, equivalent
to 50 per cent of the cubical content of the space involved, depending on the floor area
of the premises. Consideration of extra requirement due to opening in the room shall
also be given.

3.5 All the mandatory requirements of NFPA-12 shall be fully complied.

3.6 The vendor shall fill the required data in the Technical data sheet on page no. 6 of 9
and submit along with the offer.

4.0 THERMO SWITCHES

4.1 Thermo switches for releasing the C02 gas by temperature shall be of vapour proof,
single pole, open circuit and designed to close at 220 volts A.C. 11 10 volts DCII
independent battery when the surrounding air reaches 77oC / or any other desired
temperature. Each thermo switch shall be mounted on half inch conduit box. These
shall be provided around the place to the protected against fire hazard. The range of
thermoswitch is from 0 – 100 C.
STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0
GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 3 of
NEW DELHI
10

Copyright GAIL – All rights reserved


5.0 CHARACTERISTICS OF FIXED INSTALLATION

5.1 Carbon dioxide shall be stored in the high pressure steel cylinders, and when released it
shall travel in the same form through the pipe work to the discharge nozzles. The
release of pressure allows the liquid to turn partly to snow emerging at a temperature
of -110 F (-79 C). A battery of CO, cylinders fitted with the above device shall be
connected to the main manifold of the pipe work.

5.2 The storage cylinders shall be located in a dedicated room for the building for which
protection is envisaged.

5.3 The time to reach the specific concentration of CO, shall be clearly mentioned. The
system shall be interlocked with the air conditioning /ventilation system wherever
applicable. In case of CO, injection into the rooms, the relevant air handling units shall
be automatically shut off.

5.4 The distribution piping shall have to clear the RCC beams and ribs which criss cross the
ceiling, path of air ducts and electrical conduits. All supports, hangers and clips etc.
required for supporting the distribution piping, cylinders, manifold etc. shall also be
supplied along with the system. The number of supports, hangers and clips etc. shall be
as per the drawings approved by the owner.

6.0 CHARGING

Each CO, cylinder shall be equipped with a valve permitting refilling of cylinder. The
cylinder shall be sealed with a puncturable diaphragm and shall be provided with a
safety pressure relief for abnormal pressure formation.

7.0 DISCHARGE HEADS

Each cylinder in the CO, battery shall be equipped with a discharge head for automatic
piercing of the sealing diaphragm. One or two cylinders in the multiple cylinder
discharge group shall have discharge heads operated directly from the control panel
and the others shall be operable by the gas pressure discharged from the first one or
two.

8.0 MANIFOLDS WITH CONNECTIONS TO DISCHARGE HEADS

The pressure manifold shall be designed in such a way that it shall collect the gas from
all the cylinders and discharge collected quantities of the gas in the main manifold
which shall be connected with the discharge of outlets in the room.

STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0


GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 4 of
NEW DELHI
10

Copyright GAIL – All rights reserved


9.0 DISCHARGE NOZZLES

9.1 Suitable number of distribution nozzles shall be properly located within the rooms to be
protected for assuring a uniform distribution of the carbon dioxide.
9.2 The nozzles for discharging CO, gas into the hazardous areas, shall be of such shape as
to spread the gas without freezing. The shall be made of heat resisting material and
threaded to fit standard pipes, or pipe fittings.
9.3 A suitable arrangement shall be made in room for effective removal of CO, being
released.

10 CO2, SYSTEM CONTROL PANEL

10.1 The control panels shall be located in individual buildings and shall be wall mounted
type. The control panels shall be provided for manual actuation and shall be designed
to accommodate relays, auxiliary switches, pilot and signal lamps. The control panel
shall also be provided with the facility of audio alarm and on receipt of fire alarm signal
from tire alarm panel, audio alarm shall be initiated from CO, control panel with
necessary signal to shut off air conditioning/ventilations system. Manual push button for
discharge of CO, in each protected area (after audio alarm and 30 seconds time delay)
shall be provided near exit of the room.

10.2 Sign boards, caution boards, illumination board, alarm, given as per requirements of
NFPA 12 shall be provided in and around building protected with CO, system.

11.0 MATERIAL SPECIFICATION

11.1 Material for cylinder body, valve, nozzle shall conform to Clause 5 of IS:287. CO, gas
quality shall conform to IS:307.

11.2 All piping, spray nozzle shall be as per NFPA-12.

12.0 STATUTORY APPROVAL

Approval from 'Chief Controller of Explosives' for CO, system for handling, storage,
disposal shall be taken by the contractor.

13.0 TESTING AND MARKING

13.1 Every CO, cylinder shall be made and tested, approved, equipped and marked in
accordance with IS :2878.

13.2 CO2 piping shall be hydrotested as per NFPA-12.

STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0


GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 5 of
NEW DELHI
10

Copyright GAIL – All rights reserved


13.3 Each cylinder shall be clearly and permanently marked with the following information:
a) Manufacturer's name and trade mark.
b) Year of manufacture.
c) Cylinder marking as per IS:2872.

14.0 PAINTING
Painting and colouring of pipelines, nozzles, C02 cylinders, supports, etc. shall be done
as per standard practice including supply of all paints and consumables and other items
required for carrying out painting and colouring.

15.0 SPARES

15.1 The bid must include in the quoted price, the mandatory spares to be supplied with the
CO2 system.

15.2 In addition to the above spares, vendor shall recommend the list of spares required for
two years trouble free operation with unit rates and quantity along with the offer.

TECHNICAL DATA SHEETS


DETAILS TO BE FURNISHED BY THE BIDDER
STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0
GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 6 of
NEW DELHI
10

Copyright GAIL – All rights reserved


ALONG WITH THE OFFER

C MEANS VENDOR TO FURNISH DATA 1 DETAILS


1.0 Type of system- Fixed C02 Fire Extinguishing System

2.0 Design code/standard to which- NFPA-12 & SMPV Rules 198 1 (CCOE)
Design/manufacture for cylinders
/testing conforms

3.0 System designed to protect risks- Specify Area


in the building as specified.

3.1 Design Concentration- C

3.1.1 Amount of gas required- C


(Attach separate sheet, if required)

(List out gas supplied, number of


cylinders etc for working and
standby requirements, risk wise)

3.2 C02 storage cylinder details

A Manufacturer- C
B Design code- C
C Capacity in litres- C
D Gas holding capacity (kg)- C
E Total number supplied- C
F Aprpoving agency FM/UL/- C
LPC/VDS/TAC
(This must be acceptable
to TAC)
G Approval by CCE- C
H Working pressure (kglcm2)- C
Normal
I Design pressure (kglcm2)- C
J Dimension of cylinder- C
Dia x length x thickness

3.3 Pipes, Valves and Fittings


a. Manufacturers
i) Pipes- C
ii) Fittings- C
iii) Valves- C
STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0
GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 7 of
NEW DELHI
10

Copyright GAIL – All rights reserved


b. Material of Construction
i) Pipes- C
ii) Fittings- C
iii) Valves- C

c. Design Code
i) Pipes- C
ii) Fittings- C
iii) Valves- C

d. Type of joints

e. Hydraulic test pressure- C


of manifold/supply lines
(KgIcm2)

f. Discharge nozzles
i) Manufacturer and type- C
ii) Material of construction- C
iii. Number supplied- C
iv. Approved by FM/UL/VDS/ C
FOC and TAC(Yes1No)

3.4 Painting and colouring of pipeline,


nozzles, cylinder supports included
(2 coats of red oxide and synthetic
enamel)- C

3.5 Operating devices

3.5.1 Push Button Station


i) Type- C
ii)Manufacturer- C
iii) Model, numbers offered- C
iv Overall dimensions- C

3.5.2 Control Cables


i) Manufacturer- C
ii) Code/standard- C
iii) Type- C
iv) Size- C
v) Rating- C

STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0


GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 8 of
NEW DELHI
10

Copyright GAIL – All rights reserved


3.6 Main Control Panel

i) Manufacturer- C
ii) Mounting detail - C
iii) Number of entries- C
iv)Sheet thickness- C
v) Cable entry- C
vi) No. of ACIDC feeders- C
and their rating

3.7.1 Additional Requirements for Control Panel

a) Whether housing all the


necessary relays indicating lamps
push buttons, switches, etc. for the
efficient operation of the system,- C
(YesINo)

b) Input power supply requirement- C


for operation of panel.

AC/DC- C
Volts

c) Panel Signal Voltage


Volts
AC/DC- C

d) Type/APM capacity of the battery- C

e) Inter correcting cabling between


battery & panel- C

f) Power supply unit incorporated


in the panel, Yes/No- C

g) Audiovisual alarm on panel


provided for battery low
conditions Yes/No- C

h) Change over from AC main


Supply to standby power
Supply fully automatic in either
direction Yes/No- C
STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0
GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 9 of
NEW DELHI
10

Copyright GAIL – All rights reserved


i) Following push buttons provided

a. Alarm accept
b. Reset
c. Test Yes/No- C

j) Audio visual indication for AC


supply failure provided.- C
Yes/No

k) Pilot lamp for system 'ON' provided- C


Yes/No

l) Dual tone hooter for fire/fault


alarm provided & range of the same- C
Yes/No

m. Painting (External/Internal)- C

4.0 Material of instructions selected in- Yes/No


accordance with NFPA- 12.

5.0 Inspection and testing

a. Visual inspection of installed- C


system & hazard area

b. Check of labellng of devices- C

c. Check for mechanical tightness- C


of piping and associated equipment

d. Non-destructive operational tests- C


for all devices included

STANDARD SPECIFICATION FOR FIXED DOCUMENT No. REV-0


GAIL (INDIA) LTD CO2 FIRE EXTINGUISHINGSYSTEM
S-10-02-019 Page 10 of
NEW DELHI
10

Copyright GAIL – All rights reserved


STANDARD SPECIFICATION
FOR HOSE CABINET

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 1 of 4
NEW DELHI HOSE CABINET. S-10-02-020
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. DESCRIPTION

3. MATERIAL

4. PAINTING AND MARKING

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 2 of 4
NEW DELHI HOSE CABINET. S-10-02-020
Copyright GAIL – All rights reserved
1.0 SCOPE

1.1 This specification covers the general requirements regarding the material, design, and
construction of hose cabinet and fire fighting equipments, contained in the cabinet.
1.2 The Hose cabinet shall be supplied along with the fire fighting equipments
contained in it.

2.0 DESCRIPTION
2.1 Hose cabinet shall be of two types to accommodate delivery hose and jet nozzle with
branch pipe or universal branch pipe.

2.1.1 Type I shall be suitable to accommodate one delivery hose of size 63 mm, 15 metre
long with end couplings, one jet nozzle with branch pipe or one universal branch pipe.

2.1.2 Type I shall be capable of being mounted on wall. Necessary hangers and bracket for
hose, nozzle and branch pipe or universal branch pipe shall be provided, with the
cabinet.

2.1.3 Type II shall be suitable to accommodate two delivery hoses 63 mm, 15 metre long
with end couplings, two jet nozzle with branch pipe or two universal branch pipes.

2.1.4 Type II shall be of self supporting type suitable for outside installation. Necessary
hangers and brackets for hose, nozzle and branch pipe or universal branch pipe shall be
provided with the cabinet.

2.2 Type I cabinet shall be provided with single panel glass door while Type II with double
panel glass door.

2.2.1 Both the types shall be provided with handle type lock, a small recess to keep cabinet
key under glass cover, a small hammer secured to the cabinet with a chain to break key
glass cover.

3.0 MATERIAL

3.1 Cabinet shall be made of 18 gauge M. S. sheet suitably welded with single/double MS
door frame glass covered. Glass shall be securely fitted to the door frame in a standard
manner.

3.2 Door shall be provided with standard handle type lock-Godrej, Mortise or equivalent.

3.3 Hammer shall be of M.S. with G.I. chain.

3.4 Suitable size angle iron shall be provided to support type II cabinet.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 3 of 4
NEW DELHI HOSE CABINET. S-10-02-020
Copyright GAIL – All rights reserved
3.5 Delivery hose shall be either of following type
a) Flax canvas hose to I.S. 4927 or

b) Reinforced rubber lined hose to I.S. 636

or

c) Controlled percolating hose to I. S. 8423.

3.6 End couplings, jet nozzle and branch pipe shall conform to I.S. 903.

3.7 Universal branch pipe shall conform to I.S. 2871.

4.O PAINTING AND MARKING

4.1 The hose cabinet shall be painted with 3 coats of anticorrosive fire red paint from
outside and white paint from inside.

4.2 Each cabinet shall be clearly and permanently marked with following.
a) The words Hose Cabinet-Type I or II
b) Instructions for use.

4.3 Each equipment in the cabinet shall be marked with I.S. certification mark and
purchaser's name.

STANDARD SPECIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD FOR
Page 4 of 4
NEW DELHI HOSE CABINET. S-10-02-020
Copyright GAIL – All rights reserved
STANDARDS & STANDARD SPECIFICATIONS

GENERAL CIVIL

SPECIFICATION

S.NO. DOCUMENT No. NO. OF REV. TITLE


PAGES
01 Standard specification for survey
S-10-02-001 7 0
works
02 Standard specification for
S-10-02-002
6 0 earthwork for underground
piping
03 0 Standard specification for
S-10-02-003 5
barbed wire fencing
04 0 Standard specification for chain
S-10-02-004 7
link fencing.
0 Standard specification for
05 S-10-02-005 5 Classification of soil for
earthwork in site grading.
0 Standard specification for Site
06 S-10-02-006 11 grading & rock cutting
for site grading
07 0 Standard specification for
S-10-02-007 10
concrete pavements
0 Standard specification for
08 S-10-02-008 8 flexible pavements with
Bitumen premix carpet
0 Standard specification for RCC
09 S-10-02-009 5 pipe culverts and
ERC crossings etc.
0 Standard specification for U/G
10 S-10-02-010 4 and A/G GI pipeline system
(water services)
0 Standard specification for
11 S-10-02-011 13 Coating and wrapping of U/G
pipes
0 Standard specification for misc.
Civil & structural
12 S-10-02-012 6
Works for U/G piping & other
civil works
0 Standard specification for U/G
13 S-10-02-013 6 sewer system-pre cast RCC
pipes
LIST OF ATTCHMENTS CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD
0001-01-10-11-001 Page 1 of 2
NEW DELHI
Copyright GAIL – All rights reserved
S-10-02-014 0 Standard specification for
14 10 plumbing and & building
drainage
S-10-02-015 0 Standard specification for CO2
15 3
type extinguisher
S-10-02-016 0 Standard specification for
16 4 portable dry powder type
extinguishers
0 Standard specification for stand
17 S-10-02-017 4 post type fire hydrant (with or
without pumper connection)
S-10-02-018 0 Standard specification for stand
18 5
post type water monitor
S-10-02-019 0 Standard specification for fixed
19 9
CO2 fire extinguishing system
S-10-02-0120 0 Standard specification for hose
20 4
cabinet

LIST OF ATTCHMENTS CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD
0001-01-10-11-001 Page 2 of 2
NEW DELHI
Copyright GAIL – All rights reserved
ABBREVIATIONS & LEGEND

ABBRIVIATIONS AND LEGENDS STANDARD DRG. NO.


REV-0
GAIL (INDIA) LTD
NEW DELHI S-10-01-001 Page 1 of 5
Copyright GAIL – All rights reserved
ABBRIVIATIONS AND LEGENDS STANDARD DRG. NO.
REV-0
GAIL (INDIA) LTD
NEW DELHI S-10-01-001 Page 2 of 5
Copyright GAIL – All rights reserved
ABBRIVIATIONS AND LEGENDS STANDARD DRG. NO.
REV-0
GAIL (INDIA) LTD
NEW DELHI S-10-01-001 Page 3 of 5
Copyright GAIL – All rights reserved
ABBRIVIATIONS AND LEGENDS STANDARD DRG. NO.
REV-0
GAIL (INDIA) LTD
NEW DELHI S-10-01-001 Page 4 of 5
Copyright GAIL – All rights reserved
ABBRIVIATIONS AND LEGENDS STANDARD DRG. NO.
REV-0
GAIL (INDIA) LTD
NEW DELHI S-10-01-001 Page 5 of 5
Copyright GAIL – All rights reserved
CABLE CROSSINGS UNDER ROADS PVC DOCUMENT No. REV-0
GAIL (INDIA) LTD PIPES
S-10-01-002 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRGS FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD ROAD CURVES AND CROSSINGS
S-10-01-003 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD SECTION OF STORM WATER DITCHES DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-004 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
PIPE CULVERTS FOR STORM WATER DRAINAGE DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-005 Page 1 of 3
NEW DELHI
Copyright GAIL – All rights reserved
PIPE CULVERTS FOR STORM WATER DRAINAGE DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-005 Page 2 of 3
NEW DELHI
Copyright GAIL – All rights reserved
PIPE CULVERTS FOR STORM WATER DRAINAGE DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-005 Page 3 of 3
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD BOX CULVERTS TYPE-I,II,III & IV
S-10-01-006 Page 1 of 2
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD DETAILS OF RUNGS FOR MANHOLES,
S-10-01-007 Page 1 of 1
NEW DELHI VALVES, PITS , TANKS ETC.
Copyright GAIL – All rights reserved
STANDARD DRGS FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD MISC DETAILS FOR MANHOLES
S-10-01-008 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRGS FOR DOCUMENT No. REV-0
GAIL (INDIA) LTD MISC DETAILS FOR MANHOLES
S-10-01-008 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD CONC. BEDDING AND ENCASEMENT FOR
S-10-01-009 Page 1 of 1
NEW DELHI PIPES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD GULLY TRAP CHAMBER
S-10-01-010 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
INSPECTION CHAMBER S-10-01-011 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
SEPTIC TANK TYPE I, II & III S-10-01-012 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
DETAILS OF SOAKPIT DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-013 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
VALVE PIT TYPE-I FOR DIA < 1.5 “ STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 1
NEW DELHI 10-01-014

Copyright GAIL – All rights reserved


STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD VALVE PIT TPYE III FOR DIA 8” TO 16”
S-10-01-015 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
CHEQUERED PLATE DETAILS (FOR STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD MASONER VALVE TYPE-I,II,III &IV)
S-10-01-016 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
MANHOLE TYPE-I FOR DEPTH (FOR < 1 M, STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
DIA 300MM) S-10-01-017 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD DETAILS OF NEUTRALISATION PIT
S-10-01-018 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DETAILS FOR CHAIN LINK FENCING WITH DOCUMENT No. REV-0
GAIL (INDIA) LTD CONCRETE POST
S-10-01-019 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
RCC PAVEMENT DETAILS S-10-01-020 Page 1
NEW DELHI
of 1
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD CONCRETE SLIDING SLEEPER CAST IN
Page 1 of 1
NEW DELHI SITU TYPE-II S-10-01-021
Copyright GAIL – All rights reserved
CONCRETE SLIDING SLEEPER CAST-SITU- DOCUMENT No. REV-0
GAIL (INDIA) LTD TYPE-III
S-10-01-022 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
INSTALLATION DETAILS OF FIRE WATER HYDRANT, DOCUMENT No. REV-0
GAIL (INDIA) LTD WATER MONITOR & FOAM / WATER MONITOR
S-10-01-023 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD FOR INSTALLATION DETAILS OF STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
WATER MONITOR Page 1
NEW DELHI S-10-01-024
of 1
Copyright GAIL – All rights reserved
UPFLOW ANAEROBIC FILTER DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-11-01-025 Page 1 of 1
NEW DELHI
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD STANDARD FOR STEEL GATE FOR
S-10-01-026 Page 1 of 1
NEW DELHI ENTRANCE
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 1 of 7
NEW DELHI
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 2 of 7
NEW DELHI
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 3 of 7
NEW DELHI
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 4 of 7
NEW DELHI
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 5 of 7
NEW DELHI
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 6 of 7
NEW DELHI
Copyright GAIL – All rights reserved
REPEATER ROOM AT SV STATION (WITHOUT DG ROOM) DOCUMENT No. REV-0
GAIL (INDIA) LTD
S-10-01-027 Page 7 of 7
NEW DELHI
Copyright GAIL – All rights reserved
TECHNICAL SPCIFICATION
CIVIL & STRUCTURAL WORKS

GENERAL SCOPE

TECHNICAL SPCIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 1 of 4
NEW DELHI GENERAL SCOPE S-11-02-001
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 GENERAL

TECHNICAL SPCIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 2 of 4
NEW DELHI GENERAL SCOPE S-11-02-001
Copyright GAIL – All rights reserved
1.0 SCOPE

These specifications establish and define the material and constructional requirements for
CIVIL and STRUCTURAL WORKS.

2.0 GENERAL

2.1 Methods of measurements are indicated in these specifications; where not so specified,
latest revision of IS: 1200 shall be applicable.

2.2 Providing and operating all necessary measuring and testing devices including all materials
and consumables are included in the scope of work. No separate measurement or payment
for testing the quality of work and materials shall be made, but rates quoted for various
items shall be deemed to include the cost of such tests which are required to ensure
achievement of specified quality.

2.3 All materials shall be of standard quality, manufactured by renowned concerns conforming
to Indian Standards or equivalent, and shall have IS mark as far as possible unless
otherwise approved by the Engineer-in-Charge. The Contractor shall get all materials
approved by the Engineer-in-Charge prior to procurement and use. The Contractor shall
furnish manufacturer's certificates for the materials supplied by him when asked for.
Further to that he shall get the materials tested from an approved test house if asked for
by the Engineer-in- Charge. The cost for all the tests and test certificates for the material
procured by the Contractor shall be borne by the Contractor. No separate payment shall be
made for the testing. The Engineer-in-Charge shall have the right to determine whether all
or any of the materials are suitable. Any materials procured or brought to site and not
conforming to specifications and satisfaction of the Engineer-in-Charge shall be rejected
and the Contractor shall have to remove the same immediately from site at his own
expense and without any claim for compensation due to such rejection.

2.4 Wherever referred to in the tender document, only the latest revision of Specifications,
Codes of Practice and other publications of Bureau of Indian Standards shall be applicable.

2.5 Wherever the Contractor executes civil and structural works involving buildings, equipment
foundations, supporting structures, pipe racks, etc., the following works are deemed to
have been included in the quoted rates for various works.

- Marking of centre lines of foundations etc.

- Establishing layout and levels of foundations and superstructure etc., including


establishment of reference lines, bench marks on various floors, platforms etc.

- General upkeep of the plant site.


TECHNICAL SPCIFICATION DOCUMENT No. REV-0
GAIL (INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 3 of 4
NEW DELHI GENERAL SCOPE S-11-02-001
Copyright GAIL – All rights reserved
- Preparation of "As-Built" scheme of structural drawings indicating constructed details
including levels, centre lines, layouts, member sizes etc. complete.

2.6 The provisions of schedule of rates, specifications and drawings shall be read in conjunction
with each other and in case of conflict amongst them, clarification shall be obtained from
the Engineer-in-Charge whose decision shall be final and binding. However, the following
procedure may generally be followed.

- Description of items in schedule of rates shall be followed when provisions therein are
different from those in specifications.

- Where the description of item does not call for some specific requirement but the same
is given in specifications, the specifications shall be followed in addition to the
requirement given in description of item.

- Where drawings call for requirements different from or additional to those given in item
description and specifications, the decision of the Engineer-in-Charge shall be obtained
as to what shall be followed.

TECHNICAL SPCIFICATION DOCUMENT No. REV-0


GAIL (INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 4 of 4
NEW DELHI GENERAL SCOPE S-11-02-001
Copyright GAIL – All rights reserved
TECHNICAL SPECIFICATION
CIVIL AND STRUCTURAL WORKS

MATERIALS

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 1 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


CONTENTS

1.0 SCOPE

2.0 REFERENCES

3.0 WATER

4.0 AGGREGATE

5.0 SAND

6.0 CEMENT

7.0 STEEL

8.0 BRICK

9.0 STONE

10.0 ADMIXTURES

11.0 WATER BARS

12.0 BITUMEN/BITUMINOUS MATERIALS

13.0 PVC PIPES

14.0 WOODITIMBER

15.0 EPOXY COMPOUND

16.0 PAINT

17.0 ANTITERMITE COMPOUNDS

18.0 POLYSULPHIDE SEALANTS

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 2 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


1.0 SCOPE

1.1 This specification establishes and defines the requirements of various materials to be
used in Civil and Structural works.

1.2 Whenever any reference to BIS Codes is made, the same shall be taken as the latest
revision (with all amendments issued thereto) as on the date of submission of the bid.

1.3 Apart from the BIS Codes mentioned in particular in the various clauses of this
specification, all other relevant codes related to specific job under consideration
regarding quality, tests, testing and/or inspection procedures shall be applicable.
Reference to some of the Codes in the various clauses of this specification does not
limit or restrict the scope of applicability of other referred or relevant codes.

1.4 In case of any variation/contradiction between the provision of BIS Codes and this
specification, the provision given in this specification shall be followed.

1.5 All materials shall be of standard quality and shall be procured from renowned Sources
/ manufacturers approved by the Engineer-in-Charge. It shall be the responsibility of
the Contractor, to get all materials1 manufacturers approved by the Engineer-in-Charge
prior to procurement and placement of order.

1.6 Whenever called for by the Engineer-in-Charge all tests of the materials as specified by
the relevant BIS Codes shall be carried out by the Contractor in an approved laboratory
and test reports duly authenticated by the laboratory, shall be submitted to the
Engineer-in-Charge for his approval. If so desired by the Engineer-in-Charge, tests shall
be conducted in the presence of the Engineer-in-Charge or his authorized nominee.

1.7 Quality and acceptability of materials not covered under this specification shall be
governed by the relevant BIS Codes. In case BIS code is not available for the particular
material, other codes e.g. BS or DIN or API/ASTM shall be considered. The decision of
Engineer-in-Charge, in this regard, shall be final and binding on the Contractor.

1.8 Whenever asked for, the Contractor shall submit representative samples of materials to
the Engineer-in-Charge for his inspection and approval. Approval of any sample does
not necessarily exempt the Contractor from submitting necessary test reports for the
approved material, as per the specification/relevant BIS Codes.

1.9 The Contractor shall submit manufacturer's test reports on quality and suitability of any
material procured from them and their recommendation on storage, application,
workmanship etc. for the intended use. Submission of manufacturer's test reports does
not restrict the Engineer-in-Charge from asking fresh test results from an approved
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 3 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


laboratory of the actual material supplied from an approved manufacturer/source at any
stage of execution of work.

1.10 All costs relating to or arising out of carrying out the tests and submission of test
reports and or samples to the Engineer-in-Charge for his approval during the entire
tenure of the work shall be borne by the contractor and included in the quoted rates.

1.11 Materials for approval shall be separately stored and marked, as directed by the
Engineer-in-Charge and shall not be used in the works till these are approved.

1.12 All rejected materials shall be immediately removed from the site by the Contractor at
his own cost.

2.0 REFERENCES

As mentioned in the respective clauses.

3.0 WATER

3.1 Water used in construction for all civil & structural works shall be clean and free from
injurious amount of oil, acids, alkalis, organic matters or other harmful substances
which may be deleterious to concrete, masonry or steel. The pH value of water sample
shall be not less than 6. Potable water shall be considered satisfactory. Underground
water can also be used with the prior approval of Engineer-in-Charge, if it meets all the
requirements of IS:456.

3.2 Tests on water samples shall be carried out in accordance with IS:3025 and they shall
fulfill all the guidelines and requirements given in IS:456.

3.3 The Engineer-in-Charge may require the Contractor to prove, that the concrete
prepared with water, proposed to be used, shall have average 28 days compressive
strength not lower than 90% of the strength of concrete prepared with distilled water.

3.4 The Engineer-in-Charge may require the Contractor to get the water tested from an
approved laboratory before starting the construction work and in case the water
contains any oil/organic matter or an excess of acid, alkalis or any injurious amount of
salts etc., beyond the permissible maximum limits given in IS:456, the Engineerin-
Charge may refuse to permit its use. In case the water is supplied by the owner,
contractor shall get himself satisfied regarding its quality before using the same in his
works at his own expense. In case there is any change in source of water, water
samples shall be tested again to meet the specified requirements.

3.5 Water shall be stored in tin barrels, steel tanks or water-tight reservoirs made with
bricks / stone or reinforced concrete. Brick/stone masonry reservoirs shall have RCC
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 4 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


base slab and shall be plastered inside, with 1 part of cement and 4 parts of sand and
finished with neat cement punning. These reservoirs shall be of sufficient capacity to
meet the water requirement, at any stage of construction.

3.6 Water for curing shall be of the same quality as used for concreting and masonry
works. Sea water shall not be used for preparation of cement mortar, concrete as well
as for curing of plain/reinforced concrete and masonry works. Sea water shall not be
used for hydro testing and checking the leakage of liquid retaining structures also.

4.0 AGGREGATE

4.1 General

4.1.1 Coarse and fine aggregates for Civil and Structural Works shall conform in all respects
to IS:383 (Specification for coarse and fine aggregates from natural sources for
concrete). Aggregates shall be obtained from an approved source known to produce the
same satisfactorily. Aggregates shall consist of naturally occurring (crushed or
uncrushed) stones, gravel and sand or a combination thereof. These shall be chemically
inert, hard, strong, dense durable, clean and free from veins, adherent coatings,
injurious amount of alkalis, vegetable matter and other deleterious substances such as
iron pyrites, coal, lignite, mica, shale, sea shells etc.

4.1.2 Source and type of aggregates shall be got approved by the Engineer-in-Charge prior to
procurement. Change in source and type of aggregates, at later stage, shall not be
generally permitted; but under specific circumstances, Engineer-in-Charge can allow a
change in source and type of aggregate. Contractor shall produce necessary test
certificates from approved laboratories regarding the quality and suitability of the
proposed aggregates and submit fresh mix design for approval of the Engineer-in-
Charge. Any such change, if permitted by the Engineer-in-Charge, shall be without any
time and cost implication to the owner.

4.1.3 Aggregates which may chemically react with alkalis of cement or might cause corrosion
of the reinforcement, shall not be used. If so desired by the Engineer-in-Charge, the
Contractor shall carry out alkali reactivity tests and submit the results to him for
approval.

4.1.4 The maximum quantities of deleterious materials in the aggregates as determined in


accordance with IS:2386 - Part I1 (Methods of Test for aggregates for concrete), shall
not exceed the limits defined in IS:383. No special test is required to prove the absence
of such deleterious matters if the aggregates are from a known source with satisfactory
prior data on the properties of concrete made with them. In case of newly developed
quarry sites, the contractor shall submit necessary test results as per IS:383 and
IS:2386 to the Engineer-in-Charge prior to his acceptance and approval. The method of
Sampling shall be in accordance with the requirements given in IS:2430.
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 5 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


4.1.5 Coarse and fine aggregates shall be batched separately. All-in-aggregate shall be used
only where specifically permitted by the Engineer-in-Charge.

Separate sieve analysis and grading curves shall be prepared by the Contractor for
Any/all batches of coarse and fine aggregates, and submitted to the Engineer-in-
Charge, whenever asked for, to ensure conformity with those submitted along with the
mix design.

4.1.6 Whenever required by Engineer-in-Charge, the aggregates (coarse/fine) shall be


washed and/or sieved by the contractor before use in the works to obtain clean and
graded aggregate at no extra cost to the owner.

4.1.7 Aggregates not in conformity with the specifications shall be rejected and the
Contractor shall immediately remove them from the site of work.

4.2 Coarse Aggregates

4.2.1 Coarse aggregates are the aggregates, which are retained on 4.75mm BIS Sieve. It
shall have a specific gravity not less than 2.6 (saturated surface dry basis).

4.2.2 These may be obtained from crushed or uncrushed gravel or stone as per clause 3.1
and may be supplied as single sized or graded. The grading of the aggregates shall be
as per IS1383 or as required by the mix design, to obtain densest possible concrete. For
this purpose, the contractor shall submit to the Engineer-in-Charge at least three sets of
mix design and test results, each with different gradings of coarse aggregates,
proposed to be used. The Engineer-in-Charge may allow "All-in-aggregates" to be used
provided they satisfy the requirements of IS:383.

4.3 Fine Aggregates

4.3.1 Fine aggregates are the aggregates which pass through 4.75mm BIS sieve but not
more than ten percent (1 0%) pass through 150 micron BlS sieve. These shall comply
with the requirements of grading zones I ,I1 and 111 of IS:383. Fine aggregates
conforming to grade zone IV shall not be used for reinforced concrete works.

4.3.2 Fine aggregates shall consist of material resulting from natural disintegration of rock
and which has been deposited by streams or glacial agencies, or crushed stone sand or
gravel sand. Sand from sea shores, creeks or river banks affected by tides, shall not be
used for filling or concrete works.

4.4 Sampling and Testing

The Contractor shall carry out all tests including mix designs of concrete, at his own
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 6 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


expense, at the start of work as well as during any stage of construction as required by
the Engineer-in-Charge. Test shall be carried out in accordance with IS:516- Methods of
test for strength of concrete and IS:2386-Methods of test for aggregates for concrete.
Testing shall be carried out from laboratories approved by the Engineer-in-Charge. The
method of sampling shall be in accordance with the requirements given in IS:2430.

4.5 Storage of Aggregates

4.5.1 Storage of all types of aggregates at site of work shall be at contractor's expense and
risk and shall be stored as specified in IS:4082. Aggregates shall in no case be stored
near to the excavated earth or directly over ground surface.

4.5.2 The Contractor shall maintain sufficient quantities of aggregates, near to the place of
work, required for the continuity of the work. Each type and grade of aggregate shall
be stored separately on hard, firm surface having adequate slope for drainage of water.

4.5.3 Aggregates delivered at site in wet condition or becoming wet due to rain or any other
means, shall not be used for atleast 24 hours. The Contractor shall obtain prior
approval of the Engineer-in-charge for the use of such aggregates and shall adjust the
water content in accordance with IS:2386 to achieve the desired mix. In the absence of
test results, and to allow variation in mass of aggregates and water content on account
of moisture content, the Contractor can make suitable adjustment in the masses as per
IS:456, for preparation of nominal mix concrete only.

5.0 SAND

5.1 Sand for Masonry Mortars

5.1.1 The sand shall consist of natural sand, crushed stone sand or crushed gravel sand or a
combination of any of these. The sand shall be hard, durable, clean and free from
adherent coatings and organic matter and shall not contain the amount of clay, silt and
fine dust more than specified in IS:2 1 16.

5.1.2 The sand shall not contain any harmful impurities such as iron pyrites, alkalis, salts, coal
or other organic impurities, mica, shale or similar laminated materials, soft fragments,
sea shells in such form or in such quantities as to affect adversely the hardening,
strength or durability of the mortar.

5.1.3 Unless found satisfactory as a result of further tests as may be specified by the
Engineer-in-Charge, or unless evidence of such performance is offered which is
satisfactory to him, the maximum quantities of clay, fine silt, fine dust and organic
impurities in the sand, when tested in accordance with IS:2386, shall not be more than
5% by mass in natural sand, or crushed gravel sand or crushed stone sand. For organic
impurities, when determined in accordance with IS:2386, colour of the liquid shall be
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 7 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


lighter than that indicated by the standard solution specified in IS:2386.

5.1.4 Grading of Sand

The particle size grading of sand for use in mortars shall be within the limits as
specified below:

GRADING OF SAND FOR USE IN MASONRY MORTARS


------------------------------------------------------------------------------
IS SIEVE DESIGNATION PERCENTAGE REF. TO
IS:460 (PART I) PASSING BY MASS METHOD OF

4.75 mm 100 IS:2386(Part-I)


2.36 mm 90 to 100
1.18 mm 70 to 100
600 micron 40 to 100
300 micron 5 to 70
150 micron 0 to 15

In case of a sand whose grading falls outside the specified limits due to excess or
deficiency of coarse or fine particles, this shall be processed to comply with the
standard by screening through a suitably sized sieve and/or blending with required
quantities of suitable sizes of natural sand particles or crushed stone screenings which
are by themselves unsuitable. Based on test results and in the light of practical
experience with the use of local materials, deviation in grading of sand may be
considered by the Engineer-in-Charge. The various sizes of particles of which the sand
is composed shall be uniformly distributed throughout the mass.

5.1.5 Sampling and Testing

The method of sampling shall be in accordance with IS:2430. The amount of material
required for each test shall be as specified in relevant parts of 1S:2386. Any test which
the engineer-in-charge may require in connection with this, shall be carried out in
accordance with the relevant parts of IS:2386.

If further confirmation as to the satisfactory nature of the material is required,


compressive test on cement mortar cubes (1:6) may be made in accordance with
IS:2250 using the supplied material in place of standard sand and the strength value so
obtained shall be compared with that of another mortar made with a sand of acceptable
and comparable quality.

5.2 Sand for Filling

Sand for filling shall meet the requirements of IS:383 and shall be natural sand, hard,
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 8 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


strong, free from any organic and deleterious materials. Any sand proposed for filling,
shall be used only after it is approved by the Engineer-in-Charge. Sand obtained from
sea shores, creeks or river banks affected by tides, shall not be used for filling. Fine
aggregates suitable for concreting works shall be suitable for filling also. No sand below
grading zone-111 as per IS:383 shall be allowed for filling.

6.0 CEMENT

Cement to be used for civil and structural works shall be one of the following. Specific
requirement for the type of cement to be used shall be as shown in the drawings or as
specified in the contract or as directed by the Engineer-in-Charge.

Specification for 33 grade ordinary portland cement IS:269

Specification for portland slag cement IS:455

Specification for Portland pozzolana cement (fly ash based) IS: 1489 Pt. 1

Specification for Portland pozzolana cement


(calcined clay based) IS: 1489 Pt.2

Specification for Masonry Cement IS:3466

Specification for high alumina cement for structural use IS:6452

Specification for rapid hardening portland cement IS:8041

Specification for 43 grade ordinary portland cement IS:8112

Specification for 53 grade ordinary portland cement IS: 12269

Specification for Sulphate Resisting Portland cement IS: 12330

6.1 Storage at Site

6.1.1 The storage of cement (lifted from the Owner's godown or procured by the Contractor
himself) at the site of work shall be at contractor's expense and risk and shall meet the
requirements of IS:4082. The cement shall be stored above ground in a suitable
weather tight building or godown and in such a manner as to permit easy access for
proper inspection and also to prevent deterioration due to moisture. In the event of any
damage occurring to the quality of cement due to faulty storage or on account of
negligence on the part of the contractor, such damages shall be borne by the contractor
himself.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 9 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


6.1.2 All approved cement shall be arranged in batches with type, brand and date of receipt
flagged on them. A maximum of eight bags shall be stacked one over the other.
Cement bags shall be used in the same order as received from the manufactured
owner. The contractor shall maintain a register, on day to day basis, giving the details
of the receipt/consumption, source of supply and type of cement etc. The register shall
always be accessible to the Engineer-in-Charge for verification.

6.2 Tests after Delivery

Each consignment of cement supplied by Owner or contractor, shall, after delivery at


site and at the discretion of the Engineer-in-Charge, be subjected to any or all of the
tests and analyses, required by the relevant Indian Standard Codes. In case the cement
is supplied by the owner, the contractor shall get himself satisfied regarding its quality
before using the same in his works at his own expense. The contractor shall carry out
and bear the cost of all tests and analyses required to ensure quality of cement before
using in actual works, irrespective of the fact whether the cement is supplied by the
Owner or procured by him.

6.3 Rejection

The Engineer-in-Charge may reject at his discretion any cement, notwithstanding the
manufacturer's certificate or failing to meet the requirements of relevant BIS Codes for
testing of cement. He may similarly reject any cement which has deteriorated owing to
inadequate protection from moisture or due to intrusion of foreign matter or any other
cause. Any cement which is considered defective, shall not be used and shall be
promptly removed from the site by the contractor.

7.0 STEEL

7.1 General

All steel bars, sections, plates, and other miscellaneous steel materials, etc shall be free
from loose mill scales, rust as well as oil, mud, paint or other coatings. The materials,
construction specifications such as dimensions, shape, weight, tolerances, testing etc,
for all materials covered under this section, shall conform to respective BIS Codes.

7.2 Reinforcement Bars

Reinforcement bars, to be used for civil and structural works shall be one of the
following or in combination thereof.

Specification for mild steel and medium tensile steel bars


and hard drawn steel wire for concrete reinforcement (grade I). IS:432

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 10 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


Specification for hard drawn steel wire fabric for concrete
reinforcement. IS:1566

Specification for plain hand drawn steel wire for prestressed concrete. IS: 1785

Specification for High strength deformed steel bars and wires for
concrete reinforcement. IS: 1786

Steel for general structural purposes (Grade A). IS:2062

Specification for indented wire for prestressed concrete. IS:6003

7.3 Structural Steel

Structural steel to be used for general structural purposes shall be one of the following
or in combination thereof.

Structural steel sections shall conform to following BIS Codes.

Steel tubes for structural purposes. IS:1161

Mild Steel Tubes,tubulars and other wrought steel fittings. IS: 1239

Steel for general structural purposes (Grade A). IS:2062

Hollow steel sections for structural use. IS:4923

7.4 Miscellaneous Steel Materials

Miscellaneous steel materials shall be conforming to the following B IS Codes.

Expanded Metal Steel Sheets for General purposes. IS:412

Specification for mild steel and medium tensile steel bars and hard
drawn steel wire for concrete reinforcement (grade I) (For mild steel
bars of anchor bolts, rungs, metal inserts, grating etc.) IS:432

Hexagonal headbolts, screws & nuts of product grade C. IS:1363

Cold formed light gauge structural steel sections. IS:811

Technical supply conditions for threaded steel fasteners. IS: 1367

Plain washers IS:2016


TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 11 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


Steel wire ropes for general engineering purposes IS:2266

Thimbles for wire ropes. IS: 2315

Bulldog grips. IS:2361

Mild Steel Tubes, tubulars and other wrought steel fillings.


(For Hand rail tubular sections). IS: 1239

Drop forged sockets for wire ropes for general engineering purposes. IS:2485

Steel chequered plates. IS:3502

Hexagonal bolts and nuts (M42 to M1 50). IS:3138

7.4.1 Anchor Bolts

Material for Anchor Bolts such as MS bars, washers, nuts, pipe sleeves and plates etc.
shall be as per relevant BIS Codes mentioned above.

7.5 Storage

The storage of all materials at site of work shall be at the contractor's expense and risk
and shall be done as per the requirements given in IS:4082. The contractor shall
maintain the proper records of receipt/consumption. The records shall always be
accessible to the Engineer-in-Charge for verification.

The reinforcement bars, structural steel sections and other miscellaneous steel
materials etc, shall be stored in such a way as to avoid and prevent deterioration,
corrosion, bending, twisting and wrapping. In case of any damage occurring to the
material on account of faulty storage or negligence by the contractor, same shall be
borne by the contractor himself.

7.6 Tests after Delivery

Materials supplied by the Owner or Contractor, shall, after delivery at site and at the
discretion of Engineer-in-Charge, be subjected to any or all of the tests, required by the
relevant BIS Codes. The Contractor shall carry out and bear the cost of such tests
irrespective of the fact whether the material is procured by the Owner or the contractor.
In case steel is supplied by the Owner, the Contractor shall get himself satisfied
regarding its quality before using the same in his works at his own expense.

7.7 Rejection
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 12 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


The Engineer-in-charge may reject at his discretion any materia1,not withstanding the
manufacturer's certificate or failing to meet the requirements of relevant BIS Codes for
testing of materials. He may similarly reject any material, which has deteriorated or
corroded etc., due to improper storage, handling or transport. Defective materials shall
not be used and removed from the site by the contractor at his own expense.

8.0 BRICK

8.1 General

Bricks for masonry works shall conform to IS: 1077 - Specification for common burnt
clay building bricks and shall be of class 5.0 (with minimum compressive strength of
S.ON/mm' ). Specific requirement for any other class of bricks shall be as shown in
drawings or as described in the contract for a particular site or type of work. Physical
requirements, quality, dimensions, tolerances etc. of common burnt clay building bricks
shall conform to the requirements of IS:1077.

Bricks shall be hand - moulded or machine moulded and shall be made from suitable
soils. The bricks shall have smooth rectangular faces with sharp comers and shall be
well burnt, sound, hard, tough and uniform in colour. These shall be free from cracks,
chips, flaws, stone or humps of any kind.

8.2 Tests after Delivery

The Contractor shall take samples of each type of brick as directed by the Engineer-in-
Charge as per the requirements of IS:5454 and tests shall be carried out as per
IS:3495. The cost for carrying out any or all the tests, shall be borne by the Contractor.
The bricks, when tested, as per 1S:3495 shall have a minimum average compressive
strength, as given in the Code, for a particular class of brick. Water absorption shall not
be more than 20% by its dry weight, when soaked in cold water for 24 hours.

Brick samples so approved, shall be deposited with the Engineer-in-Charge. All


subsequent deliveries shall be upto the standards of the approved samples.

8.3 Stacking of Bricks

Bricks shall be stored at site as per the requirements given in IS:4082 and shall not be
dumped at site. They shall be unloaded from trucks to a place on a leveled surface near
to the work site. They shall be stacked in regular tiers even as they are unloaded, to
minimise breakages and defacement of bricks. The supply of bricks shall be so arranged
that as far as possible, at least two days' requirements of bricks are available at site at
any time. Bricks, of different class, shall be stacked separately.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 13 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


8.4 Local Bricks / Class 3.5 Bricks.

Where shown on drawings, locally available bricks of non modular size (230mm x 1
15mm x 75mm) in place of bricks of modular size (190mm x 90mm x 90mm) can be
used in case the bricks satisfy the other requirements of IS:1077. Minimum compressive
strength of these bricks shall not be less than 3.5N/mm?

9.0 STONE

9.1 General

All Stones used for masonry works shall conform to the requirements of following BIS
Codes.

Method of identification of natural building stones. IS: 1123

Recommendations for dimensions and workmanship of natural


building stones for masonry work. IS: 1127

Recommendations for dressing of natural building stones. IS: 1 129

9.2 Quality of Stones

Stones shall be of approved quality, hard, dense, strong, sound, durable, clean and
uniform in colour. They shall also be free from veins, adherent coatings, injurious
amount of alkalies, vegetable matters and other deleterious substances such as iron
pyrites, coal, lignite, mica, sea shells etc. Unless otherwise approved, stones from one
single quarry shall be used for any one work. The strength of stones should be
adequate to carry the imposed load and shall meet all the requirements of IS:1905,
taking into account the appropriate crushing strength of stone and type of the mortar
used. The percentage of water absorption, when tested in accordance with IS: 1124,
shall not exceed 5 percent.

Stones normally used, shall be small enough to be lifted and placed by hand. The
length of the stone shall not exceed 3 times the height. Width of stone on base shall
not be less than 150mm and in no case exceed 314th thickness of the wall. Height of
the stone shall not be more than 300mm.

9.3 Unloading/Stacking

The stones shall be unloaded from the trucks to a site near to the place of work as
defined in IS:4082 and shall be stacked on a firm ground having adequate stope for
drainage. The supply of stones shall be so arranged that as far as possible, at least two
days' requirements of stone are available at site at any time.
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 14 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


10.0 ADMIXTURES

10.1 General Requirements for Admixtures

10.1.1 All concrete admixtures shall in general comply with the following BIS Codes unless
otherwise stipulated in this specification.

Specification for integral cement water proofing compounds. IS:2645

Specification for other admixtures for concrete. IS:9103

10.1.2 Generally, admixtures shall have IS1 certification marks. However, even in case of BIS
certified admixtures, Engineer-in-Charge may require the Contractor to carry out and
submit any or all the tests (as specified in relevant BIS Codes), from approved
laboratories, over and above the manufacturer's test certificate, before giving his final
approval.

In case, admixtures certified by BIS are not available, the contractor shall submit to the
Engineer-in-Charge the type and/or proprietary brand of the admixture from only
reputed manufacturers along with necessary test certificates from recognised and
approved laboratories or any other document directed by Engineer-in-Charge for the
latter's final approval. In such cases, names of at least two manufacturers shall be
submitted to the Engineer-in-Charge for his selection. In case, both the names are
rejected, the contractor shall submit a fresh list of two manufacturers for approval by
the Engineer-in-Charge.

The Engineer-in-Charge may direct the contractor to submit test results as required by
IS:2645 or IS:9 103 for any admixture proposed to be used in the concrete in any
approved laboratory at his discretion at any stage of the work. The cost of any/all tests
required to satisfy compliance with this specification shall be borne by the Contractor.

In case of non-availability of any BIS code for testing and acceptability criteria, relevant
American, British or German Code shall be applicable.

10.1.3 Prior approval of the Engineer-in-Charge shall be obtained while using water
reducing admixtures in the concrete (PCCIRCC) or mortar. Other type of admixtures
such as accelerating admixtures, retarding admixtures or air entraining admixtures,
shall not be used unless specified on the design drawings or prior approval taken from
the design approving authority. Once approved, utmost care shall be exercised at site
by the Contractor to maintain the consistency in the quality of admixture and the
concrete/ mortar so produced.

10.1.4 The suitability and effectiveness of any admixture shall be verified by trial with the
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 15 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


designed concrete mixes using cement, aggregates together with any other materials to
be actually used in the works as per the direction of Engineer-in-Charge. If two or more
admixtures are to be used simultaneously in the same concrete mix, the Contractor
must submit necessary test results from an approved laboratory to show their
interaction and compatibility. Any/all tests specified in BIS Codes shall be carried out
only with the type of material and mix design, to be actually used in the work site.

10.1.5 No admixture shall impair the durability of the concrete nor combine with the
ingredients to form harmful compounds nor increase the risk of corrosion of
reinforcement. Use of admixtures shall not reduce the dry density of concrete. Once the
proportion of admixture has been established, strict check shall be maintained not to
alter the proportions of ingredients and water-cement ratio of the Design Mix during
execution.

10.1.6 The chloride contents in admixtures shall not exceed 2% by mass of the admixture or
0.03% by mass of the cement.

10.1.7 Admixtures which do not meet the requirements stipulated in this specification shall be
rejected and shall not be used.

10.2 Water Proofing Compounds

10.2.1 Water proofing compounds shall be mixed with only ordinary portland cement of grade
33, conforming to IS:269.

10.2.2 The permeability of the specimen with the admixture shall be less than half of the
permeability with similar specimen without the use of these compounds. These
compounds shall be used in such proportion as recommended by manufacturer but in
no case it shall exceed 3% by weight of cement.

10.2.3 The initial setting time of the cement with the use of these compounds shall not be less
than 30 minutes and final setting time shall not be more than 10 hours. Test shall be
carried out in accordance with IS:4031.

10.2.4 Compressive strength of specimen at 3 days shall not be less than 160kglsq.cm
nor 80% of the 3 days compressive strength of mortar cubes prepared with same
cement and sand only, whichever is higher. Similarly compressive strength at 7 days
shall not be less than 220 kg/sq.cm nor less than 80% of the 7 days compressive
strength prepared with the same cement and sand only, whichever is higher. The test
to determine the compressive strength shall conform to 1S:403 1.

11.0 WATER BARS (WATER STOPS)

11.1 PVC water bars shall be used in reinforced concrete construction of liquid retaining
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 16 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


structures or any other structure to safeguard them from hydrostatic pressure and
water leakage and any relative movement between two parts of the structure due to
thermal loading shrinkage or differential movement of foundations. Wherever desired or
shown in the drawings, they shall be used at expansion/contraction/construction joints.
These shall be pre-formed and shall provide a permanent water tight seal along the
entire joint in the poured concrete structures. These shall also be flexible enough to
withstand deflection/displacements at joints arising due to variation of temperatures or
settlement of foundations. The minimum thickness of water bar shall be as shown on
drawings or described in the schedule of rates and unless otherwise mentioned, these
shall be able to withstand a water head of at least 12 meters.

11.2 Performance requirements of P V C water bars shall meet the requirements of


IS:12200. These shall be of approved make and of ribbed/serrated/plane type with a
bulb at the centre. The thickness and width of water bars shall be as per schedule of
rates/ drawings but in no case the thickness shall be less than 5mm and width less than
150mm. The joining of the water bars shall be carried out by vulcanising strictly as per
the manufacturer's specifications. Lapped joints shall not be allowed under any
circumstances.

12.0 BITUMEN/BITUMINOUS MATERIALS

Bitumen to be used for various types of work shall meet all the requirements of relevant
BIS Codes as given below:

Specification of Paving Bitumen. IS: 73

Specification for bitumen mastic for flooring. IS: 1195

Specification for Bitumen felts for water proofing and


damp proofing. IS: 1322

Specification for Bituminous compounds for water proofing


and caulking purposes. IS: 1834

Specification for preformed fillers for expansion joint


in concrete pavements and structures. IS: 1838

Specification for bitumen mastic for use in water proofing of roofs. lS:3037

Specification for bitumen primer for use in water proofing and


damp proofing. IS:3384

Specification for Bitumen Mastic for Tanking and Damp proofing. IS:5871
TECHNICAL SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 17 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


Specification for Glass fibre base coal tar pitch & bitumen felts. IS:7193

Code of practise for damp proofing using bitumen mastic. IS:7198

Specification for bitumen Mastic, Anti Static and


electrically conducting grade. IS: 8374

The type and grade shall be as shown on the drawings or as indicated in schedule of
quantities or as directed by Engineer-in-Charge. Tests and acceptable criteria shall be
as per relevant BIS Codes.

13.0 PVC PIPES

PVC Pipes shall conform to the requirements of IS:4985.

14.0 WOOD/TIMBER

14.1 Wood recommended for platforms of cold vessels or below cold vessels/ exchangers
shall be hard and shall be of group A, grade I, and shall have safe permissible stress of
7Nlmm' in compression, perpendicular to grains on outside location as per IS3883.
General characteristics like durability, treatability etc. shall conform to IS: 883 and
IS:3629.

14.2 Timber required to be used for formwork shall be fairly dry before use. It should
maintain its shape during the use and even when it comes into contact with moisture
from the concrete. Storage of Wood/Timber shall be as per the requirements of
IS:4082.

For proper identification and selection of suitable timber for formwork, following codes
shall be referred.

Classification of commercial timbers and their zonal distribution IS:399

Specification for ballies for general purposes. IS:3337

Specification for Ply wood for concrete shuttering work. IS:4990

15.0 EPOXY COMPOUNDS

Refer relevant GAIL Specification.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 18 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


16.0 PAINT

16.1 Refer GAIL Specification No. 6-44-0004.

17.0 ANTITERMITE COMPOUNDS

17.1 Chloropyrifos emulsifiable concentrates (1%) conforming to IS:8944 shall be used for
treatment of soil for protection of buildings against attack by subterranean termites.

18.0 POLYSULPHIDE SEALANTS

Polysulphide sealents shall confirm to IS 12118 and be of approved make. Test


condition and requirements shall be as given in the above refered BIS code.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL AND STRUCTURAL WORKS
S-11-02-002 Page 19 of 19
NEW DELHI MATERIALS

Copyright – All rights reserved


TECHNICAL SPECIFICATION
CIVIL & STRUCTURAL WORKS

EARTHWORK

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 1 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
CONTENTS

1. SCOPE

2. CLASSIFICATION OF SOIL

3. BACKFILLING MATERIAL

4. SETTING OUT

5. EARTHING IN EXCAVATION

6. SHORING AND STRUTTING

7. BACKFILLING AROUND FOUNDATIONS AND PLINTH

8. TRANSPORTATION OF SURPLUS EARTH

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 2 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
1.0 SCOPE

This specification deals with earth work in excavation and filling.

2.0 CLASSIFICATION OF SOIL

2.1 Soft/Loose/Hard/Dense Soil and Mud

Generally any soil which yields to the application of pick and shovel or to phawra, rake
or other ordinary digging implement such as vegetable or organic soil, turf, gravel,
sand, silt. loam, clay. peat, cobble stone. mud etc.

2.2 Soft/Disintegrated/Weathered Rock (Not Requiring Blasting)

Rock or boulder which may be quarried or split with crowbar. This wilt also include
laterite and hard conglomerate.

2.3 Hard Rock (Requiring Blasting)

Any rock or boulder for the excavation of which blasting is required.

2.4 Hard Rock (Requiring Controlled Blasting)

Due to any reason if general blasting is prohibited, for rock excavation, controlled
blasting shall be used, with approval of the Engineer-in-Charge.

2.5 Hard Rock (Blasting Prohibited)

Hard rock requiring blasting as described under cl. No. 2.3 above, but where blasting is
prohibited for any reason(s), breaking up of rock shall be done by chiselling. wedging or
by using Hydraulic Splitter and chemical substances mixed in an appropriate proportion.

3.0 BACKFILLING MATERIAL

3.1 Backfilling material shall be as approved by the Engineer-in-Charge.

3.2 Backfilling of excavation in trenches, foundations and elsewhere shall consist of one of
the following materials as shown on drawing, or directed by the Engineer-in-Charge.

i) Soil

ii) Selected earth from heaps or brought from borrow areas.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 3 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
In case (i) or (ii) are not available, the Engineer-in-Charge may approve use of any of
the following :

iii) Stone/gravel

iv) Sand

v) CNS material.

3.3 The material shall be free from rubbish, roots, hard lumps and any other foreign
organic material.

4.0 SETTING OUT

4.1 The Contractor shall be responsible for the true and proper setting out of the work in
relation to original points, lines and levels of reference and for the correctness of the
levels, dimensions and alignment of all parts of the work. If at any time during progress
of the work any error appears or arises in the position of level, dimension, or alignment
of part of the work, the Contractor at his own expense shall rectify such errors to the
satisfaction of the Engineer-in-Charge. The checking of any line or level by the
Engineer-in-Charge shall not in any way relieve the Contractor of his responsibilities.

4.2 The Contractor shall lay out and construct one or more permanent bench marks in
some central place before the start of the work, from which all important levels for the
excavations will be set.

These permanent bench marks shall consist of masonry pillars with top neatly plastered
and levelled as per the directions of the Engineer-in-Charge. Bench marks shall be well
connected with triangular grid system or any other bench mark approved by the
Engineer-in-Charge.

5.0 EARTHWORK IN EXCAVATION

5.1 Excavation shall be carried out in any material met on the site to the lines, levels and
contours shown on the detailed drawings and the Contractor shall remove all excavated
materials to spoil heaps on site or transport for use in filling on the site or stack them
for reuse as directed.

5.2 Excavated material shall not be deposited within 1.5m from the top edge of the
excavation.

5.3 The sides of the excavation may be cut sloping, or shored and strutted to hold the face
of earth as per site requirements and as directed by the Engineer-in- Charge.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 4 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
5.4 Foundation pits/trenches shall not be excavated to the full depth unless construction is
imminent. The last fifteen (15) cm depth of the excavation shall not be done until
concreting work is imminent. The full depth may at the discretion of the Engineer-in-
Charge be excavated and the bed covered with a fifty (50) mm (minimum) thick (or as
indicated on drawing) layer of lean concrete 1 :5: 10 mix (1 cement:5 coarse sand: 10
crushed stone aggregate) or as specified in schedule of rates/shown on drawing, after
watering if required, and consolidating the bed.

5.5 If the bottom of any excavation has been left exposed by the Contractor and in the
opinion of the Engineer-in-Charge. that has become badly affected by the atmosphere
or by water, then the Contractor shall remove such portions of the deteriorated material
as the Engineer-in-Charge may direct and shall make good with lean concrete 1:5: 10
mix (1 Cement : 5 Coarse Sand : 10 Crushed Stone Aggregate). All expenses for such
additional concrete and excavation shall be borne by the Contractor.

5.6 Where excavation is made in excess of the depth required, the Contractor shall, at his
own expense, fill upto required level with lean concrete 1:5: 10 mix (1 Cement : 5
Coarse Sand : 10 Crushed Stone aggregates ) or as decided by Engineer-in-Charge.

5.7 The Contractor shall provide suitable drainage arrangement to prevent surface water
from any source entering the foundation pits at his own cost.

5.8 The Contractor shall make all arrangements for dewatering during excavation and
subsequent works, the accumulated water from any source (including subsoil water) in
the excavated pits/trenches and keeping the excavated pits/trenches dry for
subsequent works.

5.9 The Contractor shall make necessary arrangements for lighting, fencing and other
suitable measures for protection against risk of accidents due to open excavation.

5.10 Where the excavation is to be carried out below the foundation level of an adjacent
structure, the precaution to be taken such as under pinning, shoring and strutting etc.
shall be determined by the Engineer- in-Charge. No excavation shall be done unless
such precautionary measures are carried out as per directions of the Engineer-in-
Charge. The payment for such precautionary measures shall, however, be made
separately.

5.11 Loose or soft bed ground encountered in excavation at the required depth shall on the
Engineers-in-Charge's instructions be excavated to a firm bed and difference made up
to the required level with lean concrete l:5: 10 mix (1 Cement : 5 Coarse Sand : 10
Crushed Stone Aggregates).

5.12 In those cases where during excavation, side slips occur for reasons not attributable to
the Contractor (e.g. side slips which take place on their own but not due to surcharge

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 5 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
of earth kept near the edge of excavation and cracking of excavation top strata due to
clay drying out leading to collapse of excavation sides), the Engineer-in-Charge shall
admit payment at his discretion.

5.13 Any obstacle encountered during excavation shall be reported immediately to the
Engineer-in-Charge and shall be dealt with as instructed by him. Removal of buried
pipes or cables shall not be done without prior permission of the Engineer-in-Charge
and the Contractor shall provide all measures to protect the same. Cost of such
protective measures are deemed to be included in the rates for various items of
excavation.

5.14 The Contractor shall not undertake any concreting in foundation until the excavation
pit/trench is approved by the Engineer-in-Charge.

5.15 The specification for earth work shall also apply to excavation in rock in general.

5.16 In case of hardrock requiring blasting, the provisions mentioned below shall be strictly
followed.

5.16.1 General

Where hard rock is met with and blasting operations are considered necessary, the
Contractor shall intimate about the same to the Engineer-in-Charge, and obtain his
approval in writing for resorting to blasting operation.

The Contractor shall obtain licence from the district authorities for undertaking blasting
work as well as for obtaining and storing the explosive as per Explosive Rules 1983,
corrected upto date. He shall purchase the explosives, fuses, detonators etc. only from
a licensed dealer. He shall be responsible for the safe custody and proper accounting of
the explosive materials. The Engineer-in-Charge or his authorised representative shall
have the access to check the Contractor's store of explosive and his accounts.

In case where explosives are required to be transported and stored at site, relevant
clauses of the Explosive Rules, 1983 as amended subsequently, shall apply.

The Contractor shall be responsible for any accident to workmen: public or property,
due to blasting operations.

5.16.2 Precautions

Blasting operations shall be carried out under the careful supervision of a responsible
authorized and licensed blaster of the Contractor (referred subsequently as "blaster"
only) during specified hours, as approved in writing by the Engineer-in-Charge. The
blaster shall be fully conversant with the rules of blasting.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 6 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
Proper precautions for safety of persons shall be taken. Red flags shall be prominently
displayed around the area to be blasted and all the people on the work except those
who actually light the fuses, shall withdraw to a safe distance of not less than 200
metres from the blast. Precautions as per Explosive Rules 1983 with amendment shall
be followed.

5.16.3 Fuses

All fuses shall be cut to the lengths required before being inserted into the holes. Joints
in fuses shall be avoided. Where these are unavoidable: a semicircular niche shall be
cut in one piece of fuse about 2 cm. deep from the end and the end of other piece
inserted into this niche, and the two pieces then wrapped together with a string. All
joints exposed to dampness shall be wrapped with rubber tape. Fuse and detonators
shall be kept separated from the explosives.

5.16.4 Blasting with Gun Powder

Blasting shall normally be done with gun powder. Dynamite, gelatine or any other high
explosive shall only be used in special cases with the written permission of the
Engineer-in-Charge.

In case of blasting with gun powder, the position of all bore holes to be drilled shall be
marked out in circles with white paint. The bore holes shall be jumped or drilled in the
rock face. The depth of bore hole shall be about the same as that of the line of least
resistance and its size shall be such that the cartridges can easily pass down to the
bottom. The bore holes must be dried before being charged and these shall be
inspected by the Contractor's agent.

Gun powder may be used in the form of pellet blasting cartridges or as powder or
granules. Cartridges are provided with tapered central hole. One end of fuse is passed
through the narrow end of the hole and a sufficient length of the fuse is doubled back
so that when the fuse is pulled, it is held tight in the tapered hole of the cartridge.
Other cartridges are then inserted in the fuse to make up the required charge. The
cartridge along with the fuse is lowered down in the bore hole, placed in position and
gently filled and pressed home with dry hay or turf. The rest of the bore shall then be
filled with dry clay, which shall be tamped with copper or brass rod until it becomes
compact. Care shall be taken to avoid any possibility of an air space around the fuse.
The safety fuses shall be taken to the required distance so as to allow the blasting to
take place after the person lighting the fuse has withdrawn to a safe distance.

Where gun powder is used in the form of powder or granules it shall be introduced in
the bore hole by means of funnel or copper tube. The bore holes shall be loaded with

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 7 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
two thirds of the quantity of charge required. and safety fuse then directly introduced
over the charge. Remaining one third charge shall then be introduced, and gently filled
and pressed home with dry hay or turf. The rest of the bore hole shall be filled with dry
clay in the same way as for cartridges, and the safety fuse taken to the required
distance.

The charges shall be fired by igniting the fuse. The number of charges to be fired and
the actual number of shots heard, shall be compared, and the Contractor's blaster shall
satisfy himself by examination that all the charges have exploded: before workmen are
permitted to approach the site. The charge which has not exploded, shall not be
permitted to be withdrawn. The tamping and charge shall be flooded with water and
the holes marked with a red cross (X) over it. Another hole shall be jumped at a
distance of about 45 cm from the old hole and fired in the usual way. This operation
shall be continued. till the original and any subsequent unfired charges are exploded.

5.16.5 Blasting with Dynamite or any other High Explosive

In case of blasting with dynamite or any other high explosive the position of all bore
holes to be drilled shall be marked out in circle with white paint. These shall be
inspected by the Contractor's blaster. Bore holes shall be of a size that the cartridge can
easily pass down. After the drilling operation, the blaster shall reinspect the holes to see
that the holes marked out by him have been drilled. He shall then prepare all charges
necessary for the bore holes. The bore holes shall be thoroughly cleaned before a
cartridge is inserted. Wooden tamping rods (not pointed but cylindrical throughout)
shall be used, in charging holes. Metal rods shall never be used for tamping. One
cartridge shall be first placed in the bore hole. gently pressed and not rammed down.
Other cartridges shall then be added as may be required to make up the necessary
charge for the bore hole. The top most cartridge shall be connected to the detonator
which shall in turn be connected to the safety fuse of required length.

The maximum of eight bore holes shall be loaded and fired on each occasion. The
charges shall be fired successively and not simultaneously.

Immediately before firing a blast, due warning shall be given and the blaster shall see
that all persons have retired to a place of safety. The safety fuses of the charged holes
shall be ignited in the presence of the blaster, who shall see that all the fuses are
properly ignited.

Careful count shall be kept by him and others of each blast as it explodes. After the
blast the blaster shall inspect the work and ascertain that all the charged holes have
been exploded. In case of misfired holes, he shall inspect the same after half an hour
and mark red crosses (X) over the holes. During this interval of half an hour, no body
shall approach the misfired holes. None of the drillers shall work near such holes, until
one of the two following operations has been done by the blaster.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 8 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
a) Either the Contractor's blaster shall very carefully (when the tamping is of damp
clay) extract the tamping with a wooden scraper and withdraw the fuse, primer
and detonator, after which a fresh detonator, primer and fuse shall be placed in
the misfired holes and fired.

OR

b) The hole shall be cleaned for 30 cm of tamping and its direction ascertained by
placing a stick in the hole. Another hole shall then be drilled 15 cm away and
parallel to it. This hole shall be charged and fired. The misfired hole should also
explode along with the new one.

Before leaving the work, the blaster of one shift shall inform another blaster
relieving him for the next shift. of any cases of misfire, and shall point out their
positions denoted by red crosses and also state the action; if any, to be taken in
the matter.

The Engineer-in-Charge shall also be informed by the blaster of all cases of


misfire, their causes and steps taken in that connection.

5.16.6 Controlled Blasting

Whenever required by the Engineer-in-Charge, rock blasting shall be carefully controlled


so that vibrations generated during the blasting do not cause damage to the buildings
and installation around. Similarly, the rock pieces should not fly off and endanger the
buildings and installations around. Apart from the general precautions mentioned in the
preceding paragraphs, following protective measures and limits for use of explosive are
suggested as guidelines. Tenderers are requested to carefully check the site conditions
and submit details of the scheme they propose to adopt for controlling the blast.

Following protective measures shall be adopted while carrying out blasting operations

The hole shall be covered with mild steel plate of minimum 12mm thickness.

Reinforcement rod mesh not less than 20mm dia. at 150mm centre in both directions
shall be placed over the steel plates.

Steel plate and reinforcement shall be inspected after every blasting operation and all
twists shall be removed before reuse to the satisfaction of the Engineer-in- Charge.

Sand filled bags of 6 to 8 layers shall be placed over the mesh suitably covering the
whole region under blasting operation.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 9 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
The thickness of covering plate and the kind of dead weight is to be duly approved by
the Engineer-in-Charge .

5.16.7 Hard rock requiring blasting as described under cl.no. 2.3 above, but where blasting is
prohibited for any reason(s) breaking up of rock can be done by using Hydraulic Splitter
and chemical substances of approved manufacturer (Lifton or equivalent) mixed in an
appropriate proportion. The method involves drilling holes into rock and then
inserting/injecting hydraulic splitter/chemical solvents into the holes. The breaking-up of
rock takes place in a controlled fashion without much noise and spark.

5.17 Payment

5.17.1 Payment for earth work in excavation shall be made on cubic meter (m3) basis on the
measurement of volume of pit/trench of excavation with working space as per relevant
Indian Standards (IS: 1200) and slopes/steppings as permitted by the Engineer-in-
Charge. The rate shall include cost of all the operations of blasting with explosives &
accessories, making of all arrangements for dewatering the accumulated water from
any source in the excavated pit or trench, removal and disposal of surplus excavated
soil within a lead of 100m from construction areas. The rate shall also include setting
out and line out work required for the excavation.

5.17.2 The following works shall not be measured separately and allowance for the same shall
be deemed to have been made in the description of main item:

a) Setting out works, profiles, etc.;

b) Site clearance, such as cleaning grass and vegetation;

c) Unauthorized battering or benching of excavation;

d) Forming (or leaving 'dead men' or 'tell-tales' in borrow pits and their removal
after measurements;

e) Forming (or leaving) steps in sides of deep excavation and their removal after
measurements;

f) Excavation for insertion of planking and strutting;

g) Unless otherwise specified, removing slips or falls in excavations;

h) Baling out or pumping of water in excavation from rains;

i) Baling out or pumping of water in excavation from sub-soil water, and

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 10 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
j) Slinging or supporting pipes, electric cables, etc, met during excavation.

5.17.3 Special pumping other than what is included in 5.17.2 (h and i) and well point
dewatering where resorted to. shall each be measured separately, unless otherwise
stated, in kilolitres of water against separate specific provision(s) made for the purpose.

5.17.4 The Contractor shall intimate to the Engineer-in-Charge as soon as different


classification of soils are met with. The measurements of various soil classifications then
shall be worked out by either of the following alternatives in the order of their
decreasing importance.

a) Joint levels shall be taken as to the levels of different soil classifications and
volume worked out on the basis of levels only.

b) Where levels of different strata cannot be clearly marked and defined, the
Contractor shall stack different soils of various classifications separately for
measurement purpose and then dispose it off.

c) If the quantum of work involved in (b) above is extensively large & time
consuming, then the total area may be divided into various zones and reasonably
representative samples as in (b) above may be taken and quantities of soils of
various classifications finalized for the entire zone based on the representative.

If soil of any classification other than that specified in the Schedule of Rates is met with
during excavation, the decision of the Engineer-in-Charge as to the classification of soil,
levels of the strata of different classifications and their location shall be binding.

In above case, the total quantity of excavation shall be computed from the
measurement of the pit/trench excavated. The hard rock and soft rock shall be
measured separately from the relevant stacks and each shall be reduced by fifty
percent for voids, and paid under the relevant items. The balance. that is the total
quantity of excavation minus the reduced (for voids) quantity of excavation for rocks
shall be paid as softlhard soil as per the direction of the Engineer-in-Charge (However,
the maximum payment shall be limited to the volume of the excavated pit/trench as
approved by Engineer-in-Charge) .

6.0 SHORING AND STRUTTING:

6.1 The shoring and strutting of the sides to withhold the face of excavation pits/trenches
shall be done when approved or directed by the Engineer-in-Charge.

6.2 The shoring shall be of close or open timbering type depending upon the site
requirements and as directed by the Engineer-in-Charge whose decision shall be final

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 11 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
and binding as to the type of shoring to be used.

6.3 The arrangement of the shoring and strutting shall be sound and safe and shall be got
approved from the Engineer-in-Charge before installation. The approval shall not
absolve the Contractor of his responsibilities of safety and any other requirements of
the contract.

6.4 The shoring and strutting shall be kept in position till all the relevant work in the
excavated area is completed and approved. It shall be dismantled and removed only
after the permission to do so is obtained from the Engineer-in-Charge.
6.5 Payment

Payment for shoring and strutting by close and open timbering shall be made on square
meter (m2) basis as separate items. In both the cases, the measurement shall be done
on the basis of the surface area of the sides of the excavation actually shored and
strutted.

The rate shall include all labour, materials, erection of the poling boards, wales: struts,
ballies etc., fixing and keeping the same in position as required, dismantling and
removing the same after the work is over as directed.

7.0 BACK FILLING AROUND FOUNDATIONS AND IN PLINTH

7.1 Back filling around completed foundations, structures, trenches and in plinth shall be
done to the lines and levels shown on the drawings including any trimming of the
surfaces, as may be necessary. This shall be done with selected and approved earth
from excavation or otherwise with materials described under clause 3.2 as directed by
the Engineer-in-Charge. Where sufficient suitable material is not available from the
excavation, the Engineer-in-Charge may direct to import suitable earth from other
sources. The filling shall be done in layers of thickness not exceeding 15 cm with
watering, rolling and ramming by manual methods1 mechanical compactors to grade
and level as shown on drawings to obtain 90% laboratory maximum dry density.

7.2 The Contractor shall not commence filling in and around any work until it has been
permitted by the Engineer-in- Charge.

7.3 Backfilling around liquid retaining structures and pipes shall be done only after approval
of the Engineer-in- Charge is obtained.

7.4 Payment

Payment for backfilling with earth shall be based on volume in cubic meters (m3) of
consolidated fill. This volume shall be derived from the difference between the volume
of excavation and the structure or trenches as the case may be. The rate shall include

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 12 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
cost of extracting suitable approved earth from available excavated soil from spoil
heaps within a lead of 100m. placing. watering, rolling, ramming compacting in layers,
trimming and dressing finished surface and disposal of surplus material upto a lead of
100m.

However, backfilling done with materials other than earth shall be paid separately under
relevant items.

8.0 TRANSPORTATION OF SURPLUS EARTH

8.1 Surplus earth and soil from excavation shall be removed from construction area to the
area demarcated by the Engineer-in-Charge.

8.2 Payment

8.2.1 Payment shall be made only for the lead beyond initial lOOm from construction area.
Rate shall include re- excavation, loading: transportation, dumping, stacking or
spreading (as per directions of the Engineer-in-Charge) the surplus earth and the soil in
the area demarcated by the Engineer-in-Charge. Payment shall be made on cubic metre
(m3) basis on the difference of measurements of the volume of the excavated pits and
the measurement of the back filling. Quantity generated due to voids in back filled
volume of earth shall also be removed by the Contractor at no extra cost and this
disposal of earth shall not be measured and paid under any item.

8.2.2 In exceptional circumstances the Engineer-in-Charge may direct the Contractor to


remove surplus earth, concrete debris or any other waste material from site to the
areas of disposal on the basis of truck measurement. In such cases volume of material
shall be calculated on the basis of truck volume reduced by 30% for voids in case of
soft/hard soils and 50% for soft/hard rock. All other provisions of disposal such as
spreading, leveling, grading shall apply in this case also.

TECHNICAL SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRUCTURAL WORKS
Page 13 of 13
NEW DELHI EARTHWORK
S-11-02-003
Copyright – All rights reserved
TECHNICAL SPECIFICATION
CIVIL & STRUCTURAL WORKS

PLAIN AND REINFORCED CEMENT


CONCRETE

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 1 of 42
NEW DELHI
Copyright – All rights reserved
CONTENTS

1. SCOPE

2. MATERIALS

3. GRADES OF CONCRETE

4. TYPE OF CONCRETE MIX

5. CONCRETE MIX PROPORTIONING

6. BATCHING

7. CONCRETE MIXING

8. TRANSPORTATION, PLACING AND COMPACTION

9. CONSTRUCTION JOINTS

10. SEPARATION JOINTS

11. EXPANSION JOINTS/ISOLATION JOINT

12. WATER STOPS

13. PROTECTION OF FRESHLY LAID CONCRETE

14. CURING

15. FIELD TESTS

16. INSPECTION AND TESTING OF STRUCTURES

17. FINISHING OF CONCRETE

18. CEMENT WASH

19. FORM WORK

20. EXPOSEDIARCHITECTURAL CONCRETE WORK

21. REINFORCEMENT

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 2 of 42
NEW DELHI
Copyright – All rights reserved
22. PRECAST CONCRETE

23. CONTINUOUS CONCRETING

24. PAYMENT

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 3 of 42
NEW DELHI
Copyright – All rights reserved
1. SCOPE
This specification establishes the requirements of materials, mix proportioning, placing,
curing, etc. of all types of cast-in-situ and precast concrete used in foundations,
underground and overground structures, floors, pavements etc. Any special
requirements as shown or noted on the drawings shall supersede over the provisions of
this specifications.

1.1 Reference Codes and Specifications

Apart from this specification, construction of plain and reinforced concrete works shall
be in accordance with the Indian Standard Code of Practice for "Plain and Reinforced
Concrete" IS:456 and other relevant codes mentioned therein.

1.2 For Liquid Retaining Structures GAIL Specification No. 6-68-0005, shall hold good.

1.3 For Structural Steel works GAIL Specification No. 6-68-0006 & 0008, shall hold good.

1.4 In case of conflict between the clauses mentioned in this specification and those in the
Bureau of Indian Standards (BIS), this specification shall govern.

2. MATERIALS

2.1 Materials for concrete viz cement, sand, coarse aggregate, water, etc. shall be as
described in GAIL Specification No.S-11-02-002
2.2 Materials for all reinforcements, embedment, inserts, water bars etc. shall conform to
GAIL Specification No.s-11-02-005

2.3 Materials suggested to be used as additive to concrete shall conform to GAIL


specification

3.0 GRADES OF CONCRETE

Unless otherwise noted on the drawings, or called for in the schedule of rates, the
grades of concrete shall generally be as per Table-1.

TABLE-I
GRADES OF CONCRETE
Grade designation Specified Characteristic Comprehensive
Strength of 150 mm cube at 28 days
(N/mm2)
M 15 15
M20 20
M25 25

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 4 of 42
NEW DELHI
Copyright – All rights reserved
M30 30
M35 35
M40 40
M45 45
M50 50
M55 55

Note for Table - 1 : The characteristic strength is defined as the strength of material below
which not more than five (5) percent of the test results are expected to fall.

3.1 Plain and reinforced cement concrete work shall confirm to Indian Standard for plain
and concrete- Code of practice fourth revision IS 456:2000.

4.0 TYPE OF CONCRETE MIX

4.1 Unless otherwise noted on drawings, all lean/plain and reinforced concrete shall be of
M20 grade suitable for sever exposure condition and Reinforcement Cement Concrete
shall be of grade M30 suitable for sever exposure condition confirming to IS 456:2000.

4.2 Nominal Mix Concrete


This concrete shall be made (without preliminary tests) by adopting nominal concrete
mix with proportions of materials as specified in Table-1A.

TABLE - 1A
PROPORTIONS FOR NQ

Nominal mix of concrete (by Quantity of water per 50 kg of


mass) cement(Max)
Litres

1:5:10 60
1:3:6 34
M 15 (1:2:4) 32
M 20 (1:1 ½: 3) 34

Note:
1. The proportions of the fine to coarse aggregates should be adjusted
from upper
limit to lower limit progressively as the grading of the fine
aggregates becomes
finer and the maximum size of coarse aggregates becomes

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 5 of 42
NEW DELHI
Copyright – All rights reserved
1arger.Graded
coarse aggregates shall be used.

2. The cement content of the mix shall be proportionately increased if


the
quantity of water in a mix has to be increased to overcome the
difficulties of placement and compaction, so that the water-cement
ratio, as specified, is not exceeded.

4.3 Design Mix Concrete


The mix shall be designed to produce the grade of concrete having the required
workability and characteristic strength not less than appropriate values given in Table-1.
The target mean strength of concrete mix shall be equal to the characteristic strength
plus 1.65 times the standard deviation. As long as the quality of materials does not
change, a mix design done earliel; may be considered
adequate for later work. However, in case the quality of materials change or there is a
break in the continuity of construction and the same work is allocated to a new
contractor, the Engineer-in-Charge shall ask for a new design mix.

Irrespective of the grade of concrete required to be produced as per characteristic


strength criteria, the minimum cement content and maximum free water cement ratio
in the design concrete shall be strictly maintained as stipulated in Table 2A for the
corresponding grade of concrete.

5.0 CONCRETE MIX PROPORTIONING


Proportioning, as used in this specification, shall mean the process of determining the
proportions of the various ingredients to be used to produce concrete of the required
workability when freshlgreen and strength, durability and surface finish, when
hardened.The following information shall be collected prior to design of the concrete
mix :
a) Grade designation.

b) Type of cement.

c) Maximum nominal size of aggregate.

d) Minimum cement content.

e) Maximum free water cement ratio

f) Workability requirements.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 6 of 42
NEW DELHI
Copyright – All rights reserved
The Engineer-in-Charge shall verify the strength of the concrete mix, before giving his
sanction of its use. However, this does not absolve the Contractor of his responsibility
as regards achieving the prescribed strength of the mix. If during the execution of the
work, cube tests show lower strengths than required, the Engineer-in-Charge shall
order fresh trial mixes to be made by the Contractor.

No claim to alter the rates of concrete work shall be entertained due to such changes in
mix variations. Any variation in cement consumption shall be taken into consideration
for material reconciliation. Preliminary mix designs shall be established well ahead of
start of work.

5.1 Maximum Density

Suitable proportions of sand and the different sizes of coarse aggregates for each grade
of concrete shall be selected to give as nearly as practicable the maximum density. This
shall be determined by mathematical means, laboratory tests, field trials and suitable
changes in aggregate gradation. The contractor shall submit to the Engineer-in-Charge
at least three sets of mix design and corresponding test results after varying the mix
proportions and 1 or grading of aggregate so as to establish the
maximum density of any particular grade of concrete.

5.2 Free Water Cement Ratio

Once a mix, including its free water cement ratio, has been determined and approved
for use by the Engineer-in- Charge, that free water cement ratio shall be maintained.
The Contractor shall determine the water content of the aggregates frequently as the
work progresses, and the amount of mixing water shall be adjusted so as to maintain
the approved free water cement ratio.

5.3 Consistency

The concrete shall have a consistency such that it shall be workable in the required
position and when properly vibrated it flows around reinforcing steel, all embedded
fixtures, etc.

5.4 Workability

5.4.1 The concrete mix proportion shall be such that the concrete is of adequate workability
for the placing condition and can be properly compacted with the means available. Use
of additives of approved make shall be taken recourse to where required for attaining
proper workability as specified under cl. 5.4.2.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 7 of 42
NEW DELHI
Copyright – All rights reserved
5.4.2 The suggested ranges of values of workability of concrete measured in accordance with
IS: 1199 are indicated in Table-:! below. However, the actual values to be followed shall
be established depending on aggregate sizing, mix proportions, placing conditions, etc
and shall be got approved by the Engineer-in-Charge .

TABLE - 2
VALUES FOR WORKABILITY

Placing conditions Degree of workability Slump


(rnrn)

.
5.5 Durability

For achieving sufficiently durable concrete, strong, dense aggregates, low water-cement
ratio and adequate cement content shall always be used. Workability of concrete shall be
such that concrete can be completely compacted with the means available. Leak-proof
formwork shall be used so as to ensure no loss of cement-slurry during pouring and
compaction. Cover to reinforcement shaI1 be uniform and as shown on drawings. Concrete
mix design shall always take into account the type of cement, minimum cement content
irrespective of the type of cement and maximum free water cement ratio and minimum
grade of concrete conforming to the exposure conditions as given in Table-2A.

TABLE - 2A
MINIMUM CEMENT CONTENT, MAXIMUM FREE WATER CEMENT RATIO AND
MINIMUM GRADE OF CONCRETE FOR DIFFERENT EXPOSURE CONDITIONS

Plain Concrete Reinforced Concrete

Minimum Maximum Minimum Minimum Maximum Minimum


Exposure Cement Free Grade of cement Free Grade of
Content Water concrete content Water concrete
Ratio content ratio content
(Kg/M3) ratio (Kg/m3) ratio
Mild 240 0.60 M 15 330 0.55 M 20
Moderate 265 0.60 M 15 330 0.50 M 25
STATNDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 8 of 42
NEW DELHI
Copyright – All rights reserved
Sever 275 0.50 M 20 350 0.45 M 30
Very 280 0.45 M 20 375 0.45 M 35
Sever
Extreme 310 0.40 M 20 400 0.40 M 40

Generally, the following types of cement shall be used for Plain and Reinforced concrete
works:

a) 33 Grade Ordinary Portland Cement conforming to IS: 269.

b) 43 Grade Ordinary Portland Cement conforming to IS: 8112.

c) Portland Slag Cement conforming to IS:455.

d) Portland Pozzolana Cement conforming to IS: 1489.

e) Sulphate Resisting Portland Cement conforming to IS: 12330

Sulphate Resisting Portland Cement shall be used only for specific requirements
depending on environmental and process exposure conditions to which the structures
may be subjected to like high sulphate concentrations, processes involving sulphur
handling etc.

The minimum cement content as mentioned in Table-2A shall be adjusted for


aggregates other than 20mm nominal maximum size. The minimum cement content in
the concrete mix shall be increased by 40kg/m3 and decreased by 30 kg/m3 for lOmm
and 40mm nominal maximum size aggregates respectively.

5.6 Limits to Deleterious Constituents

Careful selection of the mix and the constituent materials shall be made to limit the
presence of deleterious constituents in concrete. The total acid soluble chloride content
calculated from the mix proportion and the measured chloride content of each of the
constituents shall not exceed 0.6 kg/m3 at the time of placing of concrete. The total
water soluble sulphate content of the concrete mix shall not exceed 4 percent by mass
of the cement in the mix.

6.0 BATCHING

6.1
In proportioning concrete, the quantity of both cement and aggregate shall be
determined by mass.Where the mass of cement is determined on the basis of mass of
cement per bag, a reasonable number of bags shall be weighed periodically to check
the net mass.Where the cement is weighed at site and not in bags, it shall be weighed

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 9 of 42
NEW DELHI
Copyright – All rights reserved
separately from the aggregates.Water shall be either measured by volume in calibrated
tanks or weighed.Any solid admixtures that are to be added, shall be measured by
mass; liquid and paste admixtures shall be measured by volume or mass. Batching
plant, shall conform to IS:4925. All measuring equipment shall be maintained in a clean
serviceable condition, and their accuracy shall be within +2% and t3%for measurement
of cement and aggregates/water/admixtures, respectively.

6.2 Except where it can be shown to the satisfaction of the Engineer-in-Charge that supply
of properly graded aggregate of uniform quality can be maintained over the period of
work, the grading of aggregate shall be controlled by obtaining the coarse aggregate in
different sizes and blending them in the right proportions when required, different sizes
being stacked in separate stock piles. The grading of coarse and fine aggregates shall
be checked frequently, the frequency for a given job being determined by the Engineer-
in-Charge to ensure that the approved grading is maintained.

6.3 Under very special circumstances change from weigh batching to appropriate volume
batching may be permitted by Engineer-in-Charge. However, in such cases all
conversions from mass of ingredients to volume shall be based on actual and
appropriate bulk densities physically measured at site and approved by the Engineer-in-
Charge.

6.4 The amount of added water shall be adjusted to compensate for any observed
variations in the moisture contents in both fine and coarse aggregates. For the
determination of moisture content in the aggregates, IS:2386 (Part-3) may be referred
to. To allow for the variation in mass of aggregates due to variation in their moisture
content, suitable adjustments in the mass of aggregate shall also be made. In the
absence of exact data, only in the case of nominal mixes, the amount of surface water
may be estimated from the values given in Table-3.

TABLE – 3
SURFACE WATER CARRIED BY AGGREGATE

AGGREGATE APPROX QUANTITY OF SURFACE WATER


SURFACE BY MASS LITER/M3
Very wet sand 7.5 120

Moderate wet 5.0 80


sand
2.5 40
Moist sand
1.25 – 2.5 20- 40
Moist gravel or
crushed rock

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 10 of 42
NEW DELHI
Copyright – All rights reserved
6.5 No substitutions in materials used on the work or alterations in the established
proportions, except as permitted in 6.4 shall be made without additional tests to show
that the quality and strength of concrete are satisfactory. In case the Contractor
proposes any change in the already approved mix design, fresh mix design with
supportive laboratory tests shall be submitted to the Engineer-in-Charge and his
approval has to be obtained prior to using the revised mix proportion in the works.
However, such proposals for revision shall only be entertained in case of successive
failure of test cubes to achieve the required strength.

7.0 CONCRETE MIXING

7.1 Approximate quantity of surface water The mixing of concrete shall be strictly carried
out in an approved type of mechanical concrete mixer. The mixer shall be fitted with
water measuring devices. The mixing shall be continued until there is a uniform
distribution of the material and the mass is uniform in colour and onsistency.
If there is segregation after unloading from the mixer, the concrete shall be remixed.
Percent bv mass Use of Ready Mixed Concrete supplied by Ready Mixed Concrete Plants
or from onloff-site batching plants (IS:4926) shall be prefered for structural concrete.
Litre / m3 All records and charts for the batching and mixing operations shall be
prepared and maintained by the contractor as per the instructions of Engineer-in-
Charge.

7.2 Mixer

7.2.1 Mechanical Mixers shall comply with IS:1791 and 121 19 and shall be maintained in
satisfactory operating condition. These shall be used only for producing lean/ plain
concrete and/ or nominal mix concrete wherever permitted.

7.2.2 Mixing Time

Mixing time shall be as indicated in the following table. Excessive mixing requiring
additions of water shall not be permitted. Time shall start when all solid materials are
poured in the revolving mixer drum, provided that all of the mixing water shall be
introduced before one-fourth of the mixing time has elapsed. The Engineer-in-Charge
may, however, direct a change in the mixing time, if he considers such a change
necessary.

MINIMUM MIXING TIME FOR MIXERS

Capacity of mixer Minimum mixing time

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 11 of 42
NEW DELHI
Copyright – All rights reserved
2 m3 or less 2 minutes

Above 2 m3 3 minutes or as recommended by the


mixer manufacturer.

7.3 Hand Mixing

Hand mixing of concrete shall not be permitted. However, for non-critical applications
namely foundations for crossovers, isolated operating platforms etc. using concrete of
maximum grade M20 and located at far away isolated places, this may be permitted by
the Engineer-in-charge as a special case.Ten percent (10%) extra cement shall be
added to the design proportion. Mixing shall be carried out on a water tight platform
and care shall be taken to ensure that mixing is continued until
the mass is uniform in colour and consistency. No extra payment shall be made to the
Contractor for mixing by hand or for using extra cement due to hand mixing.

7.4 Additives

Additive in concrete shall be used only with the prior approval of the Engineer-in-
Charge and shall comply with cl. 5.5 of IS:456. Any additive used for obtaining proper
workability or leak-proofness of concrete or repaidrendering works of concrete due to
non-conformance to the specifications, shall not be measured and paid for. All costs
relating to such usage shall be borne by the Contractor.

8.0 TRANSPORTATION, PLACING AND COMPACTION

8.1 General

The entire concrete placing programme including transportation arrangements,


deployment of equipment, layout, proposed procedures and methods, shall be
submitted to the Engineer-in-Charge 24 hours prior to concreting for approval. No
concreting shall be placed until his approval has been received. Approval of the
Engineer-in-Charge for pouring concrete shall be taken as 'conveyed', when the
concrete pour card is signed by him.

8.1.1 Chuting

The use of long troughs, chutes and pipes for conveying concrete from the mixer to the
forms shall be permitted only on written authorization from the Engineer-in-Charge. In
case an inferior quality of concrete is produced by the use of such conveyors, the
Engineer-in-Charge may order discontinuance of their use and the substitution of a
satisfactory method of placing the concrete. Open troughs and chutes shall be equipped

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 12 of 42
NEW DELHI
Copyright – All rights reserved
with baffles and be in short lengths to avoid segregation.

Chutes shall be designed so that the concrete is, to some extent, remixed at the lbwer
end by passing down through a funnel shaped pipe or drop chute. Alternatively, they
shall discharge into a storage
hopper from which the concrete shall be transported to the point of placing by wheel
barrows or other means. Where drop chutes are used, a sufficient number of these
must be provided, so that the concrete discharged from the chute is not required to
flow laterally more than 1.0 metre. Where a drop chute is swung from the vertical, the
bottom two sections must be maintained in a vertical position to avoid segregation. The
addition of water at any point in the system of tran~portation~to facilitate the
movement of concrete shall not be permitted. All chutes, troughs and pipes, shall be
kept clean and free from coatings of hardened concrete by thoroughly flushing them
with water after each run; water used for flushing shall be discharged clear of the
structure. Concrete shall not be normally permitted to fall freely from a height of more
than 1.5 metre nor to strike the forms at an angle. However, a deviation from this
normal practice may be allowed provided proper precaution is taken, while placing
concrete into the forms to avoid segregation, to the satisfaction of the
Engineer-in-Charge.

8.1.2 Vibrators

8.1.2.1Concrete shall be compacted with mechanical vibrating equipment supplemented, if


necessary to obtain consolidation, by hand spreading, rodding and tamping. The
vibrators shall be of immersion type with operational frequency ranging between 8,000
to 12,000 vibrations per minute. All vibrators shall comply with IS:2505. Screed board
concrete vibrators or concreting vibrating tables or form vibrators conforming to
IS:2506,2514 and 4656, respectively, shall be used where specifically required and
directed by Engineer-in-Charge. .

8.1.2.2 Immersion type vibrators shall be inserted in a vertical position at intervals of about
600mn-1, depending upon the mix, the equipment used, and experience on work. The
vibrators shall be withdrawn slowly. The spacing shall provide some overlapping of the
area vibrated at each insertion. In no case shall vibrators be used to transport concrete
inside the forms. Over vibration or under vibration shall not be permitted as both are
harmful. Hand tamping in some cases may be allowed subject to the approval of the
Engineer-in-Charge.

8.1.2.3 In placing concrete in layers which are advancing horizontally as the work
progresses, great care shall be exercised to ensure adequate vibration, bonding and
moulding of the concrete between the succeeding batches.

8.1.2.4 The vibrator shall penetrate the layer being placed and also penetrate the layer
below while the under layer is still plastic to ensure good bond and homogeneity
between the two layers and prevent the formation of cold joints
STATNDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 13 of 42
NEW DELHI
Copyright – All rights reserved
.
8.1.2.5 Care shall be taken to prevent contact of vibrators against all embedded
reinforcing steelor inserts.Vibrators shall not be allowed to come in contact with forms.

8.1.2.6 The use of form vibrators shall not be permitted for compaction of in-situ
concrete without specific authorization of the Engineer-in-Charge.

8.1.2.7 The use of surface vibrators of screed board type shall not be permitted for
consolidation of concrete under ordinary conditions. However,for thin slabs (of
thickness less than 200mm) surface vibration by such vibrators may be permitted, upon
approval of the Engineer-in-Charge.

8.1.2.8 Whenever vibration has to be applied externally, the design of formwork and the
disposition of vibrators shall be carefully planned to ensure efficient compaction and to
avoid surface blemishes.

8.2 Transportation

8.2.1 All concrete shall be conveyed from the mixer to the place of final deposit such as
formwork as rapidly as possible using suitable buckets, dumpers, pumps, transit mixers
containers or conveyors which shall be mortar leak tight.Care shall be taken to prevent
the segregation or loss of the ingredients and maintaining the required workability .For
structural concrete produced from Ready Mixed Concrete Plants as per cl. 7.1, concrete
shall be transported from the plants to the sites only by transit mixers.
8.2.2 During hot or cold weather, concrete shall be transported in deep containers.Other
suitable methods to reduce the loss of water by evaporation in hot weatherand heat
loss in cold weather may also be adopted.Al1 equipment used for transporting and
placing of concrete shall be maintained in clean condition.Al1 buckets, hoppers, chutes,
dumpers and other equipment shall be thoroughly cleaned after each use.

8.3 Placing and Compaction

8.3.1 Before placing concrete, all soil surfaces upon which or against which concrete is to be
placed shall be well compacted and free from standing water, mud or debris. Soft or
yielding soil shall be removed and replaced, with lean concrete or with selected
soils/sand and compacted to the density as directed by Engineer-in-Charge. The surface
of absorptive soil (against which concrete is to be placed) shall be moistened
thoroughly so that moisture is not drawn from the freshly placed concrete. Similarly, for
concrete to be placed on formworks, all chippings, shavings and sawdust etc. shall be
removed from the interior of the forms before the concrete is placed.

8.3.2 Concrete shall not be placed until the formwork, the placement of reinforcing steel,
embedded parts, pockets etc. have been inspected and approved by the Engineer- in-

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 14 of 42
NEW DELHI
Copyright – All rights reserved
Charge. Any accumulated water on the surface of the bedding layer shall be removed
by suitable means before start of placement.No concrete shall be placed on a water
covered surface.

8.3.3 Concrete shall be discharged by vertical drop only and the drop height shall not
normally exceed 1.5 metre throughout all stages of delivery until the concrete comes to
rest in forms. For continuous concreting operation windows of suitable size shall be kept
in the formwork or chutes shall be used to avoid segregation of concrete.

8.3.4 Concrete shall be deposited as near as practicable in its final position to avoid
rehandling. Concrete shall be placed in successive horizontal 1ayers.The bucket loads,
or other units of deposit, shall be placed progressively along the face of the layer with
such over-lap as will facilitate spreading the layer of uniform depth and texture with a
minimum of hand shovelling. Any tendency to segregation shall be corrected by
shovelling coarse aggregates into mortar rather than mortar on the coarse aggregates.
Such a tendency for segregation shall be corrected by redesign of mix, change in
process or other means, as directed by the Engineer-in-Charge.

8.3.5 All struts, stays and braces (serving temporarily to hold the forms in correct shape and
alignment pending the placing of concrete at their locations) shall be removed when the
concrete placing has reached an elevation rendering their service unnecessary.These
shall not be buried in the concrete.Concrete shall be thoroughly compacted with
vibrators and fully worked around the reinforcement, embedded fixtures and into
corners of formwork before setting commences and shall not be subsequently
disturbed.Methods of placing shall be such as to preclude segregation and avoid
displacement of reinforcement or formwork. The formation of stone-pockets or mortar
bondage in corners and against face forms shall not be permittedShould these occur,
they shall be dug out, reformed and refiIled to sufficient depth and shape for thorough
bonding as directed by the Engineer-in-Charge.Care shall be taken to avoid
displacement of reinforcement and embedded inserts or movement of formwork.

8.3.6 Unless otherwise approved, concrete shall be placed in single operation to the full
thickness of foundation rafts,slabs, beams and similar members. Concrete shall be
placed continuously until completion of the part of the work between approved
construction joints or as directed by the Engineer-in-Charge.

8.3.7 The method of placing and compaction employed in any particular section of the work
shall be to the entire satisfaction of the Engineer-in-Charge.

8.3.8 During hot weather (atmospheric temperature above 40 degree Celsius) or cold
weather (atmospheric temperature less than 5 degree Celcius, the concreting shall be
done as per the procedure set out in IS:7861.

8.3.9 Concrete that has set standing and becomes stiffened shall not be used in the work.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 15 of 42
NEW DELHI
Copyright – All rights reserved
8.4 Items Embedded in Concrete

8.4.1 Concreting shall not be started unless the electrical conduits, pipes, fixtures etc.,
wherever required ,are laid by the concerned agency. The Contractor shall afford all the
facilities and maintain co-ordination of work with other agencies engaged in electrical
and such other works as directed by the Engineer-in-Charge.

8.4.2 Before concreting the Contractor shall provide, fabricate and lay in proper position all
metal inserts, anchor bolts, pipes etc. (which are required to be embedded in concrete
members) as per relevant drawings and directions of Engineer-in-Charge.

8.4.3 All embedment, inserts etc. shall be fully held and secured in their respective positions
by the concerned agencies to the entire satisfaction of Engineer-in-Charge so as to
avoid any dislocation or displacement during the concreting operations. The Contractor
shall take all possible care during concreting to maintain these embedmenthnserts in
their exact locations.

9.0 CONSTRUCTION JOINTS

9.1 Construction joints shall be provided in position as shown or described on the


drawings or as directed by the Engineer-in-Charge. Such joints shall be kept to the
minimum. These shall be straight and at right angles to the direction of main
reinforcement and shall be placed at accessible locations to permit cleaning out of
laitance, cement slurry and unsound concrete.

9.2.1 In a colurnn,the joint shall be formed about lOO mrn to 150mrn below the lowest
soffit of the beams framing into it. Concrete in a beam and slab shall be placed
throughout without a joint but if the provision of a joint is unavoidable, the joint shall
be vertical and located within 113 to 114 of the span,unless otherwise shown on the
drawings.

9.3 When stopping the concrete on a vertical plane in slabs and beams, an approved stop
board shall be placed with necessary slots for reinforcement bars. The construction
joints shall be keyed by providing a triangular or trapezoidal fillet nailed on the stop
board. Inclined joints shall not be permitted. Any concrete flowing through the joints of
stop board shall be removed soon after the initial set. When concrete is stopped on a
horizontal the surface shall be roughened and cleaned after the initial set and a
triangular or trapezoidal groove shall be provided for keying with the new concrete
later.

9.4 When the work has to be resumed on a surface which has hardened,such surface shall
be cleared of any foreign materials and roughened to expose the tips of the coarse

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 16 of 42
NEW DELHI
Copyright – All rights reserved
aggregate. This may be done by manual chipping of concrete, with a high pressure
water jet or by any other appropriate means as per Engineer-in-Charge's directions. It
shall then be swept clean and thoroughly washed and wetted before any new concrete
is poured. Any set mortar or concrete sticking to the exposed reinforcing rods in and
around such joints shall be thoroughly removed. The reinforcements shall be wire
brushed and washed just before pouring any cement slurry or mortar. For vertical joints
neat cement slurry shall be applied on the surface before it is dry. For horizontal joints
the surface shall be covered with a layer of mortar about 10 to 15mm thick composed
of cement and sand in the same ratio as the cement and sand in concrete mix. This
layer of cement slurry or mortar shall be freshly mixed and applied immediately before
placing new concrete.

9.5 Where the concrete has not fully hardened,all laitance shall be removed by scrubbing
the wet surface with wire or bristle brushes, care being taken to avoid dislodgement of
particles of aggregate. The surface shall be thoroughly wetted and all free water
removed. The s urface shall then be coated with neat cement slurry. On this
surface layer of concrete not exceeding 150mm in thickness shall first be placed and
shall be well rammed against old work, particular attention being paid to corners and
close spots; work thereafter shall proceed in normal way.

10.0 SEPARATION JOINT


10.1 Separation joint shall be obtained by using an approved alkathene sheet stuck on the
surface against which concrete shall be placed. Adequate care shall be taken to cause
no damage to the sheet.

11.0 EXPANSION JOINTS/ISOLATION JOINT

11.1 Expansion/ Isolation joints in structures shall be formed in the positions and to the
shapes shown in the relevant drawings. Joints shall be filled with joint filling material as
stipulated in the drawing/schedule of rates. Isolation joints shall be provided around all
equipment foundations, columns, pedestals, trenches etc. on grade.

12.0 WATER STOPS


PVC water stops as per GAIL Specification No. 6-68-0002 for materials shall be
accurately cut, fitted and integrally joined as per manufacturer's specifications to
provide a continuous, watertight diaphragm at all points.

The water stops shall be located and embedded at expansion/contraction/ construction


joints as indicated in the drawings or directed by the Engineer-in-Charge.

Adequate provision shall be made for the support and protection of water stops
during the progress of the work.Damaged water stops shall be replaced and/or repaired
as directed.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 17 of 42
NEW DELHI
Copyright – All rights reserved
13.0 PROTECTION OF FRESHLY LAID CONCRETE

13.1.1 Newly placed concrete shall be protected, by approved means, from rain, sun and wind.
Concrete placed below the ground level shall be protected from falling earth during and
after placing. Surface shall be kept free from contact with such ground or with water
draining from such ground during placing of concrete for a period of at least 3 days,
unless otherwise directed by the Engineer-in-Charge. The ground water around newly
poured concrete shall be kept to an approved level by pumping or other approved
means of drainage and adequate steps shall be taken to prevent floatation and
flooding. Steps shall be taken to protect immature concrete from damage by debris,
loading, vibration, abrasion, mixing with deleterious materials, that may, in the opinion
of the Engineer-in-Charge, impair the strength and/or durability of the concrete.

14.0 CURING
Concrete shall be cured by keeping it continuously moist wet for the specified period of
ime to ensure complete hydration of cement and its hardening. Curing shall be started
after 8 hours of placement of concrete in normal weather, and in hot weather after 4
hours. The water used for curing shall be of the same quality as that used for making of
concrete.

Curing shall be assured by use of an ample water supply under pressure in pipes, with
all necessary appliances such as hose, sprinklers etc. A layer of sacking, canvas,
hessian, or other approved materia1,which will hold moisture for long periods and
prevent loss of moisture from the concrete,shall be used as covering. Type of covering
which would stain, disfigure or damage the concrete, during and after the curing
period,shall not be used. Only approved covering shall be used for curing. Exposed
surfaces of concrete shall be maintained continuously in a damp or wet condition for at
least the first 7 days after placing of concrete.

The Contractor shall have all equipment and materials required for curing on hand and
ready to use before concrete is placed.

For curing the concrete in pavements, floors, flat roofs or other level surfaces, the
ponding method of curing shall be used. For the first 24 hours after concreting the
concrete shall be cured by use of wet sacking, canvas, hessian etc. The minimum water
depth of 25mm for ponding shall be maintained.The method of containing the ponded
water shall be approved by the Engineer-in-Charge. The ponded areas shall be kept
continuously filled with water, and leaks, if any, shall be promptly repaired. Areas cured
by ponding method shall be cleared of all debris and foreign materials after curing
period is over.

Alternatively, membrane curing may be used in lieu of moist curing with the permission
of the = Engineer-in-Charge. Such compounds shall be applied to all exposed surfaces
of the concrete by spraying or brushing as soon as possible after the concrete has set.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 18 of 42
NEW DELHI
Copyright – All rights reserved
Minimum film thickness of such curing compounds shall be as per the recommendation
of the manufacturer so as to obtain an efficiency of 90% as specified by BS-8110. This
film of curing compound shall be fully removed from the concrete surface after the
curing period specified earlier. Engineer-in-Charge may not
allow curing by curing compounds for those surfaces where use of curing compound
may be detrimental to application of future finishes over the concrete. Impermeable
membranes such as polyethylene sheeting closely covering the concrete surface may
also be used.

14.2 For concretes containing Portland pozzoolana cement or Portland slag cement, the
curing period as given in 14.1 shall be doubled. Curing by ponding shall, however,
commence after the first 24 hours of concreting.

15.0 FIELD TESTS

15.1 Grading Test


Grading test on fine and coarse aggregates shall be carried out as per IS:2386 at
intervals specified by the Engineer-in-Charge.

The mandatory tests and their frequencies shall be done on sand and stone aggregates
as given in Table-4

TABLE - 4
MANDATORY TESTS ON SAND & STONE AGGREGATES

Sr No. MATERIA TEST FIELD / LAB MINIMUM


L TEST QUANTITY FREQUENCY OF TESTING
OF
MATERIAL
/ WORK
FOR
CARRYING
OUT THE
TEST

1. Sand (a) Field 20 m3 Every 20 m3 or part thereof


Bulking or
of more frequently as decided
Sand 20 m3 by
Field the Engineer-in-Charge

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 19 of 42
NEW DELHI
Copyright – All rights reserved
(b) Silt 40 m3 - DO-

Content Field or Lab


as 1)Every 40 m3 of fine
decided by aggregate1
(c) the sand required in RCC works
Particle Engineer-in- only
Size Charge As required 2)Every 80 m3 of fine
Stone distributi by Aggregate/sand required for
aggregat on Engineerin- other
e General Charge items
visual
inspecti
on, 45 m3 For all quantities
a) laboratory
Precenta test
ge where
of soft required by
or the 45 m3
Engineer-in-
deleterio Charge or as For every 45 m3 or part
us specified thereof
as decided by Engineer- in-
materials Charge
Field or lab.
as
required by
Engineer-in-
Charge Initial test and subsequent
b) test
Particle as & when required by
size Laboratory Engineer-in-Charge
distributi
on

Ten
precent
Fine
value

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 20 of 42
NEW DELHI
Copyright – All rights reserved
15.2 Vee-Bee TestISlump Test of Concrete

15.2.1 For structural quality concrete (excluding pavements, flooring etc.) at least one
Slump Test shall be made for every compressive strength test carried out. More
frequent tests shall be made if there is a distinct change in working conditions or if
required by the Engineer-in-Charge.
15.2.2 For structural quality concrete for pavements & floorings, measurement of
workability shall be by determination of compacting factor. Value of compacting factor
of 0.75 to 0.8 shall generally be acceptable.

15.3 Strength Test of Concrete


15.3.1 Samples from fresh concrete shall be taken as per IS: 1 199 and cubes shall be made,
cured and tested at 28 days in accordance with IS:516.

15.3.2 In order to get a relatively quicker idea of the quality of concrete, optional tests
on beams for modulus of rupture at 722 2 hours or at 7 days, or compressive strength
tests at 7 days may be carried out in addition to 28 days compressive strength tests.
For this purpose, the values shall be arrived at based on actual testing. In all cases, the
28 days compressive strength specified in Table-1 shall alone be the criterion for
acceptance or rejection of the concrete.

15.3.3 Procedure

A random sampling procedure shall be adopted to ensure that each concrete batch shall
have a reasonable chance of being tested, that is the sampling should be spread over
the entire period of concreting and cover all mixing units.

15.3.4 Frequency of Sampling

The minimum frequency of sampling of concrete for each grade shall be in accordance
with Table-5

TABLE - 5
FREOUENCY OF CONCRETE SAMPLING

Quantity of concrete in the Number of Samples


work in m3

1-5 1

6-15 2

16-30 3

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 21 of 42
NEW DELHI
Copyright – All rights reserved
31-50 4

51 & above 4 plus one additional sample for each


additional 50m3 or part
thereof.

At least one sample shall be taken from each shift. Where concrete is produced at
continuous production units such as ready mixed concrete plants, frequency of
sampling may be agreed upon mutually by Engineer-in-Charge.

15.3.5 Test Specimen

Three test specimens shall be made from each sample for testing at 28 days. Additional
cubes may be required for various purposes such as to determine the strength of
concrete at 7 days or at the time of striking the formwork or to check the testing error.
Additional samples may also be required for testing samples cured by accelerated
methods as described in IS:9013. The specimen shall be tested as described in IS:516.

15.3.6 Test Results of Sample


The test results of the sample shall be the average of the strength of three specimens.
The individual variation should not be more than + 15 percent of the average. If the
individual variation is more than f 15 percent, the test results of the sample shall be
considered invalid.

15.3.7 Standard Deviation


i) Standard deviation based on test results of samples :

a) The total number of test samples required to constitute an acceptable record for
calculation of standard deviation shall be not less than 30. Attempts shall be
made to obtain the 30 samples, as early as possible, when a mix is used for the
first time.

b) For design of mix in the first instance, the value of standard deviation given in
Table-6 may be assumed.
c) As soon as sufficient results of samples are available, actual calculated standard
deviation shall be used and the mix design revised/ updated.

TABLE - 6
ASSUMED STANDARD DEVIATION

Grade of Concrete Assumed Standard Deviation (N/mrn2)

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 22 of 42
NEW DELHI
Copyright – All rights reserved
M 15 3.5

M 20 4.0

M 25 4.0

M 30 5.0

M 35 5.0

M 40 5.0

M 45 5.0

M50 5.0

15.3.8 Acceptance Criteria

15.3.8.1 Compressive Strength

The concrete shall be deemed to comply with the strength requirement when both the
conditions as given in Table-7 for that particular grade of concrete are simultaneously met.

TABLE - 7
CHARACTERISTIC COMPRESSIVE STRENGTH COMPL

Specified Grade Mean of group of 4 Non- Individual Test Results


Overlapping (N/mm2)
Consecutive Test Results
(N/mm2)

M 15 Greater than or equal to Greater than or equal to


( fck+f0.825 x ) ( fck – 3)
established standard
deviation
(rounded off to nearest
0.5 )
Or fck + 3
whichever is greater

M 20 and above Greater than or equal to Greater than or equal to


STATNDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 23 of 42
NEW DELHI
Copyright – All rights reserved
( fck +0.825 x) (fck –4)
established standard
deviation above (rounded
off to nearest 0.5 )
Or fck + 4 whichever is
greater

15.3.8.2 Flexural Strength

The concrete shall be deemed to comply with flexural strength requirements when both
the following conditions are simultaneously met :

a) The mean strength determined from any group of four consecutive test results
exceeds the specified characteristic strength by at least 0.3 N / d .

b) The strength determined from any test result is not less than the specified
characteristic strength less 0.3 N/mm2.

15.3.8.3 Quantity of Concrete Represented by Strength Test Results

The quantity of concrete represented by a group of four consecutive test results shall
include the batches from which the first and last samples were taken together with all
intervening batches.

For the individual test result requirements given in Table 7 or in item (b) of 15.3.8.2,
only the particular batch from which the sample was taken shall be at risk.

Where the mean rate of sampling is not specified, the maximum quantity of concrete
that four consecutive test results represent shall be limited to 60m3 .

15.3.8.4 If the concrete is deemed not to comply persuant to 15.3.8.3, the structural
adequacy of the parts affected shall be investigated and any consequential action as
needed shall be taken (Refer cl. 16.0 & 17.0).
15.3.8.5 Concrete of each grade shall be assessed separately.

15.3.8.6 Concrete is liable to be rejected if it is porous or honey-combed, its placing has


Been interrupted without providing a proper construction joint, the reinforcement has
been displaced beyond the tolerances specified, or construction tolerances have not
been met. However, the hardened concrete may be accepted after carrying out
suitable remedial measures and tests to the fullest satisfaction of the Engineer-in-
Charge.

16.0 INSPECTION AND TESTING OF STRUCTURES

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 24 of 42
NEW DELHI
Copyright – All rights reserved
16.1 Inspection
To ensure that the construction complies with the design, an inspection procedure shall
be set up by the contractor and duly approved by Engineer-in Charge covering
materials used, receipt of materials, there test results, records, workmanship and
construction etc.

16.2 Immediately after stripping the formwork, all concrete shall be carefully inspected
and any defective work or small defects either removed or made good before concrete
has thoroughly hardened.

16.3 Testing
In case of doubt regarding the grade or soundness of concrete used, either due to poor
workmanship or based on results of cube strength, compressive strength tests of
concrete on the basis of c1.16.4, 16.5, 16.6, 16.7 and/ or load test (see cl. 16.6) shall
be carried out.

16.4 Core Test


16.4.1 The points from which cores are to be taken and the number of cores required shall be
at the discretion of Engineer-in-charge and shall be representative of whole of concrete
concerned. In no case, however, shall fewer than three cores be tested.

16.4.2 Cores shall be prepared and tested as described in IS:516.

16.4.3 Concrete in the member represented by a core test shall be considered


acceptable if the average equivalent cube strength of the cores is equal to at least 85
percent of the cube strength of the grade of concrete specified for the corresponding
age and no individual core has a strength less than 75 percent.
16.4.4 In case the core test results do not satisfy the requirements of cl. 16.4.3 or
where such tests have not been done, load test may be resorted to.

16.5 Load Tests for Flexural Member

16.5.1 Load test shall be carried out as soon as possible after expiry of 28 days from the time
of placing of concrete.

16.5.2 The structure shall be subjected to a load equal to full dead load of the structure
plus 1.25 times the imposed load for a period of 24 hours and then the imposed load
shall be removed. The dead load shall include self weight of the structural member plus
weight of finishes and wall or partitions, if any, as considered in the design.

16.5.3 The deflection due to imposed load only shall be recorded. If within 24 hours of
removal of the imposed load the structure does not recover at least 75 percent of the
deflection under superimposed load, the test may be repeated after a lapse of 72 hours.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 25 of 42
NEW DELHI
Copyright – All rights reserved
If the recovery is less than 80 percent, the structure shall be deemed to be
unacceptable.

16.5.4 If the maximum deflection in mm, shown during 24 hours under load is less than 40
L21D, where L is the effective span in m, and D, the overall depth of the section in rnm,
it is not necessary for the recovery to be measured and the recovery provisions of
16.5.3 shall not apply. 16.5.5 The Engineer-in-Charge shall be the final authority for
interpreting the results of all tests and shall decide upon the acceptance or otherwise.
The decision of the Engineer-in-Charge shall be final and binding on the contractor. In
case the results of the tests are unsatisfactory, the Engineer-in-Charge
may instruct the contractor to demolish and reconstruct the structure or part thereof
without any extra cost to the Owner.

16.6 Members other than Flexural Members


Members other than flexural members like columns etc. shall be referred to the
designer to investigate the structural adequacy. The decision of the designer shall be
final and binding on the contractor.

16.7 Non - destructive Tests


Non-destructive tests using Ultrasonic Pulse Velocity and Rebound Hammer methods
shall be resorted to for checking the soundness of concrete placed and shall be as per
the directions of Engineer-in-Charge. The testing shall be based on IS: 133 1 1, Part-1 .
However, the Rebound Hammer test shall only be used in combination with other tests
(Destructive or Non-Destructive) for checking the concrete quality.

17.0 FINISHING OF CONCRETE

17.1 On striking the formwork, all surface defects such as bulges, ridges and honey-combing
etc. observed shall be brought to the notice of the Engineer-in-Charge. The Engineer-in-
Charge may,at his discretion allow rectification by necessary chipping and packing or
grouting with concrete or cement mortar. However, if honey-combing or sagging are of
such extent as being undesirable, the Engineer-in-Charge may reject the work totally
and his decision shall be binding. No extra payment shall be made for rectifying these
defects, demolishing and reconstructing the structure. However,
quantity of cement actually used for this purpose may be considered for reconciliation
of materials. All burrs and uneven faces shall be rubbed smooth with the help of
carborundum stone.

The surface of non-shuttered faces shall be smoothened with a wooden float to give a
finish similar to that of the rubbed down shuttered faces. Concealed concrete faces shall
be Ieft as from the formwork except that honey-combed surface shall be made good as
specified above. The top faces of slabs not intended to be covered shall be levelled and
floated to a smooth finish to the rises or falls shown on the drawings or as directed.
The floating shall not be executed to the extent of bringing excess fine materials to the

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 26 of 42
NEW DELHI
Copyright – All rights reserved
surface. The top faces of slabs intended to be covered with screed, granolithic or similar
finishes, shall be left with a rough finish.

17.2 Repair and Replacement of Unsatisfactory Concrete

17.2.1 Repair shall be made as soon as possible after the forms are removed and before the
concrete becomes too hard with prior permission from the Engineer-in-Charge, in
writing. Stone pockets, segregation patches and damaged areas shall be chipped out
and the edges undercut slightly to form a key. All loose material shall be washed out
before patching. No excess water shall be left in the cavity, but the concrete shall be
damp. A good bond between the patch and parent concrete shall be obtained by
sprinkling dry cement on the wet surface or by throwing mortar with force on to the
wetted concrete, or by brush in a coat of thick cement grout of about 1 : 1 ( 1 cement:
1 sand) just before applying the patching material. Before this has dried, the remainder
of the patch shall be filled with mortar or concrete, depending on the extent of the
repair.

17.2.2 Cement concrete/mortar used in repair of exposed surfaces shall be made with cement
from the same source as that used in concrete and blended with sufficient amount of
white Portland cement to produce the same colour as in the adjoining concrete. The
proportions of ingredients shall be same as those used in parent concrete. The mortar
shall be as dry as possible and well compacted into the cavity. All filling shall be tightly
bonded to the concrete and shall be sound, free from shrinkage cracks after the filling
has been cured and dried.

17.2.3 For larger repairs to hardened concrete, necessary formwork bearing tightly at the
edges of the cavity shall be provided. Concrete shall be chipped out to a depth of at
least l00 mm and preferably 150mm. Mortar shall be scrubbed into all surfaces with a
wire brush before placing the concrete. Damaged reinforcement shall be adequately
spliced with new steel so as to maintain the original strength. Additional reinforcement,
if required in the patch, shall be provided as per the instructions of Engineer-in-Charge.

17.2.4 In case in the opinion of the Engineer-in-Charge defects in the concrete is excessive or
beyond repair, the contractor shall either redo the structure or take other remedial
measures as instructed by the Engineer-in-Charge. The decision of the Engineer-in-
Charge shall be final and binding to all in this respect.

17.2.5 Approved epoxy formulation for bonding fresh concrete used for repairs with already
hardened concrete shall be used by the Contractor if asked by the Engineer-in-Charge.
Epoxy shall be applied in strict accordance with relevant GAIL Specification and the
instructions of the manufacturer.

17.2.6 All repair works due to non-conformance or non-adherence to specification, if allowed


by the Engineer-in-Charge, shall be carried out free of cost to the owner.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 27 of 42
NEW DELHI
Copyright – All rights reserved
17.3 Curing of Patched Work
Immediately after patching is completed, the patched area shall be covered with an
approved non-staining water saturated material which shall be kept wet and protected
against sun and wind for a period of 12 hours. Thereafter, the patched area shall be
kept continuously wet by a fine spray or sprinkling for not less than 10 days.

18.0 CEMENT WASH


If not otherwise provided with protective coating due to architectural and/ or geo-
technical requirements, all concrete elements (whether cast-in-situ or precast) exposed
to atmosphere shall be provided with three coats of cement based waterproof paint as
per IS5410. Prior to application of the paint, the surface shall be prepared to remove all
foreign particles, loose materials, extra deposited concrete lumps, etc. using
appropriate mechanicall manual means.

19.0 FORM WORK

19.1 General

19.1.1 Forms for concrete shall be of plywood conforming to IS:6461 or steel or as directed by
the Engineer-in-Charge and shall give smooth and even surface after removal thereof.

19.1.2 If it is desired by the Engineer-in-Charge, the Contractor shall prepare, before


commencement of actual work, design and drawings for formwork and get them
approved by the Engineer-in-Charge. For details regarding design, detailing etc.,
reference may be made to IS: 14687.

19.1.3 Form work and its supports shall maintain their correct position and be to correct shape
and profile so that the final concrete structure is within the limits of dimensional
tolerances specified below, unless required otherwise, for functional/ aesthetic reasons.
The decision of the Engineer-in-Charge shall be final and binding in this regard.
(a) Deviation from specified dimensions - 6mm to + 12mm of cross section of columns
and beams.

(b) Deviation from dimensions of footings (see Note below)

(i) Dimensions in plan -12mm to +50mm

(ii) Eccentricity 0.02 times the width of the footing in the direction of deviation but
not more than 50 mm.

(iii) Thickness - +0.05 times the specified thickness.

Note: These tolerances apply to Cast-in-situ concrete dimensions only, not to


positioning of vertical reinforcing steel or dowels.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 28 of 42
NEW DELHI
Copyright – All rights reserved
(c) Deviation in length (major dimension of single unit)
up to 3 m +_ 6 mm

3 m to 4.5 m +_ 9 mm

4.5 m to 6.0 m +_ 12 mm

additional deviation for every subsequent 6m. - +6mm

(d) Deviation in straightness or bow (deviation from specified line) for a single or
continuous member) e.g. beam, column or slab edge.

up to 3 m 6 mm

3 m to 6 m 9 mm

6 m to 12 m - 12 mm

additional for every subsequent 6m. -6mm

(e) Deviation in squareness shall be measured taking the longer of two adjacent
sides as the base line.

The shorter side shall not vary in its distance from a perpendicular so that the
difference between the greatest and shortest dimensions exceeds 6mm. For this
purpose, any error due to lack of straightness shall be ignored. Squareness shall
be checked with respect to the straight lines that are most nearly parallel with
the features being checked. When the nominal angle is other than 90 degree
,the included angle between check lines shall be varied accordingly.

(f) Deviation in twist shall be within a limit such that any corner shall not be
more than the limit given below from the plane containing other three
comers:

upto 600mm wide and upto 6m in length -6mm

over 600mm wide and for any length -12mm

Maximum deviation in flatness from a 1.5m straight edge placed in any position on a
nominally plain surface shall not exceed 6mm.

(h) The tolerance limits for concrete columns/pedestals shall be same as given in relevant
Specification .

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 29 of 42
NEW DELHI
Copyright – All rights reserved
19.2 Form Requirement:

19.2.1 The formwork shall be true, rigid and adequately braced both horizontally as well
as diagonally. The forms shall have smooth and even surface and be sufficiently strong
to carry, without deformation, the dead weight of the green concrete, working load,
wind load and also the side pressure exerted by the green concrete. As far as practical,
clamps shall be used to hold the forms together. Where use of nails is unavoidable
minimum number of nails shall be used. Projected part of nail shall not
be bent or twisted for easy withdrawal.

19.2.2 Where through tie rods are required to be put to hold the formwork and maintain
accurate dimension, they shall always be inserted through a precast concrete block (of
same mix proportion as is to be used for concreting) with a through hole of bigger
diameter. The Precast block shall tightly fit against in inner faces of formwork. The
holes left after the withdrawal of tie rods shall be fully grouted with cement-sand
mortar of same proportion as that used for concrete. However, use of such precast
block shall in no case impair the desired appearance or durability of the structure. No
such tie rods shall be used in any liquid retaining or basement structure.

19.2.3 Tie wires shall be permitted only upon approval of the Engineer-in-Charge and
shall be cut off flush with the face of the concrete or counter sunk, filled and finished in
the manner specified in clause 17.

9.2.4 Form joints shall not permit any leakage. The formwork shall be strong enough to
withstand the effect of vibrations practically without any deflection, bulging, distortion
or loosening of its components.

9.2.5 Forms for beams and slabs (span more than 6.0m) shall have camber of 1 in 500 so as
to offset the deflection and assume correct shape and line after deposition of concrete.
For cantilevers, the camber at free end shall be 11100th of the projected length. Where
architectural considerations and adjunctive work are critical, smaller form cambers shall
be adopted as decided by the Engineer-in-Charge.

19.2.6 All vertical wall forms may be designed and constructed for the following minimum
pressure. The pressures listed in Table-8 are intended as guide only and the Contractor
shall ensure that the formwork is adequately strong and sturdy.

TABLE – 8
MINIMUM DESIGN PRESSURE FOR WALL FORMWORK

Rate of pour in Pressurc in kN/m2


meter/hour

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 30 of 42
NEW DELHI
Copyright – All rights reserved
at 10 Degree (In Celsius) at 24 Degree (in Celsius
0.6 36 29
0.9 40 32
1.2 44 35
1.5 46 37

All horizontal forms shall be designed and constructed to withstand the dead load of the
green concrete, reinforcement, equipment, material, embedment and a minimum live
load of 2.0 kN/m2.

19.3 Inspection of Forms


Temporary openings shall be provided at the base of column and wall forms and other
places necessary to facilitate cleaning and inspection. Before concrete is placed, all
forms shall be carefully inspected to ensure that they are properly placed, sufficiently
rigid and tight, thoroughly cleaned, properly treated and free from foreign material. The
complete form work shall be inspected and approved by the Engineer-in-Charge before
the reinforcement bars are placed in position. When forms appear to be unsatisfactory
in any way, either before or during the placing of concrete, the
work shall be stopped until the defects have been corrected as per the instructions of
the Engineer-in-Charge.

19.4 Cleaning and Treatment of Formwork


The surfaces of forms that would come in contact with concrete shall be well treated
with approved non- staining form release agents such as soft soap, oil, emulsions etc.
Release agents shall be - applied so as to provide a thin uniform coating to the forms
without coating the reinforcement.

19.5 Chamfers and Fillets

All corners and angles shall be formed with 45 degree mouldings to form chamfers or
fillets on the finished concrete. The standard dimensions of chamfers and fillets, unless
otherwise detailed or specified shall be 25x25mm. For heavier work chamfers or fillets
shall be 5Ox50mm. Care shall be exercised to ensure accurate mouldings. The diagonal
face of the moulding shall be planed or surfaced to the same texture as the forms to
which it is attached.

19.6 Reuse of forms


Before reuse, all forms shall be thoroughly scrapped, cleaned, examined and when
necessary, repaired and retreated, before resetting. Formwork shall not be reused, if
declared unfit or un-serviceable by the Engineer-in-Charge.

19.7 Removal of Forms/Stripping Time

In the determination of time for removal of forms, consideration shall be given to the

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 31 of 42
NEW DELHI
Copyright – All rights reserved
location and character of the structures, the weather and other conditions including the
setting and curing of the concrete and material used in the mix.

Forms and their supports shall not be removed without the approval of the Engineer-in-
Charge. Forms shall not be released until the concrete has achieved a strength of at
least twice the stress to which the concrete may be subjected at the time of removal.
The formwork shall be removed without shock and methods of form removal likely to
cause over stressing* or damage to the concrete, shall not be adopted. Supports shall
be removed in such a manner as to permit the concrete to uniformly and gradually take
the stresses due to its own weight.

In normal circumstances when average air temperature exceeds 15 degree Celsius


during the period under consideration after pouring of concrete and where ordinary
Portland cement is used, forms may generally be removed after expiry of following
periods.

(a) Walls, columns and vertical faces of all 16 to 24 hours as may be


structural members decided by the Engineer-in-
Charge.

(b) Slabs (props left under) 3 days.

( c) Beam Soffits (props left under) 7 days

(d) Removal of props under slabs: .

Spanning upto 4.5m. 7 days

Spanning over 4.5m. 14 days.

(e) Removal of props under beams and arches:

Spanning upto 6m 14 days

Spanning over 6m 21 days

(f) Cantilever Construction Formwork shall remain till


structures for counter acting or
bearing down have been erected and
have attained
sufficient strength (minimum 14 days).

Notes:
1. For other cements, the stripping time recommended for ordinary Portland cement shall

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 32 of 42
NEW DELHI
Copyright – All rights reserved
be suitably modified as per the instructions of the Engineer- in-Charge.

2. The number of props left under, their sizes, supporting arrangement, and
disposition shall be such as to be able to safely carry the full dead load of the slab,
beam or arch as the case may be together with any live load likely to occur during
curing or further construction.

3. Where the shape of the element is such that the formwork has re-entrant angles, the
form work shall be removed as soon as possible after the concrete has set, to avoid
shrinkage cracking occurring due to the restraint imposed.

4. For rapid hardening cement, 317 of the above mentioned periods shall be considered
subject to a minimum of 16 hours.

19.8 Staging scaffolding

19.8.1 Staging scaffolding shall be properly planned and designed by the Contractor. Use of
only steel tubes is permitted for staging scaffolding. The Contractor shall get it reviewed
by Engineer-in-Charge before commencement of work. While designing and during
erection of scaffolding staging, the following measures shall be considered:

(a) Sufficient sills or under pinnings in addition to base plates shall be provided particularly
where scaffolding are erected on soft grounds.

(b) Adjustable bases to compensate for uneven ground shall be used.

(c) Proper anchoring of the scaffolding staging at reasonable intervals shall be provided in
each direction with the main structure wherever available.

(d) Horizontal braces shall be provided to prevent the scaffolding staging from rocking.

(e) Diagonal braces shall be provided continuously from bottom to top between two
adjacent rows of uprights.

(f) The scaffolding staging shall be checked at every stage for plumb line.

(g) Wherever the scaffolding staging is found to be out of plumb line it shall be dismantled
and re-erected afresh and effort shall not be made to bring it in line with a physical
force.

(h) All nuts and bolts shall be properly tightened and care shall be taken that all
clamps/couplings are firmly tightened to avoid slippage

(i) Erection work of a scaffolding staging under no circumstances shall be left totally to

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 33 of 42
NEW DELHI
Copyright – All rights reserved
semi-skilled or skilled workmen and shall be carried out under the supervision of a
technically qualified civil engineer of the Contractor.

19.8.2 For smaller works or works in remote areas, wooden ballies may be permitted for
scaffolding staging by the Engineer-in-Charge at his sole discretion. The contractor
must ensure the safety and suitability of such works as described under clause 19.8.1
above.

20.0 EXPOSED/ARCHITECTURAL CONCRETE WORK

20.1 Form Work

Other things remaining same as per clause 19.0, formwork shall be of high quality. Care
shall be taken to arrange the forms so that the joints between forms correspond with
the pattern indicated in the drawings. The forms shall be butting with each other in
straight lines, the corners of the boards being truly at right angles. The joints between
the forms shall cross in the two directions at right angles. The size of forms shall be so
selected as to exactly match with the pattern of forms impression on the concrete face
indicated in the drawings. Maximum care shall be taken to make the form work
watertight. Burnt oil shall not be used for treatment of forms. The Contractor shall be
permitted reuse of forms brought new on the work for exposed concrete work as
specified below. Such reuses shall be permitted only if forms are properly cared for,
stored, repaired and treated after each use.
a) Plywood Forms 6 Reuses (max.)

b) Steel Forms 10 Reuses (max.)

The Engineer-in-Charge may, at his absolute discretion, order removal of any forms
considered unfit for use in the work irrespective of the number of uses specified above.

20.2 Finishing
Repairing to exposed concrete work shall be avoided. Rendering and plastering shall not
be done. Minor repairing if unavoidable shall be done as specified in clause 17.0 with
the written permission of the Engineer-in-Charge .

21.0 REINFORCEMENT

21.1 The Contractor shall develop the bar bending schedule for all RCC structures1 structural
parts at no extra cost to the Owner and shall get it reviewed by the Engineer-in-charge.
Reinforcement shall be cut and bent to shape as per dimensions shown in the bar
bending schedule1 drawings. If protective fusion bonded epoxy coating is required to
be applied on reinforcement bars, the same shall be done as per BS:7295. All repairs to
applied protective coating required due to mishandling
and/ or bending of reinforcement bars shall also be done as per relevant clauses of

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 34 of 42
NEW DELHI
Copyright – All rights reserved
BS:7295.

2 1.2 Straightening, Cutting and Bending


Procedure for cutting and bending shall be as given in IS:2502. In case bars are
supplied in coils, they shall be smoothly straightened without any kinks.

Cold twisted deformed bars shall be bent cold. Bars larger than 25mm in size (except
cold twisted deformed bars) may be bent hot at cherry red heat to a temperature not
exceeding 850' Celsius as per the instructions of the Engineer-in-Charge. The bars shall
be allowed to cool gradually without quenching. Bars shall be bent in a slow and regular
movement to avoid fractures.

Bars which develop cracks or splits after bending shall be rejected. A second bending of
reinforcement bars shall be avoided but when reinforcement bars are bent aside at
construction joints and afterwards bent back into their original position, care should be
taken to ensure that at no time is radius of the bend Iess than 4 times bar diameter for
plain mild steel or 6 times bar diameter for high strength deformed bars. Care shall also
be taken when bending back bars to ensure that concrete around the bars is not
damaged. All bars shall be properly tagged for easy identification.

21 .3 Placing and Fixing

All reinforcement shall be cleaned to ensure freedom from loose mill scale, loose rust,
oil, form releasing agents, grease or any other harmful material before placing them in
position. Reinforcement shall not be surrounded by concrete unless it is free from all
such materials. Rough handling, and dropping of reinforcement from a height shall be
avoided

All reinforcement shall be fixed in the correct position and shall be properly supported
to ensure that displacement will not occur when the concrete is placed and compacted.
The uncoated reinforcement bars shall be tied at every intersections by two strands of
16 SWG black soft annealed binding wire. The Epoxy coated reinforcement bars shall be
tied with 2 strands of PVC coated GI 18 SWG wire at every intersection. Crossing bars
shall not be tack welded for assembly of reinforcement. The reinforcement bars shall be
kept in position by using the following methods:

a) In case of beam and slab construction, precast cover blocks (having the same cement
sand contents as the concrete which shall be placed) of size 40 x 40 mm and thickness
equal to the specified covers shall be placed firmly in between the bars and forms so as
to secure and maintain the specified covers over the reinforcement.
When reinforcement bars are placed in two or more layers in beams, the vertical
distance between the horizontal bars shall be maintained by introducing spacer bars at
1 to 1.2m centre to centre.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 35 of 42
NEW DELHI
Copyright – All rights reserved
b) In case of thick rafts & pile caps having two or multilayers of reinforcement, the vertical
distance between the horizontal bars shall be maintained by introducing suitable chairs,
spacers, etc.

c) In case of columns and walls, the vertical bars shall be kept in position by means of
timber templates with slots accurately cut in them. The templates shall be removed
after the concreting has been done below it.
d) Exposed portions of reinforcement bars shall not be subjected to impact or rough
handling and workmen will not be permitted to climb on extending bars until the
concrete has attained sufficient strength so that no movement of the bars in the
concrete is possible.
21.4 Special requirements for Handling, Stacking, Placing of Epoxy coated
Reinforcing bars.

Epoxy coated reinforcing bars shall be carefully handled and it shall be ensured that
these do not rub on any hard surface or against another epoxy coated/uncoated
reinforcing bar whether during conveying/transportation, stacking or placing.

During transportation and while stacking the epoxy coated reinforcing bars shall be
placed on wooden planks not spaced farther than 600mm. When placed in stacks the
epoxy coated reinforcing bars shall be neatly tied in bundles using PVC binding
material.

The cut ends of bars shall be touched up with special touch up material of specifications
as provided by the coating agency. After cutting of the bar the application of touch up
material shall be completed within four hours.

While bending the bars the pins of work bench(s) shall be provided with a PVC or
plastic sleeve. Each bending operation on epoxy coated reinforcing bar shall be
completed in time not less than 90 seconds.
Epoxy coated reinforcing steel bar shall not be directly exposed to sun rays or rain, and
shall be protected with opaque polyethylene sheets or similar means as approved by
the Engineer in Charge.

While doing concreting the workmen or machinery shall not rest or move on the epoxy
coated reinforcing bars. Wooden planks shall suitably be placed to create proper gang-
way.

21.5 Splicing/ Overlapping

Only bars of full length shall be used as shown in the drawings. But where this cannot
be done, overlapping of bars shall be done as directed by the Engineer-in- Charge.
Where practicable, the overlapping bars shall not touch each other, but these shall be
kept apart by 25mm or 1.25 times the maximum size of the coarse aggregate

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 36 of 42
NEW DELHI
Copyright – All rights reserved
whichever is greater. But where this is not possible, the overlapping bars shall be tied
with two strands of 16 SWG black soft annealed binding wire for uncoated bars and
with PVC coated GI 18 SWG wire for Epoxy coated bars. The overlaps shall
be staggered for different bars and located at points along the span where neither
shear nor bending moment is maximum.

21.6 Welded Joints


Welding of reinforcing bars shall not be permitted without the written permission of the
Engineer-in-Charge. If Fusion Bonded Epoxy coated bars are used, welding of
reinforcing bars shall generally not be permitted. However, if permitted, the joint shall
be coated with epoxy as per BS:7295. Where welding of uncoated reinforcing bars is
permitted, it shall be in accordance with the recommendations of IS:2751 and IS:9417.
Welded joints shall be located at suitable staggered positions. Tests shall be made as
directed by the Engineer-in-Charge to prove that the joints are of the full strength of
the bars. Maximum one welded joint shall be allowed per bar.

21.7 Mechanical Connections


The mechanical splices in reinforcement by means of couplers, clamps etc. shall be
used (as per manufacturer's specifications) with the written approval of the Engineer-in-
Charge. However, tests shall be made as directed by Engineer-in-Charge to prove that
such connections are of the full strength of the bars on trial joints. Mechanical
connections for Fusion Bonded Epoxy coated bars shall not be used.

21.8 Tolerances on Placing of Reinforcement

Unless otherwise directed by the Engineer-in-Charge, reinforcement shall be placed


within the following tolerances:
a) For effective depth 200mm or less - + 10mm
b) For effective depth more than 200mm - + 15mm

21.9 Substitution

When indicated diameter of reinforcement bar is not available, the Contractor shall use
other diameter of reinforcement bars on written approval of the Engineer-in-Charge.

21.10 Tolerance to Cover


The actual concrete cover shall not deviate from the required nominal cover by - 0 to +
10 mm measured over the steel reinforcement including links.

22.0 PRECAST CONCRETE

22.1 Specifications contained in clauses above regarding concrete, formwork and


reinforcement shall apply in addition to the clauses given as under. The Contractor shall
get the precasting bed approved by the Engineer-in-Charge.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 37 of 42
NEW DELHI
Copyright – All rights reserved
22.2 Necessary lifting hooks of suitable (but not less than 12mm dia) diameter M.S. rounds
shall be provided for handling, as indicated in drawings or as directed by the Engineer-
in-Charge.

22.3 Unless otherwise specified, the exposed surfaces of precast members shall be integrally
finished smooth. For precast slabs or planks,the top surface shall be finished with 1:3 (
1 cement : 3 sand) cement mortar. Surface used as walkways shall be given a non-skid
finish.

22.4 The precast concrete units shall be marked clearly on top surface with the letter "T" for
identification of surfaces at the time of erection and shall be stored properly until
required for erection. The precast units shall be handled and erected by methods
approved by the Engineer-in-Charge to protect them from damage.

22.5 Precast concrete elements shall not be removed from the casting bed until the concrete
has developed its characteristic compressive strength based on cube test results.

22.6 The units shall be suitably handled, transported, stored and placed taking all necessary
safety precautions to avoid development of undue stresses caused by vibrations, impact
or lateral forces. During shipment and while in storage, the units shall be placed on
suitable blocks to provide clearance from bed/ground.

22.7 The Contractor shall take all necessary precautions for safe handling during the course
of erection. The Contractor shall replace at his own expense all such units which are
damaged during the course of erection. Cement used for a damaged/rejected precast
elements shall not be taken into account for material reconciliation.

22.8 The inspection for precast concrete units during casting shall be same as applicable to
normal concrete works. However, additional inspection checks shall be made during
and after erection of units to ensure its suitability for the required service as a
structural memeber. These checks shall include inspection to detect chipping, cracks,
warpages in the precast units etc due to improper handling and storage, improper
jointing (if required) of the precast unit with the structure and improper finishing .

22.9 Fabricated precast concrete units containing defects originating due to use of improper
materials or workmanship, excessive repair and not conforming to design drawings shall
be rejected. Such rejected units shall not be taken into account for material
reconciliation or payment.

23.0 CONTINUOUS CONCRETING

23.1 Where called out on the drawings, continuous concreting shall be done in a single

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 38 of 42
NEW DELHI
Copyright – All rights reserved
operation as per the requirements of IS:456 and IS:2974. It shall be ensured that
clause 8.3 of these specifications is not violated in case of continuous concreting.
Sufficient "Windows" shall be left in the formwork for pouring & compaction of concrete
and inspection. These windows shall be fixed tight once the level of concrete reaches
their levels.

24.0 PAYMENT
24.1 Plain and Reinforced Concrete
24.1.1 Payment for plain and reinforced cement concrete (cast- in-situ) shall be made on
cubic metre basis of the volume of the actual finished work done or as per approved
construction drawings, whichever is less and shall be inclusive of providing pockets,
openings, recesses of all sizes, chamfers, fillets, grooves, separation/ expansion/
isolation/ construction/ movement joints, cement wash, curing by normal moist curing
or using curing compound etc. as directed by Engineer-in-Charge etc.The rates shall be
deemed to include complete cost of getting the respective mix designs approved,
making and testing concrete cubes and carrying out other tests including tests of
various ingredients, as per specifications and as directed by Engineer-in-Charge.
Payment shall, however, be separately made for tests on concrete cubes done by
accelerated methods of curing as defined in IS:9013.

24.1.2 No separate payment shall be made for any additive1 admixture used by the
contractor for accelerating or retarding the strength of concrete or for achieving
specified workability/water tightness. The rate quoted shall be deemed to be inclusive
of all costs related to any such additive/admixture.

24.1.3 The rate shall however be exclusive of reinforcement, metal inserts, pipe sleeves,
formwork, water stops and any filler material in expansion/isolation joints.

24.1.4 Where the strength of concrete mix (nominal or design) as indicated by tests,
lies in between the strengths of any two grades given in Table-1 and it is accepted by
the Owner/Engineer-in-Charge, such concrete shall be classified as a grade belonging to
the lower of the two grades between which it lies. In case the cube strength shows
higher results than those specified for the particular grade of the concrete, it shall not
be placed in the higher grade nor shall the Contractor be entitled for any extra
payment on such account. The concrete giving lower strength than specified may be
accepted at reduced rates after satisfying the safety of the structure by checking it with
tests as specified or rejected entirely at the discretion of the Engineer-in- Charge. The
rejected concrete shall be dismantled at no extra cost to the owner and no payment or
extension of time shall be granted for the concrete so rejected and the formwork and
reinforcement used for the same. Cost of any material supplied by the Owner free of
cost shall be recovered from the Contractor at double the prevailing market rate. In
case the concrete of lower strength can be improved by carrying out some
strengthening measures entirely at the discretion of the Engineer-in-Charge, then the
said measures including all related tests shall be carried out by Contractor at his own

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 39 of 42
NEW DELHI
Copyright – All rights reserved
cost. If the Contractor is able to make up the strength to the required grade by such
improvement measures to the entire satisfaction of Engineer-in-Charge, payment shall
be made for the grade achieved. However, if the strength of concrete is not made up to
the strength of required grade, payment shall be made only for the lower strength if
such concrete is accepted by the Engineer-in-Charge.

24.1.5 Deductions for openings, pockets etc. shall be as specified in relevant Indian
Standard Codes.

24.1.6 Payment under continuous concreting item in the schedule of rates shall be
made only where the total quantity of concrete between two consecutive construction
joints specific all^ called-out on the drawings exceeds 250 cubic meters. For any
foundation/ structure involving concrete quantity upto 250 cubic meters between two
consecutive construction joints shown on drawings, the concrete shall not be measured
or paid for under this category (i.e. continuous concreting), although the same is
required to be constructed in single pour. The rate quoted against this item shall be
inclusive of all extra costs incurred by the Contractor for arranging continuous pouring
of concrete and others as specified complete.

24.2 Form Work

Unless otherwise specified, payment for form work shall be on square meter basis of
the actual area _ in contact with the concrete cast. The rates shall be inclusive of
keeping the formwork for the full period as specified in the above clauses and removing
the same after the period is over. No extra payment shall be made for providing
scaffolding/staging/access/stairways/ladders etc.

The rates shall be inclusive of any provision to be made or kept in the formwork for
providing dowels, inserts etc.

Superior quality formwork for exposed/architectural concrete work shall be measured


and paid separately under the relevant item in the schedule of rates.

24.3 Reinforcement

24.3.1 Payment for plain round mild steel reinforcement bars and high strength deformed
steel bars shall be on the basis of weight of bare steel irrespective of any coating
applied in metric tons. The weight of the bar shall be derived from the sizes and
corresponding unit weights given in handbook of Bureau of Indian Standards. Standard
hook lengths, chairs, spacer bars and authorised laps only shall be included in the
weight calculated. Binding wire shall not be weighed nor otherwise measured.
Measurements for weight shall not include cutting allowance etc.
24.3.2 Rate quoted for uncoated reinforcement shall include cost of supplying,
decoiling, straightening, cleaning, cutting, bending, placing, binding, welding, if

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 40 of 42
NEW DELHI
Copyright – All rights reserved
required, and providing necessary cover blocks of concrete.

24.3.3 Rate quoted for Fusion Bonded Epoxy Coated bars shall also include, apart from
those mentioned in C1. 24.3.2, cost of coating of the bars, all necessary tools and
tackles and any repairs required due to damage to coating as per BS:7295.

24.3.4 Payment for mechanical threaded couplers shall be made on number basis
(each). The rate shall include supply of complete assembly, fixing, testing etc. all
complete.

24.4 Water StopsIWater Bars & Expansion/Isolation Joints

24.4.1 Payment for PVC water bars shall be made on running metre (RM) basis of the
water stops provided in position. Rate shall include supplying cutting, fixing, jointing by
vulcanising or any other approved method, wastage, etc. complete.

24.4.2 Payment for filler materials in Expansion/Isolation joints shall be made on


running metre basis of the joint provided. For boards provided at expansion/isolation
joints, the measurement shall be made on square metre basis. Rate shall be inclusive of
supply, cutting, fixing, jointing, wastage etc.complete.

24.5 Pre-cast Concrete

24.5.1 Payment for precast concrete members shall be made on cubic metre basis of
the volume of the finished member. The rate quoted shall include cost of formwork,
preparation of casting yard, finishing as specified, curing, handling, fixing in position,
breaking masonry and/or concrete surfaces and making good the same etc.
Reinforcement shall be paid separately under relevant items. Lifting hooks shall be paid
on the same basis as reinforcement. Metal inserts shall be paid as per relevant clauses
of Specification No. 6-68-0008 (Miscellaneous Steel Works).

24.5.2 The quoted rate shall be inclusive of providing pockets, openings, recesses of all
sizes, chamfers, fillets grooves, holes, cement wash, curing (hot, cold or by using curing
compounds). The rate shall be deemed to include complete cost of taking and testing
concrete cubes and carrying out other tests including tests of various ingredients as per
specification and as directed by the Engineer-in-Charge.

24.5.3 The rate shall however be exclusive of reinforcement, metal inserts, pipe sleeves.
Where the strength of concrete mix (nominal or design) as indicated by tests, lies in
between the strengths of any two grades given in clause 3.0 and it is accepted by the
Owner/Engineer-in-Charge, such concrete shall be classified as a grade belonging to the
lower of the two grades between which it lies. In case the cube strength shows higher
results than those specified for the particular grade of the concrete, it shall not be
placed in the higher grade nor shall the Contractor be entitled for any extra payment on
such account. The concrete giving lower strength than specified may be accepted at
STATNDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 41 of 42
NEW DELHI
Copyright – All rights reserved
reduced rates after satisfying the safety of the structure by checking it with tests as
specified or rejected entirely at the discretion of the Engineer-in- Charge. The rejected
concrete shall be dismantled at no extra cost to the owner and no payment or
extension of time shall be granted for the concrete so rejected and the formwork and
reinforcement used for the same. In case the concrete of lower strength can be
improved by carrying out some strengthening measures entirely at the
discretion of the Engineer-in-Charge, then the said measures shall be carried out by
Contractor at his own cost. If the Contractor is able to make up the strength to the
required grade by such improvement measures to the entire satisfaction of Engineer-in-
Charge, payment shall be made for the grade achieved. However, if the strength of
concrete is not made up to the strength of required grade, payment shall be made only
for the lower strength if accepted by the Engineer-in-Charge.

24.6 Cement Wash

24.6.1 No payment shall be made for cement wash separately and is deemed to be
covered in cl. 24.1.1 & 24.5.2.

24.7 Continuous Concreting

Payment shall be made as per clause 24.1 of this specification. The rate shall be
deemed to be inclusive of all extra cost related to labour, shuttering, staging and
making all other arrangements for such continuous casting e.g. provisions for adequate
movement and storage spaces, special gangways, scaffolding, additional construction
equipments, adequate lighting and supervision while the work continues round the
clock etc. The rate shall also be inclusive of all costs related to concreting in any
thickness, shape and position and at any height or depth so as to avoid any cold joint
between specified construction joints.

STATNDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD PLAIN & RCC WORK
S-11-02-004 Page 42 of 42
NEW DELHI
Copyright – All rights reserved
TECHNICAL SPECIFICATION
CIVIL AND STRUCTURAL WORKS

REINFORCED CEMENT CONCRETE


FOR LIQUID RETAINING
STRUCTURES

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 1 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
CONTENTS

1.0 SCOPE

2.0 REFERENCES

3.0 MATERIALS

4.0 GENERAL REQUIREMENTS

5.0 CONCRETE

6.0 RENDERING

7.0 SLIDING LAYER

8.0 FORM WORK

9.0 CURING

10.0 FINISHES

11.0 HYDRAULIC TESTING

12.0 PAYMENT

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 2 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
SCOPE
1.1 Concrete structures meant for liquid retaining shall cover under/overground
Reservoirs/tanks, sumps, channels, launders, swimming pools, etc. which are required
to retain any liquid internally. However for basements, tunnels, ducts etc . which are in
direct contact with the sub-soil water from outside, shall also be applicable, in case
referred in drawings.

2.0 REFERENCES

2.1 BIS Codes

IS:3370, 6494, 121 18, 1838

2.2 GAIL specifications

S-11-02-002 : Materials
S-11-02-004 : Plain and Reinforced Cement Concrete

3.0 MATERIALS

3.1 Materials for concrete viz. cement, sand, aggregate, water etc., admixtures and water
stops shall be as described in relevant specification.

4.0 GENERAL REQUIREMENTS

4.1 The concrete structure by itself shall be leak proof to the extent as acceptable (refer to
cl. 1 1.0). Damp patches, if any at the initial stage, shall not be acceptable if the same
do not disappear after three months of putting the structure in service. The basic
requirement is to make the concrete sound, dense and impervious. The Contractor shall
take all necessary precautions in selecting the materials, mix design and method of
construction so as to achieve this objective. If any additional liquid-proof material is
specified and/or shown on drawings, the same shall be considered as a second-line of
defence and shall not entail the contractor to any relaxation from the conditions for the
structure being leak-proof by itself.

4.2 This specification defines the materials, constructional and performance requirements
for liquid retaining concrete structures. Any special requirements as shown or noted in
the drawings shall govern over the provisions of this specification.

4.3 The work shall be done in accordance with this specification together with IS:3370 &
IS:6494. In case of conflict between the clauses mentioned in this specification and
those in the Indian Standards, this specification shall govern.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 3 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
4.4 After construction, the structure shall be tested for watertightness11eakproofness as
detailed hereunder.

5.0 CONCRETE

5.1 GAIL specification no. 6-68-0004 shall be applicable together with the following clauses
:

5.1.1 Special care shall be taken to get the most suitable grading of aggregates so as to
produce the densest possible concrete. The maximum size of coarse aggregate shall be
limited to 20 rnm, unless shown on the drawing. Water-cement ratio shall be strictly
controlled (by making due allowance for the surface water carried by the aggregates),
consistent with the requirement of workability to produce an impervious concrete.

5.1.2 Concrete shall have a minimum cement content of 350 kg/m3. Maximum water cement
ratio permissible shall be 0.45. In order to achieve required workability and slump,
cement and water content may be suitably adjusted, keeping the water cement ratio
constant.

5.1.3 The joints of shuttering board shall be made tight to produce a face free from pores.

5.1.4 The concrete shall be so placed and vibrated that a well compacted dense concrete free
from honeycombing is produced.

5.1.5 Admixtures

Admixtures in concrete shall be used only with the prior approval of the Engineer-in-
Charge. Any admixture used for obtaining proper workability or leak-proofness of
concrete or repair/rendering works of concrete due to non-conformance to the GAIL
specifications, shall not be measured and paid for. All costs relating to such usage shall
be borne by the Contractor.

5.2 Construction, Contraction & Expansion Joints

5.2.1 All vertical and horizontal joints in liquid retaining structures shall be located and
executed as shown in the drawings. For construction joints not shown in the drawing,
specific approval of the Engineer-in-Charge shall be obtained. Every endeavour shall be
made to avoid vertical construction joints. The number of construction joints shall be
kept to the minimum. Where horizontal or vertical joints are required to be left after the
day's work, the same shall be done as per directions of the Engineer-in-Charge. The
face of the old concrete shall be well hacked to expose the aggregate, care being taken
to avoid damaging the aggregate.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 4 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
While the remainder of the concrete should be kept continuously wet, curing of the
joint surface may be suspended a few hours before concreting is to be resumed so as
to permit no more than superficial drying of the joint surface. Just before concreting is
resumed, the roughened joint surface shall be thoroughly cleaned and freed from loose
pieces of gravel, stone chips, wooden chips, nails, laitance or any other foreign
material, preferably, without re-wetting, and then treated with a thin layer of cement
grout, worked well into the surface, or treated with cement-sand mortar in which
water-cement and sand-cement ratios do not exceed those in the new concrete.

5.2.2 Horizontal joints in vertical walls of the structure shall preferably form a closed loop.

5.2.3 Water stops installation shall be done by embedding one half of the water stop
along the proposed joints on each side of the joint by suitable jigs/supporting
arrangement between the adjacent sections of the concrete as per the manufacturer's
specifications and directions of the Engineer-in-Charge. Water stops shall be positioned
accurately and supported against any displacement during concreting. All precautions
shall be taken to avoid folding or twisting of water stops during pouring and compacting
concrete. To achieve the continuity of the water stop all along the joint, at crossings
and at change of alignments, the water stops shall be joined/ vulcanised as per
manufacturer's specifications and directions of the Engineer-in-Charge. Jigs
manufactured out of reinforcing bars may be used for fixing the water stop. The jigs
shall be measured and paid under reinforcement item.

5.2.4 Expansion joints shall be filled up with non-absorbent compressible sheet/bitumen


impregnated fibre board (as per IS:1838) except the top 12rnm depth on the water
faces(or as shown on the drawings) which shall be filled with two part liquid
polysulphide sealant (as per IS: 12 1 18).In case of contraction and/or construction
joints, such polysulphide sealant shall be used for 12rnrn depth on the water faces (or
as shown on the drawings) after forming suitable grooves in concrete.

5.3 Items Embedded in Concrete

5.3.1 All sleeves, inserts, anchors and embedded items required for the work shall be
available at site prior to start of concreting. These shall be accurately placed and
embedded as described in GAIL specification no. 6-68-004. In case any protective
coating for such elements is shown, Contractor shall coat the same prior to
embedment, which shall be paid separately.

5.3.2 Every precaution shall be taken to keep all embedments and water stops in position as
shown on drawings during pouring and compacting concrete. Work in such areas shall
be carried out under strict supervision.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 5 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
6.0 RENDERING

6.1 Rendering by cement-sand mortar of same proportion as in original concrete shall be


used with the object of covering weak patches in the construction, as per the direction
of the Engineer-in-Charge. The rendering shall be applied to the concrete only after the
inspection by the Engineer-in-Charge and if approved by him. The concrete surface
shall be well wetted and if necessary, hacked prior to the application of mortar. The
mortar shall be steel trowelled and finished with a wooden float.

7.0 SLIDING LAYER

7.1 Wherever shown on drawings, a sliding layer shall be provided between the lean
concrete and the bottom raft/slab of the underground liquid retaining structure. This
layer shall consist of bitumenized kraft paper or alkathene sheet as shown on the
drawings or any other suitable material as directed by the Engineer-in-Charge. The top
surface of lean concrete shall be finished smooth with a wooden trowel to receive the
sliding layer. Joints in the sliding layers shall be lapped as shown on drawings. All care
shall be taken to keep the sliding layer in position while progressing with further work
above.

8.0 FORM WORK

8.1 GAIL specification no. 6-68-0004 for Plain & Reinforced Cement Concrete shall be
applicable together with the following:

8.2 Detailed dimensioned drawing showing the arrangement of form work including its
design if so required by the Engineer-in-Charge shall be furnished to the Engineer-in-
Charge before the form work is erected. The work shall be as per the directions and
approval of the Engineer-in-Charge. No concrete element of the liquid retaining
structure shall be loaded with any support for further form work unless it has aged for
minimum 21 days. After that if any form work rests on such element, adequate external
support shall be provided so that any unequal loading on the element does not cause
any local deformation.

9.0 CURING

Concrete shall be cured in accordance with the GAIL specification no. 6-68-0004 for
Plain & Reinforced Cement Concrete.

10.0 FINISHES

10.1 All the form work shall be so done that no plastering or other external finish is required.
All burrs shall be rubbed smooth with carborandum stone and the finished work shall
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 6 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
present a uniform shade and finish. All the exposed surfaces shall be provided with a
coat of cement wash free of cost if the rendered surfaces are not of acceptable
standard as per the sole discretion of the Engineer-in-charge. Quantity of cement
actually used for this purpose may be considered for reconciliation of materials.

11.0 HYDRAULIC TESTING

11.1 Liquid retaining structures shall be tested strictly in accordance with IS:3370 for water
tightness in addition to the structural tests as mentioned in GAIL specification no. 6-68-
0004. The total maximum drop in water surface level shall not exceed 6mm in 24 hours
in case of covered reservoirs and 12mm in 24 hours in case of open reservoirs.

11.2 If the test proves that the structure is defective, the Contractor shall rectify/repair the
same at his own cost as per the approved scheme as agreed to by the Engineer-in-
Charge. The required structure shall again be tested as per 11.1 above. If the structure
is still not found to satisfy the acceptance criteria, the same shall be dismantled and
rebuilt.

11.3 All testing after construction and remedial treatments shall conform to the provision of
IS : 6494.

11.4 Backfilling around underground structures shall be allowed only after the test results
are found satisfactory by the Engineer-in-Charge.

12.0 PAYMENT

This clause shall apply to Item Rate tender only.

12.1 Payment shall be made on cubic metre (m3) basis of the volume of the actual finished
concrete work done or as per approved construction drawings, whichever is less. The
rate shall be inclusive of all labour, material, curing, cost of leaving pockets, blockouts
for pipes/electric conduits, recesses of all sizes, embedding fixtures, vibrating,
rendering, hacking and washing old concrete faces, applying mortar/grout on them, etc
. but exclusive of reinforcement, formwork, embedded fixtures, water stops and sealing
compound which shall be paid under separate items. In case the Contractor proposes to
use any admixture in concrete for making it water Tight/leakproof, no separate
payment for such admixtures shall be made and the rate quoted for concrete under
liquid retaining structures shall be inclusive of such admixtures. However, when such
admixtures are used under GAIL specific requirements mentioned in the drawings/GAIL
specifications, these shall be separately measured and paid for, under respective item,
provided in the Schedule of Rates.

12.2 No separate payment shall be made for testing and report making which is deemed to
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 7 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
be included in the quoted concrete rate, including cost of hydraulic tests and structural
tests, all appliances and rectifications, if any.

12.2.1 If the test proves that the structure is defective, the Contractor shall develop and
execute with the approval of the Engineer-in-Charge, suitable methods for making the
structure, water tight/leakproof at his own cost. Even after this if the test fails, the
Contractor shall have to dismantle and rebuild the structure within the specified time
schedule, at his own cost.

12.2.2 Cost of initial and subsequent testing, inclusive of cost of water, shall be borne by the
Contractor. The Contractor shall make his own arrangement for filling as well as
emptying the reservoir after the completion of the test and no payment shall be made
on this account.

12.3 Payment for sliding layer shall be based on the actual surface area in square metres
(m2). The Contractor shall include in his rate all allied works viz. cleaning, preparing of
surfaces, laying etc. all materials complete.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR REINFORCED
Page 8 of 8
NEW DELHI CEMENT CONCRETE S-11-02-005
FOR LIQUID RETAINING
STRUCTURES
Copyright – All rights reserved
TECHNICAL SPECIFICATION
CIVIL & STRUCTURAL WORKS

STRUCTURAL STEEL WORKS

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 1 of 28
NEW DELHI STEEL

Copyright – All rights reserved


CONTENTS

1.0 SCOPE

2.0 REFERENCES

3.0 MATERIALS

4.0 FABRICATION DRAWINGS

5.0 FABRICATION

6.0 MARKING FOR IDENTIFICATION

7.0 SHOP ERECTION

8.0 INSPECTION & TESTING OF STRUCTURES

9.0 SHOP PAINTING

10.0 PACKING

11.0 TRANSPORTATION

12.0 SITE (FIELD) ERECTION

13.0 SAFETY & SECURITY DURING ERECTION

14.0 FIELD CONNECTIONS

15.0 GROUTING

16.0 SCHEME AND SEQUENCE OF ERECTION

17.0 PAYMENT

18.0 PAINTING AFTER ERECTION

ANNEXURE -'A'

ANNEXURE -'B'

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 2 of 28
NEW DELHI STEEL

Copyright – All rights reserved


1.0 SCOPE

This specification covers the requirements for material, storage, preparation of


fabrication drawings, fabrication, assembly, tests/examinations, transportation, erection
and painting of all types of bolted and/or welded structural steel works for general
construction work. Fabrication of structures shall also include fabricating:

(a) Built up sections/plate girders made out of rolled section and/or plates.

(b) Compound sections made out of rolled sections.

2.0 REFERENCE

2.1 BIS Codes

IS: 800, 816, 819, 822, 919, 1024, 1261, 1323, 1477, 1852, 2074, 7205, 7215, 7307,
73 10, 73 18, 9595 and other relevant BIS Codes.

SP: 6(1)

2.2 GAIL Specifications

S-11-02-002- Materials
S-04-02-014- Shop & Field Painting

2.3 In case of conflict between the clauses mentioned in this specification and those in the
Indian Standards, this specification shall govern. Any special provision as shown or
noted on the design drawings shall govern over the provisions of this specification.

3.0 MATERIALS

3.1 General

All materials shall conform to their respective specifications given in GAIL Specification
no. 6-68-0002. The use of equivalent or alternative materials shall be permitted only in
very special cases and for all such cases prior written approval of the Engineer-in-
Charge shall be obtained.

3.2 Receipt & Storing of Materials

3.2.1 Each section shall be marked for identification and each lot shall be accompanied by
manufacturer's quality certificate, chemical analysis and mechanical characteristics.

3.2.2 All sections shall be checked, sorted out and arranged by grade and quality in the store.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 3 of 28
NEW DELHI STEEL

Copyright – All rights reserved


Any instruction given by the Engineer-in-Charge in this respect shall be strictly followed.

3.2.3 All material shall be free from surface defects such as pitting, cracks, laminations, twists
etc. Defective material shall not be used and all such rejected material shall be
immediately removed from the store/site. The decision of the Engineer-in-Charge in this
regard shall be final and binding.

3.2.4 Welding wires and electrodes (packed in their original cartons) shall be stored
separately by quality and lots inside a dry and enclosed room in compliance with
IS:9595 and as per the instructions given by the Engineer-in-Charge. Electrodes shall be
kept perfectly dry to ensure satisfactory operation and weld metal soundness.

3.2.5 Each lot of electrodes, bolts, nuts etc. shall be accompanied by manufacturer's
Quality/test certificates.

3.2.6 All bolts (including nuts & washers) shall be checked, sorted out and arranged
diameter-wise by grade and quality in the store.

3.3 Material Tests

3.3.1 The Contractor shall submit manufacturers' quality certificates for all the materials
supplied by him. In case, quality certificates are not available or are incomplete or when
material quality differs from standard specifications, such materials shall not be used in
the construction. However, the Contractor shall get all appropriate tests conducted in
approved test houses for such materials as directed by the Engineer-in-Charge, at no
extra cost, and submit the same to Engineer-in-Charge for his approval. The Engineer-
in-Charge may approve the use of such materials entirely at his discretion.

3.3.2 The Contractor shall ensure that all materials brought to site are duly approved by the
Engineer-in-Charge. Rejected materials shall not be used and shall be removed from
site forthwith. Any material of doubtful quality for which specific tests are to be carried
out as per the instruction of the Engineer-in-Charge shall be separately stacked and
properly identified and shall not be used. These shall be removed from site forthwith.

4.0 FABRICATION DRAWINGS

4.1 Fabrication and erection drawings shall be prepared by the Contractor on the basis of
"Approved for Construction (AFC)" design drawings, GAIL Standards issued to the
Contractor. These drawings shall be prepared by the Contractor or by an agency
appointed by the Contractor and approved by the Engineer-in-Charge.

4.2 Fabrication and erection drawings shall be thoroughly checked, stamped "Approved for
Construction" and signed by the Contractor's own responsible Engineer irrespective of
the fact that such drawings are prepared by the Contractor or his approved agency, to
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 4 of 28
NEW DELHI STEEL

Copyright – All rights reserved


ensure accuracy and correctness of the drawings. Unchecked and unsigned drawings
shall not be used for the purpose of proceeding with the work. The Contractor shall
proceed with the fabrication and erection work only after thoroughly satisfying himself
in this regard.

4.3 All fabrication and erection drawings shall be issued for construction by the Contractor
directly to his work- site. Six copies of such drawings shall simultaneously be submitted
to the Engineer-in-Charge who may check/ review some or all such drawings at his sole
discretion and offer his comments for incorporation in these drawings by the
Contractor.

However, the Contractor shall not proceed with the fabrication of such structures whose
fabrication drawings are required to be reviewed before taking up the fabrication work
as noted on "Approved for Construction (AFC)" design drawings issued to the
Contractor or as conveyed by the Engineer-in-Charge. The fabrication of such structures
shall be done only as per the reviewed fabrication drawings.

The review of such drawings by GAIL shall be restricted to the checking of the following
only:

i) Structural layout, orientation and elevation of structures/members.

ii) Sizes of members.

iii) Critical joint details.

4.4 Fabrication drawings shall be drawn to scale and shall convey the information clearly
and adequately. Following information shall be furnished on such drawings:

- Reference to design drawing number (along with revision number) based on


which fabrication drawing has been prepared.

- Structural layout, elevations & sections (with distinct erection marking of all
members).

- Framing plans, member sizes, orientation and elevations.

- Layout and detailing of rain water pipes and gutters showing all necessary levels,
connections and provisions wherever required.

- Detailing of shop/field joints, connections, splices, for required strength and


erection.

- Location, type, size and dimensions of welds and bolts.


STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 5 of 28
NEW DELHI STEEL

Copyright – All rights reserved


- Shapes and sizes of edge preparation for welding.

- Details of shop and field joints/welds.

- Bill of materials/D.O.D. Lists.

- Quality of structural steel, plates etc., welding electrodes, bolts, nuts and
washers to be used.

- Erection assemblies identifying all transportable parts and sub-assemblies with


special erection instructions, if required.

- Method of erection and special precautions to be taken during erection as


required.

4.5 The Contractor shall additionally ensure accuracy of the following and shall be solely
responsible for the same:

i) Provision for erection and erection clearances.

ii) Marking of members

iii) Cut length of members

iv) Matching of joints and holes.

v) Provision kept in the members for other interconnected members.

vi) Bill of materials/D.O.D. Lists.

4.6 Connections, splices and other details where not shown on the design drawings shall be
suitably designed and shown on the fabrication drawings based on good engineering
practice developing full member strength. Design calculations for such
connections/splices shall be submitted to the Engineer-in-Charge along with the
fabrication drawings.

4.7 Any substitution or change in section shall be allowed only when prior written approval
of the Engineer-in-Charge has been obtained. Fabrication drawings shall be updated
incorporating all such substitutions/changes by the Contractor at no extra cost to the
Owner.

4.8 In case during execution of the work, the Engineer-in-Charge on review of drawings
considers any modifications / substitutions necessary to meet the design parameters /
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 6 of 28
NEW DELHI STEEL

Copyright – All rights reserved


good engineering practice, these shall be brought to the notice of the Contractor who
shall incorporate the same in the drawings and works without any extra cost to the
owner. The Contactor will be totally responsible for the correctness of the detailed
fabrication drawings and execution of the work.

4.9 Contractor shall incorporate all the revisions made in the design drawings during the
course of execution of work in his fabrication drawings, and resubmit the drawings at
no extra cost to the Owner. All fabrication shall be carried out only as per the latest AFC
design drawings and corresponding fabrication drawings.

4.10 The Contractor shall supply two prints each of the final/as built drawings alongwith their
transparencies to Engineer-in-Charge for reference and record. The rates quoted shall
include for the same.

5.0 FABRICATION

5.1 General

5.1.1 Fabrication of structures shall be done strictly as per "Approved for Construction"
fabrication drawings (prepared by the Contractor based on the latest design drawings)
and in accordance with IS:800, 9595 & other relevant BIS Codes and BIS Hand Book
SP:6(1).

5.1.2 Prior to commencement of structural fabrication, undulations in the fabrication yard, if


any, shall be removed and area levelled and paved by the Contractor.

5.1.3 Any defective material used in the work shall be replaced by the Contractor at his own
expense. Necessary care and precautions shall be taken so as not to cause any damage
to the structure during any such removal and replacement.

5.1.4 Any faulty fabrication pointed out at any stage of work by the Engineer-in-Charge, shall
be made good or replaced by the Contractor at his own cost.

5.l.5 Tolerances for fabrication of steel structures shall be as per IS:7215.

5.2 Fabrication Procedure

5.2.1 Straightening & Bending

5.2.1.1 All materials shall be straight and, if necessary, before being worked shall be
straightened and/or flattened (unless required to be of curvilinear form) and shall be
free from twists.

5.2.1.2 Bending of rolled sections and plates shall be done by cold process to shape/s as
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 7 of 28
NEW DELHI STEEL

Copyright – All rights reserved


shown on drawings.

5.2.2 Clearances

The erection clearance for cleated ends of members shall be not greater than 2mm at
each end. The erection clearance at ends of beams without web cleats and end plates
shall be not more than 3mm at each end but where for practical reasons, greater
clearance is necessary, suitably designed seatings approved by the Engineer-in-Charge
shall be provided.

5.2.3 Cutting

5.2.3.1 Prior to cutting, all members shall be properly marked showing the requisite cut
length/width, connection provisions e.g. location and dimensions of holes, welds, cleats
etc. Marking for cutting shall be done judiciously so as to avoid wastages or
unnecessary joints as far as practicable. Marking shall be done by placing the members
on horizontal supports/pads in order to ensure accuracy. Marking accuracy shall be
limited to + lmm.

5.2.3.2 Cutting may be affected by shearing, cropping or sawing. Gas cutting by mechanically
controlled torch shall be permitted for mild steel. Hand flame cutting may be permitted
subject to the approval of the Engineer-in-Charge.

5.2.3.3 Except where the material is subsequently joined by welding, no loads shall be
transmitted into metal through a gas cut surface.

5.2.3.4 Shearing, cropping and gas cutting shall be clean, square, free from any distortion &
burrs, and should the Engineer-in-Charge find it necessary, the edges shall be ground
afterwards, to make the same straight and uniform at no extra cost to the Owner.

5.2.4 Holing

5.2.4.1 Holes for bolts shall not be formed by gas cutting process.

5.2.4.2 Holes through more than one thickness of material of members such as compound
stanchions and girder flanges shall, where possible, be drilled after the members are
assembled and tightly clamped/bolted together. Punching may be permitted before
assembly, provided the thickness of metal is less than 16mm and the holes are punched
3mm less in diameter than the required size and reamed, after assembly, to the full
diameter. Punching shall not be adopted for dynamically loaded structures.

5.2.4.3 Holes may be drilled in one operation through two or more separable parts and burrs
removed from each part after drilling.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 8 of 28
NEW DELHI STEEL

Copyright – All rights reserved


5.2.4.4 Holes in connecting angles and plates, other than splices, also in roof members and
light framing, may be punched full size through material not over 12mm thick, except
where required for close tolerance bolts or barrel bolts.

5.2.4.5 All matching holes for black bolts shall register with each other so that a gauge of
2mm less in diameter than the diameter of hole shall pass freely through the assembled
members in the direction at right angle to such members. Finished holes shall be not
more than 2mm in diameter larger than the diameter of the black bolt passing through
them, unless otherwise specified by the Engineer-in-Charge.

5.2.4.6 Holes for turned and fitted bolts shall be drilled to a diameter equal to the nominal
diameter of the shank or barrel subject to H8 tolerance specified in IS:919. Parts to be
connected with close tolerance or barrel bolts shall be firmly held together by tacking
bolts or clamps and the holes drilled through all the thicknesses in one operation and
subsequently reamed to size. Holes not drilled through all the thicknesses in one
operation shall be drilled to a smaller size and reamed out after assembly. Where this is
not possible, the parts shall be drilled and reamed separately.

5.2.4.7 To facilitate grouting, holes shall be provided in column bases or seating plates
exceeding 300mm in width for the escape of air.

5.2.4.8 To avoid accumulation of water in gussetted column bases of laced, battened or box
type stanchions, suitable reverse U-type holes shall be provide at the junction of base
plate and column section in the vertical gussets for draining out of any water.

5.2.5 Assembly

The component parts shall be assembled and aligned in such a manner that they are
neither twisted nor otherwise damaged, and shall be so prepared that the required
camber, if any, is provided. Proper clamps, clips, jigs and other fasteners (bolts and
welds) shall be placed in a balanced pattern to avoid any distortion in the members and
to ensure their correct positioning (i.e. angles, axes, nodes etc.). Any force fitting,
pulling/stretching of members to join them shall be avoided. Proper care shall be taken
for welding shrinkage & distortion so as to attain the finished dimensions of the
structure shown on the drawings.

5.2.6 Welding

5.2.6.1 General

a) All joints shall be welded unless noted otherwise on the design drawings,

b) Welding shall be in accordance with IS:8 16, IS:8 19, IS: 1024, IS: 126 1, IS:
1323 and IS:9595 as appropriate.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 9 of 28
NEW DELHI STEEL

Copyright – All rights reserved


c) The Contractor shall make necessary arrangement for providing sufficient
number of welding sets of the required capacity, all consumables, cutting and
grinding equipment with requisite accessories/ auxiliaries, equipment & materials
required for carrying out various tests such as dye penetration, magnetic
particle, ultrasonic etc.

d) Adequate protection against rain, dust, snow & strong winds shall be provided to
the welding personnel and the structural members during welding operation. In
the absence of such a protection no welding shall be carried out.

e) It shall be the responsibility of the Contractor to ensure that all welding is carried
out in accordance with the terms of this specification and relevant BIS codes.
The Contractor shall provide all the supervision to fulfil this requirement.

5.2.6.2 Preparation of Member for Welding

a) Edge Preparation

Edge preparation/bevelling of fusion faces for welding shall be done strictly as


per the dimensions shown in the drawings. In case, the same are not indicated,
edges shall be prepared (depending on the type of weld indicated in the
drawing) as per the details given in IS:9595. Bevelling of fusion faces shall be
got checked and approved by the Engineer-in-Charge. The tolerances on limits of
gap, root face & included angle shall be as stipulated in IS:9595.

b) Cleaning

Welding edges and the adjacent areas of the members (extending upto 20mm)
shall be thoroughly cleaned of all oil, grease, scale and rust and made completely
dry. Gaps between the members to be welded shall be kept free from all foreign
matter.

c) Preheating

Preheating of members, shall be carried out as per IS:9595 when the base metal
temperature is below the requisite temperature for the welding process being
used. Preheating shall be done in such a manner that the parts, on which the
weld metal is being deposited, are above the specified minimum temperature for
a distance of not less than 75mm on each side of the weld line. The temperature
shall be measured on the face opposite to that being heated. However, when
there is access to only one face, the heat source shall be removed to allow for
temperature equalization (1 minute for each 25mm of plate thickness) before
measuring the temperature.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 10 of
NEW DELHI STEEL
28
Copyright – All rights reserved
d) Grinding

i) Column splices & butt joints of struts and compression members


(depending on contact for load transmission) shall be accurately ground
and close-butted over the whole section with a tolerance not exceeding
0.2mm locally at any place. In column caps & bases, the ends of shafts
together with the attached gussets, angles, channels etc., shall be
accurately ground so that the parts connected butt over minimum 90%
surface of contact. In case of connecting angles or channels, care shall be
taken so that these are fixed with such accuracy that they are not reduced
in thickness by grinding by more than 2mm.

ii) Ends of all bearing stiffeners shall be ground to fit tightly at both top and
bottom. Similarly bottom of the knife edge supports along with the top
surface of column brackets shall be accurately ground to provide effective
bearing with a tolerance not exceeding 0.2mm locally at any place.

iii) Slab bases and caps shall be accurately ground over the bearing surfaces
and shall have effective contact with the ends of stanchions. Bearing faces
which are to be grouted direct to foundations need not be ground if such
faces are true & parallel to the upper faces.

5.2.6.3 Welding Processes

Welding of various materials under this specification shall be carried out using one or
more of the following processes.

- Manual Metal Arc Welding Process (MMAW)

- Submerge Arc Welding Process (SAW)

- Gas Metal Arc Welding Process (GMAW)

- Flux Cored Arc Welding Process (FCAW)

The welding procedure adopted and consumables used shall be specifically approved by
the Engineer-in-Charge. A combination of different welding processes or a combination
of electrodes of different classes/makes may be employed for a particular joint only
after qualifying the welding procedures to be adopted and obtaining the written
approval of the Engineer-in-Charge.

5.2.6.4 Approval & Testing of Welders

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 11 of
NEW DELHI STEEL
28
Copyright – All rights reserved
The Contractor shall satisfy the Engineer-in-Charge that the welders are suitable for the
work upon which they will be employed. For this purpose the welders shall have
satisfied the relevant requirements of IS:7318. If the welders will be working to
approved welding procedures, they shall have satisfied the relevant requirements of
IS:7310.

Adequate means of identification shall be provided to enable each weld to be traced to


the welder by whom it was made. The Contractor shall intimate the Engineer-in-Charge
sufficiently in advance, the commencement of tests, to enable him to be present to
witness the same.

5.2.6.5 Approval & Testing of Welding Procedures

The Contractor shall carry out procedure tests in accordance with IS:7307 to
demonstrate by means of a specimen weld of adequate length on steel representative
of that to be used, that he can make welds with the welding procedure to be used for
the work to the complete satisfaction of the Engineer-in-Charge. The test weld shall
include weld details from the actual construction and it shall be welded in a manner
simulating the most unfavourable instances of fit-up, electrode condition etc., which are
anticipated to occur on the particular fabrication. Where material analysis are available,
the welding procedure shall be carried out on material with the highest carbon
equivalent value.

After welding, but before the relevant tests given in IS:7307 are carried out, the test
weld shall be held as long as possible at room temperature, but in any case not less
than 72 hours, and shall then be examined for cracking. The examination procedure
shall be sufficiently rigorous to be capable of revealing significant defects in both parent
metal and weld metal.

After establishing the welding method, the Contractor shall finally submit to the
Engineer-in-Charge for his approval the welding procedure specification in standard
format given in IS39595 before starting the fabrication.

5.2.6.6 Sequence of Welding

a) As far as practicable, all welds shall be made in a sequence that will balance the
applied heat of welding while the welding progresses.

b) The direction of the general progression in welding on a member shall be from


points where the parts are relatively fixed in position with respect to each other
towards points where they have a greater relative freedom of movement.

c) All splices in each component part of a cover-plated beam or built up member


shall be made before the component part is welded to other component parts of
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 12 of
NEW DELHI STEEL
28
Copyright – All rights reserved
the member.

d) Joints expected to have significant shrinkage shall be welded before joints


expected to have lesser shrinkage.

e) Welding shall be carried continuously to completion with correct number of runs.

f) The Contractor shall choose the welding sequence after carefully studying each
case such as to minimize distortion and shrinkage & submit the same to the
Engineer-in-Charge for comments and approval.

5.2.6.7 Welding Technique

a) After the fusion faces are carefully aligned and set with proper gaps, the root
pass of butt joints shall be executed properly so as to achieve full penetration
with complete fusion of the root edges.

b) On completion of each run, all slag and spatters shall be removed and the weld
and the adjacent base metal shall be cleaned by wire brushing and light
chipping. Visible defects such are cracks, cavities and other deposition faults, if
any, shall be removed to sound metal before depositing subsequent run of weld.

c) All full penetration butt welds shall be completed by chipping/gouging to sound


metal and then depositing a sealing run of weld metal on the back of the joints.
Where butt welding is practicable from one side only, suitable backing steel strip
shall be used and joint shall be arranged in such a way as to ensure that
complete fusion of all the parts is readily obtained.

d) While welding is in progress care shall be taken to avoid any kind of movement
of the components, shocks, vibrations to prevent occurance of weld cracks.

e) Any deviation desired from the recommended welding technique and electrodes
shall be adopted only after obtaining written approval of the Engineer-in-Charge.

5.2.6.8 Inspection & Testing of Welds

The method of inspection shall be according to IS:822 and extent of inspection and
testing shall be in accordance with the relevant applicable standard or, in the absence
of such a standard, as specified by the Engineer-in-Charge. Welds shall not be painted
or otherwise obscured until they have been inspected, approved and accepted.

The Engineer-in-Charge or his representative shall have access to the Contractor's work
at all reasonable times and the Contractor shall provide him with all facilities necessary
for inspection during all stages of fabrication and erection with, but not limited to, the
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 13 of
NEW DELHI STEEL
28
Copyright – All rights reserved
following objectives.

i) To check the conformity with the relevant standards and suitability of various
welding equipments and their performance.

ii) To witness/approve the welding procedure qualification.

iii) To witness/approve the welders performance qualification.

iv) To check whether shop/field welding being executed is in conformity with the
relevant specifications and codes of practice.

Inspection and testing of all fabricated structures shall be carried out by the
Contracator by any, or, a combination of all the following methods as directed by the
Engineer-in-Charge and no separate payment shall be made, unless otherwise
mentioned, for inspection and testing of welds/fabricated structures:

A. Visual Inspection

All finished welds (i.e. 100 percent) shall be visually inspected for identification of the
following types of weld defects & faults.

a) Weld defects occurring at the surface such as blow holes, exposed porosity,
unfused welds etc.

b) Surface cracks in the weld metal or in the parent metal adjacent to it.

c) Damages to the parent metal such as undercuts, burning, overheating etc.

d) Profile defects such as excessive convexity or concavity, overlapping, unequal leg


lengths, excessive reinforcement, incompletely filled grooves, excessive
penetration beads, root grooves etc.

e) Distortion due to welding i.e., local shrinkage, camber, bowing, twisting, rotation,
wariness etc.

f) Linear eccentric, angular and rotational misalignment of parts.

g) Dimensional errors.

B. Mechanical Tests

The mechanical testing (such as tensile load tests, bend tests, impact tests etc.) shall
be done in accordance with the relevant standards and as per the instructions of the
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 14 of
NEW DELHI STEEL
28
Copyright – All rights reserved
Engineer-in-Charge.

C. Magnetic Particle/Dye Penetration/Ultrasonic Examination:

The examination shall be done at random as directed by the Engineer-in-Charge.


Whenever such tests are directed, the tests shall be carried out on joints chosen by
him. The tests shall be carried out by employing approved testing procedure in
accordance with IS:822.

D. Radiographic Examination

Radiographic examination shall be carried out only in special cases for random joints as
directed by the Engineer-in-Charge. The Contractor shall be paid extra for such
examination except for penalty radiographic tests for which the cost shall be borne by
him. The Contractor shall make necessary arrangement at his own expense for
providing the radiographic equipment, films and all other necessary materials required
for carrying out the examination. The tests shall be carried in the presence of the
Engineer-in-Charge by employing approved testing procedure in accordance with
IS:822. The Contractor shall fulfil all the statutory safety requirements while handling X-
ray and Gamma-ray equipment and provide the Engineer- in-Charge all the necessary
facilities at site such as dark room, film viewer etc., to enable him to examine the
radiographs.

5.2.6.9 Repair of Faculty Welds

No repair of defective welds shall be carried out without proper permission of the
Engineer-in-Charge and his approval for the corrective procedure.

Welds not complying with the acceptance requirements (as specified by BIS Codes &
the Engineer-in-Charge), as revealed during inspection & testing of welds or erection or
in-situ condition, shall be corrected either by removing & replacing or as follows:

a) Excessive convexity - Reduced to size by removal of excess weld metal.

b) Shrinkage cracks, - Defective portions removed down to sound cracks in


parent plates metal and rewelded.
and craters

c) Under cutting. - Additional weld metal deposited.

d) Improperly fitted/ - Welding cut & edges suitably prepared and


misaligned parts. parts.

e) Members distorted - Member straightened by mechanical means or


STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 15 of
NEW DELHI STEEL
28
Copyright – All rights reserved
by the heat of careful application of limited amount of heat,
welding temperature of such area not to exceed 650
degree Centigrade dull red heat).

In removing defective parts of a weld, gouging, chipping, oxygen cutting or grinding


shall not extend into the parent metal to any substantial amount beyond the depth of
weld penetration, unless cracks or other defects exist in the parent metal. The weld or
parent metal shall not be undercut in chippping, grinding, gouging or oxygen cutting.

Any fabricated structure or its component which, in the opinion of Engineer-in-Charge,


is defective and/or beyond any corrective action shall be removed forthwith from the
site as instructed by the Engineer-in-Charge without any extra claim. The owner
reserves the right to recover any compensation due to any loss arising out of such
rejections.

5.2.7 Bolting

5.2.7.1 All bolts shall be provided such that no part of the threaded portion of the bolts is
within the thickness of the parts bolted together. Washers of suitable thickness shall be
used under the nuts to avoid any threaded portion of the bolt being within the thickness
of parts bolted together.

5.2.7.2 The threaded portion of each bolt shall project through the nut at least one thread.

5.2.7.3 Flat washers shall be circular and of suitable thickness. However, where bolt
Heads/nuts bear upon the bevelled surfaces, they shall be provided with square tapered
washers of suitable thickness to afford a seating square with the axis of the bolt.

5.2.8 Splicing

5.2.8.1 Splicing of built up/compound/latticed sections shall be done in such a fashion that
each component of the section is joined in a staggered manner.

5.2.8.2 Where no butt weld is used for splicing, the meeting ends of two pieces of joist /
channel / built up section shall be ground flush for bearing on each other and suitable
flange and web splice plates shall be designed and provided for the full strength of the
flange1 web of the section and welds designed accordingly.

5.2.8.3 Where full strength butt weld is used for splicing (after proper edge preparation of the
web and flange plates) of members fabricated out of joist/ channel / angles / built up
section, additional flange and web plates shall be provided, over and above the full
strength butt welds, to have 40% strength of the flange and web.

5.2.8.4 Where a cover plate is used over a joist/channel section the splicing of the cover
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 16 of
NEW DELHI STEEL
28
Copyright – All rights reserved
plate and channel/joist sections shall be staggered by minimum 500mm. Extra splice
plate shall be used for the cover plate and joist/channel section as per clause 5.2.8.2 or
5.2.8.3.

5.2.8.5 Prior approval shall be obtained by the Contractor for locations of splices where not
shown on design drawings. Only a single splice at approved location shall be allowed for
members upto a length of 6 to 7m. Maximum two numbers of splices shall be allowed
for members exceeding this length.

5.2.9 Machining & Grinding

5.2.9.1 All slab bases and slab caps shall be accurately machined over the bearing surfaces
and shall be in effective contact with the ends of column sections (shafts).

5.2.9.2 For slab bases and slab caps, ends of column shafts shall be accurately machined.
However, for gussetted bases and caps, the column shafts shall be ground flush for
effective contact with parts connected together.

5.2.9.3 Gussetted bases and caps shall be ground flush for effective contact with ends of
column sections.

5.2.9.4 End of all bearing stiffeners shall be machined or ground to fit tightly at top and
bottom without any air gap.

5.2.9.5 While machining or grinding care shall be taken so that the length or thickness of any
part does not get reduced by more than 2.0mm.

5.2.9.6 For all machining or grinding works for gassetted base and cap plates, the clearance
between the parts joined shall not exceed 0.2mm at any location.

6.0 MARKING FOR IDENTIFICATION

6.1 Each component shall be distinctly marked (with paint) before delivery in accordance
with the marking diagrams and shall bear such other marks as will facilitate erection.

6.2 For small members which are delivered in bundles or crates, the required marking shall
be done on small metal tags securely tied to the bundle.

7.0 SHOP ERECTION

The steel work shall be temporarily shop erected complete or as directed by the
Engineer-in-Charge, so that the accuracy of fit may be checked before despatch.

8.0 INSPECTION & TESTING OF STRUCTURES


STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 17 of
NEW DELHI STEEL
28
Copyright – All rights reserved
8.1 The Engineer-in-Charge (or his authorised representative) shall have free access at all
times to those parts of the Contractor's works which are concerned with the fabrication
of the steel work and shall be provided with all reasonable facilities for satisfying
himself that the fabrication is being undertaken in accordance with the provisions of
these specifications & other relevant BIS Codes.

8.2 Should any structure or part of a structure be found not to comply with any of the
provisions of this specification (or relevant BIS Codes as referred to), it shall be liable to
rejection. No structure or part of the structure, once rejected shall be resubmitted for
inspection, exception cases where the Engineer-in-Charge or his authorised
representative considers the defect as rectifiable.

8.3 Defects which may appear during/after fabrication / erection shall be made good only
with the consent of the Engineer-in-Charge and procedure laid down by him.

8.4 All necessary gauges and templates shall be supplied free to the Engineer-in-Charge by
the Contractor whenever asked for during inspection. The Engineer-in-Charge, may at
his discretion, check the test results obtained at the Contractor's works by independent
tests at a test house, and the cost of such tests shall be borne by the Contractor.

9.0 SHOP PAINTING

9.1 All components and members of steel work shall be given one shop coat of red oxide
zinc chromate primer (conforming to IS:2074) or any other primer as specified, in the
tender, immediately after the surfaces have been properly prepared (i.e. degreased,
derusted, descaled & cleaned) in accordance with IS:1477 or 6-44-0004, as applicable.
The primer coat shall be applied over completely dry surfaces (using brushes of good
quality) in a manner so as to ensure a continuous and uniform film without
"holidaying". Special care shall be taken to cover all the crevices, comers, edges etc.
However, in areas which are difficult to reach by brushing, dauberslmops shall be used
by dipping the same in paint and then pulling pushing them through the narrow spaces.
The primer coat shall be air dried and shall have a minimum film thickness of 25
microns or as per GAIL Specification no. 6-44-0004 (tolerance + 10%) after drying, as
applicable.

9.2 Surfaces which are inaccessible after shop assembly, shall receive the full specified
protective treatment before assembly (this shall not apply to the interior of sealed
hollow sections).

9.3 Steel surfaces shall not be painted within a suitable distance of any edges to be welded
if the paint specified would be harmful to welders or impair the quality of the welds.

9.4 Welds and adjacent parent metal shall not be painted prior to deslaggipg, inspection
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 18 of
NEW DELHI STEEL
28
Copyright – All rights reserved
and approval by the Engineer-in-Charge.

9.5 Parts to be encased in concrete shall have only one coat of primer and shall not be
painted after erection.

10. PACKING

10.1 All items shall be suitably packed in case these are to be despatched from the
fabrication shop to the actual site of erection so as to protect them from any
damage/distortion or falling during transit. Where necessary, slender projecting parts
shall be temporarily braced to avoid warping during transportation.

10.2 Small parts such as gussets, cleats etc., shall be securely wired on to their respective
main members.

10.3 Bolts, nuts washers etc. shall be packed in crates.

11.0 TRANSPORTATION

Loading and transportation shall be done in compliance with transportation rules. In


case, certain parts can not be transported in the lengths stipulated on the drawings, the
position details of such additional splice joints shall be got approved by the Engineer-in-
Charge.

12.0 SITE (FIELD) ERECTION

12.1 Plant & Equipment

The suitability and capacity of all plant and equipment used shall be to the complete
satisfaction of the Engineer-in-Charge.

12.2 Storing & Handling

All steel work shall be so stored and handled at site so that the members are not
subjected to excessive stresses and any damage.

12.3 Setting Out

Prior to setting out of the steel work, the Contractor shall get himself satisfied about the
correctness of levels, alignment, location of existing concrete pedestals / columns/
brackets and holding down bolts/pockets provided therein. Any minor modification in
the same including chipping, cutting and making good, adjusting the anchor bolts etc.,
if necessary, shall be carried out by the Contractor at his own expense. The positioning
and levelling of all steel work including plumbing of columns and placing of every part
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 19 of
NEW DELHI STEEL
28
Copyright – All rights reserved
of the structure with accuracy shall be in accordance with the drawings and to the
complete satisfaction of the Engineer-in-Charge.

12.4 Tolerances

Tolerances for erection of steel structures shall be as per Annexure 'A'

13.0 SAFETY & SECURITY DURING ERECTION

13.1 The contractor shall comply with IS:7205 for necessary safety and adhere to safe
erection practices and guard against hazardous as well as unsafe working conditions
during all stages of erection.

13.2 During erection, the steel work shall be securely bolted or otherwise fastened and when
necessary, temporarily braced/guyed to provide for all loads to be carried by the
structure during erection till the completion, including those due to the wind, erection
equipment & its operation etc. at no extra cost to the owner. For the purpose of guying,
the Contractor shall not use other structure in the vicinity without prior written
permission of the Engineer-in-Charge.

13.3 No permanent bolting or welding shall be done until proper alignment has been
achieved.

13.4 Proper access, platform and safety arrangement shall be provided for working and
inspection, (at no extra cost to the owner) whenever required.

14.0 FIELD CONNECTIONS

14.1 Field Bolting

Field bolting shall be carried out with the same care as required for shop bolting.

14.2 Field Welding

All field assembly and welding shall be executed in accordance with the requirements
for shop assembly and welding. Holes for all erection bolts – where removed after final
erection shall be plugged by welding. Alternatively erection bolts may be left and
secured.

15. GROUTING

15.1 Prior to positioning of structural columns/girders/ trusses over the concrete


pedestals/columns/brackets, all laitance & loose material shall be removed by wire
brushing & chipping. The bearing concrete surfaces shall be sufficiently levelled, hacked
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 20 of
NEW DELHI STEEL
28
Copyright – All rights reserved
with flat chisels to make them rough, cleaned (using compressed air) and made
thoroughly wet. All pockets for anchor bolts shall also be similarly cleaned and any
excess water removed. Thereafter, the structural member shall be erected, aligned &
plumbed maintaining the base plates/shoe plates at the levels shown in the drawings,
with necessary shims/pack plates/wedges.

15.2 After final alignment and plumbing of the structure, the forms shall be constructed
alround and joints made tight to prevent leakage. Grouting (under the base plates/shoe
plates including grouting of sleeves & pockets) shall be done with non-shrink grout
having compressive strength (28 days) not less than 40Nlsq.mm Non shrink grout shall
be of free flow premix type and of approved quality and make. It shall be mixed with
water in proportion as specified by the manufacturer. Ordinary 1 :2 cement/sand
mortar grout shall be used only for small, isolated structures e.g. operating platforms
not supporting any equipment, pipe supports, cross overs, stairs & ladders. The
thickness of grout shall be as shown on the drawings but not less than 25 mm nor more
than 40mm in any case.

15.3 The grout mixture shall be poured continuously (without any interruption till
completion) by grouting pumps from one side of the base plate and spread uniformly
with flexible steel strips and rammed with rods, till the space is filled solidly and the
grout mixture carried to the other side of the base plate.

15.4 The grout mixture shall be allowed to harden for a period as decided by the Engineer-
in-Charge. At the end of this period, the shims/wedges/pack plates may be removed
and anchor bolts tightened uniformly. The alignment of the structure shall now be
rechecked and if found correct, the voids left by the removal of shims/wedges/pack
plates (if removed) must be filled up with a similar mixture of grout. In case after
checking, serious misalignment is indicated, the grout shall be removed completely and
fresh grouting done after making appropriate correction of alignment.

16.0 SCHEME AND SEQUENCE OF ERECTION

The Contractor shall furnish the detailed scheme and sequence of erection to match
with the project schedule and get the same approved by the Engineer-in-Charge. All
necessary co-ordination and synchornization shall be done with the Civil contractor
where Civil works are not included in the scope of structural contractor at no extra cost
so as to match with the project schedule.

17.0 PAYMENT

This clause shall apply to Item Rate tender only.

17.1 Payment for structural steel works shall be made on the basis of admissible weight in
metric tons (determined as described in clause 17.2 and 17.3) of the structure accepted
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 21 of
NEW DELHI STEEL
28
Copyright – All rights reserved
by the Engineer-in-Charge. The rate shall include supplying (as per supply conditions
given in the Tender) fabricating, erecting in position (at all levels & locations),
testing/examining (excluding radiography only) of bolted and/or welded structural steel
works of all types (including all built up/compound sections made out of rolled sections
and/or plates) including all handling, transporting, storing, straightening if required,
cutting, edge preparation, preheating, bolting and welding of joints (including sealing
the joints of box sections with continuous welding), finishing edges by
grinding/machining as shown, fixing in line & level with temporary staging & bracing
and removal of the same after erection, grouting with nonshrink/ordinary grout as
specified, preparation of fabrication & erection drawings, & erection schedule and
getting them reviewed, preparation and submission of as built drawings, as built
drawings, preparing the surfaces for painting, surface cleaning, wire brushing, removal
of mill scale, dust, rust, oil or grease and applying one coat of red oxide zinc chromate
primer or any other primer as specified after fabrication, return of surplus materials to
owner's stores and material reconciliation in the case of materials supplied by the owner
as per relevant contract conditions etc. all complete for all the operations mentioned in
the foregoing clauses.

17.2 The weight for payment shall be determined from the fabrication drawings and
respective bill of materials prepared by the Contractor. The bill of materials shall be
checked and approved by the Engineer-in-Charge before making the payment. The
Contractor shall prepare full scale template in order to supplement/verify the actual
cutting dimensions where so directed by the Engineer-in-Charge. The weight shall be
calculated on the basis of BIS Hand Book wherever applicable. In case sections used
are different from BIS sections, then Manufacturers' Hand Book shall be adopted. No
allowance in weight shall be made for rolling tolerances.

17.3 Welds, bolts, nuts, washers, shims, pack plates, wedges, grout and shop painting shall
not be separately measured. The quoted rate shall be deemed to include the same.

17.4 The rate shall include all expenses related to safety & security arrangements during
erection and all plants & tools required for fabrication, transportation & erection.

18.0 PAINTING AFTER ERECTION

18.1 General

18.1.1 The scope of painting after erection shall be at the sole discretion of the Engineer-in-
Charge and the Contractor shall obtain written instruction in this regard sufficiently prior
to taking up any procurement of paint and execution of painting work after erection of
steel structures.

18.1.2 The Contractor shall carry out the painting work in all respects with the best quality of
approved materials (conforming to relevant BIS Codes or relevant Specification, as
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 22 of
NEW DELHI STEEL
28
Copyright – All rights reserved
applicable) and workmanship in accordance with the best engineering practice. The
Contractor shall furnish characteristics of paints (to be used) indicating the suitability for
the required service conditions. The paint manufacturer's instructions supplemented by
Engineer-in-Charge's direction, if any, shall be followed at all times. Particular attention
shall be paid to the following:

- Proper storage to avoid exposure & extremes of temperature.

- Surface preparation prior to painting.

- Mixing & thinning.

- Application of paint and the recommended limit on time intervals between


consecutive coats.

18.1.3 Painting shall not be done in frost or foggy weather, or when humidity is such as to
cause condensation on the surfaces to be painted.

18.1.4 Surface which shall be inaccessible after site assembly shall receive the full specified
protective treatment before assembly.

18.1.5 Primers & finish coat paints shall be from the same manufacturer in order to ensure
compatibility. Painting colour code shall be as per Annexure-'B'.

18.2 Rub Down & Primer Application

The shop coated surfaces shall be rubbed down thoroughly with emery/abrasive paper
to remove dust, rust, other foreign matters and degreased, if required, in accordance
with IS:1477 or GAIL specification no. 6-44-0004, as applicable, cleaned with warm
fresh water and air dried. The portions, from where the shop coat has peeled off, shall
be touched up and allowed to dry.

Primer coat of red oxide zinc chromate primer (conforming to IS:2074) or any other
primer as per GAIL specification no. 6-44-0004, as specified, shall be applied by
brushing/ spraying over the shop coat in a manner so as to ensure a continuous and
uniform film throughout. Special care shall be taken to cover all the crevices, comers,
edges etc. The final primer coat shall be air dried and shall have a minimum film
thickness of 25 microns or as per GAIL Specification no. 6-44-0004 (tolerance 2 10%)
after drying, as applicable.

In case a different cleaning procedure & primer specifications are specified in the
drawing / Tender, the same shall be adopted.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 23 of
NEW DELHI STEEL
28
Copyright – All rights reserved
18.3 Final Paint Application

After the primer is hard dry, the surfaces shall be dusted off and one coat of synthetic
enamel paint of approved colour & shade (conforming to IS:2932) or any other paint as
per GAIL specification no. 6-44-0004, as specified, shall be applied by brushing/spraying
so that a film free from "holidaying" is obtained. The colour & shade of first coat of
paint shall be slightly lighter than the second coat in order to identify the application of
each coat. The second coat of paint shall be applied after the first coat is hard dry. The
minimum thickness of each film shall be 20 microns (2 10% tolerance) after drying.

In case a different type of paint & painting procedure are specified in the
drawing/tender, the same shall be adopted.

18.4 Inspection & Testing of Painting Works

18.4.1 All painting materials including primers & thinners brought to site by the Contractor for
application shall be procured directly from reputed and approved manufacturers and
shall be accompanied by manufacturer's test certificates. Paint formulations without
certificates shall not be accepted.

18.4.2 The Engineer-in-Charge at his discretion may call for additional tests for paint
formulations. The Contractor shall arrange to have such tests performance including
batch wise test of wet paints for physical & chemical analysis. All costs shall be borne
by the Contractor.

18.4.3 The painting work shall be subject to inspection by the Engineer-in-Charge at all times.
In particular, the stage inspection will be performed and Contractor shall offer the work
for inspection and approval at every stage before proceeding with the next stage. The
record of inspection shall be maintained. Stages of inspection are as follows:

(a) Surface preparation


(b) Primer application
(c) Each coat of paint

18.4.4 Any defect noticed during the various stages of inspection shall be rectified by the
Contractor to the entire satisfaction of the Engineer-in-Charge before proceeding
further. Irrespective of the inspection, repair and approval at intermediate stages of
work the Contractor shall be responsible for making good any defects found during final
inspection/guarantee period/defect liability period, as defined in General Conditions of
Contract. Dry film thickness (DFT) shall be checked and recorded ater application of
each coat. The thickness shall be measured at as many locations as decided by the
Engineer-in-Charge. The Contractor shall provide standard thickness measuring
instrument such as elkometer (with appropriate range for measuring dry film thickness
of each coat) free of cost to the Engineer-in-Charge whenever asked for.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 24 of
NEW DELHI STEEL
28
Copyright – All rights reserved
18.5 Payment

Payment for painting of structural steel works shall be made on the basis of admissible
weight in metric tons of the painted structures accepted by the Engineer-in-Charge.

The rate shall include supplying & applying two coats of synthetic enamel paint or any
other paint specified in the tender of approved quality and shade over a coat of red
oxide zinc chromate primer or any other primer specified in the tender over one coat of
shop primer already applied to structural steel works of all types/shapes at all levels,
locations & positions including storage, surface preparation, degreasing, cleaning,
drying, touching up of shop primer coat, providing temporary staging, testing etc. all
complete to the entire satisfaction of the Engineer-in-Charge.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 25 of
NEW DELHI STEEL
28
Copyright – All rights reserved
ANNEXURE – ‘A’
(Clause 12.4)

Maximum Permissible Erection Tolerances


A. Columns

1. Deviation of column axes at foundation toplevel with


respect to true axes.

i) In longitudinal direction + 5mm

ii) In lateral direction + 5mm

2. Deviation in the level of bearing surface of columns at


foundation top with respect to true level + 5mm

3. Out of plumb (Verticality) of column axis from true vertical


axis, as measured at top:

i) Upto and including 30m height +H/1000 or +25mm


whichever is less.

ii) Over 30m height +H/1200 or +35mm


whichever is less.

4. Deviation in straightness in longitudinal & transverse planes


of column at any point along the height. +H/1000 or +10mm
whichever is less.

5. Difference in the erected positions of adjacent pairs of columns


along length or across width of building prior to connecting
trusses/beams with respect to true distance. +5mm

6. Deviation in any bearing or seating level with respect to true


level. +5mm

7. Deviation in difference in bearing levels of a member on


adjacent pair of columns both across & along the building. +5mm

Note: 1. Tolerance specified under 3 should be read in conjunction with 4 & 5.


Note: 2. 'H' is the column height in mm.

B. Trusses

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 26 of
NEW DELHI STEEL
28
Copyright – All rights reserved
1. Shift at the centre of span of top chord member +1/250 of height of
with respect to the vertical plane passing through truss in mm at centre
the centre of bottom chord. of span or +5mm
whichever is less.

2. Lateral shift of top chord of truss at the centre of span +1/1500 of span of
from the vertical plane passing through the centre of truss in mm or +10mm
supports of the truss. whichever is less.

3. Lateral shift in location of truss from its true position. +10mm

4. Lateral shift in location of purlin from true position +5mm

5. Deviation in difference of bearing levels of truss from +1/1200 of span of


truss in mm or 20mm
whichever is less

C. Gantry Girders & Rails

1. Shift in the centre line of crane rail with respect + [{web thickness(mm)}+2mm]
to centre line of web of gantry girder 2

2. Shift of alignment of crane rail (in plan) with respect


to true axis of crane rail at any point. +5 mm

3. Deviation in crane track gauge with respect to true


gauge.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 27 of
NEW DELHI STEEL
28
Copyright – All rights reserved
ANNEXURE-'B '
(Clause 1 8.2)

PAINTING COLOUR CODE FOR STRUCTURAL STEEL

1 GANTRY GIRDER & MONORAIL DARK GREEN

2 GANTRY GIRDER & MONORAIL STOPPER SIGNAL RED

3 BUILDING STRUCTURAL STEEL COLUMNS, DARK ADMIRALITY


BRACKETS, BEAMS, BRACINGS, ROOF TRUSS, GREY
PURLINS, SIDEGIRTS, LOUVERS, STRINGERS

4 PIPE RACK STRUCTURE & TRESTLE DARK ADMIRALITY


GREY

5 CHEQUERED PLATE (BOTH FACES) BLACK

6 GRATING BLACK

7 LADDER RUNGS - BLACK


VERTICALS & CAGE
RED

8 HAND RAILING

- HANDRAIL, MIDDLE SIGNAL RED


RAIL, TOE PLATE

- VERTICAL POST BLACK

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR STRUCTUTAL
S-11-02-006 Page 28 of
NEW DELHI STEEL
28
Copyright – All rights reserved
TECHNICAL SPECIFICATION
CIVIL & STRUCTURAL WORKS

MISCELLANEOUS STEEL WORK

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 1 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


CONTENTS

1.0 GENERAL

2.0 REFERENCES

3.0 MATERIAL

4.0 ANCHOR BOLTS

5.0 METAL INSERTS

6.0 CHEQUERED PLATES

7.0 GRATINGS

8.0 TUBULAR HAND RAILING

9.0 MILD STEEL RUNGS

9.0 LIGHT GAUGE STEEL STRUCTURALSECTIONS EXPANSION


FASTENERS SPECIFICATION

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 2 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


1.O GENERAL

1.1 All materials supplied by the Contractor shall conform to their respective specifications
given in GAIL Specification no S-11-02-011

1.2 The Contractor shall furnish test certificates for all materials prior to their use in the
works.

1.3 Other requirements not covered under this specification shall be in accordance with

specification no S-11-02-006 Structural Steel Works.

2.0 REFERENCES

As mentioned in the respective clauses.

3.0 MATERIAL

As mentioned in the respective clauses.

3.1 Plain and Reinforcement cement Concrete work shall con firm to Indian Standard for
Plain and reinforced Concrete – Code of practice

4.0 ANCHOR BOLTS

4.1 Material

Materials for anchor bolts, nuts, locknuts, washers, pipe sleeves and anchor
plates shall conform to their respective specification given in GAIL Specification

4.2 Fabrication

Fabrication of anchor bolts and their complete assemblies shall be strictly in

compliance with the specifications and drawingslstandards. Anchor bolts shall

have coarse type threads conforming to IS :421 8.

4.3 Placement

Anchor bolt assemblies shall be placed in position strictly as per drawings and
securely held during pouring and vibrating of concrete with necessary templates
and other dummy structures to prevent their dislocation.

4.4 Tolerances

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 3 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


Tolerances allowed for anchor bolts positioning shall be:

- For sleeved bolts, one tenth of the bolt nominal diameter.


-F or bolts without sleeves, one twentieth of the bolt nominal diameter.

4.5 Protection

The exposed surfaces of bolts shall be properly covered (after greasing of bolts
and packing of sleeves) with jute cloth so as to protect them from damage till
final erection of structure equipment is over.

4.6 Payments

This clause shall apply to Item Rate tender only.

4.6.1 Payment shall be made on the basis of actual weight in metric tons of the anchor
bolt/anchor bolt assembly. The rate shall include supply (as per scope of supply of all
transporting tender material handling, fabrication, turning from available size MS round
to required diameter, threading, welding, fixing in position, at all levels and locations,
providing necessary templates, greasing, packing of sleeves, covering with jute cloth
and other protective measures etc. all complete. The rate shall cover bolt of any
diameter and nomenclature. Payment for fixing in position anchor bolt assembly
(already fabricated and supplied by the Owner as free issue) shall be made on the basis
of actual weight of anchor bolts/bolt assemblies in metric tons. The rate shall include
handling, transporting, fixing in position, welding if required, providing necessary
templates, greasing, packing of sleeves, covering with jute cloth and other protective
measures etc . all complete. No separate payment shall be made for templates, dummy
structures, supports etc. and the rate quoted shall be inclusive of all cost related to
such provision required for correct and accurate installation of anchor bolts/assembly.

5.0 METAL INSERTS

5.1 Material

Materials required for fabricating metal inserts shall conform to their respective
specification given in relevant GAIL Specification.

5.2 Fabrication

Fabrication of inserts shall be done strictly as per drawingshtandards and in compliance


with the requirements given in relevant GAIL Specification for Structural Steel Works.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 4 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


5.3 Placement

Metal inserts shall be correctly embedded (in plain concrete/reinforced concrete) as per
their location shown on the drawings. Care shall be taken that these are securely held
in position and do not get disturbed during concreting. Where necessary, these may be
welded to the reinforcement bars. Suitable templates, spacers, dummy structures and
temporary staging shall be provided. Necessary cutting in the formwork and adjustment
of reinforcement bars shall be done for the placement of metal inserts where required.

5.4 Painting

The exposed surfaces of metal inserts shall be cleaned with wire brush and given one
coat of red oxide zinc chromate primer (conforming to IS: 2074) or any other primer as
per relevant Specification after fabrication.

5.5 Payments

This clause shall apply to Item Rate tender only.

5.5.1 Payment shall be made on the basis of actual weight in metric tons of the metal
inserts. The rate shall include supply (as per supply conditions given in the tender) of
all materials, handling, transporting, fabrication, welding, fixing in position, at all levels
and locations, providing necessary templates, spacers, dummy structures, adjusting the
formwork and reinforcement, staging,

preparation of surface for painting, applying one coat of red oxide zinc chromate primer
or any other primer, as specified, etc. all complete.

6.0 CHEQUERED PLATES

6.1 Material

Chequered plates shall be of mild steel and conforming to IS:3502. Chequering shall
be closed or open-ended or of any other pattern as shown on drawings.

6.2 Fabrication Drawings

Refer Specification for -Structural Steel Works.

6.3 Fabrication

Chequered plates shall be fabricated as per the "Approved for Construction"


fabrication drawings (prepared by the Contractor based on design drawings).

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 5 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


These shall be perfectly flat and without any dents / deformations and shall be cut
to the required size and shape. Holes/notches/openings of the required size, if any,
shown on drawings shall be made. Nosing for staircase treads shall be made by cold
bending of chequered plates. All edges shall be made smooth and even. All
chequered plate units shall be given distinct erection marks in accordance with the
marking drawings. Stiffeners of any description shall be welded with the chequered
plates where shown on drawings.

6.4 Erection/fixing Chequered plates shall be fixed to the bearing members by


welding/ bolting1 screwing as shown on drawings. All bolts screws shall be of
counter-sunk type so that the heads remain flush with the top of plate. Where
welding is used for fixing, stitch welds of minimum 50mm length with a pitch of
150mrn shall be used. Continuous sealing run of weld shall be provided along the
junction of two consecutive chequered plates parallel to the span. For removable
flooring, details as shown on drawings shall be followed.

6.5 Painting Chequered plates shall be cleaned (both the surfaces) with wire brush and
given one coat of red oxide zinc chromate primer (conforming to IS: 2074) or any
other primer as per GAIL Specification as specified, on both surfaces.

6.6 Payment

This clause shall apply to Item Rate tender only.

6.6.1 Payment shall be made on the basis of admissible weight in metric tons (determined as
described in clause 6.6.2) of the chequered plates accepted by the Engineer-in-Charge.
Where stiffeners are used, weight of the same shall be included in arriving at
admissible weight.

The rate shall include supplying (as per supply conditions given in the tender), fabricating,
erecting M.S. chequered plates including transporting, handling, straightening if required,
cutting to required size and shape, making holes/notches/opening of required size and
nosing, smoothening the edges, fixing by welding/ bolting /screwing, at all levels and
locations, preparing detailed fabrication drawings, surface cleaning, removal of rust, scale,
grease and applying one coat of red oxide zinc chromate primer or any other primer as per
GAIL Specification no, as specified, etc. all complete.

In any stiffening sections are provided below the chequered plates for strengthening, the
same shall be separately measured & paid under Structural Steel item (Viz. relevant GAIL
Specification.)

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 6 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


6.6.2 The weight for payment shall be determined from the fabrication drawings and respective
bill of materials prepared by the Contractor. The bill of materials shall be checked and
approved by the Engineer-in- Charge before making the payment.

The weight shall be calculated on the basis of BIS Handbook. No allowance in weight
shall be made for rolling tolerances. Welds, bolts, nuts, screws, washers, clips

7.0 GRATINGS

7.1 Categories

The gratings shall be of two categories:

i) Category 'A' - Fabricated by the Contractor as per GAIL design


drawings/standards.

ii) Category 'B' -Ready made bought out from an approved manufacturer.

7.2 Material

Materials for fabrication and fixing of Gratings shall conform to their respective
specification given in GAIL Specification no.

7.3 Fabrication Drawings

Refer GAIL Specification for Structural Steel Works.

7.4 Fabrication

7.4.1 Category 'A' Gratings

These shall be fabricated strictly as per the "Approved for Construction"


fabrication drawings prepared by the Contractor based on design drawings and
standards. All units shall be given distinct erection marks in accordance with he
marking drawing. All notchings in the flats shall be punched and not flame-cut.
Continuous around welding shall be done along the contact-lines between two
flats on both the surfaces. All fabrication shall be done in a shop under strict
supervision. Clamps shall be fabricated as shown on drawing standard.

7.4.2 Category 'B' Gratings

These shall be as per manufacturer’s details designed to carry loads as specified


on the design drawing supplied to the contractor. The deflection shall not exceed
span1200 or 6mrn whichever is minimum. The maximum clear size of voids in
the grating shall be limited to 30mm x 55mm. Thickness of grating shall be
25mm. The Contractor shall make necessary notches1 opening in the gratings as

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 7 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


shown in the drawings. All edges affected by such notches/ openings shall be
suitably stiffened by welding additional flats of the requisite size. All units shall
be given distinct erection marks in accordance with the marking drawings. Before
procurement the Contractor shall submit the design calculations, drawings and
manufacturer’s literature1 catalogues and get the same reviewed by the
Engineer-in- Charge. The Contractor shall submit sample gratings for inspection
and approval by the Engineer-in-Charge whenever asked for.

7.5 Gratings shall be fixed to the bearing members by welding /clamping and bolting
as indicated in the drawings. Minimum length and maximum pitch of welds shall
be 50mm and 150mm respectively where stitch welding is used for fixing along the
lines of supports. The edges of two consecutive gratings shall be bolted with
minimum two bolts on each side of the grating panel.

7.6 Galvanising Gratings and the fixing clamps, bolts, nuts shall be cleaned with wire
brush and galvanisation shall be done in accordance with IS:2629 and tested as per
IS:2633 & 6745. Quantity of zinc coating shall be minimum 900 gms1sq.m. of
surface area (0.12mm uniform thickness).

7.7 Payment

This clause shall apply to Item Rate tender only.

7.7.1 Payment shall be made on the basis of admissible weight in metric tons (determined
as described in clause 7.7.2) of the gratings accepted by the Engineer- in-Charge.
The rate shall include supplying, fabricating, erecting MS gratings (of the specified
category) including transporting, handling, cutting to required size and shape,
making holes/notches/ openings, smoothening the edges, fabricating clamps, fixing
by welding/clamping/ bolting, at all levels and locations, preparing detailed
fabrication drawings, surface cleaning, removal of rust, scale, grease and applying
one coat of red oxide zinc chromate primer or any other primer as per GAIL
Specification no. , as specified, or galvanising as required.

7.2 The weight for payment shall be determined from the fabrication drawings and respective

bill of materials prepared by the Contractor. The bill of materials shall be checked and
approved by the Engineer-in- Charge before making the payment. The weight, shall be
calculated on the basis of BIS Handbook as mentioned above. No allowance in weight
shall be made for rolling tolerances.

7.7.3 Welds, bolts, clamps, nuts and washers shall not be measured. The quoted rate
shall be deemed to include the same.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 8 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


8.0 TUBULAR HAND RAILING

8.1 Material

Materials for fabrication and fixing of Tubular Hand Railing shall confirm to their
respective specification given in GAIL Specification no

8.2 Fabrication Drawings

Refer clause 4.0 of GAIL Specification no. -Structural Steel Works.

8.3 Fabrication

Handrailing shall be fabricated strictly as per the "Approved for Construction"


fabrication drawings prepared by the Contractor based on design drawings and
standards. All tubes shall be straight and without any dents/ deformations. Tubes shall
be cut and ends shall be prepared to a neat and workman-like finish. All elements shall
be directly welded. All welded joints shall be cleaned and filed or ground smooth, if
required, to have a smooth surface and aesthetically pleasant appearence. Splicing of
top rail shall not be allowed. Tubes shall be coldbent to shape and curvature in case of
discontinuous ends of handrails. Ripples, kinks andlor dents at bends shall not be
accepted.

Lower ends of vertical posts shall be cut and splayed (for grouting in pockets in the
concrete members). For removable type of handrailing, suitable base plates (with
provision for bolting) shall be welded to the lower end of vertical posts. All units shall
be given distinct erection marks in accordance with the marking drawing.

8.4 Erection/ fixing


Handrailing, shall be fixed to the bearing members by welding1 bolting1 grouting as
indicated on the drawings. Local notching shall be made in the floor plate/ grating to
accomodate vertical postsltheir base plates which shall always be welded to the main
supporting member. When the posts are to be fixed in concrete members, suitable
pockets shall be made in concrete for grouting as shown on drawingdstandards.

8.5 Painting

Tubes shall be cleaned with wire brush and given one coat of red oxide zinc chromate
primer (conforming to IS:2074) or any ,other primer as per GAIL Specification no. 6-
44-0004? as specified, after fabrication.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 9 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


8.6 Payment

This clause shall apply to Item Rate tender only.

8.6.1 Payment shall be made on the basis of measured length in meters (m) of top rail only
(Horizontal andlor inclined lengths). The rate shall include preparation of fabrication
drawings, supply of all materials, handling, transporting, straightening if required,
cutting to required size, bending, welding, bolting, fixing in position at all levels and
locations, grouting with 1:2 (cement:sand) mortar, surface cleaning, removal of rust,
scale, grease and applying one coat of red oxide zinc chromate primer (conforming to
IS 2074) or any other primer as per GAIL Specification no. , as specified, after
fabrication etc. all complete.

8.6.2 The rate shall include making suitable notches in floor plates/ gratings and pockets in
concrete structures for fixing the vertical posts.

9.0 MILD STEEL RUNGS

9.1 Material

All materials shall conform to their respective specifications given in GAIL Specification
no.

9.2 Fabrication

Rungs shall be fabricated as per GAIL standards/drawings. Mild steel bars shall be
straightened if required, cut, bent to shape and given one coat of red oxide zinc
chromate primer on exposed portions.

9.3 Fixing

Rungs shall be fixed in position as per detailed drawing and firmly tiedlwelded with
reinforcement to prevent their displacement during vibrating of concrete.

9.4 Payment

This clause shall apply to Item Rate tender only.

9.4.1 Payment shall be made on the basis of actual weight in kilograms (Kgs.) of the M.S.
rungs. The rate shall include supply of all materials handling, transporting,
straightening if required, cutting to required size, bending to shape, tying /welding
with reinforcement bars, fixing at all levels and locations, adjustment of formwork,
applying one coat of red oxide zinc chromate primer (conforming to IS 2074) or any
other primer as per GAIL Specification no. , as specified, and two coats of anti-
corrosive paint or any other paint, as specified, on the exposed portion of rungs etc. all
complete.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 10 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


10.0 LIGHT GAUGE STl3EL STRUCTURAL SECTIONS

10.1 Material

All materials required for fabrication and fixing in position of Light Gauge Steel
Structural Sections shall conform to their respective specification given in GAIL
Specification no.

10.2 Fabrication Drawings

Refer GAIL Specification for -Structural Steel Works.

10.3 Fabrication

Fabrication of members shall be done strictly as per the "Approved for Construction"
fabrication drawings prepared by the Contractor based on the latest design drawings
and in accordance with IS: 800, IS: 801 and other relevant BIS Codes.

All members shall be straight and free from any dents/deformations/ twists. Members
shall be cut to the required sizes and ends prepared to a neat and workman like
finish. Holes (for sag rods and cleat bolts) of appropriate size shall be drilled and all
members/ components shall be given distinct erection marks in accordance with the
marking drawings. Holes shall not be formed by gas cutting process.

10.4 Erection

Structural members shall be erected in proper sequence and aligned properly without
causing any twist. Permanent bolting/welding shall be done only after proper alignment
has been achieved. Proper access, working platforms and safety arrangements shall be
provided by the Contractor for working and inspection.

10.5 Painting

All structural components shall be cleaned thoroughly and given one coat of red oxide zinc
chromate primer (conforming to IS:2074) or any other primer as per GAIL Specification no.
, as specified, after fabrication.

10.6 Payment

This clause shall apply to Item Rate tender only.

10.6.1 Payment shall be made on the basis of admissible weight in metric tons (determined as
described in clause 10.6.2) of the structure accepted by the Engineer-in-Charge. The rate
shall include supplying, fabricating, erecting, at all levels and locations, testing of bolted
and/or welded Light Gauge structural steel works including cleats, crook bolts,
splices/sleeves, all other fixtures and accessories, straightening if required, cutting, edge

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 11 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


preparation, welding and bolting of joints, fixing in line and level with temporary staging
and removal of the same after final alignment, handling, transporting, storage, preparation
of detailed fabrication drawings and getting them reviewed by the Engineer-in-Charge,
surface cleaning, wire brushing, removal of scale, rust, oil or grease and painting as per
8.5 above etc., all complete.

10.6.2 The weight for payment shall include all structural members, cleats, splices, gussets and sag
rods and shall be determined from the fabrication drawings along with respective bill of
materials prepared by the Contractor. The bill of materials shall be checked and approved by
the Engineer-in-Charge before making the payment. The weight shall be calculated on the
basis of BIS Handbook. Manufacturer's catalogues/ charts shall be adopted in case relevant
weights of sections used are not covered in BIS Handbook. No allowance in weight shall be
made for rolling tolerances.

10.6.3 All welds, bolts, nuts washers, fixtures and accessories shall not be measured.
The quoted rate shall be deemed to include the same.

10.6.4 The rate shall be applicable to all cleats, splices, sleeves and gussets. Sag rods.
however, shall be separately measured and paid under structural steel item (viz.

11.0 EXPANSION FASTENERS

11.1 Material

Expansion fasteners (medium and heavy duty) shall be of mild steel high tensile steel
with rust proof coating including both mechanical & chemical fasteners.

11.2 Classification

The expansion fasteners shall be designated as medium and heavy duty depending on
their usage. The broad classification is given below for general guidance.

11.2.1 Medium Duty (Mild steel/High tensile steel)

-Ladders and stairs supports.

-Cables and cable trays supports.

-Electrical panels and fixtures.

-Hangers for pipes and cable trays.

-Pipe supports.

11.2.2. Heavy Duty (Mild steel1High tensile steel).

-Platform supports (beam and columns)


STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 12 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


-Knee brackets for pipeslmulti tiers cable trays/ walkways etc.

Note:-Expansion fasteners shall not be used for

1. Members supporting equipment and pipes subjected to vibrations.

2. Cantilever connections designed to cater for effective cantilever spans


greater than lOOOrnrn and 1000Kgs. of concentracted load at the free end.

11.3 Selection

The Contractor shall submit to the Engineer-in-Charge manufacturer's catalogues along


with the specimens of expansion fasteners (proposed to be used for the job) for his
selection and approval. Selected fasteners shall be capable to carry the specified loads.

11.4 Testing

If so desired by the Engineer-in-Charge, the Contractor shall carry out all the requisite tests
(pullout test, torque test etc.) of specimen expansion fasteners (representative of those to
be used) from approved laboratory1 test house and submit the report to him for approval.
The decision of the Engineer-in-Charge regarding the adequacy of strength and load
carrying capacity of the expansion fastener shall be final and binding to all. The cost of all
such tests shall be borne by the Contractor.

11.5 Installation

The Contractor shall install the expansion fasteners at their correct location (to suit the
requirement of fixtures as shown in drawings) as per the procedure laid down by thhe
manufacturer. Location of all holes shall be pre-marked on the concrete surfaces and
then holes drilled carefully with an electric drill to the correct recommended size and
depth. Holes shall be exactly round and true perpendicular to the concrete surface. Edge
distance and pitch of fasteners shall be as recommended by the manufacturer. The
contractor shall suitably shift the hole with the approval of the Engineer-in-Charge in case
any reinforcement bar is met with while drilling the hole in RCC structure. Necessary
staging shall be provided for working and the Contractor shall take requisite safety
precautions so as not to cause any damage to the existing structure1 equipment. Any
damage done while executing the job shall be made good by the Contractor at his cost.

11.6 Protection

The exposed surfaces of expansion fasteners shall be properly greased &


covered with jute cloth so as to protect them from damage.

11.7 Payment

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 13 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


This clause shall apply to Item Rate tender only.

11.7.1 Payment for installing rust proof expansion fasteners shall be made on number
basis (each). The rate shall include supply of complete assembly, handling,
transporting, providing necessary temporary staging, installing (as per
manufacturer's specifications) in PCCIRCC structures, at all levels and locations,
testing, drilling, cleaning, covering with jute cloth, relocating and redrilling in
case of any obstruction, making good any damage done to the structure,
grouting the abandoned holes and any gap left between the contact surfaces of
PCC/RCC.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR
S-11-02-007 Page 14 of 14
NEW DELHI MISCELLANEOUS STEEL WORK

Copyright – All rights reserved


TECHNICAL SPECIFICATION
CIVIL AND STRUCTURAL WORKS

BRICK MASONRY

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 1 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


CONTENTS

SL. NO. DESCRIPTION

1.0 SCOPE

2.0 REFERENCES

3.0 MATERIALS

4.0 GENERAL REQUIREMENTS

5.0 CONSTRUCTION PROCEDURE

6.0 PAYMENT

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 2 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


1.0 SCOPE

This GAIL specification establishes the materials, dressing, laying, joining, curing,
workmanship etc. for brick masonry works. Brick masonry shall also comply with all the
requirements of IS:2212.

2.0 REFERENCES

2.1 BIS Codes

IS:2212, 2250

2.2 GAIL specifications

S-11-02-002 : Materials

3.0 MATERIALS

Refer GAIL specification no. S-11-02-002 : Materials

4.0 GENERAL REQUIREMENTS

4.1 Cement Mortar

Cement mortar shall meet the requirements of IS2250 and shall be prepared by mixing
cement and sand by volume. Proportion of cement and sand shall be 1 :6 (1 part of
cement and 6 parts of sand), or as directed by the Engineer-in-Charge/shown on the
drawing, for brick masonry of one brick thickness or more, while 1:4 cement mortar (1
part of cement and 4 parts of sand) shall be used for brick masonry of half brick
thickness. The sand being used for mortar shall be sieved. The mortar shall be used as
soon as possible after mixing and before it has begun to set and in any case within
initial setting time of cement after water is added to the dry mixture. Mortar unused for
more than initial setting time of cement, shall be rejected and removed from the site of
work.

4.1.1 Proportioning

The unit of measurement for cement shall be a bag of cement weighing 50 kgs and this
shall be taken as 0.035 cubic meter. Sand shall be measured in boxes of suitable size
on the basis of its dry volume. In case of damp sand, its quantity shall be increased
suitably to allow for bulkage.

4.1.2 Mixing
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 3 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


The mixing of mortar shall be done in a mechanical mixer operated manually or by
power. The Engineer-in-Charge may, however, permit hand-mixing as a special case,
taking into account the magnitude, nature and location of work. The Contractor shall
take the prior permission of Engineer-in-Charge, in writing, for using hand-mixing
before the commencement of work.

4.1.2.1 Mixing in Mechanical Mixer

Cement and sand in specified proportions, by volume, shall be thoroughly mixed dry in
a mixer. Water shall then be added gradually and wet mixing continued for atleast one
minute. Care shall be taken not to add more water than that which shall bring the
mortar to the consistency of stiff paste. Wet mix from the mixer shall be unloaded on
water-tight masonry platform, made adjacent to the mixer. Platform shall be atleast 150
mm above the levelled ground to avoid contact of surrounding earth with the mix. Size
of the platform shall be such that it shall extend atleast 300rnm alround the loaded wet
mix area. Wet mix, so prepared, shall be utilized within initial setting time [thirty (30)
minutes either for ordinary portland cement conforming to IS:269 or for portland slag
cement conforming to IS:455] after addition of water. Mixer shall be cleaned with water
each time before suspending the work.

4.1.2.2 Hand Mixing

The measured quantity of sand shall be levelled on a clean water-tight masonry


platform and cement bags emptied on top. The cement and sand shall be thoroughly
mixed dry by being turned over and over, backward and forward, several times till the
mixture is of uniform colour. The quantity of dry mix which can be consumed within
initial setting time of cement shall then be mixed with just sufficient quantity of water to
bring the mortar to the consistency of stiff paste.

5.0 CONSTRUCTION PROCEDURE

5.1 Soaking of Bricks

Bricks shall be soaked in water before use for a period that is sufficient for the water to
just penetrate the whole depth of bricks as well as to remove dirt, dust and sand.
Proper soaking of bricks shall prevent the suction of water from the wet mortar as
otherwise mortar will dry out soon and crumble before attaining any strength. The
bricks shall not be too wet at the time of use as they are likely to slip on mortar bed
and there will be difficulty in achieving the plumbness of wall as well as proper adhesion
of bricks to mortar. The period of soaking shall be determined at site by a field test by
immersing the bricks in water for different periods and then breaking the bricks to find
the extent of water penetration. The least period that corresponds to complete soaking,
will be the one, to be allowed for in the construction work.
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 4 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


The soaked bricks shall be removed from the tank, sufficient early, so that at the time
of laying, they are skin dry. The soaked bricks shall be stacked over a clean place,
wooden planks or masonry platforms to avoid earth, dirt being smeared on them.

5.2 Laying

5.2.1 Brick Work (one or more brick thickness)

Brick work (one or more brick thickness) shall be laid in English Bond unless otherwise
specified. Half or cut bricks shall not be used except when needed to complete the
bond. In no case the defective bricks shall be used.

A layer of average thickness of 10mm of cement mortar shall be spread on full width
over a suitable length of lower course or the concrete surface. In order to check and
achieve uniformity in masonry, the thickness of bed joints shall be such that four
courses and three joints taken consecutively shall measure equal to four times the
actual thickness of the brick plus 30mm. Each brick with frog upward, shall be properly
bedded and set in position by gently tapping with handle of trowel or wooden mallet.
Its inside faces shall be buttered with mortar before the next brick is laid and pressed
against it. After completion of the course, all vertical joints shall be filled from top with
mortar.

All brick courses shall be taken up truly plumb; if battered, the batter is to be truly
maintained. All courses shall be laid truly horizontal and vertical joints shall be truly
vertical. The level and verticality of work in walls shall be checked up at every one
metre interval.

The masonry walls of structures shall be carried up progressively, leaving no part one
metre lower than the other. If this cannot be adhered to, the brick work shall be raked
back according to bond (and not left toothed) at an angle not more than 45 degrees
but raking back shall not start within 60 cm of a corner. In all cases returns, buttresses,
counter forts, pillars etc. shall be built up carefully course by course, and properly
bonded with the main walls. The brick work shall not be raised more than fourteen (14)
courses per day.

At the junction of any two walls, the bricks shall at each alternate course, be carried
into each of the respective walls so as to thoroughly unite the work.

The courses at the top of plinth and sills, at the top of the wall just below the soffit of
the roof slab or roof beam and at the top of the parapet, shall be laid with bricks on
edge. Brick on edge course shall be so arranged as to tightly fit under the soffit of the
roof beam or roof slab, restricting the mortar layer thickness upto 12mm, however, any
gap between the finished brick work and soffit of roof slablbeam shall be suitably
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 5 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


sealed with the mortar.

52.2 Brick Work (half brick thickness)

For brick walls of half brick thickness, all courses shall be laid with stretchers. Wall shall
be reinforced with 2 nos. - 6mm diameter mild steel reinforcement bars, placed at every
fourth course. The reinforcement bars, shall be straightened and thoroughly cleaned.
Half the mortar thickness for the bedding joint shall be laid first and mild steel
reinforcement, one on each face of the wall, shall be embedded, keeping a side cover
of 12mm mortar. Subsequently, the other half of the mortar thickness shall be laid over
the reinforcement covering it fully.

The reinforcement bars shall be carried atleast 150mm into the adjoining walls or RCC
columns. In case the adjoining wall being of half brick thickness, the length of bars shall
be achieved by bending the bars in plan. During casting of reinforced concrete columns,
6mm dia. M.S. reinforcing bar shall be placed at every fourth course of brick masonry.
At the junction of two walls, the brick shall, at each alternate course, be carried into
each of the respective walls so as to thoroughly unite the work. The brick masonry work
shall not be raised more than 14 courses per day.

Brick course under the soffit of beam or slab, shall be laid by restricting the mortar
thickness to 12mm. However, any gap between the finished brickwork and soffit of
slablbeam, shall be suitably sealed with the mortar.

5.2.3 Cavity Walls

Brick work in cavity walls shall be included with general brickwork. It shall consist of
one wall of one or more brick thickness while the other wall shall be of half brick
thickness at a clear gap of 50rnm. The brick work on either side of cavity shall conform
to the specifications already stated under 5.2.1 and 5.2.2. At the base of the cavity
wall, the walls shall be solidly constructed upto 300mm above the ground level. The
cavity wall shall be terminated 300mm below the soffit of roof slab/beam and the
courses over this shall be continued in solid brickwork.

Cavity should be continuous and free from obstructions. Mortar droppings shall be
prevented from falling down the cavity by the use of laths or by hayhands which shall
be drawn up the cavity as the work proceeds. Any mortar which may unavoidably fall
on the wall-ties, shall be removed daily and temporary openings shall be provided to
permit the daily removal of mortar droppings from the bottom of the cavity.

The outer and inner leaves shall be tied by means of wall ties. Ties shall be of mild steel
round bars of 8mm dia. 200 mm long with hooks at both the ends. These shall be
placed not more than 750mm clc horizontally and not more than 300mm vertically, and
staggered. Additional ties shall be provided near the openings. There shall at least, be 5
STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 6 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


ties per square meter of surface area of the wall. Ties shall be given a bituminous coat
before placement, to protect them from corrosion.

In order to keep the cavity dry, air slots shall be provided in the cavity walls at bottom
as well as top to the extent of 50 sq.cm area of vents to every 2.0 sq. metre area of the
wall.

5.2.4 Circular Brick Work

The detailed GAIL specification for brick work covered under 5.2.1 & 5.2.2 shall apply,
in so far as these are applicable. Bricks forming skew backs, shall be dressed or cut so
as to give proper radial bearing. Defects in dressing of bricks shall not be covered up by
extravagant use of mortar, nor shall the use of chips etc, be permitted.

The circular brick work shall be carried up from both ends simultaneously and keyed in
the centre. The bricks shall be flushed with mortar and well pressed into their positions
so as to squeeze out a part of their mortar and leave the joints thin and compact. All
joints shall be full of mortar and thickness of joints shall be between 5mm and 15mm.

5.3 Jointing

Joints shall be restricted to a width of 10mm with brickwork of any classification. All bed
joints shall be normal to the pressure upon them i.e. horizontal in vertical walls, radial
in circular brick masonry and at right angles to the face in the battered retaining walls.
The vertical joints in alternate courses shall come directly one over the other and shall
be truly vertical. Care shall be taken that all the joints are full of mortar, well flushed
up. In case no pointing is to be done, cement mortar shall be neatly struck as the work
proceeds. The joints in faces which are to be plastered or pointed shall be squarely
raked out to a depth of 12mm while the mortar is still green. The rake joints shall be
brushed to remove loose particles. After the day's work, the faces of the brick work
shall be cleaned on the same day with wire brush and all mortar droppings removed.

5.4 Curing

Green work shall be protected from rain or any other running water or accumulated
water from any source, by suitable means. Masonry work, as it progresses, shall be
kept thoroughly wet by sprinkling water at regular intervals, on all faces. Curing shall be
done after 24 hours of completion of day's work and shall be done for atleast 10 days
after completion. Proper watering cans with spray nozzles, rubber or PVC pipes shall be
used for this purpose.

5.5 Staging/scaffolding

Staging/scaffolding shall be properly planned and designed by the Contractor. Use of


STANDARD SPECIFICATION DOCUMENT No. REV-0
(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 7 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


only steel tubes is permitted for Staging/scaffolding. Design of Staging/scaffolding shall
be submitted for approval of the Engineer-in-Charge, before commencement of work.

Single scaffolding having one set of vertical support, shall be used and other end of the
horizontal scaffolding member shall rest in a hole provided in the header course. The
support shall be sound and strongly clamped with the horizontal pieces over which the
scaffolding planks shall be fixed. The holes left in the masonry work for supporting the
scaffolding shall be filled and made good with plain cement concrete of grade 1:3:6
during plastering. Suitable access shall be provided to the working platform area. The
scaffolding shall be strong enough to withstand all loads likely to come upon it and shall
also meet the requirements specified in IS:2750.

Double scaffolding shall be provided for pillars less than one metre in width or for the
first class masonry or for a building having more than two storeys.

The following measures shall also be considered during erection of the scaffolding/
staging.

a. Sufficient sills or underpinnings, in addition to base plates, shall be provided,


particularly, where scaffoldings are erected on soft grounds.

b. Adjustable bases to compensate for uneven ground shall be used.

c. Proper anchoring of the scaffolding/staging at reasonable intervals shall be


provided in each direction with the main structure wherever available.

d. Horizontal braces shall be provided to prevent the scaffolding from rocking.

e. Diagonal braces shall be provided continuously from bottom to top between two
adjacent rows of uprights.

f. The scaffolding/staging shall be checked at every stage for plumb line.

g. Wherever the scaffolding/staging is found to be out of plumb line, it shall be


dismantled and re-erected afresh. Efforts shall not be made to bring it in line
with a physical force.

h. All nuts and bolts shall be properly tightened and care shall be taken that all the
clamps/couplings are firmly tightened to avoid slippage.

i. Erection work of a scaffolding/staging, under no circumstance shall be left totally


to semiskilled or skilled workmen and shall be carried out under the supervision
of Contractor's technically qualified civil engineer.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 8 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


5.5.2 For smaller works or works in remote areas wooden ballies may be permitted for
scaffolding/staging by the Engineer-in-Charge at his sole discretion. The contractor
must ensure the safety and suitability of such works as described under clause 5.5.1
above.

5.6 Embedment of Fixtures

All fixtures, pipes, conduits, holdfasts of doors and windows etc. required to be built in
walls, shall be embedded in plain cement concrete block of grade 1:3:6, at the required
positions, as the work proceeds.

6.0 PAYMENT

This clause shall apply to Item Rate tender only.

6.1 General

The payment of brick masonry shall be inclusive of all labour, material,


Scaffolding/staging sampling and testing, soaking of bricks, laying of bricks, raking of
joints, cutting of bricks, providing recesses and making rectangular or round openings,
sealing the gap between brick masonry and soffit of beam/slab with and including
cement mortar, curing, making of masonry platform for unloading the wet mix,
embedding the fittings/fixtures including providing PCC(1:3:6) etc, all as specified for all
heights and depths. Deduction for rectangular or circular openings, shall be done as per
relevant BIS Codes.

6.1.1 Payment for brick masonry works of one or more brick thickness, including circular
brickwork, shall be made on cubic meter basis of the work done.

6.1.2 Payment for half brick masonry work shall be made on square meter basis on the area
of work done and shall also include the cost of supplying and fixing of reinforcement
bars in position.

6.1.3 Payment for forming the cavity, shall be in square meters and shall include the cost of
laying of bitumen coated M.S. ties in position, labour required for keeping the cavity
clear, providing air slots etc.

STANDARD SPECIFICATION DOCUMENT No. REV-0


(INDIA) LTD CIVIL & STRL WORKS FOR BRICK
S-11-02-008 Page 9 of 9
NEW DELHI MASONRY

Copyright – All rights reserved


TECHNICAL SPECIFICATION

CIVIL & STRUCTURAL WORKS STONE


MASONRY

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 1 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
CONTENTS

1.0 SCOPE

2.0 REFERENCES

3.0 MATERIALS

4.0 GENERAL REQUIREMENTS

5.0 SPECIFIC REQUIREMENTS

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 2 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
1.0 SCOPE

This EIL specification establishes the materials, dressing, laying, jointing, workmanship,
curing etc. for stone masonry works and shall comply with all the requirements of IS
:1597.

2.0 REFERENCES

2.1 BIS Codes

IS : 269, 455, 1129, 1197, 2250, 2750

2.2 GAIL specifications for Materials

3.0 MATERIALS
Refer GAIL specification on : Materials

4.0 GENERAL REQUIREMENTS

4.1 Cement Mortar

Cement mortar shall meet the requirements of IS:2250 and shall be prepared by mixing
cement and sand by volume. Proportion of cement and sand shall be 1 :6 One part of
cement and six parts of sand) or as specified. The sand being used, shall be sieved
before use. The mortar shall be used as soon as possible after mixing and before it has
begun to set and in any case within initial setting time of cement, after the water is
added to the dry mixture. Mortar unused for more than initial setting time of cement
shall be rejected and removed from the site of work.

4.1.1 Proportioning
The unit of measurement for cement shall be a bag of cement weighing 50 kgs and
this shall be taken as 0.035 cubic meter. Sand shall be measured in boxes of
suitable size on the basis of its dry volume. In case of damp sand, its quantity shall
be increased suitably to allow for bulkage.

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 3 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
4.1.2.1 The mixing of mortar shall be done in a mechanical mixer operated manually or by
power. The Engineer-in-Charge may however, permit hand mixing, as a special case,
taking into account the magnitude, nature and location of work. The Contractor shall
take the prior permission of the Engineer-in-Charge in writing, for using hand- mix,
before the commencement of work.

4.1.2.1 Mixing in Mechanical Mixer

Cement and sand in specified proportions, by volume, shall be thoroughly mixed dry in a
mixer. Water shall then be added gradually and wet mixing continued for atleast one
minute. Care shall be taken not to add more water than that which shall bring the
mortar to the consistency of a stiff paste. Wet mix from the mixer shall be unloaded
on water-tight masonry platform, made adjacent to the mixer. Platform shall be at least
150mm above the levelled ground, to avoid contact of surrounding earth with the mix.
Size of the platform shall be such that it shall extend atleas 300mrn alround the loaded wet
mix area. Wet mix, so, prepared shall be utilised within initial setting time of cement
[thirty (30) minutes either for ordinary portland cement conforming to IS:269 or for
portland slag cement conforming to IS:455] after addition of water. Mixer shall be cleaned
with water each time before suspending the work.

4.1.2.2 Hand Mixing

The measured quantity of sand shall be levelled on a clean masonry platform and
cement bags emptied on top. The cement and sand shall be thoroughly mixed dry by
being turned over and over, backward and forward, several times till the mixture is of
uniform colour. The quantity of dry mix which can be consumed within initial setting
time of cement shall then be mixed with just sufficient quantity of water to bring the
mortar to the consistency of stiff paste.

4.2 Curing

Green work shall be protected from rain, running water or accumulated water from any
source, by suitable means. Masonry work, as it progresses shall be kept thoroughly
wet by sprinkling water at regular intervals, on all faces. Curing shall be done after 24
hours of completion of day's work and shall be done for at least 10 days after
completion. Proper watering cans with spray nozzles, rubber or PVC pipes shall be used
for this purpose.

Staging scaffolding shall be properly planned and designed by the Contractor. Use of

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 4 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
only steel tubes is permitted for staging scaffolding. Design of staging/scaffolding shall
be submitted for approval of the Engineer-in-Charge, before commencement of work.
300mrn around the loaded wet mix area. Wet mix, so, prepared shall be utilized within
initial setting time of cement [thirty (30) minutes either for ordinary Portland cement
conforming to IS:269 or for portland slag cement conforming to IS:455] after addition
of water. Mixer shall be cleaned with water each time before suspending the work.

4.3 Staginglscaffolding
Staginglscaffolding shall be properly planned and designed by the Contractor. Use of
only steel tubes is permitted for staginglscaffolding. Design of staging/scaffolding shall
be submitted for approval of the Engineer-in-Charge, before commencement of work.
Single scaffolding having one set of vertical support, shall be used and other end of the
horizontal scaffolding member shall rest in a hole provided in the header ourse. The
supports shall be sound and strongly clamped with the horizontal pieces over which the
scaffolding planks shall be fixed. The holes left in the masonry works for supporting the
scaffolding shall be filled and made good with plain cement concrete of grade 1:3:6
during plastering. Suitable access shall be provided to the working platform area. The
scaffolding shall be strong enough to withstand all loads likely to come upon it and shall
also meet all the requirements specified in IS:2750. Double scaffolding shall be
provided for pillars less than one metre in width or for the first class masonry or for a
building having more than two storeys. The following measures shall also be
considered during erection of the scaffoldinglstaging

a. Sufficient sills or underpinnings, in addition to base plates, shall be provided,


particularly, where scaffoldings are erected on soft grounds.

b. Adjustable bases to compensate for uneven ground shall be used.

c. Proper anchoring of the scaffolding/staging at reasonable intervals shall be


provided in each direction with the main structure wherever available.

d. Horizontal braces shall be provided to prevent the scaffolding from rocking.

e. Diagonal braces shall be provided continuously from bottom to top between


two adjacent rows of vertical supports.

f. The scaffolding/ staging shall be checked at every stage for plumb line.

g. Wherever the scaffolding staging is found to be out of plumb, it shall be


dismantled and re-erected afresh. Effort shall not be made to bring it in line with
a physical force.

h. All clamps and couplings shall be properly tightened with nuts and bolts to avoid
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 5 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
slippage.

i. Erection work of a scaffoldinghtaging under no circumstances shall be left totally


to semiskilled or skilled workmen and shall be carried out under the supervision of
contractor's technically qualified civil engineer.

4.3.2 For smaller works or works in remote areas, wooden ballies may be permitted for
scaffolding staging by the Engineer-in-Charge at his sole discretion. The contractor
must ensure the safety and suitability of such works as described under clause
4.3.1 above.

4.4 Embedment of Fixtures

All fixtures, pipes, conduits, holdfasts of doors and windows etc. required to be built
in walls, shall be embedded in plain cement concrete of grade 1:3:6 at the required
position as the work proceeds.

5.0 SPECIFIC REQUIREMENTS

5.1 Random Rubble Masonry

5.1.1 Dressing

Stone shall be hammer dressed on the face, the sides and the beds to enable it to
come in proximity with the neighbouring stone. The "bushing" (projection) on the
face shall not be more than 40mm on an exposed face and 19mm on the face to be
plastered. It shall not have depression more than l0mm from the average wall
surface. It shall also conform to the general requirements for dressing of stones
covered in IS :1 129.

5.1.2 Laying

All stones shall be wetted before laying to prevent absorption of water from mortar.
The stones shall be laid so that the pressure is always perpendicular to the natural
bed. The courses (if any) shall be built perpendicular to the pressure which the
masonry will bear. In case of battered walls, the base of stone and plane of courses
(if any) shall be at right angles to the batter.

The walls shall be carried up truly plumb or to the specified batter. Every stone shall
be carefully fitted to the adjacent stones, so as to form neat and close joints.
Vertical joints shall be staggered as far as possible.

Stones may be brought to level course at plinth, window sills and roof level.
Levelling up at plinth level, window sills and roof level shall be done with concrete
comprising of one part of the mortar as used for the masonry and two parts of
graded stone aggregate of 20mm nominal size.

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 6 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
The bond shall be obtained by fitting in closely the adjacent stones. Transverse
bonds shall be provided by the use of bond stones extended from the front to the
back of the wall. At angular junctions the stones at each alternate course shall be
well bonded into the respective courses of the adjacent wall. Face stones shall
extend and bond well in the back. These shall be arranged to break joints as much
as possible, and to avoid long vertical lines of joints. The depth of stone from the
face of the wall, inwards, shall not be less than the height or breadth at the face.
Where there is break in masonry work, the masonry shall be raked in sufficiently
long steps for facilitating joining of old and new work. The stepping of the raking
shall not be more than 45 degrees with the horizontal. The masonry work shall not
be raised more than 1.2 metre per day. Toothed joints in masonry shall not be
permitted.

5.1.3 Hearting Stones The hearting or interior filling of the wall shall consist of
rubble

stones which may be of any shape but shall not be less than 150mm on any face.
These

shall be carefully laid, hammered down with a wooden mallet into position and
solidly dded in mortar. The hearting should be laid nearly level with facing and
backing, except that at about one metre intervals, vertical bond stones shall be
firmly embedded to form a bond between successive courses.

5.1.4Insertion of Chips

The chips and spalls stones shall be used wherever necessary to avoid thick mortar
beds or joints and it shall also be ensured that no hollow spaces are left anywhere
in the masonry. The chips shall not be used below the hearting stone to bring
these upto the level of face stones. The use of chips shall be restricted to the filling
of interstices between the adjacent stones in hearting and this shall in no case
exceed 20% of the quantity of stone masonry.

5.1.4 Bond Stone

Bond or through stone running across the thickness of wall shall be provided in the
walls having thickness upto 600mm. If the walls are thicker than 600 rnm, two or
more bond stones overlapping each other by atleast 150mm shall be provided in a
line from face to back. Atleast one bond stone or a set of bond stones shall be
provided for every 0.5 sq.m of wall surface. These shall be provided at 1.5m to 1.8m
apart clear in every course and shall be staggered in subsequent course. An
identification mark for the bond stones shall be given on both faces.

5.1.6 Quoins The quoins shall be of selected stones neatly dressed to the required angle
and shall be of the same height as the course in which they occur and laid header
and tretcher alternately. The quoin stone shall not be less than 0.03 cubic metre in
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 7 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
volume.

5.1.7 Jointing

Stones shall be so laid that all joints are fully packed with mortar. Face joints
shall be minimum 20mm thick. The joints shall be struck flush and finished at
the time of laying; when plastering and pointing is not required. If walls are to
be plastered or pointed, joints shall be raked to a minimum depth of 20mm
during the progress of work when the mortar is still green. For the faces of the
wall which are not to be plastered, stone surfaces shall be cleared of mortar
splashing to give uniform stone appearance.

5.2 Coursed Rubble Masonry

5.2.1 Dressing

Face stones shall be hammer dressed on all beds and joints so as to give them
approximately rectangular shape. These shall be square on all joints and beds.
The bed joints shall be chisel drafted for atleast 80mm back from the face and
for theside joints atleast 40mm. No portion of the dressed surface shall show a
depth of gap more than 6mm from a straight edge placed on it. The remaining
unexposed portion of the stone shall not project beyond the surface of the bed
and side joints. The bushing on the face shall not be more than 40mm on an
exposed face and l 0mm on the face to be plastered.

The hammer dressed stone shall also have a rough tooling for a minimum width
of 25mm along the four edges of the face of the stone for the exposed stone
masonry work.

5.2.2 Laying

All stones shall be wetted before laying to prevent absorption of water from
ortar. The stones shall be laid so that the pressure is always perpendicular to
the natural bed. The courses shall be built perpendicular to the pressure which
the masonry will bear. In case of battered walls, the base of stone and plane of
courses shall be at right angles to the batter.

The walls shall be carried up truly plumb or to the specified batter. Every stone
shall be carefully fitted to the adjacent stones, so as to form neat and close
joints. All courses shall be laid truly horizontal and all vertical joints shall be
truly vertical. The quoin stones shall be laid stretchers and headers alternately
and shall be laid square on their beds, which shall be rough chisel dressed to a
depth of atleast 100mm. All courses shall be laid truly horizontal and all vertical
joints shall be truly vertical.

The tones shall be laid in horizontal courses and each course shall be of equal
height of not less than 150mm and more than 300m.m.
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 8 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
Levelling at plinth level, window sills and roof level shall be done with concrete
comprising of one part of the mortar as used for the masonry and two parts of
graded stone aggregate of 20 mm nominal size.

The bond shall be obtained by fitting in closely the adjacent stones.


Transverse bonds shall be provided by the use of bond stones extended from
the front to the back of the wall. At angular junctions the stones at each
alternate course shall be well bonded into the respective courses of the
adjacent wall.

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORK
S-11-02-009 Page 9 of 9
NEW DELHI STONE MASONARY
Copyright GAIL – All rights reserved
TECHNICAL SPECIFICATION

CIVIL & STRUCTURAL WORKS


DEMOLITION AND DISMANTLING

TECHNICAL SPECIFICATION FOR DOCUMENT No. REV-0


(INDIA) LTD DEMOLITION AND DISMANTLING
S-11-02-010 Page 1 of 6
NEW DELHI
Copyright – All rights reserved
CONTENTS

1.0 SCOPE

2.0 GENERAL

3.0 SAFETY PRECAUTIONS

4.0 PROCEDURE

5.0 CLEANING & STACKING

6.0 DISPOSAL

7.0 PAYMENT

TECHNICAL SPECIFICATION FOR DOCUMENT No. REV-0


(INDIA) LTD DEMOLITION AND DISMANTLING
S-11-02-010 Page 2 of 6
NEW DELHI
Copyright – All rights reserved
1.0 SCOPE

This specification covers the procedure and safety requirements for demolition and
dismantling of masonry (Brick & Stone), concrete (Plain /Reinforced), structural steel
(sheeted / unsheeted) works .

2.0 GENERAL

2.1 Apart from this specification, the demolition and dismantling of structures (part or
whole) shall be in compliance with all statutory safety regulations and any other special
requirement as shown/Noted on the drawings and General Conditions of Contract. Prior
consent and approval of the Engineer-in-charge shall be obtained in writing before
starting any dismantling works. Any restrictions imposed regarding working hours shall
also be strictly followed by the Contractor.

2.2 All materials obtained from dismantling/demolition operations shall be the property of
the Owner unless otherwise specified and shall be kept in safe custody until handed
over to the Engineer-in-charge.

2.3 Where it becomes necessary to disconnect any existing service line(s) (such as
eIectrica1, piping etc.) during dismantling/demolishing operation and where so
required by the Engineer-in-charge, suitable alternate arrangement shall be made by
the Contractor to maintain the continuity and proper functioning of the affected service
line(s) with the approval of the Engineer-in-charge at no extra cost to GAIL.

2.4 Specification No S-10-02-002 (Earthwork) shall be referred to the extent applicable.

3.0 SAFETY PRECAUTIONS

3.1 The Contractor shall adhere to safe demolishing/dismantling practices at all stages of
work to guard against accidents, hazardous and unsafe working procedures.

.3.2 Necessary propping ,shoring ,strutting and/or underpinning shall be done for the safety
of all surrounding structures (whose safety is likely to be endangered) before taking up
the demolishing and dismantling work.

3.3 Temporary enclosures made out of GI sheets, fencings, danger lights etc. shall be
provided by the Contractor and got approved by the Engineer-in-charge before start of
work to prevent accidents.

3.4 Contractor must ensure the availability of adequate fire fighting equipment /
arrangements before starting actual demolishing/dismantling works. These facilities
shall be made available throughout the entire operation of demolition and dismantling
of structures.

3.5 All equipments, pipes ,fittings and instruments, underground utilities etc. located in the
TECHNICAL SPECIFICATION FOR DOCUMENT No. REV-0
(INDIA) LTD DEMOLITION AND DISMANTLING
S-11-02-010 Page 3 of 6
NEW DELHI
Copyright – All rights reserved
vicinity shall be protected by suitable means, as decided by the Engineer-in-charge,
during demolishing, dismantling operations.

3.6 Roads and working spaces shall be kept free of any debri / dismantled materials at the
end of day's work.

3.7 Necessary measures shall be taken to keep the dust and noise nuisance to minimum
levels.

3,8 Dismantled elements/components shall not be dropped from a height or thrown from a
distance. Dismantling of elements fixed by screws/bolts/hooks etc. shall be fixtures with
proper tools only. Such fixtures may be allowed to be cut by sawing or flame cutting,
in the event of their being stuckup due to corrosion etc. however the decision of
Engineer-in-charge in this regard shall be final and binding., Welds shall be removed by
flame cutting. Tearing or ripping of elements shall not be resorted to under any
condition.

4.0 PROCEDURE

4.1 Entire work of demolishing & dismantling shall be meticulously planned. Prior to
start of work, the Contractor shall thoroughly understand the scope and nature of the
work, and then prepare and submit the proposed work execution plan of demolishing
& dismantling to the Engineer-in- charge for his review. Comments if any, shall be
taken care by the contractor and execution of the work shall be done based on the
revised execution plan.

4.2 Demolition and dismantling shall be restricted to the extent shown on drawings or as
directed by the Engineer-in-charge.

4.3 Demolition of any structure shall be carried out in the sequence reverse to that
followed at the time of its construction.

4.4 Dismantling shall be done in a systematic manner. All elements shall be


carefully removed without causing any damage.

4.5 Blasting in any form shall not be permitted.

4.6 Chipping of concrete grout shall be done with precision by chiseling. The finished
surfaces shall be made true to the requisite size and shape.

4.7 Pockets/holes of specified size shall be made cut by drilling/chiselling.

5.0 CLEANING & STACKING

5.1 All demolished/dismantled servicable materials such as bricks, stones, reinforcement


bars, structural steel, sheeting etc. shall be separated out, cleaned and stacked in
TECHNICAL SPECIFICATION FOR DOCUMENT No. REV-0
(INDIA) LTD DEMOLITION AND DISMANTLING
S-11-02-010 Page 4 of 6
NEW DELHI
Copyright – All rights reserved
separate lots within the plant boundary as directed by the Engineer-in-charge.

6.0 DISPOSAL

All unserviceable materials shall be disposed off in spoil heaps within or outside the plant
boundary as per the directions of the Engineer-in-charge. Areas required outside the
plant boundary for dumping of disposed material shall be arranged by the contractor and
got approved by the Engineer-in- charge.

7.0 PAYMENT

7.1 General

Measurement of all works shall be taken prior to start of demolishing / chipping /


dismantling works.

7.2 Masonry/Concrete Works (Demolition)

7.2.1 Payment shall be made on the basis of actual volume in cubic meters (cu.m.) of
masonry1 concrete works demolished. The thickness of plaster bitumen felt shall be
included in measurements. The rate for demolishing shall include supply of labour, tools
& tackles, necessary safety measures, propping, underpinning, scaffolding, handling,
cutting, straightening, scraping & cleaning of reinforcement bars and other embedment
(in case of reinforced concrete works), sorting out and stacking of all serviceable
materials, disposal of all unserviceable material, clearing the site, etc. all complete as
specified and directed by the Engineer-in-charge.

7.3 Excavation & Backfilling

7.3.1 Excavation and backfilling shall be paid separately as per relevant clauses of Specification
No. S-10-02-002 for Earth Work.

7.4 Chipping of Concrete Works

Payment shall be made on the basis of admissible area in square meters (sq.m.) of
concrete surfaces chipped, pertaining to the different categories of thicknesses specified in
the schedule of items.

The rate for chipping shall include supply of labour, tools and tackles, necessary safety
measures, scaffolding, chiselling, handling exposing, cutting, straightening, scraping,
clearing the reinforcement bars (in case of reinforced concrete works), wire brushing and
washing the exposed surfaces, disposal of all unserviceable material etc. all complete as
directed.

7.5 Making Pockets/Holes in Concrete Works

TECHNICAL SPECIFICATION FOR DOCUMENT No. REV-0


(INDIA) LTD DEMOLITION AND DISMANTLING
S-11-02-010 Page 5 of 6
NEW DELHI
Copyright – All rights reserved
Payment shall be made on the basis of number (Each) of pockets/holes of sizes upto &
inclusive of 200x200x500 mm, made or cut in the concrete works.

The rate for making pockets/holes shall include supply of labour, tools & tackles, necessary
safety measures, scaffolding, chiselling, drilling, handling, cutting or relocating
reinforcement bars, cleaning, disposal of all unserviceable material etc. all complete as
directed.

7.6 Dismantling of Structural Steel Works

Payment shall be made on the basis of weight (MT) of the structure/components being
dismantled. Assessment of weight shall be done as per the specifications or as per the
direction of Engineer-in-charge.

The rate for dismantling shall include supply of labour, tools and tackles, equipment,
consurnables, necessary safety measures, scaffolding, propping, handling, unbolting,
cutting (by sawing or flame cutting) of gussets/plates/bolts/hooks/welds, cleaning, sorting
out and stacking of all serviceable materials, disposal of all unserviceable material, etc. all
complete as specified and directed.

7.7 Dismantling of Roof & Wall Sheeting

Payment shall be made on the basis of dismantled sheeted area in square metreS (sq.m.)
of plan area in case of roof sheeting and area in elevation in case of side and louver
sheeting.

The rate for dismantling shall include supply of labour, tools and tackles, equipments,
consumables, necessary safety measures, handling, scaffolding, unbolting, cutting (by saw
or flame cutting) of hook bolts, removal of ridges, gutters, flashings, transporting, stacking
of all serviceable materials, disposal of all unserviceable material, etc. all complete as
directed.

TECHNICAL SPECIFICATION FOR DOCUMENT No. REV-0


(INDIA) LTD DEMOLITION AND DISMANTLING
S-11-02-010 Page 6 of 6
NEW DELHI
Copyright – All rights reserved
TECHNICAL SPECIFICATION FOR CIVIL
& STRUCTURAL WORKS

MISCELLANEOUS ITEMS

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 1 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
CONTENTS

1. SCOPE

2. REFERENCES

3. MATERIALS

4. GENERAL REQUIREMENTS

5. PRE-CONSTRUCTIONAL ANTI-TERMITE TREATMENT

6. ANTI-CORROSIVE LAYER

7. DRESSING & TRIMMING

8. CUTTING PILE HEADS

9. BUILDING-UP PILE HEADS

10. HARD CORE

11. SAND FILLING IN PLINTHIFOUNDATIONS

12. DAMP PROOF COURSE - (DPC)

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 2 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
1.0 SCOPE

The scope shall be as specified separately for different items below.

2.0 REFERENCES

2.1 BIS Codes


GAIL specifications

S-11-02-002: Materials

S-11-02-004: Plain and Reinforced Cement Concrete

3.0 MATERIALS

The materials shall be as specified separately for different items below.

4.0 GENERAL REQUIREMENTS

4.1 The Contractor shall test the materials, where applicable, in approved laboratory as
required by the Engineer-in-Charge and furnish test certificates for materials and obtain the
approval of the Engineer-in- Charge prior to the use of such materials in the works. All tests
shall be in accordance with relevant Indian Standards.

5.0 PRE-CONSTRUCTIONAL ANTI-TERMITE TREATMENT

5.1 Scope

This GAIL specification establishes the materials and method of accomplishing pre-
constructional anti-termite treatment of soil for protection of buildings against attack by
subterranean termites with the usage of chemical emulsions in accordance with the
procedure laid down.

5.2 Materials

Refer GAIL specification no. S-11-02-002

5.3 Procedure for Treatment

5.3.1 The treatment shall be carried out by an approved agency specialised in the field. Apart
from this specification, the work shall be carried out in compliance with IS:6313. In case of
any contradiction, this EIL specification shall govern.

5.3.2 Site Preparation

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 3 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
Prior to start of chemical treatment, area(s) shall be made free from logs, stumps, timber
offcuts, leveling pegs, roots of planted trees etc. Soil treatment shall start when foundation
trenches pits are ready to take concrete/masonry in foundations and plinth area ready for
laying the subgrade. Treatment shall not be carried out when it is raining or the subsoil
water level is at the same or higher than the level of treatment. In the event of water-
logging of foundations, the water shall be pumped out and the chemical emulsion applied
when the soil is absorbent.

5.3.3 Treatment of the excavated pitsltrenches and backfill for Foundations

a) The bottom surface and the lower 300 mm side surfaces of the excavated pitsltrenches
for foundations of masonry works and RCC plinth beams supporting such masonry
works, shall be treated with specified chemical emulsion @ 5 litres /m2 of the surface
area. However, no such treatment shall be required in case of pitsltrenches made for
RCC foundations supporting RCC walls and/or columns.

b) On completion of construction of masonry foundations, the backfill in immediate


contact with the substructure shall be treated in layers, of 300mrn, with emulsion @
7.5 litres/m2 of the vertical surface of the substructure (i.e. 7.5 x 0.300 = 2.25
Litre/ meter of perimeter) for each side. The treatment shall be given after ramming
of each layer of soil, by rodding the earth at 150mm centres close to the wall surface
and working the rod backward and forward (parallel to the wall surface) and then
spraying the specified dosage of emulsion. The emulsion shall be directed towards the
masonry surfaces so that the soil in contact with these surfaces is well treated with the
chemical. After the treatment, the soil shall be tamped back into place. This shall be
done for full depth of the fill.

c) For RCC walls and columns, the treatment as specified in (b) shall start from a depth
500 mm below the finished ground level, and shall be done upto the FGL.

5.3.4 Treatment of Plinth / Basement and Apron

The top surface of the consolidated earth below the non-suspended floor slabs and the
peripheral aprons of widths upto 750mm, the bottom surface and side surfaces of the
excavated pits for the basements shall be treated with chemical emulsion @ 5 litres/m2
of the surface area. Holes 50 to 75mm deep at 150mm centres, both ways, shall be
made on the surface with 12mm diameter mild steel rod and then emulsion shall be
sprayed uniformly over the area. At expansion joint locations, anti-termite treatment
shall be supplemented by treating through the expansion joint @ 2.0 litres per linear
meter of joint after the subgrade has been laid.

Treatment of Junctions of plinth filling and wall/column faces shall be done after
making a small channel 30rnrnx30mm, by making rod holes 150mm apart (upto the
ground level) in the channel and then by moving the rod backward and forward to
break up the earth. The chemical emulsion shall be poured along the channel @ 7.5
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 4 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
litres/m2 of the vertical wall/column surface so as to soak the soil right to the bottom.
The soil shall be tamped back into place after the treatment.

5.3.5 Treatment of Sol along External Perimeter of Bulding

After the building is complete, the earth along the external perimeter shall be rodded at
intervals of 150mm and to depth of 300mm. The rod shall be moved backward and forward
parallel to the wall to break up the earth and chemical emulsion poured along the wall @
7.5 litres/m2 of vertical surface (i.e. 7.5 x 0.300 = 2.25 litreslmetre of perimeter). After the
treatment, the earth shall be tamped back into place.

5.4 Payment

This clause shall apply to Item Rate tender only.

Payment for pre-constructional anti-termite treatment shall be made on square metre


(sq.m.) basis of plinth area of the building at ground floor only. The rate shall include
supplying all materials, spray pumps, tools, tackles & other accessories, labour, site
preparation, rodding, tamping, mixing, spraying the specified chemical emulsion at
prescribed dosage, storage facilities, handling, transporting etc. all complete as directed
& specified.

6.0 ANTI-CORROSIVE LAYER

6.1 Scope

This EIL specification covers the requirement of materials, method of preparation and
procedure for laying an anticorrosive layer over top surface of tank foundations for
protection of bottom plates of steel tanks against corrosion attack.

6.2 Materials

6.2.1 Sand shall be clean, dry, coarse, hard, angular, free from coatings of clay, dust and mix of
vegetable and organic matter and shall conform to IS:383 - Grade 111.

6.2.2 Bitumen shall be of grade A 90 conforming to IS:73.

6.3 Mixing and Laying

The bitumen shall be heated to a temperature of 175OC to 190•‹C with 3 % kerosene if


required and sand ( 8 to 10% by volume) shall be thoroughly mixed with it in a mixing
drum to give a uniform mixture and shall be laid over clean and dry surface of tank
foundation to line, grade and levels as shown on the drawings and directed by the
Engineer-in-Charge. Bitumen shall not be heated beyond the specified temperature limits.
The layer shall be tamped to form hard mass of specified compacted thickness.
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 5 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
6.4 Payment

This clause shall apply to Item Rate tender only.

The payment shall be made on square metre (sq.m.) basis of the area covered with the
anticorrosive layer. The rate shall include supplying all materials, tools, plants, labour,
transportation, handling, heating, mixing, laying, tamping etc. all complete as specified.

7.0 DRESSING & TRIMMING

7.1 Scope

This GAIL specification covers the procedure for dressing, trimming and paving with earth
the peripheral area around the completed building/structure.

7.2 Procedure

The ground all around the completed buildinglstructure for 3 metres width or as specified
by the Engineer-in-Charge, shall be cleaned and dressed to suitable slope. Over the
prepared ground a layer of approved earth shall be spread, watered and well consolidated
so as to achieve an average thickness of 75mm.

7.3 Payment

This clause shall apply to Item Rate tender only.

Payment shall be made on square metre (sq.m.) basis of the actual area dressed and paved
with earth.The rate shall include supplying all materials, labour including cleaning, dressing
the ground to required slope, spreading of earth, watering, ramming, consolidating etc. all
complete as directed.

8.0 CUTTING PILE HEADS

8.1 Scope

This GAIL specification covers procedure for cutting pile heads of cast-in-situ RCC piles.

8.2 Procedure
Head of already cast RCC piles shall be cut after 28 days of casting up to a length and
elevation as shown on the drawing by chiseling taking all necessary safety precautions.
Care shall be taken that pile reinforcement is not cut or damaged during chiseling
operation. All debris and loose or cracked concrete in the pile shall be removed and
disposed off within the plant boundary as per the directions of the Engineer-in-Charge and

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 6 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
site shall be left clean for casting of pile caps. The surface of reinforcement bars shall be
cleaned, if required by wire brushing so that no old concrete sticks to them.

8.3 Payment

This clause shall apply to Item Rate tender only.

Payment shall be made per pile basis for the actual number of pile heads cut. The rate shall
include supplying a11 tools and tackles, labour including disposal of debris, bending the pile
reinforcements for proper anchorage within the pile cap etc. all complete as directed.

9.0 BUILDING-UP PILE HEADS

9.1 Scope

This GAIL specification covers requirements of materials and procedure for building-up of
RCC Pile Heads.

9.2 Materials

9.2.1 Concrete shall be of the same grade & GAIL specification as that for the pile.

9.2.2 Reinforcement shall be of the same grade and GAIL specification as that for the pile.

9.2.3 Type of cement shall be same as that used for the pile.

9.3 Procedure

Concrete in existing piles shall be chiseled off minimum upto the lap-length of the
reinforcements in the pile. In cases where reinforcements are longer than the concreted
piles, the top concrete of the existing piles shall be chiseled off upto a length of 800mm.

Concrete surface and reinforcement of pile shall be cleaned of any dirt, grease, debris
etc. and concrete surface shall be made rough by hacking. Reinforcement shall be
lapped/welded as per the direction of the Engineer-in-Charge. Neat cement slurry shall be
applied on top surface of concrete and using approved formwork concreting shall be done
upto the level shown on the drawing or as directed by the Engineer-in-Charge.

9.4 Payment

This clause shall apply to Item Rate tender only.

Payment shall be made on cubic metre basis for the total quantity of concrete actually
poured for achieving the level as shown on drawings.
The rate shall include supply of all materials (except reinforcement which shall be paid
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 7 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
separately as per respective item) labour, cleaning, welding, shuttering, vibrating, finishing,
curing etc. all complete. Cutting of pile heads and excavation including backfilling shall be
paid separately as per respective item.

10.0 HARD CORE

10.1 Scope

This GAIL specification covers the requirements of materials and procedure for laying of
hard core.

10.2 Materials

Hard core shall consist of brokenlcrushed stones of 150mm and down size. Stones shall be
sound, angular, hard and free from flakes, dust and other impurities.

10.3 Procedure

Hard core shall be laid to the grade, level and thickness as shown on the drawing. Broken
stones of required height shall be vertically placed and blinded with approved murrum
/sand and consolidated with roller including watering, dressing etc. However, areas
inaccessible by roller may be compacted by hand rammer.

10.4 Payment

This clause shall apply to Item Rate tender only.

The hard core shall be measured on the basis of volume in cubic metres (cu.m.) of
compacted hard core laid. The rate shall include all labour, materials, consolidation by
rammer/roller, watering, dressing etc. all complete.

11.0 SAND FILLING IN PLINTH/FOUNDATIONS

11.1 Sand filling in plinth / foundation shall be as per relevant standard specifications.

11.2 Filling shall be carried out in layers not exceeding 15cms and shall be compacted
mechanically or by saturation to specified grade and level and to obtain 90% laboratory
maximum dry density or as specified in schedule of rates.

11.3 Compaction by flooding may be accepted at the discretion of the Engineer-in-Charge,


provided the required compaction is achieved.

11.4 The Contractor shall not commence filling in and around any work until it has been
permitted by the Engineer-in-Charge.
11.5 Payment
TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0
GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 8 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
This clause shall apply to Item Rate tender only.

Payment shall be made on cubic metre (cam.) basis of the finished compact volume. The
rate shall include cost of sand for any compacted thickness, wastage if any, all handling,
transport for all leads, tamping, watering, flooding, dressing etc. Any brick work required
for ponding shall be paid separately under relevant item.

12.0 DAMP PROOF COURSE - (DPC)

12.1 All materials used for Damp Proof Course shall as per relevant standard specifications.

12.2 The 40mm thick Damp Proof Course shall consist of plain cement concrete of grade M-20,
unless otherwise specified.

12.3 The Damp Proof Course shall be laid at plinth level of masonry walls, flush with the floor
surface and shall not be carried across doorways.

12.4 Before laying, the top surface of wall shall be thoroughly cleaned and watered. The
D.P.C. shall be laid in layers of 20mm thickness retaining the edges by necessary
formwork and shall be well tamped and troweled to smooth finish. The layer shall be
cured by keeping the surface wet for 40 hours and after it has dried, two coats of hot
bitumen of grade A120lS120 conforming to IS:73 shall be applied over it at the rate of
1.7 ~g./m'. Over this, the second layer of 20mm thick concrete shall be laid and cured as
described in case of the first layer and two coats of hot bitumen at the rate of 1.7 Kg./m2
shall be applied again in a similar manner.Over this, dry sharp sand shall be sprinkled
evenly before hardening of second coat of bitumen paint.

12.5 Payment

This clause shall apply to Item Rate tender only.

Payment shall be made on square metre (sq.m.) basis of the area laid. The rate shall be
inclusive of formwork, curing, providing and laying bitumen, supplying and spreading sand
over bitumen etc. complete.

TECHNICAL SPECIFICATION FOR CIVIL DOCUMENT No. REV-0


GAIL (INDIA) LTD & STRUCTURAL WORKS
Page 9 of 9
NEW DELHI MISCELLANEOUS ITEMS S-11-02-011
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-001 Page 1 of 2
NEW DELHI FLOORING DETAILS FOR BUILDINGS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-001 Page 2 of 2
NEW DELHI FLOORING DETAILS FOR BUILDINGS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 7 of 7
NEW DELHI S-11-01-002
METAL INSERT PLATES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-003 Page 1 of 5
NEW DELHI STANDARD LINTELS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-003 Page 2 of 5
NEW DELHI STANDARD LINTELS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-003 Page 3 of 5
NEW DELHI STANDARD LINTELS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-003 Page 4 of 5
NEW DELHI STANDARD LINTELS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
S-11-01-003 Page 5 of 5
NEW DELHI STANDARD LINTELS
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 7 of 7
NEW DELHI S-11-01-004
M.S. ANCHOR BOLTS ASSEMBLIES
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 7 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 8 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 9 of 10
NEW DELHI S-11-01-005
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 10 of
NEW DELHI
S-11-01-005 10
HANDRAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 7
NEW DELHI S-11-01-006
STEEL STAIR
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2 of 7
NEW DELHI S-11-01-006
STEEL STAIR
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3 of 7
NEW DELHI S-11-01-006
STEEL STAIR
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4 of 7
NEW DELHI S-11-01-006
STEEL STAIR
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5 of 7
NEW DELHI S-11-01-006
STEEL STAIR
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6 of 7
NEW DELHI S-11-01-006
STEEL STAIR
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 6
NEW DELHI S-11-01-007
STANDARD GRATING DETAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2 of 6
NEW DELHI S-11-01-007
STANDARD GRATING DETAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3 of 6
NEW DELHI S-11-01-007
STANDARD GRATING DETAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4 of 6
NEW DELHI S-11-01-007
STANDARD GRATING DETAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5 of 6
NEW DELHI S-11-01-007
STANDARD GRATING DETAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6 of 6
NEW DELHI S-11-01-007
STANDARD GRATING DETAIL
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD SMALL OPERATING FORMS ON GRADE/RCC
S-11-01-008 Page 1 of3
NEW DELHI ELEVATED STRUCTURE
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD SMALL OPERATING FORMS ON GRADE/RCC
S-11-01-008 Page 2 of3
NEW DELHI ELEVATED STRUCTURE
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD SMALL OPERATING FORMS ON GRADE/RCC
S-11-01-008 Page 3 of3
NEW DELHI ELEVATED STRUCTURE
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
HANDRAIL ON HORIZONTAL LANDING

STANDARD DRG. NO. REV-0


GAIL (INDIA) LTD
Page 7 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 8 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 9 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 10 of 10
NEW DELHI S-11-01-009
PIPESLEEPER CROSSOVER
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 1of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 2of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 3of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 4of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 5of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 6of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 7of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 8of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 9of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 10of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 11of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 12of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 13of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 14of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 15of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 16of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved
STANDARD DRG. NO. REV-0
GAIL (INDIA) LTD
Page 17of
NEW DELHI
S-11-01-010 17
CABLE TRENCH
Copyright GAIL – All rights reserved